KMC Controls HPO-6701, HPO-6702, HPO-6703, HPO-6705, HPO-6704 Installation Manual

Page 1
HPO-6700 Series Output Override Boards
Installation Guide
CONTENTS
Introduction .............................................. 1
Conquest Controllers/Modules ..................... 2
Older "Plastic" Case Controllers ................... 3
Older "Metal" Case Controllers ..................... 4
Wiring ...................................................... 4
Grounds Versus Switched Commons ............. 6
Maintenance ............................................. 6
Important Notices ...................................... 6
INTRODUCTION
Hand-Off-Auto
Switch (Not Included with HPO-670x-1)
LED Output
Indicator
Manual/Hand
Output Adjustment
(Potentiometer
on HPO-6702 and
HPO-6704)
The HPO-6704 converts a standard analog
voltage output to a 4–20 mA output while providing an adjustable potentiometer for override settings while in the “Hand” position.
power and will not work with a 4–20
mA device that also supplies its own power.
Each output board has a red LED indicator that turns On when the board’s output is turned On
either manually or automatically.
Output boards have an accessible three-position slide switch for selecting the “Hand-Off-Auto” functions:
While in the H (“Hand” or manual On) position,
the output is manually energized, and the controller is provided with a feedback signal to indicate the output has been overridden.
HPO-6701
(Triac)
HPO-6702
(0–10 VDC)
HPO-6704 (4–20 mA)
HPO-6703 (NO Relay)
HPO-6705 (NC Relay)
For enhanced controller output options (such as manual control, using large relays, or for devices that cannot be powered directly from a standard output), install output override boards (in compatible controllers). The following types of override boards are available:
The HPO-6702 enhances the analog voltage
output with a “Hand-Off-Auto” control while
providing an adjustable potentiometer for override settings while in the “Hand” position.
The HPO-6701/6703/6705 boards are
designed to convert a binary/digital output to a relay contact or triac output and to provide “Hand-Off-Auto” control and feedback functions.
While in the O (Off) position, the output is
manually de-energized, and the controller is provided with a feedback signal to indicate the output has been overridden.
While in the A (Auto) position, the output is
under the command of the controller.
NOTE: An HPO-670x-1 is always in auto mode
and does not have the manual slide switch.
NOTE: HPO-6701 triac and HPO-6703/6705
relay circuits use the Switched
Common SC terminal—not the Ground Common GND terminal.
NOTE: HPO-6701 triac outputs are for 24 VAC
only.
NOTE: Only the HPO-6701 triac and HPO-
6704 4–20 mA boards are approved for smoke control applications. For smoke control application information,
KMC Controls, 19476 Industrial Drive, New Paris, IN 46553 / 877.444.5622 / Fax: 574.831.5252 / www.kmccontrols.com
Page 2
see Smoke Control Manuals 000­035-08 (BACnet) and/or 000-035-09 (KMDigital).
2. Pull the top edge of the (translucent black) override board cover away from the case and flip open the cover.
CAUTION
Connecting 24 VAC or other signals that
exceed the operation specications of the controller before an override board
is installed will damage the controller.
For HPO-6700 series specications, see the data
sheet at kmccontrols.com.
See the sections below for installation into the
particular type of controller.
For KMC Conquest BAC-5900 series
controllers and CAN-5901 expansion modules, see Conquest Controllers/Modules on page
2.
For older controllers with “top-mounting”
raised plastic cases (BAC-5801/5802 and
newer KMD-5801/5802s), see Older “Plastic”
Case Controllers on page 3.
For older controllers with metal (e.g., BAC-
5831, BAC-A1616BC) and older “side­mounting” plastic cases (older KMD-
5801/5802s), see Older “Metal” Case
Controllers on page 4.
CONQUEST CONTROLLERS/MODULES
These instructions apply to KMC Conquest BAC­5900 series controllers and CAN-5901 expansion modules (with a flip-open lid).
1. Disconnect the power by removing the black
power terminal block.
2
3. Remove the jumper from the slot in which the override board will be installed.
3
NOTE: Each of the eight override slots ships
from KMC with a jumper installed on the two pins closest to the output terminal blocks. Only remove a jumper if an override board will be installed.
4. Orient the override board with the HOA selection slide switch toward the top of the controller.
5. Slide the override board into the slot in which the jumper was removed.
HPO-6700 Series Output Override Boards Installation Guide 2 902-019-02K
4
Page 3
6. Close the plastic cover.
7. Move the A-O-H selection switch on the override board to the appropriate position.
NOTE: A = Automatic (upper position).
O = Off (middle position). H = Hand/On (lower position).
NOTE: For more information about output
override boards, see the installation guide for the HPO-6700 Series.
OLDER "PLASTIC" CASE CONTROLLERS
7
These instructions apply to controllers with “top-mounting” raised plastic cases (e.g., BAC­5801/5802 and newer KMD-5801/5802). After installation of the boards, the existing cover is reinstalled.
To install the HPO-6700 series override boards:
1. Disconnect the power by removing the power jumper or terminal block.
8. Repeat Steps 3 through 7 for all other desired boards.
9. Wire the output device to the corresponding green (output) terminal block of the override board. (See Wiring on page 4.)
2. Remove the cover by squeezing on both sides of the cover and lifting it off.
3. Remove the jumper from the slot in which the override board will be installed.
NOTE: Each of the override slots ships from
7
KMC with a jumper installed on the two pins closest to the output terminal blocks. Only remove a jumper if an override board will be installed.
4. Orient the override board with the HOA selection slide switch toward the top of the controller.
5. Slide the override board into the slot in which the jumper was removed.
5
4
HPO-6700 Series Output Override Boards Installation Guide 3 902-019-02K
3
2
1
Page 4
6. Set the selection switch on the override board to the appropriate position.
NOTE: A = Automatic (upper position).
O = Off (middle position). H = Hand/On (lower position).
7. Repeat steps 3 through 6 for all desired boards.
8. Reinstall the cover over the boards.
9. Connect output devices to the controller outputs. (See Wiring on page 4.)
10. Reinstall the power jumper that was removed in Step 1.
OLDER "METAL" CASE CONTROLLERS
8
4
3
2
1
NOTE: Each of the override slots ships from
KMC with a jumper installed on the two pins closest to the output terminal blocks. Only remove a jumper if an override board will be installed.
4. Orient the override board with the HOA selection slide switch toward the outputs of the controller.
These instructions apply to controllers with
metal (e.g., BAC-5831, BAC-A1616BC) and older “side-mounting” plastic cases (e.g., older KMD-
5801/5802). After installation of the boards, the existing slot cover needs to be replaced by a raised HPO-6802 output board cover.
To install the HPO-6700 series override boards:
1. Disconnect the power by removing the power jumper or terminal block.
2. Remove the relevant slot cover(s) by lifting the right-hand side of the cover (within the plastic frame) toward you.
3. Remove the jumper from the slot in which the override board will be installed.
5. Slide the override board into the slot in which the jumper was removed.
6. Move the A-O-H selection switch on the override board to the appropriate position.
NOTE: H = Hand/On.
O = Off. A = Automatic.
7. Repeat steps 3 through 6 for all desired boards.
8. Remove the necessary label slots for each board location in the HPO-6802 output board
cover (purchased separately).
9. Snap the HPO-6802 cover over the boards.
10. Connect output devices to the controller outputs. (See Wiring on page 4.)
11. Reinstall the power jumper or terminal block that was removed in Step 1.
HPO-6700 Series Output Override Boards Installation Guide 4 902-019-02K
Page 5
Override
Boards
Jumpers
UO1
1
2
3
4
5
6
7
8
SC
UO2 GND
UO3
SC
UO4 GND
UO5
SC
UO6 GND
UO7
SC
UO8
GND
(+) (–)
4–20 mA Device
(on HPO-6704)
Contactor
(on HPO-6701 Triac)
Contactor
(on HPO-6703 NO Relay)
Contactor
(on HPO-6705 NC Relay)
0–10 VDC Device
Primary Voltage
(+) (–)
(on HPO-6702)
Primary Voltage
Simplified Schematic of Standard
Analog (GND) Outputs
To
Controller
Circuitry
Jumpers
CAUTION
Connecting 24 volts AC or other
signals that exceed the operation
specications of the controller to the output before the output jumper is removed will damage the controller. Remove the jumper and install the override board before connecting AC or other voltage to the output of the
controller.
NOTE: Switched Common (SC) output
terminals are unconnected in these model controllers unless an appropriate override output board is installed. Use only the Switched Common instead of Ground with the HPO-6701 triac and HPO-6703/6705 relays. Use the SC terminal in the same output bank as the output terminal. See Grounds Versus
Switched Commons on page 6.
UO3 (Analog)
SC
UO4 (Analog)
GND
Simplified Schematic of Override
Board Relay (SC) Outputs
UO7 (NO Relay)
SC (7 and 8)
UO8 (NC Relay)
GND
HPO-6703/6705 Relay Boards
(Coils Controlled by Controller Circuitry)
NOTE: The 4–20 mA HPO-6704 board
supplies the power and will not work
with a 4–20 mA device that also supplies its own power. For 4–20 ma applications, see also the 4–20 mA
Wiring for Controllers Application Guide.
NOTE: If a board is removed from a slot,
reinstall the (HPO-0063) jumper
(previously removed) on the two pins closest to the outputs. The jumper enables the analog voltage output on the terminals.
HPO-6700 Series Output Override Boards Installation Guide 5 902-019-02K
Page 6
GROUNDS VERSUS SWITCHED COMMONS
BO6 BO7
SC BO8 BO9
BO1 BO2
SC BO3 BO4
BO5
SC BO6
Triacs (HPO-6701), NO Relays (HPO-6703),
or NC Relays (HPO-6705) on Output Override Boards
Internal TriacsInternal Triacs
BAC-93x1
BAC-90x1
MAINTENANCE
Switched Common (SC) output terminals are unconnected in the controller unless the jumper is removed and an appropriate relay/triac override output board is installed.
Use only the SC instead of Ground with the HPO-6701 triac and HPO-6703/6705 relays!
Use the SC terminal in the same output bank (individual terminal block) as its output terminal. The switched common terminals are isolated from the circuit grounds used for the universal output analog circuitry in controllers.
For samples of wiring to output devices, see Wiring on
page 4.
UO1
SC UO2 GND
UO3
SC UO4 GND
UO5
SC UO6 GND
No routine maintenance is required. Each component is designed for dependable, long-term reliability and performance. Careful installation will also ensure long-term reliability and performance.
IMPORTANT NOTICES
The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice.
KMC Controls, Inc. makes no representations or warranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct, or incidental, arising out of or related to the use of this document.
The KMC logo is a registered trademark of KMC Controls, Inc. All rights reserved.