Mounting
One-Pipe, Single-Setpoint, Pneumatic, Room Thermostats
CTC-1611/1612
Installation Guide
Location
For optimum performance, the thermostat must be
mounted on an interior wall and away from heat
sources, sunlight, windows, air vents, and air circulation obstructions (e.g., curtains, furniture). Units may
be mounted horizontally or vertically to either a 2" x
4" electrical box or a hollow wall.
CTC-1611/1612 Back
Electrical Box Mounting
1. Aach the desired HMO-50xx backplate to the
box with the two 6-32 screws supplied.
2. Level the box using the slot in the backplate.
3. Fit the aluminum plate into the recess.
4. Pass the 3/32" ID tubing through access hole.
5. Make connections (see Connections section).
6. Mount the thermostat to the backplate with two
6-20 x 2" screws supplied with thermostat.
HMO-50xx
2. Loosely mount the bracket to the thermostat with
two 6-32 x 2" screws supplied.
3. Make connections (see Connections section).
4. Insert the bracket diagonally through the wall.
5. Center the thermostat and tighten the screws.
Scale Plate
All adjustments must be made with the scale plate
removed. Complete adjustments before installing the
scale plate. (See Adjustments section.)
1. Remove the gauge tap’s rubber cap.
2. Slide the scale plate under the setpoint indicator.
3 Insert the retaining pins (two supplied), twisting
to lock into place.
4. Reinstall the gauge tap’s rubber cap.
Setpoint Options
If setpoint indicator is not needed, simply snip o
the indicator with a wire cuer. Limit or lock the
range of the setpoint by installing setpoint stops
(HFO-0027) in the slider track.
Cover
Covers are available in 2 styles:
♦ Window-insert covers include a symbol-coded
label strip (HPO-1320) for setpoint indication.
Apply the label in the recessed area underneath
the window.
♦ Blank covers require the removal of the setpoint
thumb adjuster. Insert a small screwdriver in the
slot between the thumb adjuster and the cam and
pry apart. Discard the adjuster.
To install a cover:
1. Check that the thermostat is mounted securely
and gauge tap cap and accessories are installed.
Hollow Wall Mounting
NOTE: Thermostats may be mounted on hollow
walls up to 5/8" with the HMO-5023 kit.
1. Using the template, printed on the HMO-5023
package, make a 2-11/16" x 1-1/2" cutout.
CTC-1611/1612 1 Installation Guide
2. Slide the cover over the base.
3. Using a 1/16" hex wrench, turn both cover
mounting screws on the thermostat base CCW
(outward) until the cover is secured. (See the
illustration in the Adjustments section.)
Connections
The CTC-1611/1612 requires an HFO-0028 tubing kit
and a 14.4 scim restrictor T.
1. Insert the restrictor into the HFO-0028 tubing.
2. Connect the restrictor to Port T1.
3. Connect the open side of the T with tubing to the
nal device actuator (DA unit for the CTC-1611
or RA unit for the CTC-1612).
Adjustments
6. Replace the gauge tap rubber cap aer
calibrating.
7. Place the setpoint slider to the desired
temperature and replace the cover.
Throttling Range
Throling range is the temperature required to
change the thermostat output pressure from 3–15 psi.
All CTC-1600 series thermostats are factory-set for
a 3° F throling range. The approximate throling
range seing is stamped on each lever in both °F and
°C. If it is necessary to change this seing, reverify
calibration aer adjustment.
1. Remove scale plate (see the Scale Plate section).
2. Slide the black TR adjuster to appropriate value/
location.
NOTE: The hole in the TR adjuster ts a 1/16" hex
wrench. Gently rotate the adjuster back and
forth while sliding. Do not turn excessively!
3. Rotate back to a “square” position aer adjustment.
4. Reinstall the scale plate.
Calibration
These thermostats are factory calibrated and do not
require further calibration at installation. Should it
be necessary to change calibration:
1. Remove the cover and gauge tap rubber cap.
2. Install a gauge on the gauge tap using 3/32" ID
tube.
3. Measure the ambient temperature with an
accurate thermometer.
4. Move the setpoint slider to the measured ambient
temperature.
5. Use a 1/16" hex wrench and turn the calibration
adjustment until the test gauge indicates the
desired pressure. (Clockwise rotation decreases
the output pressure.)
Maintenance
Remove dust as necessary from the slots. Clean the
window with so, damp cloth and mild soap.
Care should be taken to keep the unit clean
from dust during installation. Each component is
designed for dependable, long-term reliability, and
performance. Careful installation will also ensure
long-term reliability and performance.
Important Notices
For specications and accessories, see the CTC-
1611/1622 Data Sheet on the KMC web site.
The material in this document is for information purposes only. The contents and the product it describes
are subject to change without notice. KMC Controls,
Inc. makes no representations or warranties with respect
to this document. In no event shall KMC Controls, Inc.
be liable for any damages, direct or incidental, arising
out of or related to the use of this document.