KMC Controls FlexStat BAC-10000 Series Operation Manual

Page 1
FlexStat™ BACnet Programmable Thermostats
Operation Guide
BAC-10000 Series
Contents
Overview ................................................................2
Home, Main Menu, and Override Screens Navigation Main Menu and Settings Room Temp. Setpoint Adjustment H/C, Fan, Occupancy, and Override
Configuration (Initial Setup)
Main Menu Overview About the FlexStat Advanced Menu
(Advanced) Application Options (Advanced) CB (Control Basic) Programs (Advanced) BACnet Communications (Advanced) Date/Time (Advanced) BACnet Device Properties (Advanced) Inputs (Advanced) Temp. Setpoint Limits (Advanced) Motion Sensor (Advanced) Security Levels and Passwords (Advanced) Trend Logs
(Advanced) Test Alarms Date/Time Schedules Setpoints System Setup Trend Viewer
Resetting the FlexStat
Types of Reset Warm and Cold Starts Restore Factory
Network Connection
BAC-10000 Series 1 Operation Guide, Rev. J
............................................................... 11
BACnet MS/TP Network Communication
PC Data Port Connection
....................................................3
..........................................................3
............................................... 4
..................................................5
..............................................10
......................................................... 11
.......................................................... 12
...........................................................13
.....................................................13
.....................................................13
............................................14
....................................................14
.................................................15
............................................. 16
...................................2
..........3
...................................... 3
.......................3
................... 3
...................................4
.........................................4
...................... 5
.........6
..............7
..................................... 7
.............8
............................................8
.................... 8
...............................8
....... 9
................................... 10
....................................... 14
......16
...............................16
Specifications, design, and operation are subject to change without notice.
Troubleshooting ....................................................17
Alarm Issues
Alarm, (False) Fan Fail Alarm, (False) Low Limit (Freeze Stat) Alarm, (False) Space Temp. or Humidity
Communication Issues
Firmware Upgrade Fails KMD-5576 Communication Faulty MS/TP Network Communication Faulty
Cover and Display Issues
Cover Binds on Backplate Display Is Blank or Erratic Display Freezes (Buttons Have No Effect)
Custom Programming and Web Issues
Control Basic Programs Do Not Work Custom Web Graphics Do Not Work
Input, Sensor, and Value Issues
Input Values Are Outside the Expected Range Motion/Occupancy Sensor Does Not Work Temperature Reading Is Incorrect Temperature Setpoint Is Not Maintained
Output, Fan, and Relay Issues
Analog Output Does Not Work Fan Does Not Run Relay (Internal) Does Not Work Relay (External) Does Not Work
Wiring Issues Maintenance Firmware Upgrade Programming (Custom) Accessories Support Important Notices Reference
Index
.................................................................23
Acronyms and Abbreviations
Definitions of Terms
.....................................................................26
......................................................17
.................................... 17
............ 17
........17
......................................17
.................................17
................17
......... 17
................................... 18
..............................18
.............................. 18
...... 18
............... 18
............18
.............18
.......................... 19
19
...19
.................. 19
.......19
...........................20
...................... 20
..........................................20
.....................20
....................21
..................................................... 21
.........................................................22
................................................22
.........................................22
...........................................................22
................................................. 23
..............................................................24
............................. 24
..........................................25
Page 2
Overview
Applications and Installation
The KMC FlexStat series of intelligent temperature/ humidity/occupancy-sensing, wall-mounted, ther­mostat/controllers are native BACnet Advanced Application Controllers (B-AAC) for use in a BAC­net system. The FlexStat simplies networked zone control for common packaged HVAC equipment, such as packaged rooop units, fan coil units, heat pumps, and other similar applications. In addi­tion, applications such as pressure dependent VAV, terminal reheat, and medium-sized central station air handling equipment applications may also be ad­dressed through the on-board libraries of programs built into the devices.
The on-board library of programs permits rapid conguration of a wide range of HVAC control ap­plications.
The FlexStat series also provides the capability to customize the standard library of sequences using KMC’s BACstage programming tool. This enables a local authorized KMC installing contractor to adapt the standard library to the unique site needs and ap­plication specic requirements of a particular project.
Dimensions in
inches (mm)
1.125 (28.6)
4.192 (106)
5.551 (141)
Terminal Blocks
on Removable
Backplate for
Easy Wiring
Communication with
Other BACnet Devices
Optional
Temperature
Sensing
3 Analog
Inputs
for Other
Sensors or
Contacts
24 Volts AC
Power
Humidity
and
Motion
Sensing
Up to 9
Outputs
(Analog
and/or
Relays)
Quick (Temporary) Network/
Programming Access
Applications
• AHU
• FCU
• HPU
• RTU
1. Wire the FlexStat’s backplate to the desired equipment and set the FlexStat’s end-of-line and input pull-up resistor switches.
2. Select the relevant application and options from the (Advanced) Application submenu of the Advanced Menu and other appropriate menus.
3. Congure the FlexStat for the BACnet network. (See Network Connection on page 16.)
For general mounting and connection details, including network wiring, EOL termination, power connections, input/output connections, pull-up resistor switch seings, see the relevant model’s Installation Guide. For extended information about wiring and sequences for specic applications, see the BAC-10000 Series Application Guide.
EIA-485 Data Port for
Quick Network Access
BAC-10000 Series 2 Operation Guide, Rev. J
Page 3
Operation (Basic)
Home, Main Menu, and Override Screens
Home Screen
WED 11/19 3:20 PM
Setpoint
COOL:
OCC:
FAN:
HUM: 36% RH
Override Screens
FAN MODES
UNOCC:
OCC: AUTO
AUTO
Override
Navigation
Navigate the menus and change seings by press­ing a combination of various arrow buons and the Enter buon. Push the:
• Enter buon to select and/or exit value editing.
• Up or Down buon to move among entries.
• Right or Le buon to move among value elds.
• Le buon to return to the Home screen.
Up/Setpoint Button
Enter Button
Left/Override
Button
Right/Menu
Button
Configuration Screens
MAIN MENU
ABOUT
Menu
ADVANCED ALARM DATE/TIME SCHEDULE SETPOINTS SYSTEM
Room Temp. Setpoint Adjustment
From the Home (temperature display) screen, press the Up or Down arrow buon once to view the exist­ing setpoint.
To temporarily change the setpoint, press the Up or Down arrow buon repeatedly until the desired seing is displayed and press Enter. (If Enter is not pressed, the display will return to the Home screen aer about ve seconds and the new setpoint value will still be saved.) The new setpoint will hold until the next schedule change.
To permanently change the setpoint for occupied mode, go to the Setpoints section under the Main Menu. (In the Setpoints menu, heating/cooling set­points/setbacks and deadband can be changed with, if required, the correct password access. See Set-
points on page 13.)
Down/Setpoint Button
Main Menu and Settings
From the Home (temperature display) screen, press the Right arrow buon to enter the Main Menu. You may need to enter a password to change any seings.
NOTE: Access to the Main Menu, setpoint adjust,
and System/Occupancy/Fan override may require a password.
BAC-10000 Series 3 Operation Guide, Rev. J
H/C, Fan, Occupancy, and Override
When the fan is commanded to run, the animated “FAN” icon rotates (if programmed to). When the fan command stops, the fan icon is motionless.
The “OCC” icon shows a sun when in Occupied mode and a quarter moon when in Unoccupied mode.
HEAT or COOL will show (and be animated when there is an active command), depending on the cur­rent mode. This can also be turned OFF.
To override these modes from the Home (tempera-
ture display) screen, press the Le arrow buon. Press Up or Down to get to the desired line and then Enter (twice) to edit the mode seing. Press exit to Home.
Leto
Page 4
Configuration (Initial Setup)
NOTE: Menus shown in this document reect
rmware version R1.3.0.4 or later. Actual context-sensitive screens are dependent on rmware version, FlexStat model, and options selected.
NOTE: If appear at the top of the screen
(such as in the Main Menu), scroll up or down to see the rest of the menu’s o­screen choices.
Main Menu Overview
MAIN MENU
ABOUT
ADVANCED ALARM DATE/TIME SCHEDULE SETPOINTS SYSTEM
Navigate the menus and change seings by pressing a combination of buons. Press the:
• Enter buon to select and/or exit value editing.
• Up/Down buon to move among entries (up/
down lines).
• Le/Right buon to move among value elds
(le/right spaces).
About the FlexStat
ABOUT FLEXSTAT FW: R1.3.0.0 BUILT: DEC 11 2009 @13:55:07 ASV: BAC_1xx63 R1.3.0.0 +6 MODEL: BAC–11163C APP: AIR HANDLER OPT: MOD H / MOD C INSTANCE: 1
This display-only screen shows (scroll to see all):
• Firmware version (FW)
• Build date
• Application soware version (ASV)
• Model number
• Application conguration and options (set in the Application menu)
• Device instance (set in the Device menu)
• MAC address (set in the Communications menu)
• Serial number
• Board revision
NOTE: ASV will show CUSTOM if any built-in
Control Basic program (1–5) is not running or has auto-run disabled.
• Le buon to return to the Home screen.
NOTE: A log-in may be required to access menu
items.
SETPOINTS
SAVE CHANGE?
COOL SETPT:
HEAT SETPT: 67° F COOL SETBACK: 80° F
YES
NO
When prompted about a change (on any menu), press Right/Le to select the desired choice and then Enter.
BAC-10000 Series 4 Operation Guide, Rev. J
Page 5
Advanced Menu
ADVANCED
APPLICATION
CB PROGRAMS COMMUNICATION DATE/TIME DEVICE INPUTS LIMITS
The Advanced Menu displays various submenus. Not all submenus can be seen on the screen at one time. Scroll up or down to see additional submenus. To select the desired submenu, press:
1. Up/Down to move.
2. Enter to select.
NOTE: The Advanced Menu has more submenus
than can appear on the screen at once. Keep scrolling up or down to see all the options.
(Advanced) Application Options
APPLICATION DEGREES SCALE: °F
APP:
FAN COIL OPT: 4-PIPE ADDITIONAL SETUP
ADDITIONAL SETUP
DAMPER
FAN HUMIDITY SENSORS VALVE
Auxiliary Heat (Heat Pump Only)
AUX HEAT SETUP
AUX HEAT:
DELAY (MINS): 60
COMP LOCKOUT
Damper Setup
DAMPER SETUP
ECON:
MIN POSITION (%): 10 CNTRL (0–100%): 2–10 V ECON ENBLE TEMP: 55° F LOW LIMIT ALARM: 45° F
MODULATING
NOTE: If the Economizer option is selected when
there is no mixed air temperature sensor connected, a Low Limit Alarm will result. See Alarms on page 11.
Fan Setup
FAN SETUP
SPEEDS:
OFF DELAY (SECS): 180 UNOCC: AUTO OCC: AUTO
CONSTANT SPEED
NOTE: For a Fan Fail Alarm, see Sensor Setup on
page 6 and Alarms on page 11.
To change ° F or C, preprogrammed application type, and options, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
The type of application (as well as the model of FlexStat) aects the context-sensitive options under Additional Setup.
BAC-10000 Series 5 Operation Guide, Rev. J
Humidity Setup
HUMIDITY SETUP
DEHUMIDIFICATION
HUMIDIFICATION
DEHUMIDIFICATION
DEHUM:
ALLOW HTG DEHUM: NO DEHUM SETPT: 60%RH DEHUM DEADBAND: 5%RH
ENABLE
NOTE: If a dehumidication option is enabled, the
Space Humidity Alarm will also be enabled. See Alarms on page 11.
Page 6
Sensor Setup
(Advanced) CB (Control Basic) Programs
SENSOR SETUP
IN 2:
DISCH AIR TEMP
The Input 2 sensor (AI2) can be congured for discharge air temperature (Type III thermistor is the default), fan status (dry contact), or unused.
• If set for discharge air temperature, the sensor can be calibrated and changed from the default Type III thermistor to a Type II. See (Advanced)
Inputs on page 8.
• If set for discharge air temperature, Trend Log #2 is automatically created and monitors the discharge air temperature, but it has no eect on operation.
• If set for fan status and no closed contact is detected when there is a call for fan operation, a Fan Fail Alarm is created. See Alarms on page 11.
• If set for unused, built-in applications will not use AI2, but the input would be available to custom programming.
Staging Setup
STAGING
STG DELAY (MINS):
3
Valve Setup
VALVE SETUP
TYPE:
ACTION: NRM OPEN
2–POSITION
CB PROGRAMS
PROG1:
PROG2: RUNNING PROG3: RUNNING PROG4: RUNNING PROG5: RUNNING PROG6: HALTED PROG7: IDLE
RUNNING
PROGRAM #1 SETPOINTS & MODES AUTO-RUN: TRUE CHANGE: READY STATE: RUNNING HALT REASON: NORMAL HALT DESC: OUT OF SERVICE: FALSE
To halt or load/run the built-in (1–5) and custom (6–10) Control Basic programs, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
NOTE: If custom Control Basic programs are
installed and a restore to factory seings
is performed, all factory programs are restarted but all custom Control Basic programs are halted. Change the state
of each program by loading/running the program from the CB Programs menu (or BACstage).
NOTE: If custom Control Basic programs are
installed and set to autorun, whenever the
rmware is updated, ALL (factory and custom) programs are halted.
If custom Control Basic programs are
installed but NOT set to autorun,
whenever the rmware is updated, factory programs are restarted but any (manual) running custom programs are halted at restart.
Change the state of each custom program
by using the Update Manager or loading/ running each program from the CB Programs menu (or BACstage).
UPDATE MANAGER PROGRAM CONFIG ERROR
BAC-10000 Series 6 Operation Guide, Rev. J
ENABLE FACTORY:
ENABLE CUSTOM: NO EDIT CB PROGRAMS DONE
NO
NOTE: Customized programs are the responsibility
of the user. KMC Controls does not provide
support for such programs.
Page 7
(Advanced) BACnet Communications
Sample Time Zones Oset to Equal UTC
COMMUNICATIONS
MAC ADDRESS:
BAUD RATE: 38400 MAX MASTER: 127
1
To set parameters for BACnet MS/TP EIA-485 communications, press:
1. Up/Down to move among entries.
2. Enter to select.
NOTE: The Max Master is the highest MAC
address a device will aempt to locate when polling for master devices on the local network. To avoid possible communication issues with the network or a computer connected through a KMD­5576 USB Communicator, the Max Master
number should be the lowest number needed for that network.
(Advanced) Date/Time
DATE/TIME
DATE:
TIME: 1:43:59 PM UTC OFFSET: 300 DST ENABLE: TRUE DST AUTO: TRUE DST START: >2ND SUN MAR 2:00 AM
APRIL 11 2009
Alaska 9 hours = 540 minutes
USA/Canada Pacic
8 hours = 480 minutes
Standard Time
USA/Canada Mountain
7 hours = 420 minutes
Standard Time
USA/Canada Central
6 hours = 360 minutes
Standard Time
USA/Canada Eastern
5 hours = 300 minutes
Standard Time Bolivia, Chile 4 hours = 240 minutes Argentina, Uruguay 3 hours = 180 minutes
United Kingdom,
0 hours = 0 minutes
Portugal Europe (most countries) –1 hours = –60 minutes Egypt, Israel, Turkey –2 hours = –120 minutes Kuwait, Saudi Arabia –3 hours = –180 minutes United Arab Emirates –4 hours = –240 minutes India, Sri Lanka –5.5 hours = –330 minutes China, Mongolia –8 hours = –480 minutes Korea, Japan –9 hours = –540 minutes New Zealand –12 hours = –720 minutes
NOTE: The BACnet standard for this oset value
is: “The time zones to the west of the zero degree meridian shall be positive values, and those to the east shall be negative values.” The value is in minutes, not hours.
To enter date and time information, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
For areas that observe Daylight Saving Time, select True/On for DST ENABLE.
If the FlexStat is used in a BACnet network with UTC (Coordinated Universal Time) synchronization (via broadcasting or addressing a single thermostat) set the UTC Oset value. The UTC Oset value is in minutes and corresponds to the distance of the local time zone to the zero degree meridian. In stand-alone operation or networks that do not have UTC broad­casts, seing this value is not necessary.
BAC-10000 Series 7 Operation Guide, Rev. J
Page 8
(Advanced) BACnet Device Properties
(Advanced) Temp. Setpoint Limits
DEVICE
INSTANCE:
NAME: FlexStat_101 LOCATION: KMC Controls
RESTART: NO RESTORE FACTORY: NO
1
To set the BACnet device instance, name, and location, press:
1. Up/Down to move among entries.
2. Enter to select.
The FlexStat can also be restarted or restored to factory defaults from this menu. See Reseing the
FlexStat on page 14 for more information about that
function.
(Advanced) Inputs
INPUTS 1: SPACE TEMP
2:
DISCH AIR TEMP 3: MIXED AIR TEMP 4: OUTSIDE AIR TEMP 4: SPACE HUMIDITY
Inputs vary according to model, selected application, and selected application options. See (Advanced) Ap-
plication Options on page 5.
To change sensor type and calibration oset, press:
1. Up/Down to move among entries.
2. Enter to select.
INPUT #2 DISCH AIR TEMP VALUE: 60.0° F CAL. OFFSET: 0.0 OUT-OF-SERVICE: FALSE
SENSOR:
10K TYPE III
LIMITS
OCC MIN CLG:
OCC MAX HTG: 76° F UNOCC MIN CLG: 77° F UNOCC MAX HTG: 65° F
71° F
To set the minimum and maximum allowed user/ operator setpoint values, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
(Advanced) Motion Sensor
MOTION SENSOR
MOTION OCC:
STATE: OCCUPIED
In BAC-11xxx models, a motion/occupancy sensor may be enabled to trigger occupancy override. During scheduled “o” times, the motion sensor will start occupancy override (for 1 hour as a default) when it detects motion. Occupancy override will end (with the default seing) 1 hour aer motion was last detected. The length of occupancy override is congurable in the System menu. See System Setup
on page 13.
To enable/disable or monitor the motion/occupancy sensor (if installed), press:
ENABLE
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
Value will show a temperature reading or a voltage (0.0 to 3.0), depending on the sensor. Analog sensors can be calibrated using the Calibration Oset option.
BAC-10000 Series 8 Operation Guide, Rev. J
1. Enter to select.
2. Right/Le to move among value elds.
3. Up/Down to increment/decrement value.
The State eld monitors whether motion has been detected during the last scan of the motion sensor input (BI6). Detected motion will show an “occu­pied” state. This can be used during troubleshooting to determine if motion is being detected.
Page 9
(Advanced) Security Levels and Passwords
SECURITY
ACCESS LEVELS
PASSWORDS
ACCESS LEVELS
SETPOINT ADJ:
MAIN MENU: ADMIN SYSTEM MODE: OPER OCC OVERRIDE: USER FAN OCC/UNOCC: OPER
NONE
Access to the Main Menu, Setpoint Adjust, and System/Occupancy/Fan seings have a default password level of User. This level can be changed for each function to None, Operator, or Administrator through the Access Levels menu. Passwords are set in the Passwords menu.
Any person can view the display but might not be able to change any seings without logging in with one of the three levels of passwords:
• None (Level “0”): No password is required (everyone has access).
• User (Level 1): See the Menu Items Access Levels chart.
• Operator (Level 2): See the Menu Items Access Levels chart.
• Administrator (Level 3): Can access all menus and change all editable values. DO NOT
FORGET THIS PASSWORD!
NOTE: Seing a password to (the default) 0000
eliminates the password prompt and allows full access for that level. If no password is set for ADMIN, no password prompt will occur. If any password is set for ADMIN, the menu items accessible at the various levels are shown in the following chart.
NOTE: Changes in security levels and/or
passwords take eect when the current Administrator log-in has timed out. Log-
ins last until 60 seconds (default) aer the last buon press. Desired length of inactivity time-out can be changed in the Systems submenu.
NOTE: When seing a password, the Up buon
increases the alphanumeric value (0 through 9 and then A through Z). The
Down buon decreases the value. DO NOT FORGET THE ADMIN PASSWORD!
PASSWORDS
USER:
OPERATOR: ADMIN:
1 0 0 0 1 2 3 4 5 6 7 8
To enter an alphanumeric password at the prompt:
1. Up/Down to move.
2. Enter to select.
3. Up/Down to increment/decrement value.
The required password level is specied in the prompt.
For additional security and protection from vandalism, install the FlexStat inside a third-party locking thermostat guard/cover (but proper airow must be maintained).
Menu Items Access Levels
Menus User Operator Administrator
Home Screen * = Selectable, Default is User
Setpoint Adjust (Up/Down) x* x* x*
System Mode (Auto/Heat/Cool/Off) x* x* x*
Occupancy Override (On/Off) x* x* x*
Fan Modes (Auto/On/Off) x* x* x*
Main Menu* (Default is User)
About x x x
Advanced x x
Alarm x x
Date/Time x x
Schedule x x
Setpoints x x
System x x
Trend Viewer x x x
Advanced Menu
Application x
Additional Setup x
Control Basic Programs x x
Communication x
Date/Time x x
Device x
Inputs x x
Limits x x
Motion Sensor x x
Security x
Trend Logs x x
Test x x
This chart shows conditions in which an administrator password is set (is not 0000) and default password levels are used.
BAC-10000 Series 9 Operation Guide, Rev. J
Page 10
(Advanced) Trend Logs
(Advanced) Test
TREND LOGS
TREND 1:
TREND 2: TRUE TREND 3: FALSE TREND 4: FALSE TREND 5: FALSE TREND 6: FALSE TREND 7: FALSE
TRUE
TREND #1 SPACE TEMPERATURE LOG OBJECT REF: AI1 LOG ENABLE: TRUE INTERVAL (MINS): 10 STOP W/FULL: FALSE RESET COUNT: NO COUNT: 256 TOTAL CNT: 613
VIEW LOG BUFFER
TL #1–SPACE TEMP
APR17 1:27PM, 71.4
APR17 2:27PM, 71.5 APR17 3:27PM, 71.6 APR17 4:27PM, 71.8 APR17 5:27PM, 76.3 APR17 6:27PM, 81.2 APR17 7:27PM, 82.3
NOTE: Space temperature (AI1) is the default trend
log #1. If AI2 is congured for discharge air temperature, that will become the default trend log #2. See Sensor Setup on page 6.
To set the desired object to track, press:
1. Up/Down to move among entries.
TEST
LCD/KEY TEST
The test menu merely tests the display’s pixels and key functions.
1. Up/Down to move among entries.
2. Enter to select and exit.
2. Enter to select.
The trend log buer may be viewed by scrolling down and selecting View Log Buer. The buer may also be viewed from the Main Menu by scrolling down to the Trend Viewer (see page 13).
NOTE: The BACnet standard for log intervals
is hundredths of seconds. The simplied display on the FlexStat converts the value to minutes. However, BACstage™ and TotalControl® do display hundredths of seconds but in dierent ways. For a “10” (minute) interval on a FlexStat display, TotalControl would show “00:10:00.00” (hours:minutes:seconds.hundredths of seconds) and BACstage would show “60000” (hundredths of seconds) instead.
NOTE: If applicable to the model, the humidity
sensor is AI5 and the motion sensor is BI6, which can also be congured for trend
logs. See the BAC-10000 Series Application Guide (P/N 913-019-03) or relevant BAC­10000 Series Installation Guide for other desired input and output objects in an application.
BAC-10000 Series 10 Operation Guide, Rev. J
Page 11
Alarms
Date/Time
SAT 4/11 3:20 PM
COOL:
OCC:
FAN:
SERVICE HUM: 20%RH
ALARMS
* SPACE TEMP ALARM 04/11
04/11/09 08:37:56 <AI1> SPACETEMP PRESENT VALUE = 90.1 EXCEEDS HIGH_LIMIT <EE1> SPACETEMPALARM
DELETE ALARM?
YES
NO
A ashing “SERVICE” on the Home screen indicates an alarm. To view and delete alarms, press:
1. Right to move among elds.
2. Enter to select. (Enter on Alarm Details screen to
delete the alarm.)
3. Le to go back one page.
Built-in alarms are triggered under these conditions:
Space Temp Alarm—temperature outside the range of 56 to 86° F for over 300 seconds.
DATE/TIME
DATE:
TIME: 1:43:59 PM
APR 11 2009
To enter date and time information (only), press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
More options (such as UTC oset and daylight sav­ing time options) are available in the (Advanced)
Date/Time menu (see page 7).
Space Humidity Alarm—humidity above 65% for over 300 seconds. This is available only in FlexStat models with a humidity sensor and a dehumidication option selected in the Humid­ity setup). See Humidity Setup on page 5.
Fan Fail Alarm—no fan status signal within ve seconds of call for fan (and Input 2 is congured for the fan status sensor option). See Sensor Setup
on page 6.
Low Limit Alarm (freeze stat)—space temperature is below the adjustable (under Damper Setup) low limit alarm temp for one second (when congured for the economizer option). Aer a low limit alarm is generated,
the fan will not run until aer the FlexStat is restarted. See Restart under Reseing the
FlexStat on page 14. See also Damper Setup on page 5.
(Up to six additional alarms may be added with custom programming.)
NOTE: Time delays and limits can be modied in
the corresponding Event Enrollment objects using TotalControl.
BAC-10000 Series 11 Operation Guide, Rev. J
Page 12
Schedules
SCHEDULE
WEEKDAYS [MON–FRI]
WEEKEND [SAT–SUN] ENTIRE WEEK [MON–SUN] INDIVIDUAL DAYS HOLIDAYS
To select the desired schedule, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Le to go back one page.
WEEKDAYS
1:
7:30:00 AM ON
2: 5:15:00 PM OFF 3: 4: 5: 6: [—>] DELETES ENTRY
To enter weekly schedules for occupied (ON) and unoccupied (OFF) times, press:
HOLIDAYS
HOL1:
JAN 1 2009 HOL2: MAR 21 2009 HOL3: MAY 26 2009 HOL4: JULY 4 2009 HOL5: SEPT 1 2009 HOL6: NOV 27 2009 HOL7: NOV 28 2009
The Holiday entries will override the normal occupied weekly schedule entries and keep those days’ seings at their setback values. Setback values are entered in the Setpoints section of the Main Menu. (See also the maximum and minimum setpoint values in the Limits section of the Advanced Menu.)
To enter upcoming holidays, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
1. Right/Le to move among days and Enter to
select.
2. Up/Down to move among entries and Enter to select and edit.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
5. Enter to exit value editing.
6. Le to move back to days or back one page.
BAC-10000 Series 12 Operation Guide, Rev. J
Page 13
Setpoints
SETPOINTS
COOL SETPT:
HEAT SETPT: 67° F COOL SETBACK: 80° F HEAT SETBACK: 64° F MIN SETPT DIFF: 2° F DEADBAND: 2° F DEHUM SETPT: 60 % RH
In the Setpoints menu, deadband, setbacks, and setpoints for various values are set. (The room temperature setpoint can also be manually changed from the Home menu.)
To adjust the setpoints, press:
1. Up/Down to move among entries.
74° F
When Display Blanking is enabled (Y), the display turns o at the same time the backlight goes o (aer reset, initial power-up, or time-out). When any buon is pressed, the display will reappear until the time-out is reached again.
The menu/display/backlight time-out (seconds since the last buon is pushed) is set in Inactivity.
Access to the Main Menu, setpoint adjust, and System/Occupancy/Fan override have a default password level of User. This level can be changed for each function to None, Operator, or Administrator through this screen. Passwords are set in the (Ad­vanced) Passwords menu. See (Advanced) Security
Levels and Passwords on page 9.
2. Enter to select.
3. Up/Down to increment/decrement value.
System Setup
SYSTEM
SYSTEM ENABLE:
OCC OVRIDE (HRS): 1.0 INACTIVITY (SECS): 60 DISPLAY BLANKING: NO
To adjust the system conguration values, such as system enable (auto, o, heat, or cool), occupancy override time, and display inactivity time-out:
1. Up/Down to move among entries.
2. Enter to select.
3. Up/Down to increment/decrement value.
AUTO
Trend Viewer
TREND VIEWER
1:
SPACE TEMP 34 2: SPACE HUMIDITY 27 3: FAN 19 4: COOL 1 18 5: COOL 2 21 6: 7:
To view trend log buers, press:
1. Up/Down to move among entries.
2. Enter to select.
Trend logs are set up in the (Advanced) Trend Logs menus (see page 10).
TL #1 SPACE TEMP
APR11 1:27PM, 70.3
APR11 2:27PM, 71.3 APR11 3:27PM, 71.6 APR11 4:27PM, 71.8 APR11 5:27PM, 76.3 APR11 6:27PM, 81.2 APR11 7:27PM, 82.3
Occupancy Override on this menu is the amount of time (in hours) a manual change in the setpoint (via the Up and Down buons) will be allowed to over­ride the scheduled setpoint. When the time is set to
0, the override state will last until the next schedule change.
BAC-10000 Series 13 Operation Guide, Rev. J
Page 14
Resetting the FlexStat
Types of Reset
If the FlexStat is not operating correctly or if a low limit alarm has occurred, the FlexStat should be
reset (reinitialized). Any reset interrupts normal op­eration, and three types of reset exist:
• A warm start is generally the least disruptive op-
tion (restarting normal operation the quickest).
• If problems still persist, try a cold start. (This
should also be used aer a new Control Basic program is loaded and compiled.)
• If problems still persist (or major changes in a
rmware update have taken place) restoring fac- tory defaults (and reconguring and reprogram­ming the FlexStat) may be required.
Warm and Cold Starts
CAUTION
During a restart, the analog outputs go to zero, and relays go to their normally open state. A re­start is a process that lasts around ten seconds, and it may result in several changes of state for an output, turning equipment off and on abruptly. Before resetting the FlexStat, manually override equipment as needed. If a large fan is controlled by the FlexStat, for example, set a minimum off time. See Fan Setup on page 5 (built-in, selectable applications with compres­sors have a default programmed minimum off time of 300 seconds).
A warm start does the following in the FlexStat:
• Restarts the controller’s Control Basic programs.
• Leaves conguration and programming intact.
NOTE: Menu changes may take up to about two
minutes to write to nonvolatile Flash memory. If power to the FlexStat is lost during this time, changes may be lost.
Restarting the FlexStat from its menu, TotalControl, or BACstage are the recommended methods.
NOTE: When power is restored aer an outage,
the FlexStat will aempt to do a warm start as long as the values in RAM are retained (up to about four hours). If the the RAM checksum test fails, a cold start will be done instead. (In custom Control Basic programming, using the POWERLOSS command may be desirable to determine start-up conditions and to take appropriate actions—see the Help system in TotalControl or BACstage for more information.)
ADVANCED APPLICATION CB PROGRAMS COMMUNICATION DATE/TIME
DEVICE
LIMITS SECURITY
DEVICE INSTANCE: 1
NAME: FlexStat_101 LOCATION: KMC Controls
RESTART: RESTORE FACTORY: NO
WARM START
To perform a WARM start, do one of the following:
• (Aer zeroing out objects during the restart process) restores present values of objects to their last values before the restart (until they are
updated by the FlexStat’s programs).
• Restarts the controller’s Control Basic programs.
• Leaves conguration and programming intact.
CAUTION
If the checksum test in RAM fails during a warm start, a cold start is performed instead.
A cold start does the following in the FlexStat:
• (Aer zeroing out objects during the restart process) returns all object values to their relin­quished defaults (until they are updated by the
FlexStat’s programs).
BAC-10000 Series 14 Operation Guide, Rev. J
• From the FlexStat menu, select Advanced > De­vice > Restart > Warm Start.
• From TotalControl or BACstage, select Reinitial­ize Device > Warm Start.
• Momentarily remove power to the FlexStat.
To perform a COLD start, do one of the following:
• From the FlexStat menu, select Advanced > De­vice > Restart > Cold Start.
• From TotalControl or BACstage, select Reinitial­ize Device > Cold Start.
Page 15
Restore Factory
Restore Factory (restoring the FlexStat to the factory seings) does the following:
• Clears present values.
• Restores the object database/conguration to the defaults.
• Restarts the controller’s (factory installed) Con­trol Basic programs.
NOTE: The MAC address and device instance are
not restored to their original defaults, and custom Control Basic programs are not deleted. If custom Control Basic programs are installed, all factory programs are restarted
but all custom Control Basic programs are halted. Custom programs may be restarted by
loading/running the programs from the CB Programs menu. See (Advanced) CB (Control
Basic) Programs on page 6.
CAUTION
When returned to factory defaults, analog out­puts will go to zero and relays will go to their normally open state. Before restarting the ther­mostat, manually override equipment as needed.
CAUTION
After a return to factory defaults, applications are unconfigured. You must select the desired appli­cation and appropriate settings before connected equipment will operate properly. (See (Advanced)
Application Options on page 5.)
To restore the FlexStat to factory seings:
1. Select Restore Factory from the Advanced > De­vice menu.
2. When prompted for the required restart, press Enter. (To Cancel, press the right buon and then Enter or just let the display time-out).
3. Aer the FlexStat has restarted, review the set­tings and recongure as needed.
ADVANCED APPLICATION CB PROGRAMS COMMUNICATION DATE/TIME
DEVICE
LIMITS SECURITY
DEVICE INSTANCE: 1
NAME: FlexStat_101 LOCATION: KMC Controls
RESTART: NO RESTORE FACTORY:
RESTART REQUIRED!
YES
CANCELRESTART
BAC-10000 Series 15 Operation Guide, Rev. J
Page 16
Network Connection
BACnet MS/TP Network Communication
Connect the network wiring and set the EOL switch­es accordingly. (See the Installation Guide for wiring and end-of-line switch information.)
From the FlexStat menus, adjust the device instance number, the MAC address, and baud rate from the defaults as necessary. Set the Max Master to the minimum necessary for the network. See (Advanced)
BACnet Device Properties on page 8 and (Advanced) BACnet Communications on page 7.)
NOTE: The current FlexStat MAC address and
device instance numbers can be viewed in the About menu. Each BACnet device on a network must have a unique MAC address and device instance.
   
PC Data Port Connection
The FlexStat is equipped with a PC data port located at the boom of the thermostat housing. This port provides a temporary EIA-485 (formerly RS-485) connection to the digital network for network setup or troubleshooting.
To connect a computer to the port, a means of converting the EIA-485 signal to a USB or EIA-232 (formerly RS-232) signal will be needed. For USB, use a KMC KMD-5576 USB Communicator. For EIA-232, use a third-party interface. (See the instruc­tions included with those devices and soware.) To connect to the PC data port:
1. Connect the keyed, at end of the KMD-5624 interface cable (included with the KMD-5576) to the port on the boom of the FlexStat.
2. Connect the modular plug of the cable to the interface device that converts the EIA-485 signal from the FlexStat into a USB or EIA-232 signal.
3. Connect the suitable cable from the interface device to the computer’s serial or USB port. Install any required soware and congure the port as necessary.
NOTE: To avoid faulty communication with the
KMD-5576 USB Communicator, the Max Master number may need to be reduced to the minimum required for the network and the driver and latency seings on the computer may need to be checked or updated. See Troubleshooting on page 17.
KMD-5576
KMD-5624
Cable
BAC-10000 Series 16 Operation Guide, Rev. J
Page 17
Troubleshooting
Alarm Issues
Alarm, (False) Fan Fail
• Check conguration. Be sure the Fan Status option is not selected when there is no sensor/ switch for it.
• Check that the IN2 (fan status) input pull-up resistor switches are fully latched in the correct positions. Any passive, dry contact should use the 10K Ohm seing. (See the Connections and Wiring section of the relevant BAC-10000 Series Installation Guide.)
• Check IN2 (fan status) input wiring.
• Check the connected fan status sensor/switch.
• Using BACstage or TotalControl, check that AI2 (fan status) is not congured as “Out Of Service.”
Alarm, (False) Low Limit (Freeze Stat)
• Check the Low Limit Alarm seing—see Damper
Setup on page 5.
• Check conguration. Be sure the Economizer option is not selected when there is no mixed air temperature sensor.
• Check that the IN3 (mixed air temp.) input pull-up resistor switches are fully latched in the correct positions (see the Connections and Wiring section of the relevant BAC-10000 Series Installa­tion Guide).
• Check IN3 (mixed air temperature) input wiring.
• Check the connected mixed air temperature sensor.
• Using BACstage or TotalControl, check that AI3 (mixed air temp.) is not congured as “Out Of Service.”
NOTE: Aer a low limit alarm is generated, the
fan will not run until aer the FlexStat is restarted. See Reseing the FlexStat on
page 14.)
Alarm, (False) Space Temp. or Humidity
• See Alarms on page 11.
• See Temperature Reading Is Incorrect on page 19.
• See Temperature Setpoint Is Not Maintained on
page 19.
• Using TotalControl, adjust the limits or time delay.
Communication Issues
Firmware Upgrade Fails
• Ensure the WD (watch dog) jumper is temporar­ily removed during the upgrade process (see the KMD-5699 Installation Guide, P/N 913-019-04). Reinstall the pin on the le and center pins aer the upgrade process is complete.
• Check connections.
• Ensure rmware for the correct model is selected in the Firmware Upgrade Tool.
NOTE: If rmware for a wrong model is acciden-
tally installed, the outputs will not match the applications/conguration on the display.
NOTE: Backing up the existing seings and
rmware image before or during the upgrade process is good practice.
NOTE: Restoring to the factory defaults and
reconguring might be needed if how the FlexStat operates changes. Read all notes
accompanying the rmware update!
KMD-5576 Communication Faulty
• Upgrade to the latest version of BACstage (ver.
2.4.0.25 or later required).
• Check the seings for the USB port on the computer (Device Manager > Ports) and the MS/TP port in BACstage (Access > Connection Parameters).
• Reduce the Max Master number down to the minimum needed for that network—see (Ad-
vanced) BACnet Communications on page 7.
• Install latest driver and check latency seings. See Latency Seings for KMD-5576 Service Bul­letin (SB0308A) on the KMC web site.
• See also MS/TP Network Communication Faulty below.
MS/TP Network Communication Faulty
• Reduce the Max Master number down to the minimum needed for that network—see (Ad-
vanced) BACnet Communications on page 7.
• Check that EOL switches are fully latched in the correct positions (see the relevant BAC-10000 Series Installation Guide).
• Check MAC address and device instance num­bers.
BAC-10000 Series 17 Operation Guide, Rev. J
• Check baud rate.
Page 18
Cover and Display Issues
Custom Programming and Web Issues
Cover Binds on Backplate
• Carefully remove the FlexStat cover from the
backplate and inspect for bent pins and/or termi­nal socket connectors. If cover pins are bent, use a needle-nose pliers to straighten them. If socket connectors are bent, use a pointed object (such as a thumbtack or straightened paperclip) to straighten them. (Pushing the pointed object into the socket from the back side can be helpful.)
• Replace the backplate.
NOTE: When installing the cover on the
backplate, be sure to not pinch or dislodge any wiring. Do not use excessive force. If there is any binding, pull out cover and examine pins and terminal socket connectors.
Display Is Blank or Erratic
• Check that Display Blanking is not unintention-
ally enabled. (See System Setup on page 13.)
• Check for a tripped circuit breaker to the trans­former.
• Check for proper supply voltage from trans­former and that the transformer has enough capacity (VA) for all connected devices (see their respective data sheets).
• Carefully remove the FlexStat cover from the backplate, check pins and connectors, and rein­sert. (See Cover Binds on Backplate on page 18.)
• Check connections.
• Put another FlexStat on the installed backplate, and if the second FlexStat functions properly, replace the rst FlexStat.
Display Freezes (Buttons Have No Effect)
• Carefully remove the FlexStat cover from the backplate and ensure the WD (watch dog) jumper (near the boom of the board) is installed on the le and center pins. The jumper is tem­porarily removed during a rmware update and should be reinstalled when the process is com­pleted. (See the KMD-5699 Installation Guide, P/N 913-019-04, for more information.) Reinstall­ing the cover on the backplate will restart the FlexStat.
Control Basic Programs Do Not Work
NOTE: The FlexStat has a library of built-
in applications and options that are congured through the FlexStat’s display. Beyond these standard congurations, custom changes can be added to a FlexStat using KMC’s BACstage (ver. 2.4.0.26 or later) or TotalControl (ver. 2.0.5 or later).
NOTE: Control Basic (read-only) programs 1
through 5 are used for built-in applications and can not be modied directly. Programs 6 through 10 are empty and can be used for additional programming. Using BACstage or TotalControl, a program (1 through 5) can be copied, pasted into a new program code object (6 through 10), edited, and run in place of the original. (Although programs 1–5 cannot be edited, they can be halted and set to not autorun aer restart.)
NOTE: Customized programs are the responsibility
of the user. KMC Controls does not provide support for such programs.
• In the BAC-10000 Series Application Guide (P/N 913-019-03), carefully REVIEW ALL the infor-
mation in the Custom Programming section!
• Set programs to autorun and/or check if they have halted. Review (Advanced) CB (Control
Basic) Programs on page 6.
• Ensure objects are wrien to correct priority levels. See the Custom Web Graphics section in the BAC-10000 Series Application Guide (P/N 913-019-03).
• Custom programming requires BACstage (ver.
2.4.0.26 or later) or TotalControl (ver. 2.0.5 or later). Upgrade to the latest version for the most complete functionality.
• For assistance with Control Basic commands, see the Help system in TotalControl or BACstage.
Custom Web Graphics Do Not Work
• In the BAC-10000 Series Application Guide (P/N 913-019-03), review the Custom Web Graphics section.
• See also Control Basic Programs Do Not Work above.
BAC-10000 Series 18 Operation Guide, Rev. J
Page 19
Input, Sensor, and Value Issues
Input Values Are Outside the Expected Range
• Check that ALL the input pull-up resistor
switches are fully latched in the correct positions. See the Connections and Wiring section of the relevant BAC-10000 Series Installation Guide. A
single incorrect switch position may aect mul­tiple inputs. All input switches must be latched in either 10K Ohm or 0–12 VDC positions even if no input is connected! Input switch pairs (3-4, 5-6, and 7-8) must never have both switches set to the le or both to the right—if switch 3 is set to the le, for example, 4 must be set to the right (or vice versa).
• Check that the correct input type is selected on the Inputs screen. A Type III thermistor is the default on IN2 through IN4. See (Advanced)
Inputs on page 8.
• Check input wiring. See Wiring Issues on page 21.
• Check connected sensors.
• Using BACstage or TotalControl, check that the input is not congured as “Out Of Service.”
• Restore the FlexStat to factory seings (see Reset-
ting the FlexStat on page 14) and recongure.
Motion/Occupancy Sensor Does Not Work
• The initial rmware (R.1.0.0.0 and earlier) did not support this sensor within the built-in selectable programs. Custom programming was required— see the BAC-10000 Series Application Guide, P/N 913-019-03. Upgrade to the latest rmware for built-in support.
• Aer an initial power-up or restart, the motion/ occupancy sensor requires about 30 seconds before it will begin responding to motion.
• The motion/occupancy sensor initiates override only during “o” times in the schedule. See
Schedules on page 12.
• Check that the motion sensor is enabled and detects motion. See (Advanced) Motion Sensor on
page 8.
• Using BACstage or TotalControl, check that BI6 (occ status) is not congured as “Out Of Service.”
• The FlexStat must be installed where there is a clear view of typical trac area (reliable range is out to about 33 feet). Remove or move obstacles. Reinstall the FlexStat in a more optimal location if necessary.
• Connect remote motion sensors to an input (requires custom programming).
• For more information on detection performance, paerns, conguration, programming, and other issues, see the Motion/Occupancy Sensor section in the BAC-10000 Series Application Guide.
Temperature Reading Is Incorrect
• Aer applying power for the rst time (or aer an outage), allow the FlexStat to self-calibrate a few minutes before verifying temperature read­ing.
• If the discrepancy is small, adjust the calibration oset—see (Advanced) Inputs on page 8.
• Check that the thermistor is centered in its hole at the boom of the case and has an air gap around it. Also check that its leads are not pinched, shorted, or broken and that the tape holding down the leads is not loose. (Some early models with humidity sensors did not have the addi­tional thermistor—temperature was derived from the same chip that measured humidity.)
• Using BACstage or TotalControl, check that AI1 (space temp.) is not congured as “Out Of Service.”
• Check that the FlexStat is not mounted on an outside wall, is not exposed to heat sources or sunlight, is not exposed to dras from windows or air vents, or is not blocked from normal air circulation.
• See also Input Values Are Outside the Expected
Range on page 19.
Temperature Setpoint Is Not Maintained
• Select Occupied mode from the Home Menu— see H/C, Fan, Occupancy, and Override on page 3.
• Override the fan to On from the Home Menu— see H/C, Fan, Occupancy, and Override on page 3.
• Check that the appropriate application is se­lected—see (Advanced) Application Options on
page 5.
• Check that room temperature is being sensed correctly—see Temperature Reading Is Incorrect
on page 19.
BAC-10000 Series 19 Operation Guide, Rev. J
Page 20
Output, Fan, and Relay Issues
Analog Output Does Not Work
CAUTION
Do not mistakenly connect 24 VAC to an analog output ground. This is not the same as a relay’s switched common. See the backplate’s terminal label for the correct terminal.
NOTE: The maximum current of an analog output
is 20 mA @ 12 VDC. Excessive loads will
be clamped at the maximum. Relays may chaer or fail to latch if they need more current than the maximum allowed. KMC REE-3111/3112 relays, for example, could be connected to the analog outputs, but REE­3211/3221/3213 relays would not operate reliably with analog outputs because their required power exceeds the FlexStat’s capacity. (REE-3211/3221/3213 relays could, however, be used with the FlexStat relays and a separate power source.)
• Check current draw of load—it must be 20 mA or less. Substitute an output device that draws less current.
• Check that the output is on.
• See Wiring Issues on page 21.
• See also Fan Does Not Run on page 20.
• If Restore Factory has just been performed, see the Note and Cautions in Restore Factory on
page 15.
• If the rmware has just been upgraded, rm­ware for the wrong model type may have been installed (e.g., BAC-1xx63 rmware accidentally installed in a model BAC-1xx36). In the About menu, ASV may simply read “CUSTOM” instead of something like “BAC_1xx36 R1.1.0.5” as it normally would have done. If so, repeat the rm­ware upgrade and ensure that the correct type of rmware is selected for the connected model.
NOTE: ASV in the About menu will also show
CUSTOM if any built-in Control Basic program (1–5) is not running or has auto­run disabled.
Fan Does Not Run
NOTE: The animated fan icon is coupled with
BV18 in the packaged programming (not the actual fan output terminal).
• Select Occupied mode from the Home Menu—
see H/C, Fan, Occupancy, and Override on page 3.
• Override the fan to On from the Home Menu—
see H/C, Fan, Occupancy, and Override on page 3.
• See Wiring Issues on page 21.
• Check that the appropriate application is se-
lected—see (Advanced) Application Options on
page 5.
• Check the fan conguration—see Fan Setup on
page 5.
• Restart the FlexStat. Aer a low limit alarm is generated, the fan will not run until aer the FlexStat is restarted. (See Reseing the FlexStat
on page 14.)
Relay (Internal) Does Not Work
CAUTION
Relays are for Class-2 voltages (24 VAC) only. Do not connect line voltage to the relays!
NOTE: Max. output current is 1 A for individual
relays @ 24 VAC/VDC or a total of 1.5 A per bank of 3 relays (relays 1–3, 4–6, and
7–9). Do not aach a device that draws current that exceeds the corresponding value. Relays are NO, SPST (Form “A”).
• Check current draw of load. Substitute an output device that draws less current.
• Check that the output is on.
• See Wiring Issues on page 21.
• Restart the FlexStat.
• If Restore Factory has just been performed, see the Note and Cautions in Restore Factory on
page 15.
BAC-10000 Series 20 Operation Guide, Rev. J
Page 21
Wiring Issues
• If the rmware has just been upgraded, rm­ware for the wrong model type may have been installed (e.g., BAC-1xx63 rmware accidentally installed in a model BAC-1xx36). In the About menu, ASV may simply read “CUSTOM” instead of something like “BAC_1xx36 R1.1.0.5” as it normally would have done. If so, repeat the rm­ware upgrade and ensure that the correct type of rmware is selected for the connected model.
NOTE: ASV in the About menu will also show
CUSTOM if any built-in Control Basic program (1–5) is not running or has auto­run disabled.
Relay (External) Does Not Work
• See Analog Output Does Not Work on page 20.
• See Relay (Internal) Does Not Work on page 20
CAUTION
Do not mistakenly connect 24 VAC to an analog output ground. This is not the same as a relay’s switched common. See the backplate’s terminal label for the correct terminal.
CAUTION
Relays are for Class-2 voltages (24 VAC) only. Do not connect line voltage to the relays!
• Remove the FlexStat from the backplate and inspect the terminals for loose or shorted wires.
• Use a voltmeter and ohmmeter to check the terminals for expected values. See the illustration below and the the Connections and Wiring sec­tion of the relevant BAC-10000 Series Installation Guide.
NOTE: Voltage on the BACnet MS/TP terminals
changes according to the signals (passing of the token) between controllers on the network. No voltage indicates a bad connection or simply no active network.
NOTE: Values Shown Are Approximate!
NOTE: BAC-1xxx63 Backplate Terminals Shown
NOTE: SC = Switched (Relay) Common, Should
BACnet MS/TP Network
Inputs
24 VAC
with FlexStat Removed; Outputs and Inputs Vary According to Application
Have the Phase Side of 24 VAC Connected
(Wiring Inputs and Outputs Dependent on Application)
+B
–A
IN4
IN3
GND
IN2
Common/– / C
Phase/ /R
0.1–0.2 VDC (If Network
}
Token Passing is Present)
10K Ohms (Thermistor) or
}
O Ohms (Closed Contact)
24 VAC
}
• Check the wiring at the connected devices.
Outputs
Analog 9
Resistance
Dependent
on Device
24 VAC
(Jumper to
Turn Device
On Manually)
GND 7–9
Analog 8
Analog 7
Relay 6
SC 4–6
Relay 5
Relay 4
Relay 3
SC 1–3
Relay 2
Relay 1
Terminal Voltages and Resistances with FlexStat REMOVED from Backplate
BAC-10000 Series 21 Operation Guide, Rev. J
Page 22
Maintenance
Accessories
Remove dust as necessary from the holes in the top and boom. Clean the display with so, damp cloth and mild soap.
To maintain maximum sensitivity of optional built-in motion sensors, occasionally wipe dust or dirt o the lens—but do not use any uid on the sensor.
Firmware Upgrade
The existing version of rmware can be viewed from the About the FlexStat screen. (See About the Flex-
Stat on page 4).
Firmware in the FlexStat can be upgraded using a PC and a KMD-5699 rmware ash upgrade kit available from KMC Controls. (For full upgrade instructions, see the KMD-5699 Installation Guide, P/N 913-019-04.)
HMO-10000 Horizontal or 4 x
4 handy box wall mounting plate, light almond
HMO-10000W HMO-10000 in
white
HPO-0044 Replacement cover
hex screw
KMD-5567 Network surge
suppressor
KMD-5575 Network repeater/
isolator
KMD-5576 EIA-485 to USB
Communicator
Programming (Custom)
The FlexStat has a library of built-in applications and options that are congured through the FlexStat’s display. Beyond these standard congurations, cus­tom changes can be added to a FlexStat using KMC’s BACstage (ver. 2.4.0.26 or later) or TotalControl (ver.
2.0.5 or later). See the BAC-10000 Series Application Guide (P/N 913-019-03) for more information.
NOTE: Customized programs are the responsibility
of the user. KMC Controls does not provide support for such programs.
KMD-5624 PC data port
(EIA-485) cable (FlexStat to USB Communicator)— included with the KMD-5576 (buy for third-party EIA­232 interfaces)
KMD-5699 FlexStat rmware
ash upgrade kit
SP-001 Flat blade and hex
end screwdriver (with KMC logo) for cover hex screws
XEE-6111-040 Transformer, 120-
to-24 VAC, 40 VA, single-hub
XEE-6112-040 Transformer, 120-
to-24 VAC, 40 VA, dual-hub
BAC-10000 Series 22 Operation Guide, Rev. J
Page 23
Support
Important Notices
FlexStats come with a printed Installation Guide. Additional resources for conguration, application, operation, programming, upgrading and much more is avail­able on the award-winning KMC Controls web site (www.kmccontrols.com).
The collection of FlexStat documents won a prestigous publications award for techni­cal marketing support from the Chicago chapter of the Society for Technical Commu­nication in March 2010.
The KMC logo and TotalControl are registered trademarks and BACstage is a trademark of KMC Controls, Inc. All rights reserved. No part of this publication may be reproduced, transmied, tran­scribed, stored in a retrieval system, or translated into any language in any form by any means without the wrien permission of KMC Controls, Inc.
The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this document.
BAC-10000 Series 23 Operation Guide, Rev. J
Page 24
Reference
Acronyms and Abbreviations
Common acronyms and abbreviations in FlexStat and related documents include:
amp = amperes
A = amperes
AAC = Advanced Application Controller
A/C = air conditioning
AC = alternating current
AHU = air handling unit
avg. = average
AWG = American Wire Gauge
BACnet = Building Automation Control network
BTL = BACnet Testing Laboratories
C = Celsius
c = cubic feet per hour
cfm = cubic feet per minute
cm = centimeters
DA = direct acting
DC = direct current
DPDT = double pole double throw
DPST = double pole single throw
EIA = Electronic Industries Alliance
EOL = end of line
F = Fahrenheit
FCU = fan coil unit
FIU = fan induction unit
-lbs. = foot pounds
g = grams
LCD = liquid crystal display
mA = milliamperes
MAC = media access control
max. = maximum
min. = minimum
mm = millimeters
MS/TP = master-slave/token-passing
NC = normally closed
NO = normally open
pF = picofarad
RA = reverse acting
RH = relative humidity
RS = Recommended Standard
RTC = real time clock
RTU = roof top unit
SPDT = single pole double throw
SPST = single pole single throw
UL = Underwriters Laboratories
USB = universal serial bus
UTC = Coordinated Universal Time
V = volts
VA = volt-ampere
VAC = volts alternating current
VAV = variable air volume
VDC = volts direct current
W = was
HPU = heat pump unit
HVAC = heating ventilating and air conditioning
Hz = hertz
IP = Internet protocol
BAC-10000 Series 24 Operation Guide, Rev. J
NOTE: See also the Green Building and Controls
Glossary (SB-046) for denitions of various terms in this catalog.
Page 25
Definitions of Terms
For denitions of various terms in this document, refer to the award-winning pocket-sized Green Building and Con- trols Glossary (SB-046). A hyperlinked online version can be downloaded from the Brochures section of KMC Controls web site, www.kmccontrols.com. Some
of the more important glossary terms for this document are included on this page:
Air Handling Unit (AHU)—An HVAC system compo-
nent that conditions and delivers air through the system. It typically contains one or more supply and return fans, heating/cooling coils, and lters to condition the air.
®
BACnet
(Building Automation Control Network)
An interoperable, nonproprietary, communica­tion protocol standard conceived by a consor­tium of building managers, system users, and manufacturers. BACnet denes how information is packaged for transportation between building automation system vendors.
EIA-485—A serial communications standard in
which the voltage dierence between two wires conveys the data. It is commonly used to network controllers via twisted-pair wiring. It was for­merly known as RS-485.
Fan Coil Unit (FCU)—A fan terminal unit that condi-
tions the air in a single room or zone. FCUs gen­erally contain heating and cooling coils and have the ability to supply outside air to a space.
Heat Pump Unit (HPU)—A unit that uses direct
expansion to remove or add heat to a space. On a call for heat, the heat pump pulls heat from a source such as outside air or the ground and puts it into a space. On a call for cooling, the process is reversed.
Max Master—The highest MAC address a device will
aempt to locate when polling for master devices on the local network.
MS/TP (Master Slave/Token Passing)—A protocol
(using the EIA-485 signaling standard) in which master devices can initiate requests for data but slave devices cannot (since slaves can only reply to messages from other devices). KMC advanced application controllers are all MS/TP master devices.
Native BACnet Device—A device that is fully BACnet
compatible and uses BACnet as its primary, if not exclusive, method of communication.
PID (Proportional Integral Derivative) Control—A
control algorithm that enhances the PI control algorithm by adding a component that is pro­portional to the rate of change (derivative) of the deviation of the controlled variable. This com­pensates for system dynamics and allows faster control response.
PID Loop Controller—A controller with an algorithm
that calculates an output value that is based on the sensed value and the required setpoint. PID loop controllers provide more accurate and stable control than simpler controllers.
Proportional Control—A type of control in which a
controlled device may operate at any position be­tween fully closed to fully open. Within a specic range, the output response maintains a constant ratio to the input signal.
Protocol—A denition or set of communication rules
by which information is exchanged between de­vices on a network.
Real Time Clock (RTC)—A device that keeps track of
the current time in a controller even if power is interrupted for a period of time.
Relative Humidity (RH)—The ratio of the amount of
water vapor in air to the maximum amount of water vapor that could be in the air if the vapor were at its saturation conditions.
Roof Top Unit (RTU)—An HVAC unit that is supplied
as a package and installed outside of a building.
Router—A device that connects two or more networks
and chooses the best path for data packets.
USB (Universal Serial Bus)—A popular, plug-and-
play, high-speed, serial computer interface.
UTC (Coordinated Universal Time)—An international
standard for determining time zones.
Variable Air Volume (VAV)—A method of tempera-
ture control in which the volume of constant tem­perature supply air exiting a duct is modulated (via dampers) to maintain a temperature setpoint in an individual space.
BAC-10000 Series 25 Operation Guide, Rev. J
Page 26
Index
Symbols
4 x 4 Handy Box Mounting Plate: 22
A
Abbreviations: 24 About the FlexStat: 4 Access Levels, Password: 9 Accessories: 22 Acronyms: 24 Adjustment. See Configuration; Override; Setpoint Administrator Password: 9 Advanced Menu: 5 Alarms: 5, 6, 11, 17 Analog Outputs: 14, 20 Application Options: 2, 5, 15 Application Software Version (ASV): 4 ASV (Application Software Version): 4 Auto, Off, Heat, or Cool (System Enable): 13 Auxiliary Heat, Heat Pump: 5
B
Backlight: 13 Backplate: 2, 18 BACnet: 2, 7, 16, 17 Baud Rate: 16 Binding, Cover on Backplate: 18 Blanking, Display: 13 Board Revision: 4 Build Date: 4 Buttons: 3
C
Calibration Offset: 8 Cold Start: 14 Communication
Settings: 7
Troubleshooting: 7, 17 Configuration: 4 Control Basic Programs: 6, 15, 18 Cool, Heat, Auto, Off (System Enable): 13 Coordinated Universal Time (UTC): 7 C or F, Selecting Temp. Scale: 5 Cover: 18 Custom
Programs: 6, 18, 22
Web Graphics: 18
CUSTOM in ASV: 4, 20
D
Damper Set-Up: 5 Data Port: 16 Date: 7, 11 Deadband: 13 Definitions of Terms: 25 Degrees F or C: 5 Delay, Fan: 5, 14 Detector. See Motion Sensor Device Instance: 4, 8, 15, 16 Device Properties: 8 Discharge Air Temperature: 6 Display
Blanking: 13 Overview: 3 Time-Out: 13 Troubleshooting: 18
E
Economizer (Damper): 5 EIA-485: 16 EOL (End Of Line) Switches: 17
F
Factory Defaults: 8, 14 Fan
Delay: 5, 14 Fail Alarm: 6, 11, 17 (Manual) Override: 3 Set-Up: 5 Status: 6 Troubleshooting: 19
Firmware
Troubleshooting: 17, 19 Upgrading: 6, 22
Viewing Current: 4 F or C, Selecting Temp. Scale: 5 Freeze Stat. FW. See Firmware
See Low Limit Alarm
BAC-10000 Series 26 Operation Guide, Rev. J
Page 27
G
Glossary, Green Buildings Controls: 25
H
Heat, Cool, Auto, Off (System Enable): 13 HMO-10000 Mounting Plate: 22 Home (Temperature Display) Screen: 3 Horizontal Handy Box Mounting Plate: 22 HPO-0044 Cover Screw: 22 Humidity
Alarm: 11 Dehumidification Setpoint: 13 Setup: 5 Trend Log: 10
I
IN2: 6 Inactivity Time-Out: 13 Initial Set-Up: 4 Inputs: 8 Installation: 2
J
Jumper, WD: 18
K
KMC Controls: 23 KMD-5567 Surge Suppressor: 22 KMD-5575 Repeater/Isolator: 22 KMD-5576 USB Communicator: 16, 17, 22 KMD-5624 PC Data Port Cable: 22 KMD-5699 Firmware Upgrade Kit: 22
L
Limits: 8, 11 Low Limit Alarm: 5, 11, 17
M
MAC Address: 4, 7, 15, 16 Main Menu: 3, 4 Maintenance: 22 Max Master: 7, 16, 17 Menu
Advanced: 5
Main: 4 Model Number: 4 Motion Detector. See Motion Sensor Motion Sensor: 8, 19 MS/TP: 7, 16, 17
N
Navigation: 3 Network: 7, 16, 17, 22 Notices: 23
O
Occupancy
Mode: 3 Override: 3, 13
Sensor. See Motion Sensor Off, Auto, Heat, or Cool (System Enable): 13 Offset, Calibration: 8 Operation
Basic: 3
Configuring (Set-Up): 4 Operator Password: 9 Outage, Power: 14 Outputs: 14, 20 Override: 3, 13
P
Passwords: 9, 13 PC Data Port: 16 Power Outage/Removal: 14 Programming, Custom: 6, 18, 22 Pull-Up Resistor Switches: 17, 19
R
Reference: 24 Reinitialize: 8, 14 Relays: 21 Reset: 8, 14 Restart: 8, 14 Restore: 8, 15 RS-485.
See EIA-485
S
Schedules: 12 Security: 9 Sensor
Calibration: 8
Setup: 6
Troubleshooting: 19
Type: 8
Value: 8 Serial Number: 4 Setbacks: 13
BAC-10000 Series 27 Operation Guide, Rev. J
Page 28
Setpoints
Adjustment: 3, 13 All: 13 Temperature (Only): 3
Troubleshooting: 19 Setup and Configuration: 4 SP-001 Screwdriver: 22 Space
Humidity Alarm: 11
Temp Alarm: 11 Staging: 6 Start (Reset), Cold or Warm: 14 Support, Technical: 23 Switches
EOL (End of Line): 17
Pull-Up Resistors: 19 System
Enable: 13
Setup: 13
T
Temperature
Alarm: 11
Limits: 8
Scale, Selecting: 5
Setpoint: 3, 8, 13
Trend Log: 10
Troubleshooting: 19 Terminals: 2, 18 Terms: 25 Test Menu: 10 Time: 7, 10, 11 Time-Out (Inactivity): 13 Transformer: 22 Trend Logs
Inputs: 6, 10
Intervals: 10
Setup: 10
Viewer: 13 Troubleshooting: 17
U
Universal Time, Coordinated (UTC): 7 Update Manager: 6 Upgrading Firmware: 17, 22 USB Communicator: 16 User Password: 9 UTC (Coordinated Universal Time): 7
V
Value, Sensor: 8 Valve Set-Up: 6 Viewer
Alarms: 11 Trends: 13
W
Warm Start: 14 WD (Watch Dog) Jumper: 18 Web Site, KMC Controls: 23 Wiring: 2, 21
X
XEE-6000 Series Transformers: 22
BAC-10000 Series 28 Operation Guide, Rev. J
© 2010 KMC Controls, Inc. 913-019-02J
KMC Controls, Inc.
19476 Industrial Drive, New Paris, IN 46553
574.831.5250
www.kmccontrols.com
info@kmccontrols.com
Loading...