KMC Controls CTE-3017, CTE-3026, CTE-3016, CTE-3027 Installation Manual

Low Limit Controllers, DPDT
Installation Guide
CTE-3016/3017/3026/3027
Mounting
The controller can be mounted in any position, but avoid locations subject to excessive vibration. For manual reset models, position the controller to permit convenient access to the reset buon.
1. Loosen the front screw and remove the cover.
2. Using the two 3/8" mounting keyholes, mount the case ush against the duct work or any at surface.
3. Install the sensing capillary in a horizontal serpentine fashion across the downstream side of a water coil.
4. Using the included HMO-4523 capillary clips, support the sensing capillary at sucient points to prevent damage from vibration and/or air movement.
CAUTION
Do not kink or apply excessive force to the capillary element.
5. Make the appropriate connections to the terminal blocks. (See the Wiring section.)
Wiring
An opening for installing a connector for 1/2" conduit is provided in the boom of the case.
All wiring should comply with national and local electrical codes. Using 14 AWG solid copper wire is recommended.
Strip wire ends 3/8", insert the wire ends under the cup washers on the switch block, and securely retighten terminal screws. Wire terminals according
to the Actuation and Reset section on the next page.
CTE-3016/3017/3026/3027 1 Installation Guide
CTE-3017 Shown
Actuation and Reset
Specifications
Terminals 11 and 21 are “common” terminals, 14 and 24 are Normally Closed (above setpoint), and 12 and 22 are Normally Open (see the diagram below). When the sensed temperature falls below setpoint, connections “11–14” and “21–24” open and connections “11–12” and “21–22” close. The switch
latches in this position until the sensed temperature rises 5° F (3° C) above setpoint and the controller is reset either (depending on the model) automatically or manually by depressing the reset buon located in the top of the controller case.
The controller cannot be manually reset until the sensed temperature is at least 5° F (3° C) above the setpoint.
22 (NO)
24 (NC)
21
(Common)
(Connections Shown in Above-Setpoint, NC, Unactuated Position)
11
(Common)
12 (NO, Closes on Low Temp.)
14 (NC, Opens on Low Temp.)
Setpoint Adjustment
The setpoint is the temperature at which contacts “11–14” and “21–24” open as the unit senses a fall in temperature. To adjust the setpoint:
• Turn the range adjustment screw CW to decrease the setpoint.
• Turn the range adjustment screw CCW to increase the setpoint.
Range 34° to 70° F (1.1° to 21° C)
Dierential 4.5° F xed (2.5° C) Switch Action DPDT
Element
Electrical Ratings
Inductive 14 FLA (Full Load Amperes)
84 LRA (Locked Rotor
3/4 HP @ 120 VAC, 2 HP @ 240
Pilot Duty 720 VA max. @ 120 to 600 VAC,
Approvals CUL US Listed, CE Compliant,
Weight 1.2 lbs. (0.54 kg)
Materials Plated steel case, plastic cover
Mounting Surface mount with capillary
Temperature Limits
Operating –60 to 160° F (–51 to 71° C) Shipping –60 to 160° F (–51 to 71° C)
NOTE: See the CTE-3016/3017/3026/3027 Data
3/32" (2.4 mm) diameter, 6-foot
(183 cm) or 20-foot (607 cm) length, vapor-lled, tin-plated copper capillary, maximum temperature 300° F (149° C)
@ 120 VAC, 12 FLA @ 240 VAC
Amperes) @ 120 VAC, 72 LRA @ 240 VAC
VAC
144 VA max. @ 24 VAC
RoHs compliant
installed in horizontal serpen­tine paern
Sheet (717-035-21) for more information.
Testing
A manual test lever located under the cover (below and to the le of the controller spring) allows the unit to be manually actuated during system tests.
Accessories
HMO-4523 Capillary Clip (3 or 5 provided,
depending on length)
Maintenance
No routine maintenance is required. Each compo­nent is designed for dependable, long-term reliabil­ity, and performance. Careful installation will also ensure long-term reliability and performance.
© 2010 KMC Controls, Inc. 717-019-21B
CTE-3016/3017/3026/3027 2 Installation Guide
Important Notices
The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warran­ties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this document.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250
www.kmccontrols.com; info@kmccontrols.com
Loading...