1. Complete rough-in wiring at each location prior
to the FlexStat’s installation. Cable insulation
must meet local building codes.
CAUTION
To prevent mounting screw heads from touching
the circuit board in the thermostat, use only the
mounting screws supplied by KMC Controls.
Using other screws may damage the FlexStat.
Do not turn screws in farther than necessary to
remove the cover.
2. If the cover is locked on the backplate, turn the
hex screws in the boom and top of the FlexStat
CLOCKWISE until they (just) clear the cover.
(See Illustration 1.) Pull the cover away from the
backplate (mounting base).
3. Route the wiring through the backplate.
4. With the embossed “UP” and arrows toward the
ceiling, fasten the backplate to a wall electrical
box. This FlexStat mounts directly on vertical 2 x
4 inch boxes but requires an HMO-10000W wall
mounting plate for horizontal or 4 x 4 boxes.
5. Make connections to the terminal blocks. (See
Connections and Wiring on page 5.)
6. Push the FlexStat cover over the backplate while
being careful not to pinch or dislodge any
wiring. Back the hex screws (counterclockwise)
out of the brackets until they engage the FlexStat
cover and hold it in place.
IF BOTH RC AND RH TERMINALS ARE PRESENT:
WIRE RC TO SC 1-3 AND RH TO SC 4-6.
IF ONLY ONE “R” TERMINAL IS PRESENT:
WIRE BOTH SC 1-3 AND SC 4-6 TO R.
NOTE: Althoughtypicalterminalcodeleersare
shown, check the schematics of your unit
for wiring details!
APPLICATION
DEGREES SCALE: °F
APP:
ROOF TOP
OPT: 1H/1C
ADDITIONAL SETUP
ZONE
Input
Terminals
IN9Static Pressure Feedback (Optional)AI9
IN8(Unused in this application)AI8
IN7(Unused in this application)AI7
IN4(Unused in this application)AI4
IN3(Unused in this application)AI3
GNDGround
IN2DAT *AI2
*NOTE: The DAT sensor is congured for IN2 in the ADVANCED >
APPLICATION > ADDITIONAL SETUP > SENSORS menu.
Output
Terminals
Typical
Terminal
Codes
RTU Input Connections
RTU Output Connections
(1 or 2 H and 1 or 2 C)
BACnet
Objects
BACnet
Objects
Analog 9O. A. Damper (Optional)AO9
Ground
Optional Network
From
Previous
Network
Device
To
Next
Network
Device
RTU
Terminals
GND
Analog 8Heat or Cool Valve (Optional)AO8
Analog 7Static Pressure Setpoint (Optional)AO7
Relay 6O. A. Damper (Optional)BO6
SC 4–6RH/R24 VAC (for Relay terminals 4–6)
Relay 5W2Heat 2 (Optional)BO5
Relay 4W1Heat 1BO4
Relay 3Y2Cool 2 (Optional)BO3
SC 1–3RC/R24 VAC (for Relay terminals 1–3)
Relay 2Y1Cool 1BO2
Relay 1GFanBO1
NOTE: Connections above are for rmware R2.0.0.4 and later. Earlier
rmware had the optional static pressure setpoint on Analog Output
9 instead of Analog Output 7, and it did not have the heating/cooling
coil valve option (Analog Output 8) or outside air damper (economizer)
option (Analog Output 9 or Relay 6).
(for Analog Output terminals 7–9)
Illustration 3—RTU Application Connections
BAC-120063CW-ZEC FlexStat 3 Installation and Configuration Guide, Rev. G
Heat Pump Unit (HPU)
1 or 2 Compressors with Auxiliary and Emergency Heat
reversing valve is energized in
cooling mode; wire to “B”
terminal if reversing valve is
energized in heating mode.
HPU
Terminals
From
Previous
Network
Device
Optional Network
To
Next
Network
Device
Illustration 4—HPU Application Connections
CAUTION
Relays are for Class-2 voltages (24 VAC) only. Do not
connect line voltage to the relays!
Do not mistakenly connect 24 VAC to an analog
output ground.
NOTE: Althoughtypicalterminalcodeleersare
shown, check the schematics of your unit
for wiring details!
APPLICATION
DEGREES SCALE: °F
APP:
HEAT PUMP
OPT: 1 STAGE
ADDITIONAL SETUP
ZONE
Input
Terminals
HPU Input Connections
IN9Static Pressure Feedback (Optional)AI9
IN8(Unused in this application)AI8
IN7(Unused in this application)AI7
IN4(Unused in this application)AI4
IN3(Unused in this application)AI3
GNDGround
IN2DAT *AI2
*NOTE: The DAT sensor is congured for IN2 in the ADVANCED >
APPLICATION > ADDITIONAL SETUP > SENSORS menu.
Output
Terminals
Typical
Terminal
Codes
HPU Output Connections
Analog 9O. A. Damper (Optional)AO9
GND
(for Analog Output terminals 7–9)
Ground
Analog 8Heat or Cool Valve (Optional)AO8
Analog 7Static Pressure Setpoint (Optional)AO7
Relay 6W2/EEmergency Heat (Optional)BO6
SC 4–6R24 VAC (for Relay terminals 4–6)
Relay 5WAuxiliary Heat (Optional)BO5
Relay 4Y2Compressor 2 (Optional)BO4
Relay 3Y1Compressor 1BO3
SC 1–3R24 VAC (for relay terminals 1–3)
Relay 2O/B
Reversing Valve
(see O/B Note in schematic)
Relay 1GFanBO1
NOTE: Connections above are for rmware R2.0.0.4 and later. Earlier
rmware had the optional static pressure setpoint on Analog Output
9 instead of Analog Output 7, and it did not have the heating/cooling
coil valve option (Analog Output 8) or outside air damper (economizer)
option (Analog Output 9).
BACnet
Objects
BACnet
Objects
BO2
BAC-120063CW-ZEC FlexStat 4 Installation and Configuration Guide, Rev. G
Loading...
+ 8 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.