KMC Controls BAC-4000 series Installation, Operation, And Application Manual

Page 1
Installation, Operation, and Application Guide
for
AppStat™
BAC-4000 series controllers for
Fan Coil Units, Roof Top Units, and Heat Pump Units.
Revision G
Page 2
Installation, Operation, and Application Guide for AppStat
©2014, KMC Controls, Inc.
NetSensor, WinControl, and the KMC logo are registered trademarks of KMC Controls, Inc.
AppStat, BACstage, FlexStat, FullBAC, TotalControl, SimplyVAV, and the SimplyVAV logo are trademarks of KMC Controls, Inc.
All rights reserved. No part of this publication may be reproduced, transmitted, transcribed, stored in a retrieval system, or translated into any language in any form by any means without the written permission of KMC Controls, Inc.
Printed in U.S.A.
The material in this manual is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this manual. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this manual.
KMC Controls, Inc.
19476 Industrial Drive New Paris, IN 46553 U.S.A. TEL: 1.574.831.5250 FAX: 1.574.831.5252 E-mail: info@kmccontrols.com
2 Revision G
Page 3
Installation, Operation, and Application Guide for AppStat Contents

C o n t e n t s

Contents 3
Section 1: Introduction to the AppStat 7
Specifications 8 Installation accessories 12 AppStat model numbers 13 Safety considerations 16
Section 2: Installing the AppStat 17
Planning for motion sensing 17 Mounting the AppStat 18
Rough-in preparation 19 Installing the AppStat 19
Connecting inputs 20
Remote space temperature sensor (optional) 20 Discharge air temperature sensor 21 Fan status switch (optional) 21 Water temperature sensor 22 Outside air temperature 23
Connecting outputs 24
Connecting to a three-speed fan 24 Connecting to a modulating fan 25 Connecting on/off valves 26 Connecting to modulating valves 27
Connecting an economizer 28 Connecting power 28 Maintenance 29
Section 3: User functions 31
Operating the AppStat 31 Entering a user password 34 Changing the active setpoints 35 Setting the operating modes 36
Section 4: Commissioning functions 39
Enter the commissioning mode 40 Setting the commissioning setpoints 41 Set up communications 43 Set the time and date 45 Setting the occupancy schedule 47 Set fan coil unit system options 50 Set roof top unit system options 53 Set heat pump unit system options 56
Revision G 3
Page 4
Contents KMC Controls, Inc.
Advanced options 60
Section 5: Sequences of operation 65
Room temperature setpoints 66
Types of setpoints 66
Setpoint limits 67 Occupancy, motion sensing, and standby 67 Automatic cooling and heating changeover 68 Scheduling occupancy 68 Dehumidification sequence 68 Fan status 68 Display blanking and backlight 69 Temperature sensing inputs 69
Space temperature sensing 69
Outside air temperature sensing 69
Water temperature sensor 69
Discharge air temperature sensor 70 PID control loops 70 Valve operation for fan coil units 70
On/Off valves 70
Modulating valves 71
Two-pipe water supply temperature evaluation 71 Electric heat for fan coil units 72 Fan operation for fan coil units 72
One, two, and three speed fans 72
Modulating fans 72
Automatic fan control 73 Modulating cooling and heating for Roof Top Units 73
Cooling 73
Heating 73
Valve action 73 Staged heating and cooling for for roof top and heat pump units 74
Staged cooling 74
Staged heating 74 Fan control for roof top and heat pump units 74 Economizer cooling for roof top and heat pump units 75 Heat pump unit specific functions 75
Reversing valve action 75
Auxiliary or emergency heat action 75
Section 6: Application drawings 77
Fan Coil Unit applications 78
Fan Coil Unit—Four-pipe with three-speed fan and on/off valves 78
Fan Coil Unit—Four-pipe with three-speed fan and modulating valves 80
Fan Coil Unit—Four-pipe with modulating fan and on/off valves 82
Fan Coil Unit—Four-pipe with modulating fan and modulating valves 84
4 Revision G
Page 5
Installation, Operation, and Application Guide for AppStat Contents
Fan Coil Unit—Two-pipe with three-speed fan and on/off valves 86 Fan Coil Unit—Two-pipe with three-speed fan and modulating valve 88 Fan Coil Unit—Two-pipe with modulating fan and on/off valve 90 Fan Coil Unit—Two-pipe with modulating fan and modulating valve 92 Fan Coil Unit—Two-pipe with three-speed fan, modulating valve, and electric heat 94 Fan Coil Unit—Two-pipe with modulating speed fan, modulating valve, and electric heat 96
Roof Top Unit applications 98
Roof Top Unit—Two-stage gas heat and two-stage DX cooling 98 Roof Top Unit—Two-stage gas heat and two-stage DX cooling with economizer 100 Roof top unit—Cooling and heating with modulating valves and economizer 102 Roof Top Unit—Two-stage gas heat, chilled water cooling with modulating valve and economizer 104 Roof Top Unit—Two-stage DX cooling, hot water heating with economizer 106
Heat Pump Unit applications 108
Heat pump unit—Three heat, two cool 108 Heat Pump Unit—Three heat, two cool and economizer 110
Section 7: System integration 113
BACnet objects 114
Input objects 114 Output objects 115 Value objects 117 Schedule object 119 Loop objects 119
Connecting to an MS/TP network 121
Index 125
Revision G 5
Page 6
Contents KMC Controls, Inc.
6 Revision G
Page 7
Installation, Operation, and Application Guide for AppStat

Sec tion 1: Introductio n to t h e A ppSt at

This section provides a description of the BAC-4000 series of controllers KMC Controls, Inc.. It also introduces safety information. Review this material before installing or operating the controllers.
The BAC-4000 series of controllers are space mounted devices that combine a BACnet controller with temperature, humidity and motion sensors. The controllers include programs for the following applications.
Roof top units, both single or multi-stage, or similar split or unitary packaged systems
Heat pumps
Two and four pipe fan coil units
The AppStat controllers are native BACnet, Application Specific Controllers. BACnet communication parameters, device instance, MAC address, baud rate, room occupant adjustments, and application configuration values are set from password protected front panel controls.
All models feature an integrated BACnet schedule and hardware real-time clock with 72-hour capacitor backup for standalone operation or network time synchronization.
A two-piece mechanical design, featuring a removable backplate, facilitates easy wiring and installation.
Revision G 7
Page 8
Section 1: Introduction to the AppStat KMC Controls, Inc.

Specifications

AppStat specifications are subject to change without notice.
User Interface
The user interface is a color display and with five push buttons. Through the menu driven display, an operator can do the following.
Add or change user passwords
Change setpoints
Set BACnet addressing
Set up and commission the installation
Configure any available options
Security
Separate passwords for users and controls technicians.
Display type
128 × 128 pixels
Active color LCD with LED back lighting
1.00 x 1.04 inches (25 x 26 mm)
Inputs and outputs
All inputs and outputs are preprogrammed and application specific. No field configuration is required for most installations. For details on input and output connections see the section Application drawings on page 77.
Analog inputs
Analog inputs represent BACnet analog input objects and are configured for discharge air temperature, remote temperature sensor, water temperature sensor, and fan status. Not all input sensors are applicable or required for all models.
Sensors are automatically detected.
Inputs accept industry-standard 10,000 Ω, Type II or Type III thermistors sensors.
Input overvoltage protection up to 24 volts AC, continuous.
12-bit analog-to-digital conversion
Analog outputs
Analog outputs are configured to represent BACnet analog objects. The outputs control modulating valves, variable speed fans, damper positions or other equipment that requires a proportional input signal.
8 Revision G
Page 9
Installation, Operation, and Application Guide for AppStat Section 1: Introduction to the AppStat
Short-circuit protected
Loads up to 10 mA at 0–12 volts DC
8-bit PWM digital-to-analog conversion
Relay outputs
Relay outputs are configured to represent BACnet binary objects. The outputs control on/off valves, speeds for three-speed fans, fan start circuits, or other equipment that requires an on or off input signal.
All relay outputs are normally open, SPST, Form “A” relays
1 Ampere maximum per relay at 24 volts AC or DC for each output. Maximum for all relay outputs is 3 amperes (72VA).
Connectors
Screw terminal block mounted to backplate
Wire size 14-22 AWG
Communications—BACnet MS/TP
Integral peer-to-peer BACnet MS/TP network communications.
Network speeds from 9600 to 76,800 baud.
Front panel configurable device instance, MAC address, and baud.
Automatic baud detection.
Screw terminal block mounted to backplate. Wire size 14–22 AWG
Meets or exceeds ANSI/ASHRAE BACnet Standard 135-2008 for Application Specific Controllers
Accuracy–temperature only models
Type Thermistor
Accuracy ±0.36° F (±0.2° C)
Resistance 10,000 Ω at 77° F (25° C)
Operating range 48 to 96° F (8.8 to 35.5° C)
Accuracy–temperature and humidity models
Temperature Sensor
Type CMOS
Accuracy ±0.9° F offset (±0.5° C) from 40° to 104° F
(4.4 to 40° C)
Resolution ±0.1°F (±0.1° C)
Operating range 36 to 120° F (2.2 to 48.8° C)
Response time 5 to 30 seconds
Revision G 9
Page 10
Section 1: Introduction to the AppStat KMC Controls, Inc.
Humidity Sensor
Type CMOS
Humidity 0 to 100% RH
Accuracy at 25° C ± 2% RH from 10 to 90% RH
Response time 4 seconds or less
Regulatory
UL 916 Energy Management Equipment
FCC Class A, Part 15, Subpart B and complies with Canadian ICES-003 Class B
BACnet Testing Laboratory listed as an application specific controller
SASO PCP Registration KSA R-103263
This device complies with part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation.
Environmental limits
Operating 32 to 120° F (0 to 49° C)
Shipping –40 to 140° F (–40 to 60° C)
Humidity 0–95% relative humidity
(non-condensing)
Installation
Supply voltage 24 volts AC (–15%, +20%), 50-60 Hz, 12 VA, Class 2
only, non-supervised. All circuits, including supply voltage, are power limited circuits.
Weight Approximately 6 ounces (170 grams)
Case material Flame retardant plastic
10 Revision G
Page 11
A
B
C
Installation, Operation, and Application Guide for AppStat Section 1: Introduction to the AppStat
Dimensions
Table 1–1 AppStat Dimensions
A B C
3.50 in. 5.12 in. 1.12 in.
89 mm 130 mm 29 mm
Motion sensor
Motion sensors are options available only on select models.
Detector type Passive infrared
Range 33 feet (10 meters). See the following
diagrams.
Revision G 11
Page 12
10 m
32.8 ft
10 m
32.8 ft
46.5
°
Y
55
°
10 m
32.8 ft
10 m
32.8 ft
X
Side viewTop view
Section 1: Introduction to the AppStat KMC Controls, Inc.

Installation accessories

The following accessories are available from KMC Controls, Inc.
XEE-6111-040 Single-hub 120 volt power transformer
XEE-6112-040 Dual-hub 120 volt power transformer
XEE-6311-075 120/240/277/480VAC, 24 VAC, 75 VA transformer
HMO-10000W White mounting plate kit for retrofit on horizontal
boxes or 4 x 4 handy boxes
12 Revision G
Page 13
BAC-4 _ _ _ CW0001
1 3-speed fan, On/off valves 2 3-speed fan, Modulating valves 3 3-speed or modulating fan, modulating or On/Off valves 7 Modulating fan, On/Off valves 8 Modulating fan, Modulating Valves
0 Without humidity 2 With humidity
0 Without motion 2 With motion
Installation, Operation, and Application Guide for AppStat Section 1: Introduction to the AppStat

AppStat model numbers

Use the following charts to identify features in a specific AppStat model.
Fan coil units—The model numbers for these controllers end with "0001".
The inputs, outputs, and sequences of operation are configured and programmed for the following functions.
Two-pipe heating and cooling with on/off valves, modulating valves or both
Four-pipe heating and cooling with on/off valves, modulating valves or both
Three-speed or modulating fan control
Automatic or manual fan control
Remote space temperature sensor
Local temperature setback mode based on optional built-in motion sensor
Dehumidification on models with humidity sensor
See the following chart for the specific features included with each model.
Illustration 1–1 Model numbers for fan coil units
Revision G 13
Page 14
BAC-4 _ _ _ CW0002
1
2H/2C On/off valves or stages
3 2H/2C On/off or modulating valves
and economizer
0 Without humidity 2 With humidity
0 Without motion 2 With motion
Section 1: Introduction to the AppStat KMC Controls, Inc.
Roof top units—The model numbers for these controllers end with "0002".
These models control roof top or similar packaged or split unitary units. The inputs, outputs, and sequences of operation are configured and programmed for the following functions.
Automatic or manual fan control
Modulating valves or on/off heating and cooling valves.
One or two stage heating
One or two stage cooling
Optional economizer
Remote space temperature sensor
Local temperature setback mode based on optional built-in motion sensor
Dehumidification on models with humidity sensor
See the following chart for the specific features included with each model.
Illustration 1–2 Model numbers for roof top units
14 Revision G
Heat pump units—The model numbers for these controllers end with "0003".
The inputs, outputs, and sequences of operation are configured and programmed for the following functions.
Two stages of heat and two stages of cooling plus auxiliary heat
Optional economizer
Dehumidification-in models with auxiliary heat and a humidity sensor
Local temperature setback mode based on optional built-in motion sensor
Automatic or manual fan control
Page 15
BAC-4 _ _ _ CW0003
1
3H/2C
3 3H/2C and economizer
0 Without humidity 2 With humidity
0 Without motion 2 With motion
Installation, Operation, and Application Guide for AppStat Section 1: Introduction to the AppStat
See the following chart for the specific features included with each model.
Illustration 1–3 Model numbers for heat pump units
Revision G 15
Page 16
Danger
Warning
Caution
Section 1: Introduction to the AppStat KMC Controls, Inc.

Safety considerations

KMC Controls, Inc. assumes the responsibility for providing you a safe product and safety guidelines during its use. Safety means protection to all individuals who install, operate, and service the equipment as well as protection of the equipment itself. To promote safety, we use hazard alert labeling in this manual. Follow the associated guidelines to avoid hazards.
Danger represents the most severe hazard alert. Bodily harm or death will occur if danger guidelines are not followed.
Warning represents hazards that could result in severe injury or death.
Caution indicates potential personal injury, equipment damage, or property damage if instructions are not followed.
Note: Notes provide additional information that is important.
Tip: Provides programing tips and shortcuts that may save time.
16 Revision G
Page 17
Installation, Operation, and Application Guide for AppStat

Sec tion 2: Installing the AppS tat

This section provides important instructions and guidelines for installing the AppStat. Carefully review this information before installation begins.
Installing the sensors includes the following topics that are covered in this section.
Planning for motion sensing on page 17
Mounting the AppStat on page 18
Connecting inputs on page 20
Connecting outputs on page 24
Connecting power on page 28
Maintenance on page 29

Planning for motion sensing

For models with a motion sensor mount the AppStat on a wall that will have an unobstructed view of the typical traffic in the coverage area. When choosing a location, do not install the sensor in the following areas.
Behind curtains or other obstructions
In locations that will expose it to sunlight or heat sources
Near a heating or cooling inlet or outlet.
For details on the coverage pattern, see Specifications on page 8.
Illustration 2–1 Typical motion sensing coverage area
Revision G 17
Page 18
Section 2: Installing the AppStat KMC Controls, Inc.
The effective detection range is approximately 10 meters or 33 feet. Factors that may reduce the range include:
The difference between the surface temperature of the object and the background temperature of the room is too small.
Object movement in a direct line toward the sensor.
Very slow or very fast object movement.
Obstructions as shown in the illustration Typical motion sensing coverage
area on page 17.
False detections may be triggered by:
The temperature inside the detection range suddenly changes because of the entry of cold or warm air from an air-conditioning or heating unit.
The sensor being directly exposed to sunlight, an incandescent light, or other source of far-infrared rays.
Small animal movement.

Mounting the AppStat

For the most accurate performance, install the AppStat on an inside wall where it can sense the average room temperature. Avoid locations with direct sunlight, heat sources, windows, air vents, and air circulation or obstructions such as curtains, furniture, etc.
The AppStat must not be:
Mounted on an exterior wall.
Mounted on or near an object with large a thermal mass such as a concrete block wall.
Blocked from normal air circulation by obstructions.
Exposed to heat sources such as lights, computers, copiers, or coffee makers, or to direct sunlight at any time of the day.
Exposed to drafts from windows, diffusers, or returns.
Exposed to air flow through connecting conduits or empty spaces behind walls.
For models with motion sensing, see the topic, Planning for motion sensing.
18 Revision G
Page 19
A
5.12 in.
130 mm
3.50 in. 89 mm
Inputs and
network
Power and outputs
Turn clockwise to remove from base.
Installation, Operation, and Application Guide for AppStat Section 2: Installing the AppStat

Rough-in preparation

Complete rough-in wiring at each location before mounting an AppStat. This includes the following steps.
Install the supplied mounting base directly to a wall, a vertical electrical box, or a box with a wall plate kit.
Routing the connecting cable or cables from the AppStat to the equipment it is controlling.
If required, install an appropriate wall plate kit.
Block leaks and airflow from conduits with plumber’s putty or similar material.
If replacing an existing thermostat, label existing wires for reference when removing the existing thermostat.
Illustration 2–2 AppStat mounting base details

Installing the AppStat

To install the controller on a mounting base, do the following:
1. Turn the Allen screw in the base of the sensor clockwise until it clears the case.
2. Swing the AppStat away from the mounting base to remove it.
3. Route wiring for the AppStat through the mounting base.
Revision G 19
Page 20
Turn counterclockwise until the screw engages the base.
Caution
Section 2: Installing the AppStat KMC Controls, Inc.
4. Position the base with the embossed UP toward the ceiling and fasten it directly to a vertical 2x4 inch electrical box. For horizontal boxes or 4x4 applications, use a wall plate kit. See Installation accessories on page
12 for part numbers.
5. Connect the wires for the AppStat to the terminals in the mounting base.
6. Place the top of the sensor over the top of the mounting base and swing it down over the Allen screw bracket. Be careful not to pinch any wiring.
7. Turn the Allen screw counterclockwise until it backs out of the mounting base and engages the case.
To prevent mounting screw heads from touching the circuit board in the controller, use only the mounting screws supplied with the controller. Using screws other than the type supplied may damage the AppStat.

Connecting inputs

The inputs for the AppStat are configured for specific functions and do not require set up in the field. Not all inputs are required for every model or application. See the topic BACnet objects on page 114 for the configuration properties of the input objects.

Remote space temperature sensor (optional)

Connect a 10kΩ, TypeII thermistor temperature sensor to the remote space temperature (RS) input and ground (GND) terminals. The input includes the internal pull-up resistor. An STE-6011W10 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation.
When a remote space temperature input is connected to the AppStat, the remote temperature is used instead of the internal temperature sensor.
20 Revision G
Page 21
STE-6011W10
or equivalent
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
STE-1405 or
equivalent
DAT
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 2: Installing the AppStat
Illustration 2–3 Wiring for remote space temperature sensor

Discharge air temperature sensor

Connect a 10kΩ, Type III thermistor temperature probe to the discharge air temperature (DAT) input. The input includes the internal pull-up resistor. An STE-1405 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation.
Illustration 2–4 Wiring for Discharge Air Temperature Sensor

Fan status switch (optional)

Connect a Normally Closed Fan Status switch to the Discharge Air
Revision G 21
Temperature (DAT) input and ground (GND) terminals. The input includes the internal pull-up resistor. A CSE-1102 differential pressure switch is
Page 22
FST
N.C Fan Status
CSE-1102
FAN
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Section 2: Installing the AppStat KMC Controls, Inc.
suitable for this application. Follow the instructions supplied with the switch for installation.
Illustration 2–5 Wiring for a fan status switch

Water temperature sensor

Connect a 10kΩ, Type III thermistor temperature probe to the water temperature (WST) input. The input includes the internal pull-up resistor. An STE-1455 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation.
Note: The water temperature sensor is a required input sensor for 2-pipe fancoil
units.
22 Revision G
Page 23
STE-1455 or
equivalent
WST
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
STE-1451 or equivalent
MS/TP
+B
A
RS
OAT
GND
DAT
ECON
G
Y1
Y2
RC
W1
W2 RH
AO6
AO7
COM
24VAC
OAT
Installation, Operation, and Application Guide for AppStat Section 2: Installing the AppStat
Illustration 2–6 Wiring for a water temperature sensor

Outside air temperature

Connect a 10kΩ, Type III thermistor temperature probe to the outside air temperature (OAT) input. The input includes the internal pull-up resistor. An STE-1451 sensor is suitable for this application. Follow the instructions supplied with the sensor for installation.
Illustration 2–7 Wiring for an outside air temperature sensor
Revision G 23
Page 24
Caution
Section 2: Installing the AppStat KMC Controls, Inc.

Connecting outputs

The AppStat outputs are model dependent and are configured for specific applications.
No field programming or set up is required or possible.
Depending on model and application, the AppStat outputs are designed for either 24 voltAC or 0-10 voltDC loads.
The outputs may represent analog or digital signals.
See the topic BACnet objects on page 114 for the configuration properties of the output objects.
Improperly connecting loads or equipment to output terminals may damage the equipment. Connect only as shown in the following diagrams or application drawings.

Connecting to a three-speed fan

The following diagram shows the connections for a three-speed fan. The fan circuits must be a 24-volt AC pilot duty only.
For a single-speed fan, use only the FAN-L connection.
For a two-speed fan, use the FAN-L and FAN-H connections.
For a three-speed, use FAN-L, FAN-M, and FAN-H
24 Revision G
Page 25
High
Med
LoW
Com
24 VAC
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 2: Installing the AppStat
Illustration 2–8 Connections to a three-speed fan

Connecting to a modulating fan

The following diagram shows the connections for a modulating speed fan.
The fan start circuit must be a 24-volt AC circuit. Connect it to the FAN-L output.
The speed control is a 0-10 volt DC analog output.
Revision G 25
Page 26
Speed
Start
Com
24 VAC
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Cooling Heating
24 VAC
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Section 2: Installing the AppStat KMC Controls, Inc.
Illustration 2–9 Connections for a modulating fan

Connecting on/off valves

The following diagram shows the connections on/off valves.
The valves are activated by 24-volts AC.
The outputs are 24-volt relays.
Illustration 2–10 Connections to on/off valves
26 Revision G
Page 27
0-10 VDC
0-10 VDC
Cooling Heating
24 VAC
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 2: Installing the AppStat

Connecting to modulating valves

The following diagram shows the connections for a modulating mixing valves. The valve control signal is a 0-10 volt analog output.
Illustration 2–11 Modulating heating and cooling valves
Revision G 27
Page 28
0-10
VDC
24 VAC
MS/TP
+B
A
RS
OAT
GND
DAT
ECON
G
Y1
Y2
RC
W1
W2 RH
AO6
AO7
COM
24VAC
Section 2: Installing the AppStat KMC Controls, Inc.

Connecting an economizer

The following diagram shows the connections for an economizer. The damper control signal is a 0-10 volt analog output.
Illustration 2–12 Wiring for an economizer

Connecting power

The AppStat requires an external, 24 volt, AC power source. Use the following guidelines when choosing and wiring transformers.
Use only a Class-2 transformer of the appropriate size to supply power.
KMC Controls recommends powering the AppStat from a dedicated controls transformer.
Connect the transformer’s neutral lead to the COM terminal.
Connect the AC phase lead to the 24VAC terminal.
Power is applied to the controller when the transformer is powered.
See Installation accessories on page 12 for a list of transformers available from
28 Revision G
KMC Controls, Inc.
Page 29
24 VAC Class-2
Controls
transformer
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 2: Installing the AppStat
Illustration 2–13 Wiring for AppStat power

Maintenance

Remove dust as necessary from the holes in the top and bottom. Clean the display with soft, damp cloth and mild soap.
Revision G 29
Page 30
Section 2: Installing the AppStat KMC Controls, Inc.
30 Revision G
Page 31
COOLING SETPT
Up and down buttons
Soft key
buttons
Soft key
bar
Optional motion sensor
72
F
°
AUTO AUTO
DoneEnterCncl
Installation, Operation, and Application Guide for AppStat

Sec tion 3: Use r f u n c tio ns

This section covers topics for the end user in a facility.
AppStat user functions are limited to changing the following functions.
Active temperature setpoints
Fan operation
Changing between heating and cooling
Override scheduled occupancy or occupancy based on the schedule in the AppStat.
Change the display between Fahrenheit and Celsius

Operating the AppStat

AppStat functions are accessible through a user interface consisting of simple, context sensitive menus. The menus are opened and options are selected by using the buttons and a color display on the front of the AppStat.
Pressing either the up button or down button changes a selection, setting, or value.
Pressing the Enter button saves the selected setting or value. Typically the Enter button is the middle of the three buttons below the display.
Saving a selection also advances to the next display.
Illustration 3–1 AppStat display and buttons
Revision G 31
Page 32
Section 3: User functions KMC Controls, Inc.
The three buttons below the display are defined by labels in the soft key bar. Typically the buttons are designated for the following functions.
Back—Returns to the previous menu.
Cncl—Cancels current changes.
Done—Push this button at any point while entering a value. For example,
if you have entered the first two digits of a password and the remaining two digits are correct, pushing Done completes the entry of the password.
Enter—Pushing this button enters the selection and advances to the next
step.
Exit—Returns to temperature display.
The operating modes of the AppStat are represented by the display icons.
Table 3–1 Operating mode icons
Icon Description Mode
The fan icon rotates when the system fan is operational. In systems with multispeed fans the icon rotation is the same regardless of speed. When fan operation is set to automatic, the word "Auto" is placed under the icon.
Occupied—Occupancy is set to occupied by the schedule maintained in the controller.
Unoccupied—Occupancy is set to unoccupied by the schedule maintained in the controller.
Standby—The space is temporarily unoccupied because of lack of detected motion in the room.
Override—A user has entered temperature setpoints that override the unoccupied setpoints.
Fan
Occupancy
Occupancy
Occupancy
Occupancy
Cooling—The system will cool the space until the cooling setpoint is reach. The icon is in motion when cooling is taking place.
32 Revision G
Heating/Cooling
Page 33
Installation, Operation, and Application Guide for AppStat Section 3: User functions
Operating mode icons (continued)
Icon Description Mode
Heating—The system will heat the space until the heating setpoint is reached. The icon is in motion when heating is taking place.
Off System is off Heating/Cooling
Dehumidification—During dehumidification the system will heat and cool at the same time to remove humidity and maintain the active temperature setpoint. The icon is in motion while dehumidification is taking place.
Heating/Cooling
Heating/Cooling
Revision G 33
Page 34
F
°
70
AUTO AUTO
SECURITY
ADMIN LEVEL
0 0 0 0
Section 3: User functions KMC Controls, Inc.

Entering a user password

User functions may require a password consisting of four numbers. Once a user password is entered it will remain active for 60-seconds after the last button is pushed.
Enter a user password
Procedure Steps Display
1 Starting display
2 Enter the Level 1
password.
Start at the temperature display.
1.
Press any button on the AppStat. The display changes to the Security User Level display.
2.
Press either the or button to change the first digit of the password.
3.
Press the Enter button to select the next digit. Repeat for all four digits.
4.
If the password is correct, the display will advance to the first menu.
34 Revision G
Page 35
F
°
70
AUTO AUTO
F
°
68
HEATING SETPT
Done
Enter
Cncl
F
°
72
COOLING SETPT
Done
Enter
Cncl
Installation, Operation, and Application Guide for AppStat Section 3: User functions

Changing the active setpoints

To enter or change the active temperature setpoints you may need user password. To enter the password, see Entering a user password on page 34.
Note: In the following procedure the current active setpoint–either cooling or
heating–is the first setpoint to change. Once that setpoint is entered, the display advances to the next setpoint.
To change the operation of the fan, occupancy, or heating/cooling, see the topic Setting the operating modes on page 36.
Change the active temperature setpoints
Procedure Steps Display
1 Starting display
2 Change the active
setpoints
Start at the temperature display.
Note:
The next step may require a user
password. See
34
.
1.
Press either the or button to change the active temperature setpoint.
Entering a user password on page
Note: A user password may be required
after pushing the first button.
2.
Press the Enter button to save the value. The display will advance to the next setpoint
3.
Press either the or button to change the next setpoint.
4.
Press the Enter button to save the value. The display will return to the temperature display.
Revision G 35
Page 36
F
°
70
AUTO AUTO
Enter
Cncl
MODE: HEAT COOL
AUTO
OFF
Enter
Cncl
MODE: EMERGENCY HEAT COOL
AUTO
OFF
Section 3: User functions KMC Controls, Inc.

Setting the operating modes

The operating modes set the following functions.
Fan operation
Changing between heating and cooling
Override scheduled occupancy or occupancy that has been set by a schedule.
Change the display units from Fahrenheit to Celsius.
To change the occupied temperature setpoints, see the topic Changing the
active setpoints on page 35.
Set the operating modes
Procedure Steps Display
1 Starting display
2 Change the heating
or cooling mode.
Start at the temperature display.
Note:
The following procedures may require a
user password. See
page 34
1.
.
Push the button under the heating/cooling
Entering a user password on
icon.
Note: If a user password has previously been
entered or if the AppStat has not been set up with a user password, entering a password is not required.
2.
Press either the or button to select the heating/cooling mode. The mode may be one of the following.
Emergency—(Option) Turns on the auxiliary heating in a heat pump unit.
Heat—The system will only heat the space.
Cool—The system will only cool the space.
Auto—The system will switch between heating and cooling.
Heating/cooling icons
Off—The system is turned off.
3.
Press the Enter button to save the setting. The display returns to the temperature display.
36 Revision G
Page 37
Enter
Cncl
FAN: ON AUTO
Enter
Cncl
FAN: HIGH MED LOW AUTO
Installation, Operation, and Application Guide for AppStat Section 3: User functions
Set the operating modes (continued)
Procedure Steps Display
1.
3 Set the fan mode.
Push the button under the fan icon.
Note: If a user password has previously been
entered or if the AppStat has not been set up
Fan icon
with a user password, entering a password is not required.
2.
Press the Enter button to select the next digit. Repeat for all four digits.
3.
Press either the or button to select the fan mode from the following options.
Auto—Sets the fan to run only when
1-speed fan option
there is a call for heat or cooling. The word AUTO will be placed under the fan icon.
On—Sets a single speed fan will run continuously.
Low, Med, High—Sets the speed at which 3-speed or modulating fans will run
Multi-speed fan option
continuously.
4.
Press the Enter button to save the setting. The display returns to the temperature display.
Revision G 37
Page 38
F
°
65
AUTO AUTO
Enter
Cncl
LOCAL OVRD: ON OFF
F
°
70
AUTO AUTO
°
21
c
.0
AUTO AUTO
Section 3: User functions KMC Controls, Inc.
Set the operating modes (continued)
Procedure Steps Display
4 Change the override
setpoint
Entering an override setpoint can only take place if the AppStat is in the unoccupied mode.
1.
Push the button under the unoccupied icon
.
Note: If a user password has previously been
entered or if the AppStat has not been set up with a user password, entering a password is not required.
2.
Press either the or button to change the first digit of the password.
3.
Press the Enter button to select the next digit. Repeat for all four digits.
4.
Press either the or button to turn the override on or off.
Override Off—The controller uses the unoccupied setpoint as the active setpoint.
Override On—the controller changes to the occupied setpoint which can then be temporarily changed.
5.
Press the Enter button to save the setting.
5 Change the display
38 Revision G
units
Note: When the system is in the unoccupied
mode, changing the active setpoint will automatically place the system in the override mode.
To temporarily change the display units to either Celsius or Fahrenheit, press and hold the middle button under the display until the units change.
Page 39
Installation, Operation, and Application Guide for AppStat

Sec tion 4: Co m m i s s io n ing f u n c t ions

This topics in this section are advanced topics for control technicians and engineers. These topic cover procedures for the initial AppStat setup.
The AppStat commissioning functions are values and settings that are entered during the installation and commissioning of a controller and the equipment it is controlling. Typically these functions do not change after the installation and commissioning process.
To set up the commissioning functions, you will need the following information.
Information about the equipment
The sequence of operation for the equipment
The building automation system plans for controllers that are part of a network.
Users may change the occupied heating and cooling setpoints without accessing the commissioning functions. This procedure is covered in the topic
User functions on page 31.
Note: The instructions for the AppStat commissioning functions cover all of the
functions that can be set in the controller. Not all functions are available on every model of controller. Consult the installation and operation manual supplied with the controller to verify the application programming in the AppStat.
Revision G 39
Page 40
F
°
70
AUTO AUTO
Push together for commissioning
AUTO AUTO
70
F
°
SECURITY
ADMIN LEVEL
0 0 0 0
Enter
Cncl
MAIN
SETPOINT
SCHEDULE SYSTEM COMM ADVANCED
Section 4: Commissioning functions KMC Controls, Inc.

Enter the commissioning mode

For access to the commissioning functions you will need to know Password 2.
If the controller has not been previously set up, no password is required.
A new Password 2 can be entered in the advanced commissioning functions. See the topic Advanced options on page 60.
Enter the commissioning mode
Procedure Steps Display
1 Starting display
2 Enter the
commissioning password
Start from the temperature display.
1.
Press the left and right buttons below the display at the same time and hold them until the display changes to the SECURITY USER LEVEL display.
Note: If Password 2 has not previously been
entered, the display will change to the MAINmenu.
2.
Press either the or button to change the first digit of Password 2.
3.
Press the Enter button to select the next digit. Repeat for all four digits. The Enter button is the middle of the three buttons below the display.
3 Select a
40 Revision G
commissioning function
Access to the commissioning functions always starts at the MAIN menu display.
Page 41
F
°
70
AUTO AUTO
SECURITY
ADMIN LEVEL
0 0 0 0
Enter
Cncl
MAIN
SETPOINT
SCHEDULE SYSTEM COMM ADVANCED
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions

Setting the commissioning setpoints

The commissioning setpoints set the operational setpoints and limits for the AppStat. The functions of the setpoints and how they are used are describe in the topic Room temperature setpoints on page 66. Setting commissioning setpoints requires entering Password2 which is described in the topic Enter
the commissioning mode on page 40.
Note: Not all setpoints in the following procedure are applicable to all models of
AppStat. Those setpoints are marked as (optional).
Procedure to set the commissioning setpoints
Procedure Steps Display
1.
1 Starting display
Start at the temperature display.
2.
Enter Password 2. The display changes to the MAIN menu display.
2 Choose and set the
setpoints.
1.
From the MAIN menu , press either the or
button to select SETPOINTS.
2.
Press Enter. The SETPOINT menu opens
3.
Choose and set each of the following setpoints.
Revision G 41
Page 42
Back
Enter
Cncl
SETPOINT
OCC COOL
OCC HEAT
UNOCC COOL UNOCC HEAT MIN COOLING MAX HEATING DIFFERENTIAL
Section 4: Commissioning functions KMC Controls, Inc.
Procedure to set the commissioning setpoints (continued)
Procedure Steps Display
OCC COOL—The cooling setpoint that is used as the active setpoint when the system is occupied.
OCC HEAT—The heating setpoint that is used as the active setpoint when the system is occupied.
UNOCC COOL—The cooling setpoint that is used as the active setpoint when the system is unoccupied.
UNOCC HEAT—The heating setpoint that is used as the active setpoint when the system is unoccupied.
MIN COOLING—The minimum cooling setpoint that a user can select as the active setpoint.
MAX HEATING—The maximum heating setpoint that a user can select as the active setpoint.
DIFFERENTIAL—The minimum value between the cooling or heating setpoints. The AppStat will always maintain this difference between setpoints.
STBY OFFSET—(optional) A value used to calculate the standby setpoint. The standby setpoint is calculated by adding or subtracting the offset value to or from the value of the occupied setpoint.
DEHUM SETPOINT—(optional) Sets the setpoint for dehumidification. Dehumidification starts when the relative humidity is above the dehumidification setpoint.
DEHUM DEADBAND—(optional) The system will remain in dehumidification until the relative humidity falls below a value of dehumidficaion setpoint minus the dehumidification deadband value.
42 Revision G
Page 43
F
°
70
AUTO AUTO
SECURITY
ADMIN LEVEL
0 0 0 0
MAIN SETPOINT SCHEDULE SYSTEM
COMM
ADVANCED
BackEnterExit
COMM
DEVICE ID
MAC BAUD
BackEnterExit
D ID: 0000001
DoneEnterEnter
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions

Set up communications

Setting BACnet communications properties is required only if the AppStat is integrated into a network with other BACnet controllers. Entering the communications properties requires entering Password 2 which is described in the topic Enter the commissioning mode on page 40.
See the topic Connecting to an MS/TP network on page 121 for network wiring details.
Set BACnet communication properties
Procedure Steps Display
1.
1 Starting display
Start at the temperature display.
2.
Enter Password 2. The display changes to the MAIN menu display.
2 Change the network
communication properties.
1.
From the MAIN menu , press either the or
button to select COMM.
2.
Press Enter. The COMMmenu opens.
3.
Choose and set the following properties.
l DEVICE ID—This is the BACnet device
instance. The device instance must be within the range of 1 to 4,194,302.
l MAC—The MAC address must be in the
range of 1-127.
l BAUD—Set to match other devices on
the BACnet MS/TP network. The choices are Auto, 9600, 19,200, 38,400, or 76,800.
Note: After changing a communication
property the AppStat will reset.
Revision G 43
Page 44
MAC: 1
DoneEnterEnter
BAUD: 76800
38400 19200 9600
Auto
DoneEnterCncl
Section 4: Commissioning functions KMC Controls, Inc.
Set BACnet communication properties (continued)
Procedure Steps Display
44 Revision G
Page 45
F
°
70
AUTO AUTO
SECURITY
ADMIN LEVEL
0 0 0 0
MAIN SETPOINT
SCHEDULE
SYSTEM COMM ADVANCED
BackEnterExit
SCHEDULE
SET CLOCK
SETPOINT HOLD ENTIRE WEEK WEEKDAYS WEEKEND INDV DAYS HOLIDAYS
DelEnterExit
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions

Set the time and date

Setting the time and date requires entering Password 2 which is described in the topic Enter the commissioning mode on page 40.
Note: If the AppStat is connected to a BACnet network that includes a time service
master, the time and date are automatically set to the network time and date.
To change the schedule, see the procedure Setting the occupancy schedule on
page 47.
Set the time and date
Procedure Steps Display
1.
1 Starting display
Start at the temperature display.
2.
Enter Password 2. The display changes to the MAIN menu display.
1.
2 Select the
SCHEDULE menu.
From the MAIN menu , press either the or
button to select SCHEDULE.
2.
Press Enter. The SCHEDULE menu opens.
3.
Choose SET CLOCK and then press Enter. The SET Clock menu opens.
Revision G 45
Page 46
SET CLOCK
DATE
TIME UTC OFFSET DST ENABLE DST AUTO DST START DST END
BackEnterExit
Section 4: Commissioning functions KMC Controls, Inc.
Set the time and date (continued)
Procedure Steps Display
3 Choose a clock
function to set.
Choose one of the features in the SET CLOCK menu to change the date, time, or Daylight Saving Time (DST) setting.
DATE—The current calendar date.
TIME—Time is set according to a 12-hour clock.
UTC OFFSET—Enter the time offset—in minutes—between local standard time and Universal Time Coordinated. The value of the property ranges from -780 to +780 seconds. The time zones to the west of the zero degree meridian are positive values; those to the east are negative values. The value of the UTC Offset property is subtracted from the UTC received in a UTC Time Synchronization service request to calculate the correct local standard time.
DST ENABLE—Set to TRUE to enable Daylight Saving Time and FALSE to use standard time year around.
DST AUTO—When set to TRUE, the AppStat automatically calculates the start and end dates from relative dates. For example, set DST START to the first Sunday in March instead of a calendar date.
DST START and DST END—Enter the dates and time to begin observing DST. If DST AUTO is set to TRUE the dates are relative; if set to FALSE the date is a calendar date.
46 Revision G
Page 47
F
°
70
AUTO AUTO
SECURITY
ADMIN LEVEL
0 0 0 0
MAIN SETPOINT
SCHEDULE
SYSTEM COMM ADVANCED
BackEnterExit
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions

Setting the occupancy schedule

The schedule in the AppStat controls the occupancy mode. If the schedule is set to ON, the AppStat uses the occupied setpoint as the active setpoint. If the schedule is OFF, the unoccupied setpoint is used.
Note: The schedule in the AppStat is a BACnet schedule object. If the AppStat is
connected to a BACnet network the schedule can be set up with a BACnet operator workstation.
Setting the occupancy schedule requires entering Password2 which is described in the topic Enter the commissioning mode on page 40.
To change the time and date, see the procedure Set the time and date on page
45.
Set up schedules
Procedure Steps Display
1.
1 Starting display
Start at the temperature display.
2.
Enter Password 2. The display changes to the MAIN menu display.
1.
2 Select the
SCHEDULE menu.
Revision G 47
From the MAIN menu , press either the or
button to select SCHEDULE.
2.
Press Enter. The SCHEDULE menu opens.
Page 48
SCHEDULE SET CLOCK SETPOINT HOLD
ENTIRE WEEK
WEEKDAYS WEEKEND INDV DAYS HOLIDAYS
BackEnterExit
ENTIRE WEEK
1: 12:00:00 AM ON
2:
--:--:---- ----
3:
--:--:---- ----
4:
--:--:---- ----
5:
--:--:---- ----
6:
--:--:---- ----
DelEnterExit
Section 4: Commissioning functions KMC Controls, Inc.
Set up schedules (continued)
Procedure Steps Display
1.
3 Choose and set a
weekly schedule.
From the SCHEDULE menu, choose one of the following schedule entry methods to enter a weekly schedule.
l ENTIRE WEEK—Sets the schedule for
all seven days of the week at one time.
l WEEKDAYS—Sets the schedule for
Monday to Friday. Saturday and Sunday are not changed
l WEEKEND—Sets the schedule for
Saturday and Sunday. Monday to Friday remain unchanged.
l INDIVIDUAL DAYS—Sets the schedule
for just the selected day of the week.
2.
Change the daily times and values in the schedule to set the occupancy mode to either ON or OFF.
l When finished with each pair push Enter
or Done.
l When finished with the schedule push
Exit to return to the SCHEDULE menu.
48 Revision G
Page 49
HOLIDAYS HOL1 HOL2 HOL3 HOL4 HOL5 HOL6 HOL7
DelEnterExit
HOL2 DATE DEC 12 2013 TYPE: DATE
DelEnterExit
HOL3
START DATE:
NOV 27 2013 END DATE: DEC 12 2013 TYPE: DATE RANGE
DelEnterExit
HOL5
MON WK DAY:
OCT 31 THU TYPE: WEEK N DAY
DelEnterExit
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions
Set up schedules (continued)
Procedure Steps Display
4 Choose and set a
holiday schedule
Use a holiday schedule to override the values in the weekly schedule. Months and years can be entered as follows:
To choose ANY as the year, select the year and push the down arrow past the current year
For month the choices are any of the twelve months of the year, ANY, EVEN, and ODD.
1.
From the SCHEDULE menu, choose HOLIDAYS.
2.
From the HOLIDAYS list, choose a holiday to edit.
3.
From the menu for the holiday, choose
l DATE—Snter a single date on which the
holiday schedule will override the values of the weekly schedule.
l DATE RANGE—Enter a range of dates
on which the values and times listed in the holiday schedule will override the values of the weekly schedule.
l WEEK N DAY—A day of the week and
month on which the values and times listed in the holiday schedule will override the values of the weekly schedule.
Revision G 49
Page 50
F
°
70
AUTO AUTO
SECURITY
ADMIN LEVEL
0 0 0 0
MAIN SETPOINT SCHEDULE
SYSTEM
COMM ADVANCED
BackEnterExit
SYSTEM
LOCAL OVRD TIME
FAN OFF DELAY OCCUPIED FAN CL VALVE ACTION HT VLV ACTION FAN MAXIMUM FAN MINIMUM
BackEnterExit
SYSTEM
LOCAL OVRD TIME
FAN OFF DELAY OCCUPIED FAN VLV ACTION FAN MAXIMUM FAN MINIMUM AUX HEAT
BackEnterExit
BackEnterCncl
LOCAL OVRD TIME
2 60 mins
Section 4: Commissioning functions KMC Controls, Inc.

Set fan coil unit system options

The items in the system menu control application specific functions for fan coil units. Entering the system options requires entering Password 2 which is described in the topic Enter the commissioning mode on page 40.
Set up fan coil unit system options
Procedure Steps Display
1.
1 Starting display.
Start at the temperature display.
2.
Enter Password 2. The display changes to the MAIN menu display.
1.
2 Choose and set the
fan coil system options.
From the MAIN menu , press either the or
button to select SYSTEM.
2.
Press Enter. The SYSTEM menu opens.
3 Set the local override
time.
3.
Choose any of the following items.
LOCAL OVRD TIME
FAN OFF DELAY
OCCUPIED FAN
CL VALVE ACTION (Four-pipe only)
HT VLV ACTION (Four-pipe only)
VLV ACTION (Two-pipe only)
FAN MAXIMUM (Modulating fans only)
FAN MINIMUM (Modulating fans only)
FAN SPEEDS (Three speed fans only)
AUX HEAT (Two-pipe only)
From the SYSTEM menu choose LOCAL OVRD TIME to set the time the AppStat will hold an override temperature setpoint as the active setpoint. At the end of the period, the AppStat will use either an occupied or unoccupied setpoint as the active setpoint.
50 Revision G
Page 51
BackEnterCncl
FAN OFF DELAY
2 2 mins
BackEnterCncl
OCCUPIED FAN:
ON
OFF
CL VLV ACTION:
NORMAL OPEN
NORMAL CLOSED
DelEnterCncl
HT VLV ACTION:
NORMAL OPEN
NORMAL CLOSED
DelEnterCncl
VLV ACTION:
NORMAL OPEN
NORMAL CLOSED
DelEnterCncl
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions
Set up fan coil unit system options (continued)
Procedure Steps Display
4 Set the fan delay.
5 Set the occupied fan
control.
6 Set the valve action.
From the SYSTEM menu choose FAN DELAY OFF to set the time the system fan will continue to run after the last heating or cooling stage is turned off.
From the SYSTEM menu choose OCCUPIED FANto choose the following:
When ON, the fan will run continuously when the schedule is occupied (On).
When the schedule is unoccupied (Off) the fan will run only when there is a call for heating or cooling.
Select one of the valve actions from the SYSTEMmenu. Not all choices apply to every application.
CL VALVE ACTION—(Four-pipe only)
HT VLV ACTION—(Four-pipe only)
VLV ACTION—(Two-pipe only)
Valve action selections are the same for all three types of valves.
NORMAL OPEN—The valve changes from fully open to fully closed as the AppStat varies the valve output from 0 to 10 volts.
NORMAL CLOSED—The valve changes from fully closed to fully open as the AppStat varies the valve output from 0 to 10 volts.
Revision G 51
Page 52
BackEnterCncl
FAN MINIMUM:
35 %utoz
BackEnterCncl
FAN MAXIMUM:
100 %utoz
BackEnterCncl
FAN SPEEDS:
THREE SPEEDS
TWO SPEEDS SINGLE SPEED
AUX HEAT:
Enable
Disable
DelEnterCncl
Section 4: Commissioning functions KMC Controls, Inc.
Set up fan coil unit system options (continued)
Procedure Steps Display
7 Set fan speeds for
modulating speed fans.
8 Set fan speeds for
three-speed fans.
9 Enable auxiliary heat
Select FAN MINIMUM or FAN MAXIMUM from the SYSTEM menu to set fan speed for modulation fans.
FAN MINIMUM—Sets the slowest speed at which the fan will run when a user sets the fan speed to LOW.
FAN MAXIMUM—Sets the fastest speed at which the fan will run when a user sets the fan speed to HIGH.
The MED speed is automatically set halfway between the LOW and HIGH settings.
Select FAN SPEEDS from the SYSTEM menu to designate the number of speeds at which the installed fan will run.
Choose AUX HEAT from the SYSTEM menu to enable auxiliary heat in two-pipe applications.
52 Revision G
Page 53
F
°
70
AUTO AUTO
SECURITY
ADMIN LEVEL
0 0 0 0
MAIN SETPOINT SCHEDULE
SYSTEM
COMM ADVANCED
BackEnterExit
BackEnterExit
SYSTEM
LOCAL OVRD TIME
FAN OFF DELAY OCCUPIED FAN MIN OFF TIME STAGE DELAY ECON ENABLE MIN ECON DAMPER
SYSTEM STAGE DELAY ECON ENABLE MIN ECON DAMPER ECON ENABLE TEM MIN DAT DEHUM ENABLE HEATING FAN
BackEnterExit
BackEnterCncl
LOCAL OVRD TIME
2 60 mins
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions

Set roof top unit system options

The items in the system menu control application specific functions for roof top units. Entering the system options requires entering Password 2 which is described in the topic Enter the commissioning mode on page 40.
Set up roof top unit system options
Procedure Steps Display
1.
1 Starting display.
Start at the temperature display.
2.
Enter Password 2. The display changes to the MAIN menu display.
1.
2 Choose and set the
roof top system options.
From the MAIN menu , press either the or
button to select SYSTEM.
2.
Press Enter. The SYSTEM menu opens.
3 Set the local override
time.
3.
Choose any of the following items.
LOCAL OVRD TIME
FAN OFF DELAY
OCCUPIED FAN
MIN OFF TIME
STAGE DELAY
ECON ENABLE
MIN ECON DAMPER
ECON ENABLE TEM
MIN DAT
HEATING FAN
From the SYSTEM menu choose LOCAL OVRD TIME to set the time the AppStat will hold an override temperature setpoint as the active setpoint. At the end of the period, the AppStat will use either an occupied or unoccupied setpoint as the active setpoint.
Revision G 53
Page 54
BackEnterCncl
FAN OFF DELAY
2 2 mins
BackEnterCncl
OCCUPIED FAN:
ON
OFF
BackEnterCncl
MINOFF TIME:
5 mins
BackEnterCncl
STAGE DELAY:
10 mins
Section 4: Commissioning functions KMC Controls, Inc.
Set up roof top unit system options (continued)
Procedure Steps Display
4 Set the fan delay.
5 Set the occupied fan
control.
6 Set up staged cooling
and heating.
From the SYSTEM menu choose FAN OFF DELAY to set the time the system fan will continue to run after the last heating or cooling stage is turned off.
From the SYSTEM menu choose OCCUPIED FANto choose the following:
When ON, the fan will run continuously when the AppStat schedule is ON (occupied).
When the AppStat schedule is OFF (Unoccupied) the fan will run only when there is a call for heating or cooling.
To set up staged cooling and heating do the following:
1.
From the SYSTEM menu choose MIN OFF TIME to enter the time a stage must remain turned off before it can be turned on again.
2.
From the SYSTEM menu choose STAGE DELAY to enter the time the first stage must remain turned on before the second stage can be turned on.
54 Revision G
Page 55
BackEnterCncl
ECON ENABLE:
ENABLED
DISABLED
BackEnterCncl
MIN ECON DAMPER:
10%
BackEnterCncl
ECON ENABLE TEM:
60 °F
BackEnterCncl
MIN DAT:
55 °F
BackEnterCncl
DEHUM ENABLE:
ENABLE
DISABLE
BackEnterCncl
HEATING FAN:
AUTO
OFF
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions
Set up roof top unit system options (continued)
Procedure Steps Display
7 Enable the
economizer. (Optional feature)
The economizer feature is an option and not available on all models.
To set up the economizer do the following:
1.
From the SYSTEM menu choose ECON ENABLE to enable the economizer application.
2.
From the SYSTEM menu choose MIN ECON DAMPER to set the minimum position for the economizer damper.
3.
From the SYSTEM menu choose ECON ENABLE TEM. Enter the value that the outside air temperature must fall below before the economizer damper can open.
4.
From the SYSTEM menu choose MIN DAT. Enter the minimum discharge air temperature that will be allowed during cooling when the economizer is enabled.
8 Enable
9 Set heating fan
Revision G 55
dehumidification. (Optional feature)
control.
From the SYSTEM menu choose DEHUM ENABLE to enable or disable dehumidification. Dehumidification is only available on models with a humidity sensor.
From the SYSTEM menu choose HEATING FAN and then choose one for the following.
AUTO—The fan runs only on a call for heat.
OFF—The AppStat will not command the fan to run. Typically this setting used for systems with baseboard heat or some similar split system configuration.
Page 56
F
°
70
AUTO AUTO
SECURITY
ADMIN LEVEL
0 0 0 0
MAIN SETPOINT SCHEDULE
SYSTEM
COMM ADVANCED
BackEnterExit
BackEnterExit
SYSTEM
LOCAL OVRD TIME
FAN OFF DELAY OCCUPIED FAN MIN OFF TIME STAGE DELAY ECON ENABLE MIN ECON DAMPER
SYSTEM
ECON ENABLE TEM
MIN DAT REV VLV PLRTY AUX HEAT AUX HT LOCKOUT COMP LOCK TEMP DEHUM ENABLE
BackEnterExit
Section 4: Commissioning functions KMC Controls, Inc.

Set heat pump unit system options

The items in the system menu control application specific functions for heat pump units. Entering the system options requires entering Password 2 which is described in the topic Enter the commissioning mode on page 40.
Set up heat pump unit system options
Procedure Steps Display
1.
1 Starting display.
Start at the temperature display.
2.
Enter Password 2. The display changes to the MAIN menu display.
1.
2 Choose and set the
heat pump system options.
From the MAIN menu , press either the or
button to select SYSTEM.
2.
Press Enter. The SYSTEM menu opens.
3.
Choose any of the following items.
LOCAL OVRD TIME
FAN OFF DELAY
OCCUPIED FAN
MIN OFF TIME
STAGE DELAY
ECON ENABLE (optional)
MIN ECON DAMPER (optional)
ECON ENABLE TEM (optional)
MIN DAT (optional)
REV VLV PLRTY
AUX HEAT (optional)
AUX HT LOCKOUT (optional)
COMP LOCK TEMP
DEHUM ENABLE (optional)
56 Revision G
Page 57
BackEnterCncl
LOCAL OVRD TIME
2 60 mins
BackEnterCncl
FAN OFF DELAY
2 2 mins
BackEnterCncl
OCCUPIED FAN:
ON
OFF
BackEnterCncl
MINOFF TIME:
5 mins
BackEnterCncl
STAGE DELAY:
10 mins
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions
Set up heat pump unit system options (continued)
Procedure Steps Display
3 Set the local override
time.
4 Set the fan delay.
5 Set the occupied fan
control.
6 Set up staged cooling
and heating.
From the SYSTEM menu choose LOCAL OVRD TIME to set the time the AppStat will hold an override temperature setpoint as the active setpoint. At the end of the period, the AppStat will use either an occupied or unoccupied setpoint as the active setpoint.
From the SYSTEM menu choose FAN DELAY OFF to set the time the system fan will continue to run after the last heating or cooling stage is turned off.
From the SYSTEM menu choose OCCUPIED FANto choose the following:
When ON, the fan will run continuously when the AppStat schedule is ON (occupied).
When the AppStat schedule is OFF (Unoccupied) the fan will run only when there is a call for heating or cooling.
To set up staged cooling and heating do the following:
1.
From the SYSTEM menu choose MIN OFF TIME to enter the time a stage must remain turned off before it can be turned on again.
2.
From the SYSTEM menu choose STAGE DELAY to enter the time the first stage must remain turned on before the second stage can be turned on.
Revision G 57
Page 58
BackEnterCncl
ECON ENABLE:
ENABLED
DISABLED
BackEnterCncl
MIN ECON DAMPER:
10%
BackEnterCncl
ECON ENABLE TEM:
60 °F
BackEnterCncl
MIN DAT:
55 °F
DelEnterCncl
RV VLV PLRTY:
ACTIVE HEATING
ACTIVE COOLING
DelEnterCncl
AUX HEAT:
Comp Lockout 3rd Stage
None
Section 4: Commissioning functions KMC Controls, Inc.
Set up heat pump unit system options (continued)
Procedure Steps Display
7 Enable the
economizer. (Optional feature)
The economizer feature is an option and not available on all models.
To set up the economizer do the following:
1.
From the SYSTEM menu choose ECON ENABLE to enable the economizer application.
2.
From the SYSTEM menu choose MIN ECON DAMPER to set the minimum position for the economizer damper.
3.
From the SYSTEM menu choose ECON ENABLE TEM. Enter the value that the outside air temperature must fall below before the economizer damper can open.
4.
From the SYSTEM menu choose MIN DAT. Enter the minimum discharge air temperature that will be allowed during cooling when the economizer is enabled.
8 Set the reversing
9 Set up auxiliary heat.
58 Revision G
valve polarity.
(Optional feature)
From the SYSTEM menu choose REV VLV PLRTY. Select one of the polarity settings.
Active Heating—The O/B output terminal is active on a call for heating.
Active Cooling—The O/B output terminal is active on a call for cooling.
From the SYSTEM menu choose AUX HEAT.
Comp Lockout—The AppStat will enable auxiliary heat only when the compressors are locked out because of low outside air temperature.
3rd Stage—The AppStat uses the auxiliary heat as a third stage of heating.
None—No auxiliary heat is enabled.
Page 59
DelEnterCncl
AUX HT LOCKOUT:
60 °F
DelEnterCncl
COMP LOCK TEMP:
25 °F
BackEnterCncl
DEHUM ENABLE:
ENABLE
DISABLE
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions
Set up heat pump unit system options (continued)
Procedure Steps Display
10 Set the lockout
temperature for auxiliary heat.
11 Set the compressor
low temperature lockout.
12 Enable
dehumidification. (Optional feature)
From the SYSTEM menu choose AUX HT LOCKOUT to set the minimum outside air temperature for auxiliary heat lockout. Auxiliary heat will not operate above this temperature.
From the SYSTEM menu choose COMP LOCK TEMP to set the minimum outside air temperature for compressor operation. Compressors will not operate below this temperature.
From the SYSTEM menu choose DEHUM ENABLE to enable or disable dehumidification. Dehumidification is only available on models with a humidity sensor and auxiliary heat is enabled.
Revision G 59
Page 60
F
°
70
AUTO AUTO
MAIN SETPOINT SCHEDULE SYSTEM COMM
ADVANCED
BackEnterExit
ADVANCED
RESTORE APP
LOOPS PASSWORDS CALIBRATION DISPLAY KEY LOCKOUT
BackEnterExit
Section 4: Commissioning functions KMC Controls, Inc.

Advanced options

Use the advanced options to set up the following items.
Choosing an application and units of measure.
Adjusting the PID loops
Changing passwords
Calibrating inputs
Setting the display blanking
Modifying access to users with Password 1.
Setting the advance options requires entering Password 2 which is described in the topic Enter the commissioning mode on page 40.
Choosing advance options
Procedure Steps Display
1.
13 Starting display.
Start at the temperature display.
2.
Enter Password 2. The display changes to the MAIN menu display.
14 Choose the
ADVANCED menu.
1.
From the MAIN menu , press either the or
button to select ADVANCED.
2.
Press Enter. The ADVANCED menu opens.
3.
Choose any of the following functions.
RESTORE APP
LOOPS
PASSWORDS
CALIBRATION
DISPLAY
KEY LOCKOUT
60 Revision G
Page 61
RESTORE APP
2P FCU-METRIC 4P FCU-METRIC 2P FCU-ENGLISH 4P FCU-ENGLISH
BackEnterCncl
RESTORE APP
RTU-METRIC RTU-ENGLISH
BackEnterCncl
RESTORE APP
HPU-METRIC HPU-ENGLISH
BackEnterCncl
LOOPS
COOL PROP
COOL INTG HEAT PROP HEAT INTG
BackEnterExit
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions
Choosing advance options (continued)
Procedure Steps Display
15 Reset the
application and choose units of measure.
16 Adjust the PID
loops.
Choose RESTORE APP from the ADVANCED menu to reset the AppStat to the original configuration and settings. Use it also to change the AppStat application program and the units of measure to display. There are two versions of each application program in every AppStat.
The Metric version displays temperature in Celsius and uses metric values for units of measure.
The English version displays temperature in Fahrenheit and uses English values for units of measure.
Note: Choosing an application will reset the
AppStat.
Choose LOOPS from the ADVANCED menu to adjust the values for the cooling or heating PID loops. Only the proportional and integral properties can be changed from the display.
The proportional default is 2° F.
The integral default is zero (0).
Revision G 61
Page 62
PASSWORDS
PASSWORD1
PASSWORD2
BackEnterExit
PASSWORD1:
0 0 0 0
DelEnterCncl
CALIBRATION
CAL INTERNAL
CAL EXTERNAL
BackEnterExit
CAL INTERNAL:
0.0
BackEnterCncl
Section 4: Commissioning functions KMC Controls, Inc.
Choosing advance options (continued)
Procedure Steps Display
17 Enter or change
passwords.
18 Calibrate the
inputs.
Choose PASSWORDS from the ADVANCED menu to set either Password 1 or Password 2.
Password 1 is for a facility user and limits changes to active setpoints, fan operation, occupancy, and heating and cooling modes.
Password 2 is for a controls technician to set up and commission the AppStat.
Note: Entering four zeros (0000) removes the
password. The AppStat is supplied without passwords.
1.
From the PASSWORD1 or PASSWORD2 menu press either the or buttons to change the first digit of the password.
2.
Press the Enter button to select the next digit. Repeat for all four digits.
3.
When the Enter button is pressed for the last digit, the new password is saved and the display advances.
Choose CALIBRATION from the ADVANCED menu to calibrated an input. The AppStat includes two calibration entries; one for the internal temperature sensor and one for the optional remote temperature sensor connected to the RS terminal.
62 Revision G
Enter a calibration factor to adjust either input for sensor inaccuracies.
For a low input reading enter a positive correction value.
For a high input reading enter a negative correction value.
Page 63
DISPLAY BLANKING
DIM LEVEL
BackEnterExit
BLANKING
ANALOG CLOCK
BACKLIGHT OFF NONE
DelEnterCncl
DIM LEVEL:
50%
DelEnterCncl
KEY LOCKOUT:
MODE/SETPOINT
MODE NONE
DelEnterCncl
Installation, Operation, and Application Guide for AppStat Section 4: Commissioning functions
Choosing advance options (continued)
Procedure Steps Display
19 Set the display
blanking.
20 User lockout
buttons.
Choose DISPLAY from the ADVANCED menu to set the display appearance after the last button is pushed.
BLANKING—Choose one of the blanking options.
l CLOCK—An analog clock replaces the
temperature and mode icons.
l BACKLIGHT OFF—The display
brightness changes to the level set by DIM LEVEL after the last button interaction.
l NONE—The temperature and mode icons
always remain visible.
DIM LEVEL—Sets the level of brightness of the display back light if BACKLIGHT OFF is the selected blanking option.
Choose KEY LOCKOUT from the ADVANCED menu to limit accessibility to users with Password 1, the user password.
MODE/SETPOINT—Users with Password 1 cannot change any value or mode.
MODE—Users with Password 1 cannot change the heating/cooling, fan, or occupancy modes.
NONE—Users with Password 1 have full access to active setpoints, heating/cooling, fan, and occupancy modes.
Revision G 63
Page 64
Section 4: Commissioning functions KMC Controls, Inc.
64 Revision G
Page 65
Installation, Operation, and Application Guide for AppStat

Sec tion 5: Sequenc e s o f o pe r atio n

Topics in this section cover the sequences of operation for the AppStat. These are advanced topics for control's technicians and engineers.
This section covers the following sequences of operation.
Room temperature setpoints on page 66
Occupancy, motion sensing, and standby on page 67
Automatic cooling and heating changeover on page 68
Scheduling occupancy on page 68
Dehumidification sequence on page 68
Fan status on page 68
Display blanking and backlight on page 69
Temperature sensing inputs on page 69
PID control loops on page 70
Valve operation for fan coil units on page 70
Electric heat for fan coil units on page 72
Fan operation for fan coil units on page 72
Modulating cooling and heating for Roof Top Units on page 73
Staged heating and cooling for for roof top and heat pump units on page 74
Fan control for roof top and heat pump units on page 74
Economizer cooling for roof top and heat pump units on page 75
Heat pump unit specific functions on page 75
Revision G 65
Page 66
Section 5: Sequences of operation KMC Controls, Inc.

Room temperature setpoints

There are four temperature setpoints each for heating and cooling for a total of eight setpoints.
Active cooling
Occupied cooling
Unoccupied cooling
Standby cooling
Active heating
Occupied heating
Unoccupied heating
Standby heating

Types of setpoints

The AppStat uses any of the following setpoints based on a user entered setpoint or the state of occupancy and standby which is described in the topic
Occupancy, motion sensing, and standby on page 67.
Active setpoint—The active setpoint is the current setpoint. The active
setpoint is determined by the following.
If the space is occupied, the controller uses the occupied setpoint as the active setpoint.
If the space is unoccupied the controller uses the unoccupied setpoint as the active setpoint.
If controller occupancy is in standby, the controller calculates the standby setpoint.
A user with Password 1 can enter an active setpoint from the display. This change is for a limited time or until the next time the space status changes from either unoccupied or standby to occupied.
Occupied setpoint—A temperature setpoint entered by the controls
technician during controller setup and system commissioning. This is the setpoint used when the system is occupied which is usually controlled by the schedule in the controller.
Unoccupied setpoint—A temperature setpoint entered by the controls
technician during controller setup and system commissioning. This is the setpoint used when the system is unoccupied which is usually controlled by the schedule in the controller.
Standby setpoint—The standby setpoint is used when the controller is in the
standby state. It is a value calculated from the occupied setpoint and the value of Standby Offset. The standby offset value is entered by the controls technician during controller setup and system commissioning. See the topic
Occupancy, motion sensing, and standby on page 67.
66 Revision G
Page 67
Installation, Operation, and Application Guide for AppStat Section 5: Sequences of operation

Setpoint limits

The programming in the AppStat will limit the setpoint entry so that no heating setpoint is set higher than its corresponding cooling setpoint.
If a user is adjusting a setpoint and it falls within the range set by the value of Minimum Setpoint Differential, the corresponding setpoint will be changed to maintain the differential. For example, the Minimum Setpoint Differential is 4°F and the Occupied Heating setpoint is 70°F. If the user lowers the Occupied Cooling setpoint to 71°F, the controller recalculates the Occupied Heating setpoint and changes it to 67°F.

Occupancy, motion sensing, and standby

The AppStat is designed to operate as a stand-alone controller and can determine occupancy based on its internal occupancy schedule and, on models with motion sensors, motion in the space. The AppStat can be in any one of the following occupancy states.
Occupied
Unoccupied
Standby
The controller chooses which setpoint to use based on the occupancy and standby states. See the topic Room temperature setpoints on page 66 for the sequence on determining setpoints.
The occupancy and standby states can also be commanded by another BACnet device or an operator workstation connected to the building automation network. See the topic BACnet objects on page 114 for details on BACnet value object configuration.
Occupied—For controllers without a motion sensor, the AppStat starts in the
occupied state. If the internal schedule is enabled, the state of the schedule is set to either occupied or unoccupied as the initial state. See the topic Scheduling
occupancy on page 68.
Unoccupied—The controller changes to the Unoccupied state only if the
internal occupancy schedule is enabled and if the schedule is inactive.
Standby—In units with a motion sensor, the controller starts in standby and
changes to occupied only after detecting motion in the space. The controller will change from occupied to standby after a lack of motion for the period specified by the variable Standby Time.
Revision G 67
Page 68
Section 5: Sequences of operation KMC Controls, Inc.

Automatic cooling and heating changeover

Scheduling occupancy

The AppStat can be set to automatically change between the heating and cooling modes.
If the space temperature rises above the active cooling setpoint, the mode is set to cooling.
If the space temperature falls below the heating setpoint, the mode is set to heating.
For fan coil models, the changeover is immediate. For other models, the changeover does not take place until the time set by Fan Off Delay expires.
The schedule in the controller is a standard BACnet schedule object. It can be changed from the display by a technician with Password2 or a BACnet operator workstation.
The internal occupancy schedule changes the AppStat between the occupied (Active) and unoccupied (inactive) states. If the AppStat includes a motion sensor, the motion sensor may change the AppStat between occupied and standby based on motion detected in the space.
See also the topic Occupancy, motion sensing, and standby on page 67.

Dehumidification sequence

Fan status

Dehumidification control is available only on models with internal humidity sensors. Dehumidification is not available for fan coil units configured for two-pipe operation.
The AppStat can run the dehumidification sequence only if the heating and cooling modes are set to automatic. The dehumidification sequence can then start if the space humidity rises above the value of Dehumidification Setpoint. Dehumidification stops when the space humidity drops to a value below the Dehumidification Setpoint minus the value of Dehumidification Differential. The dehumidification setpoint and differential are both adjustable from the user interface.
When Dehumidification is active, cooling output is activated to 100%. Heating then reheats the discharge air to maintain the space temperature to the value of Active Cooling setpoint.
The controller continuously runs the fan during dehumidification regardless of other fan settings.
Fan status is a second function of the Discharge Air Temperature (DAT) input. The function requires a normally closed fan status switch connected across the DAT input terminals. When the fan is started at any speed, the AppStat program waits 10 seconds for the Fan Status switch (FST) to open. If the status switch does not open within 10 seconds after the fan is commanded to start, all heating and cooling is commanded to stop heating and cooling at
68 Revision G
Page 69
Installation, Operation, and Application Guide for AppStat Section 5: Sequences of operation
BACnet priority 5. The fan output remains enabled until the fan status switch opens. The state of fan status is stored in a binary variable. See the topic Value
objects on page 117 for variable object details.
When the fan is functioning normally and the fan status switch is open the DAT input is normal temperature sensing input. When the fan status switch is closed, the value for the DAT input is greater than 260. See the topic
Temperature sensing inputs on page 69.

Display blanking and backlight

Temperature sensing inputs

The AppStat display and backlight can be set to take any of the following actions one minute after the last button is pushed.
Display an analog clock instead of the temperature display.
Dim the display to a preset level.
Remain unchanged.
When the display is dimmed or the clock is visible, the display returns to normal when any button is pushed. See the topic Advanced options on page 60 for the procedure to change the display.
The AppStat includes inputs for sensing space, discharge air, fan coil unit supply water, and outside air temperature.

Space temperature sensing

All models of AppStat include an internal temperature sensor for measuring space temperature. For remote temperature sensing, an external, 10,000 ohm, TypeIIthermistor sensor can be connected to terminals RS. If the AppStat detects that a remote sensor is connected, the internal sensor is not used for determining space temperature. See the topics Input objects on page 114 and
Value objects on page 117 for object details.

Outside air temperature sensing

The outside air temperature (OAT) input is a required input for compressor lockout and economizer applications and is an optional input for others. The AppStat is configured for a TypeIIIthermistor sensor to monitor outside air temperature. The outside air temperature is also stored in an analog value object. See the topics Input objects on page 114 and Value objects on page 117 for object details.

Water temperature sensor

The Water Temperature Sensor input (WST) is a required sensor for two-pipe fan coil units and is optional for other fan coil applications. The AppStat is configured for a TypeIIIthermistor sensor to monitor water temperature. The water temperature can be monitored as an analog input and is also
Revision G 69
Page 70
Section 5: Sequences of operation KMC Controls, Inc.
stored in an analog value object. See the topics Input objects on page 114 and
Value objects on page 117 for object details.

Discharge air temperature sensor

The Discharge Air Temperature (DAT) input is a required input for economizer applications and is an option for other applications. The AppStat is configured for a TypeIIIthermistor sensor for DAT applications. Discharge air temperature can be monitored as an analog input and is also stored in an analog value object. See the topics Input objects on page 114 and Value objects
on page 117 for object details.
The DAT input is a dual function input. It is used also as the input for the fan status switch. See the topic Fan status on page 68 for details.

PID control loops

A PID control loop calculates an error value from the difference between the measured room temperature and the active setpoint. The error value is expressed as a percentage and is typically used in a BAS controller to control the state of an output. When the difference between the setpoint and room temperature is large, the error is large. As the system reduces the difference between the setpoint and space temperature, the error becomes smaller. In a simple example, if the output of the PID loop that is controlling a modulating valve is 50% the valve would be opened half way; if the output of the loop is 100% the valve position is fully open.
The AppStat uses up to four PID loops.
The heating and cooling PID loops are implemented in all models.
The discharge air loop controls the position of the economizer damper. For this loop the setpoint is the measured temperature of the air that is discharged by a roof top or heat pump unit. See Economizer cooling for
roof top and heat pump units on page 75.
The reheat loop is used only for heating outputs unit during dehumidification. See the sequence description Heat pump unit specific
functions on page 75.
The PID loops in the AppStat are standard BACnet objects.

Valve operation for fan coil units

Hot and chilled water valves are used for heating and cooling in the fan coil unit versions of the AppStat. The fan coil two-pipe programming includes also a method to determine supply water temperature.

On/Off valves

On a call for cooling or heating, the valve will open once the PID loop controlling the valve has reached 50%. The valve will close once the loop has
70 Revision G
Page 71
Installation, Operation, and Application Guide for AppStat Section 5: Sequences of operation
fallen to 5%. The controller programming supports both normal and reverse action valves which can be set from the user interface.
Normal—The valve is closed when the output is inactive and open when the output is active.
Reverse—The valve is closed when the output is active and open when the output is inactive.

Modulating valves

On a call for cooling or heating, a modulating valve will modulate from 0 to 100% over the first half (0 to 50%) of the PID loop output controlling the valve. The AppStat supports both normal and reverse action valves which can be set from the user interface.
Normal—The valve is fully closed when the output signal is 0 volts and fully open when the output is 10 volts DC.
Reverse—The valve is fully closed when the output signal is 10 volts and fully open when the output is 0 volts DC.

Two-pipe water supply temperature evaluation

For two-pipe fan coil units, the AppStat uses the water supply temperature sensor—input WST–to determine if chilled or hot water is being supplied to the unit. The water type is determined by comparing the value of the water temperature sensor input to the room temperature. The AppStat programming then determines that the water temperature is one of the following.
Chilled—the water temperature is 10°F below room temperature.
Hot—the water temperature is 10°F above room temperature.
None—the water temperature is within 7°F of room temperature.
If the water temperature is evaluated as None, the AppStat runs the water evaluation program every six hours. During a water evaluation, the AppStat opens the valve until a water type is determined or for five minutes, whichever is reached first. If a water evaluation is not being performed, the valve remains closed.
The supply water type is stored in multistate variable Water Available.
Revision G 71
Page 72
Section 5: Sequences of operation KMC Controls, Inc.

Electric heat for fan coil units

Fan operation for fan coil units

For AppStat fan coil models that support both on/off and modulating valves, electric heat can be added to two-pipe systems. Typically this heat is a duct or baseboard resistance heater controlled by a relay.
When the supply water type is chilled water and there is a call for heat, the AppStat controls the heating element through output terminal BO5. The output turns on when the heating loop is greater than 99%. The output is turned off when the loop falls to 5%. If the supply water type is hot water, only the water valve output is used to satisfy a call for heat.
The AppStat supports both modulating fans and fans with one, two, or three speeds. Speed for either type of fan is determined by the PID loop that is currently controlling the heating or cooling. Fan speed control is set up from the user interface by a user with Password 2. See the topic Set fan coil unit
system options on page 50.

One, two, and three speed fans

For one, two, and three speed fans, the AppStat controls the fan speed with terminals FAN-L, FAN-M, and FAN-H.
Single speed fans use terminal FAN-L only
Two speed fans are controlled with terminals FAN-Land FAN-H
Thee speed fans use terminals FAN-L, FAN-M, and FAN-H
The fan output terminals are energized as the cooling or heating loop varies from 0-100%. Terminal activation is shown in the following table.
Table 5–1 Fan speed
Fan L terminal Fan M terminal Fan H terminal
Fan
On Off On Off On Off
speed
One Active valve 5% n/a n/a n/a n/a
Two Active valve 5% n/a n/a 95% 80%
Three Active valve 5% 65% 50% 95% 80%

Modulating fans

The fan starts a modulation fan on a call for either heating or cooling. The fan runs at the minimum fan speed until the heating or cooling loop reaches 50%. From 50% to 100% of the loop, the fan speed ramps from the minimum speed to maximum speed. The minimum and maximum fan speeds are set from the
72 Revision G
Page 73
Installation, Operation, and Application Guide for AppStat Section 5: Sequences of operation
user interface during system setup. See the topic Set fan coil unit system
options on page 50.

Automatic fan control

A user with Password 1 can set the AppStat controlled fan to either run continuously or to start automatically on a call for cooling or heating.
Auto—When Auto is selected, the fan runs only when there is a call for
cooling or heating. It continues to run after the call for cooling or heating for the period set by the fan delay timer.
On—The fan will run continuously regardless of the heat/cool modes or
occupied/standby states.
Low, Medium, High—For systems with three-speed fans, the user has the
choice of low, medium or high speed as the continuous running speed for the fan.

Modulating cooling and heating for Roof Top Units

Modulating cooling and heating is used in AppStat controlled systems with modulating valves and chilled or hot water coils. A single modulating valve can be used with staged cooling or heating.

Cooling

Modulating cooling does not start until the cooling loop reaches 100%. Once the loop reaches 100%, the analog cooling output modulates over 10 volts DC as the cooling loop changes from 0 to 100%. When the cooling loop returns to 0%, cooling stops until the loop again reaches 100%.
If the economizer is enabled, cooling will not start modulating until the economizer damper is fully open.

Heating

Modulating heating does not start until the heating loop reaches 100%. Once the loop reaches 100%, the analog heating output modulates over 10 volts DC as the heating loop changes from 0 to 100%. When the heating loop returns to 0%, heating stops until the loop reaches 100% again.

Valve action

The AppStat supports both normal and reverse valve action that can be set from the user interface.
Normal—The valve is fully closed when the output signal is 0 volts and fully open when the output is 10 volts DC.
Reverse—The valve is fully closed when the output signal is 10 volts and fully open when the output is 0 volts DC.
Revision G 73
Page 74
Section 5: Sequences of operation KMC Controls, Inc.

Staged heating and cooling for for roof top and heat pump units

Staged heating and cooling is used for applications other than chilled or hot water systems. Typically the AppStat controls gas heat, electric heat, or direct expansion (DX) cooling with staged heating and cooling. Staged cooling or heating can be mixed with a modulating valve for cooling or heating.

Staged cooling

As the demand for cooling increases, the AppStat starts the first stage of cooling when the cooling PID loop rises above 95% and the first stage of cooling has been turned off for at least the time set by the value of MINIMUM OFF TIME. The second stage of cooling is turned on when the cooling loop rises above 99% and the first stage has been turned on for the period set by STAGE DELAY and the second stage has been turned off for at least as long as the value of MINIMUM OFF TIME.
As the demand for cooling is satisfied, the second stage is turned off when the cooling PID loop drops below 50%. This first stage is turned off when the cooling loop drops below 5%.

Staged heating

As the demand for heating increases, the AppStat starts the first stage of heating when the heating PID loop rises above 95%. The second stage of heatingis turned on when the heating loop rises above 99% and the first stage has been turned on for period set by STAGE DELAY.

Fan control for roof top and heat pump units

As the demand for heating is satisfied, the second stage is turned off when the heating PID loop drops below 50%. This first stage is turned off when the heating loop drops below 5%.
A user with Password 1 can set the AppStat controlled fan to either run continuously or to start automatically on a call for cooling or heating. See the topic Setting the operating modes on page 36 to set the fan configuration.
On—The fan will run continuously regardless of the heat/cool modes or
occupied/standby states.
Auto—When Off is selected, the fan runs only when there is a call for heating
or cooling. It continues to run for the period set by the fan delay timer after the call for heating or cooling.
74 Revision G
Page 75
Installation, Operation, and Application Guide for AppStat Section 5: Sequences of operation

Economizer cooling for roof top and heat pump units

Note: The optional economizer can be enabled only if outside air temperature and
Some models of the AppStat include programming for an economizer. This programing controls an economizer outside air damper connected to the output terminal (ECON).
discharge air temperature sensors are connected to the AppStat.
The optional economizer mode is enabled for cooling when the outside air temperature(OAT) is 2° F below the value of the limit set by Economizer Enable Temperature and disabled if the OAT is 2° F above the value of Economizer Enable Temperature.
Once enabled, the economizer outside air damper opens to the larger value of either the minimum damper position limit (Minimum Econ Damper) or the Discharge Air Temperature loop. The Discharge Air Temperature PID loop modulates from 0% to 100% as the Discharge Air Temperature rises above the Discharge Air Temperature setpoint. The Discharge Air Temperature setpoint resets between room temperature and the limit for minimum discharge air temperature as the cooling loop varies between 0 and 50%. If the Discharge Air Temperature decreases below 55° F, the Outside Air Damper returns to the minimum damper position.

Heat pump unit specific functions

The fan and staging sequences for heat pump units are similar to the roof top unit fan and staging sequences. See the topics Staged heating and cooling for for
roof top and heat pump units on page 74 and Fan control for roof top and heat pump units on page 74.

Reversing valve action

The AppStat reversing valve output, terminal O/B, is energized on a call for cooling (‘O’ function). The action can be changed from the user interface to be active on a call for heating (‘B’ function). The ‘O’ function is the default.

Auxiliary or emergency heat action

The heat pump unit AUX/E output is for auxiliary or emergency heat. Operation can be configured for one of three modes.
Compressor lockout —The AUX/E output terminal is active only on a call
for heating when the compressors are locked out. The compressors are locked out when the outside air temperature drops below the value of the Compressor OAT Low Limit. The lockout is cleared when the outside air temperature rises 2° F above the value of Compressor OAT Low Limit.
Third stage—The AUX/E output functions as the output for a third stage of
heat.
Revision G 75
Page 76
Section 5: Sequences of operation KMC Controls, Inc.
None—This function is a manual operation that can only be turned on from
the user interface. When emergency heat is turned on, the AUX/E output is used to maintain the active heating setpoint and both compressor outputs are locked-out.
76 Revision G
Page 77
Installation, Operation, and Application Guide for AppStat

Sec tion 6: A pplic ati o n draw ings

This section covers the drawings, materials, and instructions for specific AppStat applications.
Each AppStat model is designed for a specific application. The following topics are for control technicians and engineers that will plan and install AppStat controllers for the following applications.
Fan Coil Unit applications on page 78
Roof Top Unit applications on page 98
Heat Pump Unit applications on page 108
Revision G 77
Page 78
Section 6: Application drawings KMC Controls, Inc.

Fan Coil Unit applications

This section covers applications for fan coil units. For other applications see
Roof Top Unit applications on page 98 or Heat Pump Unit applications on page
108.

Fan Coil Unit—Four-pipe with three-speed fan and on/off valves

This application applies to models BAC-4001CW0001, BAC-4021CW0001, BAC-4201CW0001, and BAC-4221CW0001.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
For dehumidification, the AppStat must include a humidity sensor.
The remote temperature sensor (RS) is optional.
Valves are 24 Volt AC.
Fan outputs are for 24 volt AC pilot duty inputs.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–1 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Controls transformer
78 Revision G
Page 79
H M L
STE-1405
FAN
24 VAC Class-2
STE-6011W10
or equivalent
(optional)
FST N.C Fan Status
CSE-1102
Controls
transformer
DAT
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–1 Wiring details: Four-pipe FCU with on/off valves
Revision G 79
Page 80
Section 6: Application drawings KMC Controls, Inc.

Fan Coil Unit—Four-pipe with three-speed fan and modulating valves

This application applies to models BAC-4002CW0001, BAC-4022CW0001, BAC-4202CW0001, and BAC-4222CW0001.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
For dehumidification, the AppStat must include a humidity sensor.
The remote temperature sensor (RS) is optional.
Valves are 24 Volt AC with a 0–10 Volt DC control signal.
Fan outputs are for 24 volt AC pilot duty inputs.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–2 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Controls transformer
80 Revision G
Page 81
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
H M L
FAN
STE-1405
24 VAC Class-2
0-10
VDC
0-10 VDC
FSTN.C Fan Status
CSE-1102
Controls
transformer
DAT
STE-6011W10
or equivalent
(optional)
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–2 Wiring details: Four pipe FCU with three-speed fan and modulating valves
Revision G 81
Page 82
Section 6: Application drawings KMC Controls, Inc.

Fan Coil Unit—Four-pipe with modulating fan and on/off valves

This application applies to models BAC-4007CW0001, BAC-4027CW0001, BAC-4207CW0001, and BAC-4227CW0001.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
For dehumidification, the AppStat must include a humidity sensor.
The remote temperature sensor (RS) is optional.
Valves are 24 Volt AC.
Fan starting input is 24 volt AC pilot duty.
Fan speed input is 0-10 volts DC.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–3 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Controls transformer
82 Revision G
Page 83
FAN
24 VAC Class-2
FST
Controls
transformer
N.C Fan Status CSE-1102
STE-1405
STE-6011W10
or equivalent
(optional)
DAT
SPD SRT
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–3 Wiring details: Four-pipe FCU with modulating fan and on/off valves
Revision G 83
Page 84
Section 6: Application drawings KMC Controls, Inc.

Fan Coil Unit—Four-pipe with modulating fan and modulating valves

This application applies to models BAC-4008CW0001, BAC-4028CW0001, BAC-4208CW0001, and BAC-4228CW0001.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
For dehumidification, the AppStat must include a humidity sensor.
The remote temperature sensor (RS) is optional.
Valves are 24 Volt AC.
Fan start output is for a 24 volt AC pilot duty input.
Fan speed input is 0-10 volts DC.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–4 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
STE-1455 Strap-on water temperature sensor, 10 kΩ Type
III
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Water temperature sensor
Controls transformer
84 Revision G
Page 85
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
24 VAC Class-2
0-10
VDC
0-10 VDC
FAN
FST
Controls
transformer
N.C Fan Status
CSE-1102
STE-1405DAT
STE-6011W10
or equivalent
(optional)
SPD SRT
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–4 Wiring details: Four-pipe FCU with modulating fan and modulating valves
Revision G 85
Page 86
Section 6: Application drawings KMC Controls, Inc.

Fan Coil Unit—Two-pipe with three-speed fan and on/off valves

This application applies to models BAC-4001CW0001, BAC-4201CW0001, BAC-4021CW0001, and BAC-4221CW0001.
The water temperature sensor (WST) is required for two-pipe units.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
The remote temperature sensor (RS) is optional.
The valve is 24 Volt AC.
Fan outputs are for 24 volt AC pilot duty inputs.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–5 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
STE-1455 Strap-on water temperature sensor, 10 kΩ Type
III
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Water temperature sensor
Controls transformer
86 Revision G
Page 87
H M L
FAN
24 VAC Class-2
FST N.C Fan Status
CSE-1102
STE-1455
Controls
transformer
STE-1405DAT
WST
STE-6011W10
or equivalent
(optional)
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–5 Wiring details: Two-pipe FCU with three-speed fan and on/off valves
Revision G 87
Page 88
Section 6: Application drawings KMC Controls, Inc.

Fan Coil Unit—Two-pipe with three-speed fan and modulating valve

This application applies to models BAC-4002CW0001, BAC-4022CW0001, BAC-4202CW0001, and BAC-4222CW0001.
The water temperature sensor (WST) is required for two-pipe units.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
The remote temperature sensor (RS) is optional.
Valves are 24 Volt AC. with a 0-10 Volt DC control signal.
Fan outputs are for 24 volt AC pilot duty inputs.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–6 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
STE-1455 Strap-on water temperature sensor, 10 kΩ Type
III
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Water temperature sensor
Controls transformer
88 Revision G
Page 89
H M L
FAN
24 VAC Class-2
0-10 VDC
FST N.C Fan Status
CSE-1102
Controls
transformer
STE-1455
STE-1405
DAT
WST
STE-6011W10
or equivalent
(optional)
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–6 Wiring details: Two-pipe FCU with three-speed fan and modulating valve
Revision G 89
Page 90
Section 6: Application drawings KMC Controls, Inc.

Fan Coil Unit—Two-pipe with modulating fan and on/off valve

This application applies to models BAC-4007CW0001, BAC-4027CW0001, BAC-4207CW0001, and BAC-4227CW0001.
The water temperature sensor (WST) is required for two-pipe units.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
The remote temperature sensor (RS) is optional.
Valves are 24 Volt AC.
Fan start output (FAN-L) is for a 24 volt AC pilot duty input.
Fan speed output (AO8) is 0-10 volts DC.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–7 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
STE-1455 Strap-on water temperature sensor, 10 kΩ Type
III
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Water temperature sensor
Controls transformer
90 Revision G
Page 91
FAN
24 VAC Class-2
FSTN.C Fan Status
CSE-1102
Controls
transformer
STE-1455
STE-1405
DAT
WST
STE-6011W10
or equivalent
(optional)
SPD SRT
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–7 Wiring details: Two-pipe FCU with modulating fan and on/off valve
Revision G 91
Page 92
Section 6: Application drawings KMC Controls, Inc.

Fan Coil Unit—Two-pipe with modulating fan and modulating valve

This application applies to models BAC-4008CW0001, BAC-4028CW0001, BAC-4208CW0001, and BAC-4228CW0001.
The water temperature sensor (WST) is required for two-pipe units.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
The remote temperature sensor (RS) is optional.
Valves are 24 Volt AC.
Fan start output (FAN-L) is for a 24 volt AC pilot duty input.
Fan speed output (AO8) is 0-10 volts DC.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–8 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
STE-1455 Strap-on water temperature sensor, 10 kΩ Type
III
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Water temperature sensor
Controls transformer
92 Revision G
Page 93
FAN
24 VAC Class-2
0-10 VDC
FST
N.C Fan Status
CSE-1102
Controls
transformer
STE-1455
STE-1405
DAT
WST
STE-6011W10
or equivalent
(optional)
SPD SRT
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–8 Wiring details: Two-pipe FCU with modulating fan and modulating valve
Revision G 93
Page 94
Section 6: Application drawings KMC Controls, Inc.

Fan Coil Unit—Two-pipe with three-speed fan, modulating valve, and electric heat

This application applies to models BAC-4003CW0001, BAC-4023CW0001, BAC-4203CW0001, and BAC-4223CW0001.
The water temperature sensor (WST) is required for two-pipe units.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
The remote temperature sensor (RS) is optional.
Valves are 24 Volt AC. with a 0-10 Volt DC control signal.
Fan and heat outputs are for 24 volt AC pilot duty inputs.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–9 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
STE-1455 Strap-on water temperature sensor, 10 kΩ Type
III
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Water temperature sensor
Controls transformer
94 Revision G
Page 95
H M L
FAN
24 VAC Class-2
0-10
VDC
FST N.C Fan Status
CSE-1102
Controls
transformer
STE-1455
STE-1405
DAT
WST
STE-6011W10
or equivalent
(optional)
24 VAC
Relay
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–9 Wiring details: Two-pipe FCU with three-speed fan, modulating valve, and electric heat
Revision G 95
Page 96
Section 6: Application drawings KMC Controls, Inc.
Fan Coil Unit—Two-pipe with modulating speed fan, modulating valve, and electric heat
This application applies to models BAC-4003CW0001, BAC-4023CW0001, BAC-4203CW0001, and BAC-4223CW0001.
The water temperature sensor (WST) is required for two-pipe units.
Fan status switch (FST) and discharge air temperature sensor (DAT) are optional. They are typically used only when the AppStat is connected to a network.
The remote temperature sensor (RS) is optional.
Valves are 24 Volt AC. with a 0-10 Volt DC control signal.
Heat output is for a 24 volt AC pilot duty input.
Fan starting input is 24 volt AC pilot duty.
Fan speed input is 0-10 volts DC.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–10 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
STE-1455 Strap-on water temperature sensor, 10 kΩ Type
III
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Water temperature sensor
Controls transformer
96 Revision G
Page 97
FAN
24 VAC Class-2
0-10
VDC
FST N.C Fan Status
CSE-1102
Controls
transformer
STE-1455
STE-1405
DAT
WST
STE-6011W10
or equivalent
(optional)
24 VAC
Relay
SPD SRT
MS/TP
+B
A
RS
WST
GND
DAT
COM
FAN-L
FAN-M
FAN-H
R
BO4
BO5
GND
AO6
AO8
AO7
24VAC
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–10 Wiring details: Two-pipe FCU with modulating fan, modulating valve, and electric heat
Revision G 97
Page 98
Section 6: Application drawings KMC Controls, Inc.

Roof Top Unit applications

This section covers applications for roof top units. For other applications see
Fan Coil Unit applications on page 78 and Heat Pump Unit applications on page 108.

Roof Top Unit—Two-stage gas heat and two-stage DX cooling

This application applies to models BAC-4221CW0002, BAC-4021CW0002, BAC-4201CW0002, and BAC-4001CW0002.
Fan status switch (FST) and discarge air temperature (DAT) and outdoor air temperature (OAT) sensors are optional. They are typically used only when the AppStat is connected to a network.
For dehumidification, the AppStat must include a humidity sensor.
The remote temperature sensor (RS) is optional.
For single stage heating, delete connection W2.
For single stage cooling, delete connection Y2.
Connect outputs to 24 volt AC pilot duty inputs.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–11 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
STE-1451 Outdoor air temperature sensor, 10 kΩ Type III Outdoor air temperature
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Controls transformer
98 Revision G
Page 99
MS/TP
+B
A
RS
OAT
GND
DAT
ECON
G
Y1
Y2
RC
W1
W2 RH
AO6
AO7
COM
24VAC
FAN
24 VAC Class-2
STE-1451
FST
W2 W1 GY2 Y1CR
N.C Fan Status CSE-1102
STE-1405
STE-6011W10
or equivalent
(optional)
DAT
OAT
Controls
transformer
GAS
GAS
DX DX
Installation, Operation, and Application Guide for AppStat Section 6: Application drawings
Illustration 6–11 Wiring details: RTU two-stage gas heat and two-stage DX cooling
Revision G 99
Page 100
Section 6: Application drawings KMC Controls, Inc.

Roof Top Unit—Two-stage gas heat and two-stage DX cooling with economizer

This application applies to models BAC-4223CW0002, BAC-4023CW0002, BAC-4203CW0002, and BAC-4003CW0002
Fan status switch (FST) is optional. Typically it is used only when the AppStat is connected to a network.
Discharge air temperature (DAT) and outdoor air temperature (OAT) sensors are required for economizer operation.
For dehumidification, the AppStat must include a humidity sensor.
The remote temperature sensor (RS) is optional.
For single stage heating, do not connect W2.
For single stage cooling, do not connect Y2.
Connect outputs to 24 volt AC pilot duty inputs.
For additional details on connecting sensors, see Connecting inputs on
page 20.
For additional detail on connecting the fan and valves, see Connecting
outputs on page 24.
Table 6–12 Materials list
KMC Part
Description Function
No.
CSE-1102 Differential Pressure Switch, Barb Fittings Fan status switch
STE-1405 Duct temperature sensor, 10 kΩ Type III Discharge air temperature
STE-1451 Outdoor air temperature sensor, 10 kΩ Type III Outdoor air temperature
STE-6011W10 Temperature sensor, 10 kΩ Type II Remote space temperature
XEE-6111-040 XEE-6112-040 XEE-6311-075
Single-hub 120 volt power transformer Dual-hub 120 volt power transformer 120/240/277/480VAC, 24 VAC, 75 VA transformer
Controls transformer
100 Revision G
Loading...