KMC Controls FlexStat BAC-12xx36 Series, FlexStat BAC-13xx36 Series, FlexStat BAC-14xx36 Series Installation Manual

BAC-12xx36/13xx36/14xx36 Series FlexStat
3 Relays, 6 Analog Outputs, 6 External Inputs
Installation Guide (3/6 Outputs)
MountingQuick Start
CAUTION
This document is for 3-relay, 6-analog-output, 6-external-input BAC-12xx36/13xx36/14xx36 series
only. THESE MODELS ARE NOT COMPATIBLE
WITH THE BACKPLATES OF OLDER BAC-10000 SERIES FLEXSTATS (WITH ONLY 3 EXTERNAL INPUTS)! If replacing an older 3-input FlexStat,
replace the backplate as well. See other installation guides for other models.
To select and use a FlexStat in an application:
1. Select the appropriate model for the intended application and options (see the FlexStat Data
Sheet).
2. Mount and wire the unit (see this Installation Guide).
3. Congure/program the unit (see the FlexStat
Operation and Application Guides).
4. If necessary, troubleshoot any issues (see the
FlexStat Operation Guide).
5. Operate the unit (see the FlexStat Operation
Guide).
NOTE: This document gives basic mounting,
wiring, and setup information only. For
conguration, programming, operation,
and other information, see the KMC Controls web site for the latest documents.
Models
BAC-12xxxx (shown) 1.125 (29)
BAC-13xxxx/14xxxx 1.437 (36.5) 5.192 (132)
A
Dimensions in Inches (mm)
A B C
4.192 (106)
5.551 (141)
Embossed “UP” indicator
For optimum temperature sensor performance, the FlexStat must be mounted on an interior wall
and away from heat sources, sunlight, windows, air vents, and air circulation obstructions (e.g.,
curtains, furniture). Additionally, for a model with an occupancy sensor option, install it where it will
have unobstructed view of the most typical trac
area. (See the FlexStat Application Guide for more information.)
If replacing an existing thermostat, label wires as needed for reference when removing the existing thermostat.
1. Complete rough-in wiring at each location prior to thermostat installation. Cable insulation must meet local building codes.
CAUTION
To prevent mounting screw heads from touching the circuit board in the thermostat, use only the mounting screws supplied by KMC Controls. Using other screws may damage the FlexStat. Do not turn screws in farther than necessary to remove the cover.
2. If the cover is locked on the backplate, turn the
hex screws in the boom and top of the FlexStat
CLOCKWISE until they (just) clear the cover. (See Illustration 1.) Pull the cover away from the backplate (mounting base).
3. Route the wiring through the backplate.
4. With the embossed “UP” and arrows toward the
ceiling, fasten the backplate to a wall handy-box. BAC-12xxxx models mount directly on vertical 2 x 4 inch boxes, but they require an HMO-10000/ HMO-10000W wall mounting plate for horizontal or 4 x 4 boxes. BAC-13xxxx/14xxxx models mount directly on any of those types of boxes.
EIA-485 data
B
port (for quick
network access)
5. Make the appropriate connections to the terminal
blocks. (See Connections and Wiring on page 2.)
6. Place the FlexStat cover over the backplate while
Terminal blocks on
backplate (rotated on
BAC-13xxxx/14xxxx)
C
Illustration 1—Dimensions and Installation
BAC-12xx36/13xx36/14xx36 Series FlexStat 1 Installation Guide, Rev. E
Cover locking hex screws
being careful not to pinch or dislodge any wiring. Back the hex screws (counterclockwise)
out of the brackets until they engage the FlexStat cover and hold it in place.
Connections and Wiring
Wiring Considerations
• Because of the many connections (power, network, inputs, outputs, and their respective grounds or switched commons), be sure wiring is well planned before installation of conduit!
• Make sure that conduit for all wiring has ad­equate diameter for all necessary wiring. Using 1-inch conduit and junction boxes is recommend­ed! Use external junction boxes above the ceiling or in another convenient location as needed to make connections that run to the FlexStat’s junction box.
• To prevent excessive voltage drop, use a conduc-
tor size that is adequate for the wiring length!
Allow plenty of “cushion” to allow for tran-
sient peaks during startup.
• Using multiple conductor wires for all inputs (e.g., 8 conductor) and outputs (e.g., 12 conduc­tor) is recommended. Grounds for all the inputs can be combined on one wire.
CAUTION
To avoid damage from ground loops and other communication issues in networked FlexStats, correct phasing on MS/TP network and power connections on ALL the networked controllers is critically important.
Network Wiring
For Ethernet or IP communications, plug an Ethernet cable into the RJ-45 jack on the back of the FlexStat.
MS/TP EOL (End-Of-Line) Termination
The controllers/thermostats on the physical ends of an EIA-485 wiring segment must have end-of-line termination installed for proper network operation. (See Illustrations 2 through 4.) If a FlexStat is at the physical end of the MS/TP network line, set both the EOL termination switches to On (to the right/up) on the back of the circuit board. If not on the end,
ensure that both switches are O (left/down).
   
Illustration 2—MS/TP Network End-Of-Line Termination
Input Pull-Up Switches
EOL Switches
OFF
ON
NOTE: EOL = End Of Line of BACnet MS/TP network.
NOTE: 10K inputs are configurable for Type II or Type III thermistors in FlexStat’s menu.
Left
0-12 V
Switch
Pushed
Right
IN9
IN8
IN7
IN4
IN3
IN2
10K
Switch
Pushed
Illustration 3—BAC-12xxxx EOL/Pull-Up Switch Positions
For MS/TP communications, connect the –A termi­nals in parallel with all other –A terminals on the network and the +B terminals in parallel with all other +B terminals. (See Illustrations 2 and 5.) Con­nect the shields of the cable (Belden cable #82760 or equivalent) together at each device. Use a wire nut or the S terminal in KMC BACnet controllers. (FlexStats, however, do not have an S terminal.) Connect the cable shield to a good earth ground at one end only.
NOTE: The S terminal in KMC controllers is
provided as a connecting point for the shield. The terminal is not connected to the ground of the controller. When connecting to controllers from other manufacturers, verify the shield connection is not connected to the controller’s ground.
For more information on principles and good practic­es when connecting an MS/TP network, see Planning
BACnet Networks (Application Note AN0404A).
BAC-12xx36/13xx36/14xx36 Series FlexStat 2 Installation Guide, Rev. E
ON
Switch Pushed Up
OFF
EOL
Switches
Illustration 4—BAC-13xxxx/14xxxx Switch Positions
Pushed Down
IN2 IN3 IN4 IN7 IN8
Input Pull-Up Switches
0-12 VDC
10K Ohm
IN9
CAUTION
This document is for 3-relay, 6-analog-output, 6-external-input BAC-12xx36/13xx36/14xx36 series ONLY. THESE MODELS ARE NOT COMPATIBLE WITH THE BACKPLATES OF OLDER BAC-10000 SERIES FLEXSTATS (WITH ONLY 3 EXTERNAL INPUTS)! If replacing an older 3-input FlexStat, replace the backplate as well.
NOTE: SC = Switched
(relay) Common
NOTE: IN1 and IN5–6 are
reserved for internal sensors
Inputs
(Wiring is dependent on application)
MS/TP Network
Inputs
24 VAC
Illustration 5—(BAC-12xx36) Terminals and Connections
Common/–/C
Phase/ /R
IN9
IN8
GND
IN7
+B
–A
IN4
IN3
GND
IN2
(Wiring Cutout in Backplate)
IP/Ethernet
Network
(Optional)
Outputs
Analog 9
GND 7–9
Analog 8
Analog 7
Analog 6
GND 4–6
Analog 5
Analog 4
Relay 3
SC 1–3
Relay 2
Relay 1
NOTE: On BAC-13xxxx/14xxxx models, terminals
are rotated 90° CCW.
Input Connections
Passive input devices require pull-up resistors in the circuit. For passive input devices (e.g., switch con­tacts and 10K ohm thermistors) on IN2 through IN4 and IN7 through IN9, set the pull-up switches on the back of the circuit board to the 10K position. For
active voltage devices, set the switches to the 0–12 VDC position. (See Illustrations 3 through 5.)
NOTE: Unlike the EOL switch pairs, the INPUT
switch pairs must NOT have both switch-
es set to the same direction—if one of the pair’s switches is set to the left, for example, the other must be set to the right (or vice versa). ALL the input pull-up resistor
switch pairs must be fully latched in ei­ther 10K Ohm or 0–12 VDC position even
if a switch pair has no input connected! A single incorrect switch position may cause errors in multiple inputs.
NOTE: To use a 4–20 current loop input or map
analog inputs as binary values, see the
FlexStat Application Guide.
NOTE: To use a remote SAE-10xx CO
sensor, see
2
the FlexStat Operation Guide.
NOTE: For more information on wiring specic
applications (AHU and FCU), see Appli-
cations on page 5. (These applications
are the packaged programs selectable from the Advanced > Application menu in the BAC-1xxx36 models.) See also the FlexStat
Application Guide.
CAUTION
Relays are for Class-2 voltages (24 VAC) only. Do not connect line voltage to the relays!
CAUTION
Do not mistakenly connect 24 VAC to an analog output ground. This is not the same as a relay’s switched common. See the backplate’s terminal label for the correct terminal.
Output Connections
Connect the device under control between the desired output terminal and the related SC (Switched Com- mon for relays) or GND (Ground for analog outputs) terminal. (See Illustration 5). For the bank of three relays, there is one Switched (relay) Common connec­tion (in place of the GND terminal used with analog outputs). (See Illustration 6.) For the relay circuit, the
phase side of the AC should be connected to the SC terminal.
One Switched Common Connection in Bank of Three Normally Open Relays
Relay 3
SC (Phase) 1–3
Relay 2
Relay 1
NOTE: Type II or III 10K ohm thermistors can be
selected by changing the menu seing in
Advanced > Inputs > Input # > Sensor (see
Conguration on page 4). If a remote
space temperature sensor is connected to
AI7, space temperature can be congured
for onboard, remote, averaging of the two, the lowest reading, or the highest reading.
NOTE: FlexStat inputs do not support 1K ohm
RTDs.
BAC-12xx36/13xx36/14xx36 Series FlexStat 3 Installation Guide, Rev. E
Illustration 6—Switched (Relay) Common and Relays
Do not aach a device that draws current exceeding
the FlexStat’s output capacity:
• Maximum output current for individual ANA­LOG outputs (4–9) is 20 mA @ 12 VDC (each).
Max. output current is 1 A for individual RELAYS @ 24 VAC/VDC or a total of 1.5 A for relays 1–3.
For example, (discontinued) KMC REE-3211 relays would exceed the FlexStat’s analog output capacity, but they can be used with the FlexStat’s internal relays 1–3 as shown in the following applications pages. (Use a Core Components CVR11C-0/LD96200 in the REE-3211’s place in those applications.)
FlexStat relays 1–3 are NO, SPST (Form “A”). (To emulate binary outputs with the analog outputs, set the output voltage to be either 0 or 12 VDC in Control Basic.)
NOTE: Applications on pages 5–11 are the
packaged programs selectable from the Advanced > Application menu in the BAC-1xxx36 (only) models. Other FlexStat models have other applications.
NOTE: Humidity, motion, and CO
sensor options
2
in menus are dependent on the FlexStat model and selected application.
For detailed conguration, operation, troubleshoot- ing, and other information, see the FlexStat Opera-
tion Guide.
Power Connection
The FlexStat requires an external, 24 volt, AC power source. Use a KMC Controls Class-2 transformer to supply power. Connect the transformer’s neutral lead to the 24 VAC Common/–/C terminal and the AC phase lead to the 24 VAC Phase/~/R terminal. (See Illustration 5.) Power is applied to the FlexStat when the transformer is powered.
KMC Controls recommends powering only one con­troller/thermostat from each transformer. If installing a FlexStat in a system with other controllers/thermo­stats powered from a single transformer, however, phasing must be correct and the total power drawn from the transformer must not exceed its rating.
Configuration
To congure the FlexStat, navigate the menus and change seings by pressing a combination of buons.
Press the Right (Menu) buon and then the:
Enter buon to select and/or exit value editing.
Up/Down buon to move among entries (up/ down lines).
Left/Right buon to move among value elds (left/right spaces).
Left buon to return to the Home screen.
MAIN MENU ABOUT
ADVANCED
ALARM DATE/TIME SCHEDULE SETPOINTS SYSTEM
Illustration 7—Configuration Screens
ADVANCED
APPLICATION
CB PROGRAMS COMMUNICATION DATE/TIME DEVICE INPUTS LIMITS
(See
menus
on the
following
pages)
For additional wiring, customization, program­ming, and application information, see the FlexStat
Application Guide.
Applications Notes and Cautions
CAUTION
Relays are for Class-2 voltages (24 VAC) only. Do not connect line voltage to the relays!
Do not mistakenly connect 24 VAC to an analog output ground.
NOTE: Although typical terminal code leers are
shown, check the schematics of your unit
for wiring details!
NOTE: These applications are for 3 relay and 6 ana-
log output BAC-12xx36/13xx36/14xx36 series only. See other installation guides for other models.
NOTE: CO2, humidity, and motion sensor options
are dependent on FlexStat model.
NOTE: For Bill of Materials listings of the various
accessories shown in the sample diagrams, see the FlexStat Application Guide.
NOTE: Since the KMC REE-3211 is discontin-
ued, use Core Components CVR11C-0/
LD96200 in its place. Do not use either with analog outputs! See Output Connec-
tions on page 3.
Maintenance
Remove dust as necessary from the holes in the top
and boom. Clean the display with a soft, damp
cloth and mild soap.
To maintain maximum sensitivity of the built-in
motion sensor, occasionally wipe dust or dirt o the lens—but do not use any uid on the sensor.
BAC-12xx36/13xx36/14xx36 Series FlexStat 4 Installation Guide, Rev. E
Loading...
+ 7 hidden pages