KMC Controls HPO-5074 User Manual

CEP/MEP-4xxxV Actuator Quick-Mount Valve Adapter
Installation Guide

Assembly

NOTE: If a VFB-4____BC is ordered, this kit is
already installed on the valve body— proceed to Actuator Mounting section on the next page!
NOTE: Only CEP-4703V and MEP-4xxxV actuators
can be used with this adapter. They have
an aached handle and shaft as well as a plastic mounting bracket on the boom of the actuator.
Beaded Tie
12 mm Screws
(VFB-4303_SX Bodies
and VEB-4303_SDL Valves)
Locking
Bail/Clip
HPO-5074
15 mm Screws
(VFB-4____BX Bodies
NOTE: See the relevant MEP-4xxx series data sheet
for valve date code and actuator replace­ment information.
1. Assemble the kit (as shown in Illustrations 1 through 4) to the valve body by installing the two appropriate screws from the kit through the adapter’s valve base into the two holes of the valve body. Be sure the valve base, the yellow
high-pressure indicator (if present), and the “T” or “—” engraved in the valve stem are all oriented properly as shown in Illustration 2 and 3! Two-way valve bodies should be full open, and three-way bodies should be positioned for
A-AB ow.
NOTE: The two shorter machine screws with the
Philips heads are for the (VSI) steam­rated valve bodies (VFB-4303_SX or VEB-4303_SDL valves). The two longer machine screws with the hex heads are for the regular (Griswold) valve bodies (VFB­4____BX or VEB-4____B__ valves).
NOTE: If desired for space reasons, the valve base
can be installed at a 90° degree angle by removing the two existing screws in the valve body and reinstalling them in the positions 90° from the original position. After assembly, the actuator will be at a 90° angle from the pipe.
2. To prevent the locking bail/clip from being lost in future use, aach the beaded tie around the valve bonnet and aach the other end in the hole of the bail.
3. See the Actuator Mounting section for mounting the actuator on the assembled valve body.
Valve Base
Illustration 1—HPO-5074 Adapter Parts
Stem “T
Screws
Flow Indicator
Illustration 2—Valve Body and Base Orientation (Griswold)
Illustration 3—Valve Body and Base Orientation (VSI)
Stem “T”
for 2-way
Screws
Flow Indicator
High
Pressure
Indicator
Ports Indicators
Stem “—”
for 3-way
T
HPO-5074 1 Installation Guide

Actuator Mounting

Valve Base
High
Pressure
Indicator
(Not on VSI
Valves)
Illustration 6—Assembled Valve
Stem “T” Indicator
Illustration 4—MEP-4002V and Assembled Valve Body
1. On the actuator, push and hold the manual release lever (at the rear of the actuator) and rotate the actuator to the full counter-clockwise position so that the handle is pointing out in a straight line from the actuator. See Illustrations 4 and 6.
2. The valve stem must be oriented as shown in Illustration 2 or 3. If necessary, use a needle-nose pliers to carefully reposition it.
3. Push the actuator onto the valve stem until it is fully seated.
4. Insert the bail all the way into the two holes until it clicks in position and locks the assembly. See Illustration 5.
5. Push and hold the manual release buon and verify operation of the assembled valve.
NOTE: For more information, see the relevant
data sheet and installation guide for the CEP-4703/4703V, MEP-4000/4800, MEP­4200/4500/4900 series actuators and the VEB-43 and VEB-46 series valves!

Cross-Reference

Typical
Application
KMC Valve
Body
KMC Valve
Valve
Solutions
(VSI)
Griswold UR3 Series UR2 Series SPV Series
Delta Control
Products
Honeywell VBN3 Series VBN2 Series
Siemens 599 Series 599 Series
*VFB-4___BC valve bodies come with the HPO-5074 installed.
3-way H/C
Water
VFB-46__BX,
VFB-46__BC*
VEB-
46___B__
UR3 Series UR2 Series SPV Series
ST Series ST Series ATI Series
2-way H/C
Water
VFB-43__BX,
VFB-43__BC*
VEB-
43___B__
2-way PIC-V
H/C Water
N/A
N/A

Important Notices

The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this docu­ment. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related
Illustration 5—Locking the Assembled Valve

Maintenance

No routine maintenance is required. Each compo­nent is designed for dependable, long-term reliabil­ity, and performance. Careful installation will also ensure long-term reliability and performance.
HPO-5074 2 Installation Guide
© 2014 KMC Controls, Inc. 050-019-72B
to the use of this document.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com; info@kmccontrols.com
Loading...