the primary input (Port 1) that causes a
100% change in the branch output (Port B).
Authority is the change in the secondary
input (Port 3) in relation to the change in
the primary input that will cause the same
change in the output and is expressed as a
percentage (see the Authority Calibration
section).
1. Remove cover before making any adjustments.
2. Set the desired throling range:
A. Loosen large center screw (1 turn
maximum).
B. Remove main control air from Port M.
C. Move the setpoint indicator to the desired
% throling range (4 to 40%) on the DA
or RA scale. See the Throling Range
Adjustment section on page 3.
D. Connect main air to “M.”
3. Set the desired authority:
A. Calculate the required authority. See the
Authority Calibration section.
B. Set the authority indicator to the desired
value.
C. Tighten center screw.
4. Adjust the setpoint output by turning the setpoint
screw (located at the lower right of the unit). See
the Setpoint Calibration section on page 3.
5. Reinstall the cover.
CCC-1002 Controller
NOTE: Follow the steps 1 through 4 for adjusting
the CCC-1001, and then continue with steps
5 through 8.
Throttling Range Adjustment
Throling range % can be calculated by the following formula:
Port 1 Units Desired to Make
100% Change in Port B (Output)
Port 1 Primary Input Span
(Same Units as Above)
x
Span of Controlled
12
x 100
Device (psi)
Example: Port 1 is connected to a temperature
transmier with a range of 40 to 240° F
(200° F span). Branch output is controlling
a 3 to 8 psi (5 psi span) device. Desired
throling range is 20° F. Then throling
range % = (20° F)/(200° F) x (12 psi)/(5 psi) x
100 = 24%.
Authority Calibration
This adjustment determines the eect of a secondary
transmier (Port 3) on the setpoint of the receivercontroller.
Example: Reset the HWS (Hot Water Supply)
temperature setpoint based on OAT
(Outside Air Temperature). The HWS
transmier has a range of 40 to 240° F for 3
to 15 psi (0.06 psi/° F), and it is connected
to the Port 1 primary input. The OAT
transmier has a range of –40 to 160° F for 3
to 15 psi (0.06 psi/° F), and it is connected to
the Port 3 secondary input.
NOTE: This example does not compensate for TR
(throling range) across the reset schedule
but assumes a constant branch pressure.
The reset schedule shows the temperatures and pressures at the extreme ends of the operating schedule.
5. Turn the face dial until the desired input signal
(Port 1) pressure value lines up with the clear
arrow indicator.
6. Carefully slide the cover straight down, so that
the cover gear teeth and the setpoint adjustment
sha mesh.
Initial setpoint calibration is done aer the spring
tube on the back of the controller has been properly
connected and secured and the throling range and
authority adjustments have been set and locked.
1. Make the following connections:
A. Main air supply (20 psi) to MAIN.
B. Branch (output) gauge to Port B.
C. For SINGLE input operation, connect
pressure to Port 1 equal to the desired
setpoint, OR for DUAL input operation,
connect pressures to Ports 1 and 3 that
correspond to the reset schedule at
approximately midrange.
D. If the remote setpoint adjustment is to
be used, connect pressure to Port 2 that
corresponds to zero oset.
E. Unused inputs are le unconnected.
2. Turn the setpoint adjustment screw to obtain an
output equal to the midrange pressure of the
controlled device.
A. If in the DA mode and branch pressure
is high, turn the setpoint screw CW; if
branch pressure is low, turn the setpoint
screw CCW.
B. If in the RA mode and branch pressure
is high, turn the setpoint screw CCW; if
branch pressure is low, turn the setpoint
screw CW.
Aer the system is live, minor adjustments to the
setpoint calibration can easily be done if the setpoint
oset is known. Each complete clockwise rotation, of
the screw, is equivalent to a 1.75 psi increase in Port
1 pressure. To increase the setpoint, turn the adjustment screw CW; to decrease the setpoint, turn the
adjusment screw CCW. The number of turns equals:
Setpoint Offset (° F)
Port 1 Primary Input Span
(° F)
Port 1 Primary Input Span (psi)
x
1.75
Remote Setpoint Adjustment
An input pressure change of 3 to 15 psi to Port 2 will
change the setpoint 20% of the span of the primary
transmier. The eect of the change is direct in
nature. An increase in Port 2 pressure from 9 to 15
psi increases the setpoint 10% and a decrease in Port
2 pressure from 9 to 3 psi decreases the setpoint 10%.
Example: If the Port 1 transmier has a range of 40
to 240° F (200° F span), then the remote
setpoint adjustment pressure on Port 2 can
change the setpoint +/– 20° F or a total of
40° F or 20% of the Port 1 primary input
span.
Accessories
External restrictor HFO-0022 (Restrictor T, 28.8 scim)
might be required if replacing a receiver/controller
using internal restrictors. All transmiers used with
the CCC-1001/1002 require an external restrictor.
For other pneumatic accessories, such as connectors,
tubing, ings, lters, and gauges, see the Compressed Air Accessories section in the Electronic and
Pneumatic Controls Condensed Catalog (SP-071).
Maintenance
No routine maintenance is required. Each component is designed and manufactured for reliability
and performance. Careful installation will ensure
long term dependability.
Example: Port 1 is connected to a temperature
transmier with a range of 40 to 240° F
(200° F span) and an output of 3 to 15 psi
(12 psi span). The desired control point is
7° F higher than the actual control point.
Then, the number of turns = (7°)/(200°)
x (12 psi)/1.75 = 0.24. Thus, the set point
adjustment screw should be turned 1/4 of a
turn CW.