KMC Controls CTE-5202 Application Manual

Analog Electronic Thermostat w/ LCD Display
Applications Guide

Contents

General Information (All Applications) .................................................................................. 3
Important Notices ..........................................................................................................................................................4
Accessories ....................................................................................................................................................................4
Connection and Configuration .......................................................................................................................................5
Connections ...............................................................................................................................................................5
External Input (AI1) ....................................................................................................................................................5
Change Setpoint .........................................................................................................................................................6
Change Configuration ................................................................................................................................................6
Sequences ..................................................................................................................................................................7
Cross-References ............................................................................................................................................................8
CTE-5202 Troubleshooting ...........................................................................................................................................10
Display Is Blank ........................................................................................................................................................10
Setpoint Is Not Maintained ......................................................................................................................................10
Temperature Reading Is Incorrect ............................................................................................................................10
Wiring Issues ............................................................................................................................................................10
Single-Zone Proportional Heating and Cooling Applications ............................................... 11
Heating, RA and DA .....................................................................................................................................................12
Chilled Beam Cooling ..................................................................................................................................................13
Chilled Beam 4-Pipe Heating and Cooling ...................................................................................................................14
Chilled Beam 2-Pipe Heating and Cooling with Changeover ........................................................................................15
Pressure Dependent VAV Applications with MEP-4xx2 ........................................................ 16
Cooling or Heating .......................................................................................................................................................17
Auto and Override (to Fully Closed) ............................................................................................................................18
Other Applications .......................................................................................................................................................18
CTE-5202 Analog Electronic Thermostat w/ LCD Display 1 Applications Guide, AN0912A Rev. D
Pressure Independent VAV Applications with CSP-4702 ...................................................... 19
Replacing a CSP-5001/5002 .........................................................................................................................................20
Replacing a CEP-4xxx or CSP-40xx/42xx/44xx/46xx ...................................................................................................21
Cooling or Heating .......................................................................................................................................................22
Auto and Override (to Fully Open) ..............................................................................................................................23
Cooling and 3-Stage Reheat .........................................................................................................................................24
Cooling with 3-Stage Reheat and Night Setback/Setup ................................................................................................25
Cooling with Heating Changeover ...............................................................................................................................26
Cooling with Heating Changeover and Electric Reheat ................................................................................................27
Cooling with Heating Changeover and Hot Water Reheat ...........................................................................................28
Cooling with Hot Water Reheat ...................................................................................................................................29
Fan Induction with 2-Stage Electric Heat .....................................................................................................................30
Dual Duct, Minimum Air from Cold Duct ....................................................................................................................31
Pressure Independent VAV Applications with CSP-5001/5002 ............................................. 32
Cooling or Heating .......................................................................................................................................................33
Auto and Override (to Fully Closed or Fully Open) ......................................................................................................34
Cooling and 3-Stage Reheat .........................................................................................................................................35
Cooling with 3-Stage Reheat and Night Setback/Setup ................................................................................................36
Cooling with Heating Changeover ...............................................................................................................................37
Cooling with Heating Changeover and Electric Reheat ................................................................................................38
Cooling with Heating Changeover and Hot Water Reheat ...........................................................................................39
Cooling with Hot Water Reheat ...................................................................................................................................40
Fan Induction with 2-Stage Electric Heat .....................................................................................................................41
Dual Duct, Minimum Air from Cold Duct ....................................................................................................................42
Pressure Independent VAV and CAV Applications with CEP/CSP-4000 Series ...................... 43
9.1 VDC vs. 24 VAC Power Options .............................................................................................................................44
Cooling ........................................................................................................................................................................45
Cooling with Morning Warm-Up ..................................................................................................................................46
Cooling with 3-Stage Reheat ........................................................................................................................................47
Cooling/Heating Changeover .......................................................................................................................................48
Cooling with Proportional Hot Water Reheat ...............................................................................................................49
Fan Induction with 2-Stage Electric Heat .....................................................................................................................50
Damper Tracking (Master/Slave) ..................................................................................................................................51
Dual Duct Heating and Cooling VAV ...........................................................................................................................52
Dual Duct Heat/Cool Constant Volume with Hot Deck Make-Up ................................................................................53
Barber Colman TP-81xx Thermostats Replacement Applications ..........................................54
TP-8101/8102/8103 Replacement (General) ...............................................................................................................55
TP-8101/8102/8103 Replacement with MP-52xx Actuators ........................................................................................56
TP-8124/8125 Replacement with One or No MP-52xx Actuators ................................................................................57
TP-8124/8125 Replacement with Two MP-52xx Actuators ...........................................................................................58
Index .................................................................................................................................... 59
CTE-5202 Analog Electronic Thermostat w/ LCD Display 2 Applications Guide, AN0912A Rev. D
General Information
(All Applications)
This document gives schematics of sample (new and
retrot) applications, cross-references, troubleshoot­ing, and other related information.
For general mounting and connection details, including power connections and input/output connections, see the CTE-5202 Installation Guide.
For specications and other information, see the
CTE-5202 Data Sheet.
The latest support les are always available on the KMC Controls web site (www.kmccontrols.com).
(Shown adjusting the Cooling
setpoint— during normal operation,
only room temperature is shown in
the upper right of the screen)
Specifications, design, and operation are subject to change without notice.

General Information (All Applications) 3 CTE-5202 Applications Guide, AN0912A Rev. D

Important Notices

Accessories

The KMC logo and KMC Controls are registered
trademarks of KMC Controls, Inc. Other products and name brands mentioned may be trademarks of their respective companies or organizations.
All rights reserved. No part of this publication may be reproduced, transmied, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the wrien permis­sion of KMC Controls, Inc.
The material in this document is for information
purposes only. The contents and the product it de­scribes are subject to change without notice. KMC
Controls, Inc. makes no representations or warran­ties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this document.
HMO-1161 Wall plate, al-
lows mounting to horizontal 2
x 4", 4 x 4", or other boxes,
light almond
HMO-1161W HMO-1161 in
white
HPO-0044 Replacement
cover hex screws
HPO-1161 Foam insulating
gasket
REE-50xx Electric relay
modules, stag-
ing and reheat
STE-140x Duct tempera-
ture (Type III)
sensors
STE-1454/1455 Strap-on tem-
perature (Type III) sensors
NOTE: See sample applications for additional
information.
General Information (All Applications) 4 CTE-5202 Applications Guide, AN0912A Rev. D
Connection and Configuration

Connections

AO2 AO1
AI1
T T
~
Standard connections to the terminal block are:
“Heating” output (REE-50xx reheat relay mod- ules and heating valves) to AO2 and mon)
“Cooling” output (VAV dampers and cooling valves) to AO1 and
Changeover (temperature) sensor (Type III, 10K ohm thermistor) and/or standby/unoccupied setback contact to AI1 and
External Input (AI1) on page 5.)
24 VAC transformer’s neutral lead to
mon) and phase lead to ~. Alternately, 14–35 VDC can be used with + connected to ~ and – connected to T (Common).
“Heating” Output “Cooling” Output Input Common Common Power (AC Phase or DC +)
T
(Com-
T
(Common)*
T
(Common). (See
T
(Com-

External Input (AI1)

Hot/Cold Changeover
For hot/cold air changeover on Sequence 1 or 2, connect a changeover sensor to the AI1 input. The sensor should be a Type III thermistor (10K ohm @ 77° F), such as KMC STE-140x duct or STE-
1454/1455 strap-on sensors. (An internal 10K ohm
pullup resistor is provided on AI1.)
See, for example, Cooling with Heating Changeover
on page 26 and Chilled Beam 2-Pipe Heating and Cooling with Changeover on page 15.
At power-up, the default mode for Sequences 1 and 2 is Cold Air mode with a default changeover set­point of 77° F. If the AI1 sensor reads a temperature higher than 79° F, the Hot Air mode becomes active. Hot Air mode stays active until the AI1 temperature falls below 75° F. Then Cold Air mode is active until the AI1 temperature rises above 79° F, which makes Hot Air mode active. At power-up, if the tempera­ture is between 75° F and 79° F, the thermostat will assume Cold Air mode.
For continuous cold air mode, leave the sensor o.
*NOTE: AO1 also controls heating in morning
warm-up, changeover, and some other congurations. For examples, see:
Heating, RA and DA on page 12, Chilled Beam 2-Pipe Heating and Cooling with Changeover on page 15, Cooling or Heating on page 17, Cooling and 3-Stage Reheat on page 24, Dual Duct, Minimum Air from Cold Duct on page 31, Cooling with Heating Changeover on page 37,
Cooling with Morning Warm-Up on page
46, and TP-8101/8102/8103 Replacement
(General) on page 55.
NOTE: For additional information on mounting
and installation, see the CTE-5202
Installation Guide.
The changeover temperature setpoint is adjustable between 55 and 85° F in the ADVANCE menu, and the default is 77° F. See Change Conguration on
page 6.
Unoccupied/Standby Setback
Contact closure across AI1 and Common initiates the standby setback oset sequence, which causes the cooling setpoint (in all Sequences) to increase and
the heating setpoint in Sequence 2 or 3 to decrease
by the amount of the setback oset. This setback does not apply during the morning warm-up se­quence.
See, for example, Cooling with 3-Stage Reheat and
Night Setback/Setup on page 25 and Cooling with 3-Stage Reheat and Night Setback/Setup on page
36.
General Information (All Applications) 5 CTE-5202 Applications Guide, AN0912A Rev. D

Change Setpoint

To change the setpoint:
MAX = 12, and AUX = 0 as defaults.) Use the Up and Down buons to change the desired values. (If no Auxiliary Flow is desired, set AO1 AUX to 0.)
1. Push the Setpoint buon (or either Up/Down buon) to display the current value.
NOTE: Sequences 2 and 3 have two setpoints
indicated by “snowake/cool” and “re/ heat” icons. When the Cooling setpoint is showing, pushing the Setpoint buon will display the Heating setpoint.
2. Use the Up/Down buons to change the value.
3. Press the Setpoint buon again, and the thermo­stat will control at the new setpoint. (Alternately, after about 30 seconds of no activity, the display reverts back to displaying room temperature.)
NOTE: Setpoint range is 55 to 85° F (13 to 30° C),
with a default of 74° (for cooling or 70° for heating).
Max. Limit
Output
Span
Min.
Limit
(Colder Room Temperature Warmer)
Cooling
Setpoint
(Cooling)
Setback
(Heating)
Setback
Heating
Setpoint
To change any of the system or advanced features, press the Up or Down buon until the desired (ash­ing) ADVANCE or SYSTEM menu appears and then press the Setpoint buon.
The ADVANCE menu enables changing (via the Up/Down buons) the values of:
DEAD BDDeadband or “minimum setpoint
dierential” (adjustable from 1 to 10° F, 2° F de- fault)
SETBACK—Standby/unoccupied setback o-
set (adjustable from 0 to 10° F, 2° F default)—does
not apply to morning warm-up
PROP BD—Loop proportional band or “throt-
tling range” (adjustable from 1 to 10° F, 2° F default)
Rm OFST—Room temperature oset (adjust-
able ±5° F, 0 default)
CNG OVR—changeover temperature (adjustable
from 55 to 85° F, 77° F default)
I TIME—Loop integral time (adjustable from 0 to
60, 30 minutes default, 0 = cancel integral action)*
The SYSTEM menu enables changing:
Proportional
Band
Deadband
Proportional
Band
Change Configuration
Press and hold both the Up and Down arrows but­tons for about ten seconds until the display starts
ashing “LIMITS.” NOTE: When a menu is ashing (LIMITS,
ADVANCE, SYSTEM, or EXIT), pressing Up or Down displays the next
menu item and pressing Setpoint selects
that menu. When a menu is NOT ashing (e.g., DEAD BD), pressing Up or Down
changes the value and pressing Setpoint
displays the next menu item.
To change any of the limits (output span) when LIMITS” is ashing, press the Setpoint buon
until the desired limit (AO1 MIN, AO1 MAX, AO1 AUX, AO2 MIN, or AO2 MAX) is displayed.
(Limits are adjustable from 0 to 12 VDC, with MIN = 0,
• Sequence (SEQ1, SEQ2, or SEQ3)—see
Sequences on page 7
• °F (ENGLISH) or °C (METRIC)
BLANK—Display blanking (NO or YES)—
when blanked, the temperature will display for no more than 30 seconds after a buon is pushed
When done, navigate to (ashing) Exit to save changes. Leing the menu time-out (about 30
seconds) will not permanently save changes.
*NOTE: As long as there is an error between room
temperature and setpoint, the integral
action will cause the output to integrate up
or down. I TIME is the time it takes the integral action to repeat the eect of the proportional action.
General Information (All Applications) 6 CTE-5202 Applications Guide, AN0912A Rev. D

Sequences

6 Volts
AO1 MIN
12 Volts
AUX
AO2 (DA) 0-12 Volts
10%
Of Loop
COLD AIR SEQUENCE
AO1 (DA)
2° F
2° F
Setpoint
SEQUENCE 1:
COLD AIR SEQUENCE
AO2 (RA)
AO1 (DA)
HOT AIR SEQUENCE (Morning Warm Up)
12 Volts
AO1 (RA)
AO1 MAX
Temp. Increasing
AO1 MAX
2° F
Setpoint
Single Duct Cooling, Fan Box (with REE-5002 or REE-5017)
HOT AIR SEQUENCE (Morning Warm Up)
AO1 (RA) 0 Volts AO1 MAX
AO1 MAX
AO1 MIN
AO2 Disabled
(12 Volts)
AO2 Disabled
(0 Volts)
AO1 MIN
AO1 MIN
AO2 MAX
AO1 MIN
2° F
Heating
Setpoint
SEQUENCE 2:
AO2 (RA)
Cooling
Setpoint
AO1 (DA)
2° F
Single Duct Cooling with Reheat and Auxiliary Flow
2° F 2° F
Heating Setpoint
Cooling
Setpoint
SEQUENCE 3:
Independent Heating and Cooling Control
(Dual Duct VAV, Baseboard, Single Zone AHU)
Temp. Increasing
AO2 MIN
AO1 MAX
Temp. Increasing
2° F
Heating
Setpoint
NOTE: AO1 is typically used to control the cooling
output (primary air damper or cooling valve), and AO2 is used to control the
heating output (VAV reheat or heating
valve).
General Information (All Applications) 7 CTE-5202 Applications Guide, AN0912A Rev. D

Cross-References

Barber Colman (TAC, Invensys, Schneider Electric)
Thermostat Replaced
TP-8101, TP-8102, and TP-8103 #1
TP-8124 and TP-8125 #3
For wiring and sample applications, see Barber Colman TP-81xx Thermostats Replacement Applications on page 54.
Thermostat Replaced
KMC /
Nailor /
Dynacon*
CTE-1001
CTE-1002
CTE-1003 13-29 01EC-2146
CTE-1004 13-28 01EC-2129 THM1004 10027403 #2
CTE-1005 THM1005
CTE-1008
CTE-1101 004643 THM1101 10027415 #1
CTE-1103 01EC-9229 THM1103 10027411
CTE-1105 THM1105 10027413 #1
CTE-1108
*NOTE: CTE-1x0x thermostats require a power supply of 9.1 VDC, typically supplied by a CEP/CSP-4xxx controller/actuator, and they have a 0–6 VDC output range. The CTE-5202 can also operate on the 9.1 VDC power supplied by CEP/CSP-4xxx controller-actuators, but the CTE-5202’s outputs will be reduced to a maximum of about 5.3 VDC (or a maximum of about 2000 fpm from the CEP/CSP­4xxx). In almost all such applications, this is adequate. In a rare application that requires a full 6 VDC output (or 3000 fpm maximum from the CEP/CSP-4xxx), the CTE-5202 can be powered by the 24 VAC transformer, which can be easily done by switching the wire from Terminal #5 (+9.1 VDC) to Terminal #10 (24 VAC, phase) on the CEP/CSP-4xxx. See 9.1 VDC vs. 24 VAC Power Options on page
44. See also the CEP-4000 Series Applications Guide.
Anemostat
(East/West)*
13-27,
004100
Metal
Industries*
Metalaire* Nailor*
B3-3001-
015 or
B3-015
ASC / Titus*
10027401 #1
#3 (disregard cooling
setpoint) or #1 (with
8K–10K ohm resistor for
#1 (setback used for night
#1 (setback used for day
#1 (single duct) or #3
(dual duct)
#1 (setback used for day
CTE-5202 Sequence Selected
CTE-5202 Sequence
Selected
RA mode)
#3
setpoint)
setpoint)
setpoint)
Example
Replacement
Applications
See page 45
See page 47 and page 49
See page 45, page 50, and
page 51
See page 48, page 52, and
page 53
General Information (All Applications) 8 CTE-5202 Applications Guide, AN0912A Rev. D
KMC CTE-50xx
Thermostat Replaced
CTE-5202 Sequence Selected Example Replacement Applications
CTE-5001/5011* #1
CTE-5002/5012* #2
CTE-5003/5013* (No Replacement) (9.1 VDC)
CTE-5006/5016** #2
CTE-5015** #1
*NOTE: These models require a power supply of 9.1 VDC, typically supplied by a CEP/CSP-4xxx controller/actuator, and they have a 0–6 VDC output range. See the discussion on 9.1 VDC power under the CTE-1x0x cross-reference NOTE on page 8. Need for the REE­1014 in applications is eliminated. **NOTE: These models require a power supply of 14–20 VDC, typically using the 16 VDC power supplied by a CSP-5001/5002 controller/actuator. The CTE-5202 can use the same 16 VDC power (or 14–35 VDC or 24 VAC).
Thermostat Replaced
KMC / Nailor /
Dynacon*
CTE-5101 999-2662 01EC-2119
CTE-5102 13-33 10269607
CTE-5103 13-35 999-2663 01EC-2122
CTE-5104 13-34 999-2664 01EC-2120 H1-981
CTE-5105 019822-001 10269610
*NOTE: CTE-510x thermostats require a power supply of 14–20 VDC, typically using the 16 VDC power supplied by a CSP-5001/5002 controller/actuator. The CTE-5202 can use the same 16 VDC power (or 14–35 VDC or 24 VAC). See also the CSP-5001/5002
Applications Guide.
**For applications requiring limited T1 and/or T2 signals and unlimited T3 and/or T4 signals, flow limits may need to be set on the controller (allowing the controller to use an unlimited signal). Limits for the CTE-5202 and AO1 and AO2 would then be left at the default 0 and 12.
Anemostat* Carnes*
Metal
Industries*
Nailor*
B3-3001-191
or B3-191
B3-3001-186
or B3-186
Price
Industries*
019814-001
019810-001
019726-001
/ 019816-
001
See page 45 and page 48 (9.1 VDC)
See page 47 (9.1 VDC)
See page 35 (16 VDC)
See page 33 (16 VDC)
CTE-5202 Sequence
ASC / Titus*
10269601 /
10269606
10269608 /
10269603
10269604 /
10269609
Selected
#1
#3 (if T4 is not
used)**
#3 (if T3 and
T4 are not
used) **
#2
#1 (if the
setback feature
is acceptable
in place of two
independent
setpoints)
Example
Replacement
Applications
See page 33,
page 34, and
page 41
See page 33
See page 35,
page 37, page
38, page 39, and
page 42
See page 35,
page 36, and
page 40
Other thermostats that the CTE-5202 can be a functional/upgrade replacement for include:
Honeywell TB7980 (check application and specications)
• Johnson Controls (various—check application
and specications)
Kele RTC-2P (with one or less remote inputs— check application and specications)
PEKO (various—check application and specica­tions)
Siemens (various—check application and speci­cations)
• Viconics (various—check application and speci­cations)
NOTE: Products and name brands mentioned
may be trademarks of their respective companies.
General Information (All Applications) 9 CTE-5202 Applications Guide, AN0912A Rev. D

CTE-5202 Troubleshooting

Display Is Blank

If the display comes on for no more than 30 seconds after a buon is pushed and then blanks out, Display Blanking is enabled in the SYS- TEM menu. See Change Conguration on page 6.
Check for a tripped circuit breaker to the trans­former.
Check for proper supply voltage from the transformer and that the transformer has enough
capacity (VA) for all connected devices See their
respective data sheets and Tips for Connecting
24-Volt Power Application Note (AN0604D).

Setpoint Is Not Maintained

Check that room temperature is being sensed correctly. See Temperature Reading Is Incorrect
on page 10.
• Check that the appropriate sequence is selected in the SYSTEM menu. See Change Congura-
tion on page 6 and the relevant sample applica-
tion.
If changeover is used on AI1, check the sensor and the changeover seing in the ADVANCE menu. If a resistor is used on AI1 to force a changeover without a temperature sensor, the value of the resistor may be too high or too low. See External Input (AI1) on page 5, Change
Conguration on page 6, and the relevant sample
application.
If a setback switch/relay is used on AI1, the switch may be (stuck) in the setback position. See
page 36.
If an override switch/relay is used on AO1, the switch may be (stuck) in the override position.
See page 18, page 34, and page 46.
If space temperature is overshooting the setpoint
or oscillating, try increasing the proportional band by a degree in the ADVANCE menu. If the problem persists, try increasing the integral value slightly (up to 20%). If the problem still persists, try seing the integral value to 0. (The
optimal integral value is dependent on the characteristics of the particular space and HVAC
system.) See Change Conguration on page 6.

Temperature Reading Is Incorrect

• Check that the correct °F/C temperature scale
is selected in the SYSTEM menu. See Change
Conguration on page 6.
If the discrepancy is small, adjust the room
temperature oset in the ADVANCE menu. See
Change Conguration on page 6.
• Check that the thermostat is NOT mounted on
an exterior wall, mounted on or near a large thermal mass (e.g., concrete block wall), blocked from normal air circulation by obstructions, exposed to heat sources (e.g., lights, computers, copiers, coee makers) or to sunlight (at any time of the day), exposed to drafts from win­dows or air vents, or exposed to air ow through
the conduit from leaks in plenum ducts (put
plumber’s puy or other sealant inside conduit to block air leaks).

Wiring Issues

Check for correct wiring for the application. See
Connections on page 5 and the various applica-
tion examples in this document.
Remove the thermostat from the backplate and inspect the terminals for loose wires. See the
CTE-5202 Installation Guide.
Check the wiring at the connected devices.
Check seings of auxiliary ow and other limits
as relevant in the LIMITS menu. See Change
Conguration on page 6.
If the HVAC system has trouble recovering from the unoccupied setback to the occupied setpoint during very cold weather, adjust the setback in
the ADVANCE menu. See Change Congura-
tion on page 6.
General Information (All Applications) 10 CTE-5202 Applications Guide, AN0912A Rev. D
• Use a voltmeter and ohmmeter to check the
terminals for expected values.
NOTE: Wiring must be adequate to avoid
excessive voltage drop on long runs! Allow plenty of “cushion” in
measurements A meter may be too slow to register transient dips or peaks during startup.
Single-Zone Proportional Heating and
Cooling Applications
This section gives sample applications for using
the CTE-5202 in single zone proportional heating (baseboard heaters) and cooling (chilled beams) with valves or SCR control.
NOTE: For chilled beam applications, separate
control of humidity is required to prevent condensation.
ReturnFrom Coil
CTE-5202
To Coil Supply
Valve
24 VAC
Common
Input
– ~
Single-Zone Heating and Cooling Applications 11 CTE-5202 Applications Guide, AN0912A Rev. D
Thermostat
T
AI1
AO1
AO2
T
~

Heating, RA and DA

~
(Phase)
CTE-5202 thermostats can use a variety of valves for
heating/cooling applications with hot and chilled
water. For Reverse Acting control, connect a 5K to 10K ohm resistor between Common and AI1. Select
Sequence 1 (from the CTE-5202 SYSTEM menu) and lower the Changeover (in the ADVANCE
menu) to the lowest seing (55° F). See Change
Conguration on page 6. The resistor simulates a
changeover sensor and puts the thermostat in Re­verse Acting mode.
NOTE: If the resistor value is too high, the
thermostat will not go into RA mode. If the resistor value is too low, the thermostat may go into setback mode.
Valve
This RA control works for NO 2–10 and 0–10 VDC valves or NC 10–2 and 10–0 VDC valves as well as equivalent SCR controls.
For Direct Acting control, select Sequence 1 (from the CTE-5202 SYSTEM menu). See Change Con-
guration on page 6. (Do not connect the resistor.)
This DA control works for NC 2–10 and 0–10 VDC valves or NO 10–2 and 10–0 VDC valves as well as equivalent SCR controls.
CTE-5202
Thermostat
T
AO1
AO2
AI1
T
~
Select Sequence 1
10 VDC
24 VAC
Common
Input
24 VA C
(Neutral)
DA Heating
Heating
Valve Closed
Heating
Valve Open
Setpoint
(Colder Room Temperature Warmer)
Select Sequence 1 Select Sequence 1
AO1
Signal
10 VDC
(5K–10K Ohm Resistor between AI1 and Common
for RA Mode Only)
RA Heating
Heating
Valve Open
Heating
Valve Closed
Setpoint
(Colder Room Temperature Warmer)
AND Set Changeover to 55° F
AO1
Signal
Single-Zone Heating and Cooling Applications 12 CTE-5202 Applications Guide, AN0912A Rev. D

Chilled Beam Cooling

This application controls cooling in a chilled beam or equivalent installation.
This works for NC 2–10 and 0–10 VDC valves or NO 10–2 and 10–0 VDC valves.
Valve
24 VAC
Common
Input
24 VA C
(Neutral)
(Phase)
– ~
Select Sequence 1 (from the CTE-5202 SYSTEM menu). See Change Conguration on page 6.
CTE-5202
Thermostat
T
T
AI1
~
Select Sequence 1
AO1
AO2
Cooling Max.
Cooling Min.
Setpoint
(Colder Room Temperature Warmer)
Single-Zone Heating and Cooling Applications 13 CTE-5202 Applications Guide, AN0912A Rev. D

Chilled Beam 4-Pipe Heating and Cooling

This application enables both heating and cooling in a chilled beam and baseboard or equivalent installation.
This works for NC 2–10 and 0–10 VDC valves or NO 10–2 and 10–0 VDC valves.
Cooling Valv e
24 VAC
Common
Input
24 VA C
(Neutral)
(Phase)
– ~
Select Sequence 3 from the CTE-5202 SYSTEM menu. See Change Conguration on page 6.
CTE-5202
Thermostat
T
T
AI1
~
Select Sequence 3
AO1
AO2
AO2 MAX
AO1 MIN
Heating Valv e
24 VAC
Common
Input
AO2 (RA)
AO1 (DA)
2° F 2° F
Heating
Setpoint
Cooling Setpoint
AO2 MIN
AO1 MAX
Temp. Increasing
Single-Zone Heating and Cooling Applications 14 CTE-5202 Applications Guide, AN0912A Rev. D

Chilled Beam 2-Pipe Heating and Cooling with Changeover

An STE-1454/1455 strap-on (Type III) temperature sensor provides the CTE-5202 an automatic change-
over for heating/cooling applications using hot and
chilled water. The sensor will switch the thermostat between cooling and heating modes based on the temperature of the water in the pipe. A water temperature higher than changeover temperature, switches control to heating mode, and a temperature lower than changeover temperature, switches con­trol to cooling mode.
Valve
24 VAC
Common
Input
Select Sequence 1 from the CTE-5202 SYSTEM menu. Change the default changeover temperature to the maximum of 85° in the CTE-5202 ADVANCE menu. See Change Conguration on page 6 and Hot/
Cold Changeover on page 5.
CTE-5202
Thermostat
T
T
AI1
~
Select Sequence 1
AO1
AO2
AO1 MIN
24 VA C
(Neutral)
(Phase)
STE-1454/1455 Strap-On Sensor on Supply Pipe
COLD SEQUENCE
AO1 (DA)
2° F
Setpoint
2° F
– ~
HOT SEQUENCE
AO1 (RA)
AO1 MAX
Temp. Increasing
AO1 MAX
AO1 MIN
2° F
Setpoint
Single-Zone Heating and Cooling Applications 15 CTE-5202 Applications Guide, AN0912A Rev. D
Pressure Dependent VAV
Applications with MEP-4xx2
This section gives sample applications for using the
CTE-5202 with the MEP-4xx2 actuator in pressure dependent VAV applications.
The MEP-4xx2’s default direction is CCW to close (CW to open or CW with increasing voltage), but this can be reversed by a switch during installation and conguration.
See also the MEP-4000 Series Installation Guide.
For additional applications, see Pressure Indepen-
dent VAV Applications with CSP-5001/5002 on page
32 and make the corresponding wiring adjustments
for power to the MEP-4xx2 and CTE-5202.
Damper
24 V AC CTE-5202
MEP-4xx2
SET
POINT
Pressure Dependent VAV Applications with MEP-4002 16 CTE-5202 Applications Guide, AN0912A Rev. D

Cooling or Heating

CTE-5202 thermostats can use MEP-4xx2 actuators to operate damper boxes in a pressure-dependent VAV system. As shown in the diagram, a “requested ow” voltage signal (AO1) is connected to the MEP­4002 to adjust airow from minimum to maximum ow according to space demand. Minimum and maximum ow limit adjustments can be made at the thermostat (recommended) or at the actuator. (See
the MEP-4000 Series Installation Guide.)
For cooling, select Sequence 1 (from the CTE-5202
SYSTEM menu). See Change Conguration on
page 6.
MEP-4002
Actuator
24 VAC
Common
Out
Input
24 VA C @ 5 VA
(Neutral)
(Phase)
– ~
For heating, connect a 5K to 10K ohm resistor between Common and AI1. Select Sequence 1 and lower the Changeover to the lowest seing (55° F).
See Change Conguration on page 6. The resistor simulates a changeover sensor and puts the thermo-
stat in Reverse Acting mode.
NOTE: If the resistor value is too high, the
thermostat will not go into RA mode. If the resistor value is too low, the thermostat may go into setback mode.
CTE-5202
Thermostat
T
T
AI1
~
(5K–10K
Ohm Resistor
between AI1
and Common
for Heating
Mode Only)
AO1
AO2
3300
fpm
1650
fpm
Cooling Min.
0 fpm
Setpoint
(Colder Room Temperature Warmer)
Cooling Air
Select Sequence 1 Select Sequence 1
Cooling Max.
AO1
Signal
3300
fpm
Heating Max.
1650
fpm
0 fpm
(Colder Room Temperature Warmer)
Heating Air
Setpoint
AND set Changeover to 55° F
Heating Min.
AO1
Signal
Pressure Dependent VAV Applications with MEP-4002 17 CTE-5202 Applications Guide, AN0912A Rev. D

Auto and Override (to Fully Closed)

Adding a Normally Closed SPST relay or switch enables overriding the air ow to fully closed. (Otherwise the example below is the same as the conguration in Cooling or Heating on page 17).
The default seing is Auto. When the NC relay energizes, the thermostat signal is removed from the actuator’s input. The resulting 0 VDC “signal” on the actuator’s input overrides the actuator to fully closed.
NC SPST
(Override
to Fully
Closed)
24 VA C @ 5 VA
(Neutral)
(Phase)
– ~
MEP-4002
24 VAC
Common
Actuator
Out
Input
NOTE: An override to fully open does not apply
to the MEP-4xx2 in a way that is analogous to the CSP-5001 as shown in Auto and
Override (to Fully Closed or Fully Open)
on page 34.
CTE-5202
Thermostat
T
Relay
T
AI1
~
(5K–10K
Ohm Resistor
between AI1
and Common
for Heating
Mode Only)
AO1
AO2

Other Applications

See the corresponding application in Pressure
Independent VAV Applications with CSP-5001/5002
on page 32 and make the corresponding wiring adjust-
ments for power to the MEP-4xx2 and CTE-5202. The MEP-4xx2’s default direction is the same as the CSP-5001.
Pressure Dependent VAV Applications with MEP-4002 18 CTE-5202 Applications Guide, AN0912A Rev. D
Loading...
+ 42 hidden pages