KMC Controls FlexStat BAC-1xx63 Series Installation Manual

FlexStat™ BACnet Programmable Thermostats
BAC-1xx63 Series (6 Relays, 3 Analog Outputs)
Installation Guide (6/3 Outputs)

MountingQuick Start

The KMC FlexStat series of intelligent temperature/ humidity-sensing, wall-mounted, thermostat/ controllers are native BACnet Advanced Application Controllers (B-AAC) for use in a BACnet system. The FlexStat simplies networked zone control for common packaged HVAC equipment by including an on-board library of programs that permits rapid conguration of a wide range of HVAC control applications.
To use the FlexStat:
1. Mount and wire the unit (see this Installation Guide).
NOTE: This document gives basic mounting,
wiring, and setup information only. For conguration, programming, operation, and other information, see the KMC Controls web site (www.kmccontrols.com) for the latest documents and rmware. For installation instructions of FlexStats with output congurations other than 6 relays and 3 analog outputs, see that model’s respective installation guide.
2. Congure/program the unit (see the FlexStat
Operation and Application Guides).
3. If necessary, troubleshoot any issues (see the FlexStat Operation Guide).
4. Operate the unit (see the FlexStat Operation Guide).
1.125" (29)
Dimensions in inches (millimeters)
For optimum temperature sensor performance, the FlexStat must be mounted on an interior wall and away from heat sources, sunlight, windows, air vents, and air circulation obstructions (e.g., curtains, furniture). (See the Application Guide for
more information.)
Additionally, for a model with an occupancy sen­sor option, be sure to install it where it will have unobstructed view of the most typical trac area
(see the Application Guide for more information).
If replacing an existing thermostat, label wires as needed for reference when removing the existing thermostat.
1. Complete rough-in wiring at each location prior to thermostat installation. Cable insulation must meet local building codes.
2. Turn the hex screws in the boom and top of
the FlexStat clockwise until they clear the cover. (See Illustration 1.) Pull the cover away from the backplate (mounting base).
3. Route the wiring through the backplate.
4. With the embossed UP toward the ceiling, fasten
the backplate directly to a vertical 2 x 4 inch wall handy-box. (For horizontal or 4 x 4 applications, use the HMO-10000 wall mounting plate.)
5. Make the appropriate connections to the terminal
blocks. (See the Connections and Wiring section.)
6. Place the FlexStat cover over the backplate while
being careful not to pinch or dislodge any wiring. Back the hex screws (counterclockwise)
out of the brackets until they engage the FlexStat cover and hold it in place.
5.551" (141)
4.192" (106)
EIA-485 data
port for quick
network access
Terminal blocks
on backplate for
easy wiring
Cover hex screws
CAUTION
To prevent mounting screw heads from touching the circuit board in the thermostat, use only the mounting screws supplied by KMC Controls. Using screws other than the type supplied may damage the FlexStat.
NOTE: This document is for 6 relay and 3 analog
output BAC-1xx63 series only. See other in-
Illustration 1—Dimensions and Connections
BAC-1xx63 Series (6 Relays, 3 Analog Outputs) 1 Installation Guide
stallation guides for the proper FlexStat series.

Connections and Wiring

Wiring Considerations

• Because of the many connections (power, network, inputs, outputs, and their respective grounds or switched commons), be sure wiring is well planned before installation of conduit!
• To prevent excessive voltage drop, use a conduc-
tor size that is adequate for the wiring length! Allow plenty of “cushion” to allow for tran­sient peaks during startup.
• Make sure that conduit for all wiring has ad­equate diameter for all necessary wiring. Using 1-inch conduit and junction boxes is recommend­ed! Use external junction boxes above the ceiling or in another convenient location as needed to make connections that run to the FlexStat’s junction box.
• Using multiple conductor wires for all inputs (e.g., six conductor) and outputs (e.g., 12 conduc­tor) is recommended. Grounds for all the inputs can be combined on one wire.
CAUTION
To avoid damage from ground loops and other communication issues in networked FlexStats, correct phasing on MS/TP network and power connections on ALL the networked controllers is critically important.

MS/TP EOL (End-Of-Line) Termination

The controllers/thermostats on the physical ends of the EIA-485 wiring segment must have end-of-line termination installed for proper network operation. (See Illustrations 2 and 3.) If a FlexStat is at the physi­cal end of the MS/TP network line, set both the EOL termination switches (1 and 2) to On (to the right) on the back of the circuit board. If not on the end, ensure that both switches are O (le).
   
Illustration 2—MS/TP Network End-Of-Line Termination
Pushed Left Pushed Right
OFF
10K
EOL =
1 2
IN3 =
0-12 V
5 6
ON
1 2
1 2
5 6
3 4
5 6
7 8
10K
10K
IN4 =
0-12 V
3 4
IN2 =
0-12 V
7 8
3 4
7 8

MS/TP Wiring

Connect the –A terminals in parallel with all other –A terminals on the network and the +B terminals in paral- lel with all other +B terminals. (See Illustrations 2 and
4.) Connect the shields of the cable (Belden cable #82760
or equivalent) together at each device. Use a wire nut or the S terminal in KMC BACnet controllers. (FlexStats, however, do not have an S terminal.) Connect the cable shield to a good earth ground at one end only.
NOTE: The S terminal in KMC controllers is
provided as a connecting point for the shield. The terminal is not connected to the ground of the controller. When connecting to controllers from other manufacturers, verify the shield connection is not connected to the controller’s ground.
For more information on principles and good practic­es when connecting an MS/TP network, see Planning BACnet Networks (Application Note AN0404A).
Illustration 3—EOL and Pull-Up Switch Resistor Positions
NOTE: IN1 is the room temp.
sensor AI1
NOTE: SC = Switched
(Relay) Common
BACnet MS/TP Network
Inputs
(Wiring Inputs and Outputs Dependent on Application)
Common/–/C
24 VAC
Illustration 4—(BAC-1xx63C) Terminals and Connections
Phase/ /R
+B
–A
IN4
IN3
GND
IN2
(Wiring Cutout in Backplate)
Outputs
Analog 9
GND 7–9
Analog 8
Analog 7
Relay 6
SC 4–6
Relay 5
Relay 4
Relay 3
SC 1–3
Relay 2
Relay 1
BAC-1xx63 Series (6 Relays, 3 Analog Outputs) 2 Installation Guide

Input Connections

Output Connections

Passive input devices require pull-up resistors in the circuit. For passive input devices (e.g., switch contacts and Type III 10K ohm thermistors) on IN2 through IN4, set the pull-up switches on the back of the circuit board to the 10K position. For active voltage devices, set the switches to the 0–12 VDC position. (See Illustrations 3 and 4.)
NOTE: Unlike the EOL switch pairs (1-2), the
INPUT switch pairs (3-4, 5-6, and 7-8) must NOT have both switches set to the le or both set to the right—if switch 3 is
set to the le, for example, switch 4 must be set to the right (or vice versa). ALL the
input pull-up resistor switch pairs must be fully latched in either 10K Ohm or 0–12 VDC positions even if a switch pair has no input connected! A single incorrect
switch position may cause errors in mul­tiple inputs.
NOTE: For more information on wiring specic
applications (AHU, FCU, HPU, RTU), see the Applications section starting on page
4. (These applications are the packaged
programs selectable from the Advanced > Application menu in the BAC-1xx63C mod­els.) See also the FlexStat Application Guide on www.kmccontrols.com.
NOTE: FlexStat inputs do not support 1K ohm
RTDs. To use a 4–20 current loop input or map analog inputs as binary values, see the FlexStat Application Guide.
Connect the device under control between the desired output terminal and the related SC (Switched Com- mon for relays) or GND (Ground for analog outputs) terminal. (See Illustration 4). For the bank of three relays, there is one Switched (relay) Common connec­tion (in place of the GND terminal used with analog outputs). (See Illustration 5).
One Switched Common Connection Per Bank of Three Normally Open Relays
Illustration 5—Switched (Relay) Common and Relays
Relay 3 (or 6)
SC 1–3 (or 4–6)
Relay 2 (or 5)
Relay 1 (or 4)
Do not aach a device that draws current exceeding the FlexStat’s output capacity:
• Maximum output current for individual ANA­LOG outputs (7–9) is 20 mA @ 12 VDC (each).
• Max. output current is 1 A for individual RELAYS @ 24 VAC/VDC or a total of 1.5 A per bank of 3 relays (relays 1–3 and 4–6).
For example, KMC REE-3111/3112 relays could be connected to the analog outputs, but REE-
3211/3221/3213 relays would exceed the FlexStat’s analog output capacity (although the REE-3211 can
be used with the FlexStat’s internal relays 1–6 as shown in the following applications pages).
FlexStat relays 1–6 are NO, SPST (Form “A”). (To emulate binary outputs with the analog outputs, set the output voltage to be either 0 or 12 VDC in Control
Basic.)
CAUTION
Relays are for Class-2 voltages (24 VAC) only. Do not connect line voltage to the relays!
CAUTION
Do not mistakenly connect 24 VAC to an analog output ground. This is not the same as a relay’s switched common. See the backplate’s terminal label for the correct terminal.
BAC-1xx63 Series (6 Relays, 3 Analog Outputs) 3 Installation Guide
Loading...
+ 6 hidden pages