KMC Controls BAC-14xx63 User Manual

BAC-12xx63/13xx63/14xx63 Series FlexStat
6 Relays, 3 Analog Outputs, 6 External Inputs
Installation Guide (6/3 Outputs)

MountingQuick Start

CAUTION
This document is for 6-relay, 3-analog-output, 6-external-input BAC-12xx63/13xx63/14xx63 series
ONLY. THESE MODELS ARE NOT COMPATIBLE
WITH THE BACKPLATES OF OLDER BAC-10000 SERIES FLEXSTATS (WITH ONLY 3 EXTERNAL INPUTS)! If replacing an older 3-input FlexStat,
replace the backplate as well. See other installation guides for other models.
To select and use a FlexStat in an application:
1. Select the appropriate model for the intended
application and options (see the FlexStat Data Sheet).
2. Mount and wire the unit (see this Installation Guide).
3. Congure/program the unit (see the FlexStat
Operation and Application Guides).
4. If necessary, troubleshoot any issues (see the FlexStat Operation Guide).
5. Operate the unit (see the FlexStat Operation Guide).
NOTE: This document gives basic mounting,
wiring, and setup information only. For conguration, programming, operation, and other information, see the KMC Controls web site for the latest documents.
Models
BAC-12xxxx (shown) 1.125 (29)
BAC-13xxxx/14xxxx 1.437 (36.5) 5.192 (132)
A
Dimensions in Inches (mm)
A B C
4.192 (106)
5.551 (141)
Embossed “UP” indicator
For optimum temperature sensor performance, the FlexStat must be mounted on an interior wall and away from heat sources, sunlight, windows, air vents, and air circulation obstructions (e.g., curtains, furniture). Additionally, for a model with an occupancy sensor option, install it where it will have unobstructed view of the most typical trac area. (See the FlexStat Application Guide for more
information.)
If replacing an existing thermostat, label wires as needed for reference when removing the existing thermostat.
1. Complete rough-in wiring at each location prior to thermostat installation. Cable insulation must meet local building codes.
CAUTION
To prevent mounting screw heads from touching the circuit board in the thermostat, use only the mounting screws supplied by KMC Controls. Using other screws may damage the FlexStat. Do not turn screws in farther than necessary to remove the cover.
2. If the cover is locked on the backplate, turn the
hex screws in the boom and top of the FlexStat CLOCKWISE until they (just) clear the cover. (See Illustration 1.) Pull the cover away from the backplate (mounting base).
3. Route the wiring through the backplate.
4. With the embossed “UP” and arrows toward the
ceiling, fasten the backplate to a wall handy-box. BAC-12xxxx models mount directly on vertical 2 x 4 inch boxes, but they require an HMO-10000/ HMO-10000W wall mounting plate for horizontal or 4 x 4 boxes. BAC-13xxxx/14xxxx models mount directly on any of those types of boxes.
EIA-485 data
B
port (for quick
network access)
5. Make the appropriate connections to the terminal
blocks. (See the Connections and Wiring section.)
6. Place the FlexStat cover over the backplate while
Terminal blocks on
backplate (rotated on
BAC-13xxxx/14xxxx)
C
Illustration 1—Dimensions and Installation
BAC-12xx63/13xx63/14xx63 Series FlexStat 1 Installation Guide, Rev. C
Cover locking hex screws
being careful not to pinch or dislodge any wiring. Back the hex screws (counterclockwise)
out of the brackets until they engage the FlexStat cover and hold it in place.

Connections and Wiring

Wiring Considerations

• Because of the many connections (power, network, inputs, outputs, and their respective grounds or switched commons), be sure wiring is well planned before installation of conduit!
• Make sure that conduit for all wiring has ad­equate diameter for all necessary wiring. Using 1-inch conduit and junction boxes is recommend­ed! Use external junction boxes above the ceiling or in another convenient location as needed to make connections that run to the FlexStat’s junction box.
• To prevent excessive voltage drop, use a conduc-
tor size that is adequate for the wiring length! Allow plenty of “cushion” to allow for tran­sient peaks during startup.
• Using multiple conductor wires for all relevant inputs (e.g., 8 conductor) and outputs (e.g., 12 conductor) is recommended. Grounds for all the inputs can be combined on one wire.
CAUTION
To avoid damage from ground loops and other communication issues in networked FlexStats, correct phasing on MS/TP network and power connections on ALL the networked controllers is critically important.

Network Wiring

For Ethernet or IP communications, plug an Ethernet cable into the RJ-45 jack on the back of the FlexStat.

MS/TP EOL (End-Of-Line) Termination

The controllers/thermostats on the physical ends of an EIA-485 wiring segment must have end-of-line termination installed for proper network operation. (See Illustrations 2 through 4.) If a FlexStat is at the physical end of the MS/TP network line, set both the EOL termination switches to On (to the right/up) on the back of the circuit board. If not on the end, ensure that both switches are O (le/down).
   
Illustration 2—MS/TP Network End-Of-Line Termination
Input Pull-Up Switches
EOL Switches
OFF
ON
NOTE: EOL = End Of Line of BACnet MS/TP network.
NOTE: 10K inputs are configurable for Type II or Type III thermistors in FlexStat’s menu.
Left
0-12 V
Switch
Pushed
Right
IN9
IN8
IN7
IN4
IN3
IN2
10K
Switch
Pushed
Illustration 3—BAC-12xxxx EOL/Pull-Up Switch Positions
For MS/TP communications, connect the –A terminals
ON
0-12 VDC
in parallel with all other –A terminals on the network and the +B terminals in parallel with all other +B termi- nals. (See Illustrations 2 and 4.) Connect the shields of
OFF
Switch Pushed Up
Pushed Down
10K Ohm
the cable (Belden cable #82760 or equivalent) together at each device. Use a wire nut or the S terminal in KMC BACnet controllers. (FlexStats, however, do not have an S terminal.) Connect the cable shield to a good earth ground at one end only.
EOL
Switches
IN2 IN3 IN4 IN7 IN8
Input Pull-Up Switches
IN9
NOTE: The S terminal in KMC controllers is
provided as a connecting point for the shield. The terminal is not connected to the ground of the controller. When connecting to controllers from other manufacturers, verify the shield connection is not connected to the controller’s ground.
For more information on principles and good practic­es when connecting an MS/TP network, see Planning BACnet Networks (Application Note AN0404A).
BAC-12xx63/13xx63/14xx63 Series FlexStat 2 Installation Guide, Rev. C
Illustration 4—BAC-13xxxx/14xxxx Switch Positions
CAUTION
This document is for 6-relay, 3-analog-output, 6-external-input BAC-12xx63/13xx63/14xx63 series ONLY. THESE MODELS ARE NOT COMPATIBLE WITH THE BACKPLATES OF OLDER BAC-10000 SERIES FLEXSTATS (WITH ONLY 3 EXTERNAL INPUTS)! If replacing an older 3-input FlexStat, replace the backplate as well.
NOTE: SC = Switched
(relay) Common
NOTE: IN1 and IN5–6 are
reserved for internal sensors
Inputs
(Wiring is dependent on application)
MS/TP Network
Inputs
24 VAC
Illustration 5—(BAC-12xx63) Terminals and Connections
Common/–/C
Phase/ /R
IN9
IN8
GND
IN7
+B
–A
IN4
IN3
GND
IN2
(Wiring Cutout in Backplate)
IP/Ethernet
Network
(Optional)
Outputs
Analog 9
GND 7–9
Analog 8
Analog 7
Relay 6
SC 4–6
Relay 5
Relay 4
Relay 3
SC 1–3
Relay 2
Relay 1
NOTE: On BAC-13xxxx/14xxxx models, terminals
are rotated 90° CCW.

Input Connections

Passive input devices require pull-up resistors in the circuit. For passive input devices (e.g., switch con­tacts and 10K ohm thermistors) on IN2 through IN4 and IN7 through IN9, set the pull-up switches on the back of the circuit board to the 10K position. For
active voltage devices, set the switches to the 0–12 VDC position. (See Illustrations 3 through 5.)
NOTE: Unlike the EOL switch pairs, the INPUT
switch pairs must NOT have both switch­es set to the same direction—if one of the
pair’s switches is set to the le, for example, the other must be set to the right (or vice versa). ALL the input pull-up resistor
switch pairs must be fully latched in ei­ther 10K Ohm or 0–12 VDC position even if a switch pair has no input connected! A
single incorrect switch position may cause errors in multiple inputs.
NOTE: Type II or III 10K ohm thermistors can
be selected by changing the menu seing in Advanced > Inputs > Input # > Sensor (see the Conguration section). If a remote space temperature sensor is connected to AI7, space temperature can be congured for onboard, remote, averaging of the two, the lowest reading, or the highest reading.
NOTE: FlexStat inputs do not support 1K ohm
RTDs.
NOTE: To use a 4–20 current loop input or map
analog inputs as binary values, see the FlexStat Application Guide.
NOTE: To use a remote SAE-10xx CO2 sensor, see
the FlexStat Operation Guide.
NOTE: For more information on wiring specic
applications (AHU, FCU, HPU, RTU), see the Applications section starting on page
5. (These applications are the packaged
programs selectable from the Advanced > Application menu in the BAC-1xxx63C models.)
CAUTION
Relays are for Class-2 voltages (24 VAC) only. Do not connect line voltage to the relays!
CAUTION
Do not mistakenly connect 24 VAC to an analog output ground. This is not the same as a relay’s switched common. See the backplate’s terminal label for the correct terminal.

Output Connections

Connect the device under control between the desired output terminal and the related SC (Switched Com- mon for relays) or GND (Ground for analog outputs) terminal. (See Illustration 5).
For the bank of three relays, there is one Switched (relay) Common connection (in place of the GND terminal used with analog outputs). (See Illustration
6.) For the relay circuit, the phase side of the AC
should be connected to the SC terminal.
One Switched Common Connection Per Bank of Three Normally Open Relays
Illustration 6—Switched (Relay) Common and Relays
Do not aach a device that draws current exceeding the FlexStat’s output capacity:
• Maximum output current for individual ANA­LOG outputs (7–9) is 20 mA @ 12 VDC (each).
• Max. output current is 1 A for individual RELAYS @ 24 VAC/VDC or a total of 1.5 A per bank of 3 relays (relays 1–3 and 4–6).
Relay 3 (or 6)
SC (Phase) 1–3 (or 4–6)
Relay 2 (or 5)
Relay 1 (or 4)
BAC-12xx63/13xx63/14xx63 Series FlexStat 3 Installation Guide, Rev. C
For example, (discontinued) KMC REE-3211 relays would exceed the FlexStat’s analog output capacity, but they can be used with the FlexStat’s internal relays 1–3 as shown in the following applications pages. (Use a Core Components CVR11C-0/LD96200 in the REE-3211’s place in those applications.)
FlexStat relays 1–6 are NO, SPST (Form “A”). (To emulate binary outputs with the analog outputs, set the output voltage to be either 0 or 12 VDC in Control
Basic.)
NOTE: Applications on pages 5–9 are the packaged
programs selectable from the Advanced > Application menu in the BAC-1xxx63 (only) models. Other FlexStat models have other applications.
NOTE: Humidity, motion, and CO2 sensor options
are dependent on the FlexStat model.
For detailed conguration, operation, troubleshoot- ing, and other information, see the FlexStat Opera­tion Guide.

Power Connection

The FlexStat requires an external, 24 volt, AC power source. Use a KMC Controls Class-2 transformer to supply power. Connect the transformer’s neutral lead to the 24 VAC Common/–/C terminal and the AC phase lead to the 24 VAC Phase/~/R terminal. (See Illustration 5.) Power is applied to the FlexStat when the transformer is powered.
KMC Controls recommends powering only one con­troller/thermostat from each transformer. If installing a FlexStat in a system with other controllers/thermo­stats powered from a single transformer, however, phasing must be correct and the total power drawn from the transformer must not exceed its rating.
Configuration
To congure the FlexStat, navigate the menus and change seings by pressing a combination of buons. Press the Right (Menu) buon and then the:
• Enter buon to select and/or exit value editing.
• Up/Down buon to move among entries (up/ down lines).
• Le/Right buon to move among value elds (le/right spaces).
• Le buon to return to the Home screen.
For additional wiring, customization, program- ming, and application information, see the FlexStat Application Guide.

Applications Notes and Cautions

CAUTION
Relays are for Class-2 voltages (24 VAC) only. Do not connect line voltage to the relays!
Do not mistakenly connect 24 VAC to an analog output ground.
NOTE: Although typical terminal code leers are
shown, check the schematics of your unit for wiring details!
NOTE: These applications are for 6 relay and 3 ana-
log output BAC-12xx63/13xx63/14xx63 series
only. See other installation guides for other models.
NOTE: CO2, humidity, and motion sensor options
are dependent on FlexStat model.
NOTE: For Bill of Materials listings of the various
accessories shown in the sample diagrams, see the FlexStat Application Guide.
NOTE: Do not use REE-3211s with analog outputs!
See Output Connections on page 3.
NOTE: The KMC REE-3211 is discontinued. Use Core
Components CVR11C-0/LD96200 in its place.
MAINMENU ABOUT
ADVANCED
ALARM DATE/TIME SCHEDULE SETPOINTS SYSTEM
Illustration 6—Configuration Screens
ADVANCED
APPLICATION
CBPROGRAMS COMMUNICATION DATE/TIME DEVICE INPUTS LIMITS
(See
menus
on the
following
pages)

Maintenance

Remove dust as necessary from the holes in the top and boom. Clean the display with a so, damp cloth and mild soap.
To maintain maximum sensitivity of the built-in motion sensor, occasionally wipe dust or dirt o the
Do not use either with analog outputs! See Output Connections on page 3.
lens—but do not use any uid on the sensor.
BAC-12xx63/13xx63/14xx63 Series FlexStat 4 Installation Guide, Rev. C

Applications

Air Handler Unit (AHU)—
Modulating Heat and Modulating Cool
NOTE: See also the RTU section
for 2-stage options.
REE-3211 Multi-Voltage Relay
XEE-6311-075/6311-100 Transformer
MEP-5372/7252/7552/7852 Fail-Safe Actuators
XEE-6311-075 Transformer
VEP-45xxB895/VEB-43xxxBDL Valves with MEP-5372 Fail-Safe Actuators
AHU LAYOUT
APPLICATION DEGREESSCALE:°F
APP:
AIRHANDLER
ADDITIONALSETUP
ADDITIONALSETUP
DAMPER
FAN HUMIDITY OPTIMUMSTART SENSORS
Input Terminals AHU Input Connections BACnet Objects
IN9 Opt. Remote CO
Sensor* AI9
2
IN8 AI8
IN7 Opt. Remote Temp. Sensor* AI7
IN4 Opt. Outside Air Temp. (OAT)** AI4
IN3 Opt. Mixed Air Temp. (MAT)** AI3
GND Ground
IN2 Optional FST or DAT* AI2
*Fan Status (FST), Discharge Air Temperature (DAT), and (not shown on the diagram) remote temp./CO pull-up resistor switch positions appropriately (see the Input
sensors are optional inputs. Set
2
Connections section). **When using the optional Outside Air Damper, MAT/OAT inputs must also be connected.
CSE-1102 Air Differential
Pressure Switch
STE-1402 Duct Sensor, Type III
Output
Terminals
AHU Output Connections
(Modulating)
BACnet Objects
Analog 9 Outside Air Damper (OAD/RTD)* AO9
NOTE: EITHER FAN STATUS (FST) OR
DISCHARGE AIR TEMP (DAT) CAN BE USED ON IN2, BUT NOT BOTH.
GND Ground (for analog output terminals 7–9)
Analog 8 Heating Valve (HTV) AO8
Analog 7 Cooling Valve (CLV) AO7
Relay 6 BO6
STE-1416 Duct Averaging Temp. Sensor
SC 4–6
Relay 5 BO5
Relay 4 BO4
STE-1451 Outside Air Temp. Sensor
Relay 3 BO3
SC 1–3 24 VAC (for relay terminals 1–3)
Relay 2 BO2
Relay 1 Fan BO1
*If optional Outside Air Damper is used, must also have MAT/OAT inputs.
BAC-12xx63/13xx63/14xx63 Series FlexStat 5 Installation Guide, Rev. C
Heat Pump Unit (HPU)—
1 or 2 Compressors with Auxiliary and Emergency Heat
NOTE: To see Humidity options in the
Additional Setup menu, select an Aux. Heat option other than None (the default).
XEE-6311-075 or XEE-6311-100 Transformer
HPU LAYOUT
MEP-5372/7252/7552/7852 Fail-Safe Actuators
CSE-1102 Air Differential
Pressure Switch
STE-1402 Duct Sensor, Type III
NOTE: EITHER FAN STATUS (FST) OR
DISCHARGE AIR TEMP (DAT) CAN BE USED ON IN2, BUT NOT BOTH.
STE-1416 Duct Averaging Temp. Sensor
STE-1451 Outside Air Temp. Sensor
NOTE: WIRE TO “O” TERMINAL IF
REVERSING VALVE IS ENERGIZED IN COOLING MODE; WIRE TO “B” TERMINAL IF REVERSING VALVE IS ENERGIZED IN HEATING MODE.
APPLICATION DEGREESSCALE:°F
APP:
HEATPUMP OPT:1STAGE ADDITIONALSETUP
ADDITIONALSETUP
AUXHEAT
DAMPER FAN HUMIDITY OPTIMUMSTART SENSORS
Input Terminals HPU Input Connections BACnet Objects
IN9 Opt. Remote CO
Sensor* AI9
2
IN8 AI8
IN7 Opt. Remote Temp. Sensor* AI7
IN4 Opt. Outside Air Temp. (OAT)** AI4
IN3 Opt. Mixed Air Temp. (MAT)** AI3
GND Ground
IN2 Optional FST or DAT* AI2
*Fan Status (FST), Discharge Air Temperature (DAT), and (not shown on the diagram) remote temp./CO pull-up resistor switch positions appropriately (see the Input
sensors are optional inputs. Set
2
Connections section). **When using the optional Outside Air Damper, MAT/OAT inputs must also be connected.
Output
Terminals
Typical
Terminal
Codes
HPU Output Connections
BACnet Objects
Analog 9 Outside Air Damper (OAD/RTD)* AO9
GND
(for analog output terminals 7–9)
Ground
Analog 8 AO8
Analog 7 AO7
Relay 6 W2/E Emergency Heat (Optional) BO6
SC 4–6 R 24 VAC (for relay terminals 4–6)
Relay 5 W Auxiliary Heat (Optional) BO5
Relay 4 Y2 Compressor 2 (Optional) BO4
Relay 3 Y1 Compressor 1 BO3
SC 1–3 R 24 VAC (for relay terminals 1–3)
Relay 2 O/B
Reversing Valve
(see O/B Note in schematic)
BO2
Relay 1 G Fan BO1
*If optional Outside Air Damper is used, must also have MAT/OAT inputs.
BAC-12xx63/13xx63/14xx63 Series FlexStat 6 Installation Guide, Rev. C

Roof Top Unit (RTU)— 1 or 2 Heat and 1 or 2 Cool

XEE-6311-075 or XEE-6311-100 Transformer
RTU 2H/2C LAYOUT
MEP-5372/7252/7552/7852 Fail-Safe Actuators
CSE-1102 Air Differential
Pressure Switch
NOTE: EITHER FAN STATUS (FST) OR
DISCHARGE AIR TEMP (DAT) CAN BE USED ON IN2, BUT NOT BOTH.
STE-1416 Duct Averaging Temp. Sensor
STE-1451 Outside Air Temp. Sensor
RC AND RH TERMINALS ARE PRESENT:
IF BOTH WIRE RC TO SC 1-3 AND RH TO SC 4-6.
IF ONLY ONE “R” TERMINAL IS PRESENT: WIRE BOTH SC 1-3 AND SC 4-6 TO R.
STE-1402 Duct Sensor, Type III
APPLICATION DEGREESSCALE:°F
APP:
ROOFTOP OPT:1H/1C ADDITIONALSETUP
ADDITIONALSETUP
DAMPER
FAN HUMIDITY OPTIMUMSTART SENSORS
Input Terminals RTU Input Connections BACnet Objects
IN9 Opt. Remote CO
Sensor* AI9
2
IN8 AI8
IN7 Opt. Remote Temp. Sensor* AI7
IN4 Opt. Outside Air Temp. (OAT)** AI4
IN3 Opt. Mixed Air Temp. (MAT)** AI3
GND Ground
IN2 Optional FST or DAT* AI2
*Fan Status (FST), Discharge Air Temperature (DAT), and (not shown on the diagram) remote temp./CO pull-up resistor switch positions appropriately (see the Input
sensors are optional inputs. Set
2
Connections section). **When using the optional Outside Air Damper, MAT/OAT inputs must also be connected.
Output
Terminals
Typical Terminal
Codes
RTU Output Connections
(1 or 2 H and 1 or 2 C)
BACnet Objects
Analog 9 Outside Air Damper (OAD/RTD)* AO9
GND
(for analog output terminals 7–9)
Ground
Analog 8 AO8
Analog 7 AO7
Relay 6 BO6
SC 4–6 RH/R 24 VAC (for relay terminals 4–6)
Relay 5 W2 Heat 2 (Optional) BO5
Relay 4 W1 Heat 1 BO4
Relay 3 Y2 Cool 2 (Optional) BO3
SC 1–3 RC/R 24 VAC (for relay terminals 1–3)
Relay 2 Y1 Cool 1 BO2
Relay 1 G Fan BO1
*If optional Outside Air Damper is used, must also have MAT/OAT inputs.
BAC-12xx63/13xx63/14xx63 Series FlexStat 7 Installation Guide, Rev. C
Fan Coil Unit (FCU)—
2 or 4 Pipe, Modulating or 2 Position
FCU 4-PIPE
MODULATING LAYOUT
(See the FCU—Other Options section on the next page for more options)
CSE-1102 Air Differential
Pressure Switch
4-PIPE MODULATING OPTION
XEE-6311-050 Transformer
VEP-45xxB745/ VEB-43xxxBCK
MEP-4002 0–10
VDC Actuators
NOTE: EITHER FAN STATUS (FST) OR
DISCHARGE AIR TEMP (DAT) CAN BE USED ON IN2, BUT NOT BOTH.
Valves with
STE-1402 Duct Sensor, Type III
NOTE: To see
Humidity options in the Additional Setup menu, select the 4-Pipe option.
Input Terminals FCU Input Connections BACnet Objects
IN9 Opt. Remote CO
IN8 AI8
IN7 Opt. Remote Temp. Sensor* AI7
IN4 AI4
IN3 Supply Water Temp. (W-TMP)** AI3
GND Ground
IN2 Optional FST or DAT* AI2
*Fan Status (FST), Discharge Air Temperature (DAT), and (not shown on the diagram) remote temp./CO pull-up resistor switch positions appropriately (see the Input Connections section). **W-TMP is for 2-pipe applications only (see drawings on the next page)
Sensor* AI9
2
sensors are optional inputs. Set
2
REE-3211 or CVR11C-0/LD96200 Multi-Voltage Relays
NOTE: Do not use REE-3211/
CVR11C-0/ LD96200 relays
with analog outputs! See
Output Connec­tions on page 3.
APPLICATION DEGREESSCALE:°F
APP:
FANCOIL OPT:4–PIPE ADDITIONALSETUP
Output Terminals
(BAC-12xxx63C)
Analog 9 AO9
GND
Analog 8
Analog 7
Relay 6 BO6
SC 4–6 24 VAC (for relay terminals 4–6)
Relay 5
Relay 4
Relay 3 Fan 3 BO3
SC 1–3 24 VAC (for relay terminals 1–3)
Relay 2 Fan 2 BO2
Relay 1 Fan 1 BO1
*If optional Outside Air Damper is used, must also have MAT/OAT inputs.
FCU Output Connections
2-Pipe 4-Pipe
(for analog output terminals 7–9)
Valve,
Proportional (VLV)
Valve,
2-Position (VLV)
ADDITIONALSETUP
FAN
HUMIDITY OPTIMUMSTART SENSORS VALVE
Ground
Heat Valve,
Proportional (HTV)
Cool Valve,
Proportional (CLV)
Heat Valve,
2-Position (HTV)
Cool Valve,
2-Position (CLV)
BACnet Objects
AO8
AO7
BO5
BO4
BAC-12xx63/13xx63/14xx63 Series FlexStat 8 Installation Guide, Rev. C

Fan Coil Unit (FCU)—Other Options

Additional Resources

NOTE: See the FCU—Overview section on the
previous page for the 4-Pipe Modulating option and the general schematic.
(4-PIPE 2-POSITION FCU OPTION)
XEE-6311-050 Transformer
BL U (V EP Series) or BLK (VEZ Series
BR N (V EP Series) or RED (VEZ Series
VEP-1xxx0186/VEZ-4xxxxMBx
Valves with 24 VAC Actuators
(See Wire
Colors Above
)
(2-PIPE MODULATING FCU OPTION)
N.O.
)
)
N.C.
The latest support les are always available on the KMC Controls web site (www.kmccontrols.com). To see all available les, you will need to log-in to the Partners site
For specications and accessories, see the BAC-
12xxxx/13xxxx/14xxxx Series FlexStat Data Sheet.
For operation, congura­tion, troubleshooting, and other information, see the
FlexStat Operation Guide.
For additional wiring, ap­plication, and programming information, see the Flex-
Stat Application Guide.
For additional instructions on programming, see the Help system for BACstage or TotalControl.
XEE-6311-050 Transformer
STE-1454 Temp. Sensor
(2-PIPE 2-POSITION FCU OPTION)
XEE-6311-050 Transformer
VEP-1xxx0186/VEZ-4xxxxMBx
Valve with 24 VAC Actuator
BL U (V EP Series) or BLK (VEZ Series
BR N (V EP Series) or RED (VEZ Series
STE-1454
Temp. Sensor
)
)
VEP-45xxB745/ VEB-43xxxBCK
Valve with
MEP-4002 0–10
VDC Actuator

Important Notices

The material in this document is for information purposes only. The contents and the product it describes are subject to change without notice. KMC Controls, Inc. makes no representations or warranties with respect to this document. In no event shall KMC Controls, Inc. be liable for any damages, direct or incidental, arising out of or related to the use of this document.
This device complies with Part 15 of the FCC Rules. Operation is subject to the following two conditions: (1) this device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. A BAC-12xxxx Class B digital apparatus complies with Canadian ICES-003. A BAC-13xxxx/14xxxx Class A digital apparatus com­plies with Canadian ICES-003 Class A.
KMC Controls, Inc.
19476 Industrial Drive
New Paris, IN 46553
574.831.5250; Fax 574.831.5252
www.kmccontrols.com; info@kmccontrols.com
BAC-12xx63/13xx63/14xx63 Series FlexStat 9 Installation Guide, Rev. C
© 2013 KMC Controls, Inc. 913-019-21C
Loading...