KMC BAC-10000 User Manual

FlexStat™ BACnet Programmable Thermostats
Operation Guide
BAC-10000 Series
Contents
Overview ................................................................2
Home, Main Menu, and Override Screens Navigation Main Menu and Settings Room Temp. Setpoint Adjustment H/C, Fan, Occupancy, and Override
Configuration (Initial Setup)
Main Menu Overview About the FlexStat Advanced Menu
(Advanced) Application Options (Advanced) CB (Control Basic) Programs (Advanced) BACnet Communications (Advanced) Date/Time (Advanced) BACnet Device Properties (Advanced) Inputs (Advanced) Temp. Setpoint Limits (Advanced) Motion Sensor (Advanced) Security Levels and Passwords (Advanced) Trend Logs
(Advanced) Test Alarms Date/Time Schedules Setpoints System Setup Trend Viewer
Resetting the FlexStat
Types of Reset Warm and Cold Starts Restore Factory
Network Connection
BAC-10000 Series 1 Operation Guide, Rev. J
............................................................... 11
BACnet MS/TP Network Communication
PC Data Port Connection
....................................................3
..........................................................3
............................................... 4
..................................................5
..............................................10
......................................................... 11
.......................................................... 12
...........................................................13
.....................................................13
.....................................................13
............................................14
....................................................14
.................................................15
............................................. 16
...................................2
..........3
...................................... 3
.......................3
................... 3
...................................4
.........................................4
...................... 5
.........6
..............7
..................................... 7
.............8
............................................8
.................... 8
...............................8
....... 9
................................... 10
....................................... 14
......16
...............................16
Specifications, design, and operation are subject to change without notice.
Troubleshooting ....................................................17
Alarm Issues
Alarm, (False) Fan Fail Alarm, (False) Low Limit (Freeze Stat) Alarm, (False) Space Temp. or Humidity
Communication Issues
Firmware Upgrade Fails KMD-5576 Communication Faulty MS/TP Network Communication Faulty
Cover and Display Issues
Cover Binds on Backplate Display Is Blank or Erratic Display Freezes (Buttons Have No Effect)
Custom Programming and Web Issues
Control Basic Programs Do Not Work Custom Web Graphics Do Not Work
Input, Sensor, and Value Issues
Input Values Are Outside the Expected Range Motion/Occupancy Sensor Does Not Work Temperature Reading Is Incorrect Temperature Setpoint Is Not Maintained
Output, Fan, and Relay Issues
Analog Output Does Not Work Fan Does Not Run Relay (Internal) Does Not Work Relay (External) Does Not Work
Wiring Issues Maintenance Firmware Upgrade Programming (Custom) Accessories Support Important Notices Reference
Index
.................................................................23
Acronyms and Abbreviations
Definitions of Terms
.....................................................................26
......................................................17
.................................... 17
............ 17
........17
......................................17
.................................17
................17
......... 17
................................... 18
..............................18
.............................. 18
...... 18
............... 18
............18
.............18
.......................... 19
19
...19
.................. 19
.......19
...........................20
...................... 20
..........................................20
.....................20
....................21
..................................................... 21
.........................................................22
................................................22
.........................................22
...........................................................22
................................................. 23
..............................................................24
............................. 24
..........................................25

Overview

Applications and Installation

The KMC FlexStat series of intelligent temperature/ humidity/occupancy-sensing, wall-mounted, ther­mostat/controllers are native BACnet Advanced Application Controllers (B-AAC) for use in a BAC­net system. The FlexStat simplies networked zone control for common packaged HVAC equipment, such as packaged rooop units, fan coil units, heat pumps, and other similar applications. In addi­tion, applications such as pressure dependent VAV, terminal reheat, and medium-sized central station air handling equipment applications may also be ad­dressed through the on-board libraries of programs built into the devices.
The on-board library of programs permits rapid conguration of a wide range of HVAC control ap­plications.
The FlexStat series also provides the capability to customize the standard library of sequences using KMC’s BACstage programming tool. This enables a local authorized KMC installing contractor to adapt the standard library to the unique site needs and ap­plication specic requirements of a particular project.
Dimensions in
inches (mm)
1.125 (28.6)
4.192 (106)
5.551 (141)
Terminal Blocks
on Removable
Backplate for
Easy Wiring
Communication with
Other BACnet Devices
Optional
Temperature
Sensing
3 Analog
Inputs
for Other
Sensors or
Contacts
24 Volts AC
Power
Humidity
and
Motion
Sensing
Up to 9
Outputs
(Analog
and/or
Relays)
Quick (Temporary) Network/
Programming Access
Applications
• AHU
• FCU
• HPU
• RTU
1. Wire the FlexStat’s backplate to the desired equipment and set the FlexStat’s end-of-line and input pull-up resistor switches.
2. Select the relevant application and options from the (Advanced) Application submenu of the Advanced Menu and other appropriate menus.
3. Congure the FlexStat for the BACnet network. (See Network Connection on page 16.)
For general mounting and connection details, including network wiring, EOL termination, power connections, input/output connections, pull-up resistor switch seings, see the relevant model’s Installation Guide. For extended information about wiring and sequences for specic applications, see the BAC-10000 Series Application Guide.
EIA-485 Data Port for
Quick Network Access
BAC-10000 Series 2 Operation Guide, Rev. J

Operation (Basic)

Home, Main Menu, and Override Screens

Home Screen
WED 11/19 3:20 PM
Setpoint
COOL:
OCC:
FAN:
HUM: 36% RH
Override Screens
FAN MODES
UNOCC:
OCC: AUTO
AUTO
Override

Navigation

Navigate the menus and change seings by press­ing a combination of various arrow buons and the Enter buon. Push the:
• Enter buon to select and/or exit value editing.
• Up or Down buon to move among entries.
• Right or Le buon to move among value elds.
• Le buon to return to the Home screen.
Up/Setpoint Button
Enter Button
Left/Override
Button
Right/Menu
Button
Configuration Screens
MAIN MENU
ABOUT
Menu
ADVANCED ALARM DATE/TIME SCHEDULE SETPOINTS SYSTEM

Room Temp. Setpoint Adjustment

From the Home (temperature display) screen, press the Up or Down arrow buon once to view the exist­ing setpoint.
To temporarily change the setpoint, press the Up or Down arrow buon repeatedly until the desired seing is displayed and press Enter. (If Enter is not pressed, the display will return to the Home screen aer about ve seconds and the new setpoint value will still be saved.) The new setpoint will hold until the next schedule change.
To permanently change the setpoint for occupied mode, go to the Setpoints section under the Main Menu. (In the Setpoints menu, heating/cooling set­points/setbacks and deadband can be changed with, if required, the correct password access. See Set-
points on page 13.)
Down/Setpoint Button

H/C, Fan, Occupancy, and Override

When the fan is commanded to run, the animated

Main Menu and Settings

“FAN” icon rotates (if programmed to). When the fan command stops, the fan icon is motionless.
From the Home (temperature display) screen, press the Right arrow buon to enter the Main Menu. You may need to enter a password to change any seings.
The “OCC” icon shows a sun when in Occupied mode and a quarter moon when in Unoccupied mode.
HEAT or COOL will show (and be animated when
NOTE: Access to the Main Menu, setpoint adjust,
and System/Occupancy/Fan override may require a password.
there is an active command), depending on the cur­rent mode. This can also be turned OFF.
To override these modes from the Home (tempera-
ture display) screen, press the Le arrow buon. Press Up or Down to get to the desired line and then
Enter (twice) to edit the mode seing. Press
Leto
exit to Home.
BAC-10000 Series 3 Operation Guide, Rev. J
Configuration (Initial Setup)
NOTE: Menus shown in this document reect
rmware version R1.3.0.4 or later. Actual context-sensitive screens are dependent on rmware version, FlexStat model, and options selected.
NOTE: If appear at the top of the screen
(such as in the Main Menu), scroll up or down to see the rest of the menu’s o­screen choices.

Main Menu Overview

MAIN MENU
ABOUT
ADVANCED ALARM DATE/TIME SCHEDULE SETPOINTS SYSTEM
Navigate the menus and change seings by pressing a combination of buons. Press the:
• Enter buon to select and/or exit value editing.
• Up/Down buon to move among entries (up/
down lines).
• Le/Right buon to move among value elds
(le/right spaces).

About the FlexStat

ABOUT FLEXSTAT FW: R1.3.0.0 BUILT: DEC 11 2009 @13:55:07 ASV: BAC_1xx63 R1.3.0.0 +6 MODEL: BAC–11163C APP: AIR HANDLER OPT: MOD H / MOD C INSTANCE: 1
This display-only screen shows (scroll to see all):
• Firmware version (FW)
• Build date
• Application soware version (ASV)
• Model number
• Application conguration and options (set in the Application menu)
• Device instance (set in the Device menu)
• MAC address (set in the Communications menu)
• Serial number
• Board revision
NOTE: ASV will show CUSTOM if any built-in
Control Basic program (1–5) is not running or has auto-run disabled.
• Le buon to return to the Home screen.
NOTE: A log-in may be required to access menu
items.
SETPOINTS
SAVE CHANGE?
COOL SETPT:
HEAT SETPT: 67° F COOL SETBACK: 80° F
YES
NO
When prompted about a change (on any menu), press Right/Le to select the desired choice and then Enter.
BAC-10000 Series 4 Operation Guide, Rev. J

Advanced Menu

ADVANCED
APPLICATION
CB PROGRAMS COMMUNICATION DATE/TIME DEVICE INPUTS LIMITS
The Advanced Menu displays various submenus. Not all submenus can be seen on the screen at one time. Scroll up or down to see additional submenus. To select the desired submenu, press:
1. Up/Down to move.
2. Enter to select.
NOTE: The Advanced Menu has more submenus
than can appear on the screen at once. Keep scrolling up or down to see all the options.

(Advanced) Application Options

APPLICATION DEGREES SCALE: °F
APP:
FAN COIL OPT: 4-PIPE ADDITIONAL SETUP
ADDITIONAL SETUP
DAMPER
FAN HUMIDITY SENSORS VALVE
Auxiliary Heat (Heat Pump Only)
AUX HEAT SETUP
AUX HEAT:
DELAY (MINS): 60
COMP LOCKOUT
Damper Setup
DAMPER SETUP
ECON:
MIN POSITION (%): 10 CNTRL (0–100%): 2–10 V ECON ENBLE TEMP: 55° F LOW LIMIT ALARM: 45° F
MODULATING
NOTE: If the Economizer option is selected when
there is no mixed air temperature sensor connected, a Low Limit Alarm will result. See Alarms on page 11.
Fan Setup
FAN SETUP
SPEEDS:
OFF DELAY (SECS): 180 UNOCC: AUTO OCC: AUTO
CONSTANT SPEED
NOTE: For a Fan Fail Alarm, see Sensor Setup on
page 6 and Alarms on page 11.
To change ° F or C, preprogrammed application type, and options, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
Humidity Setup
HUMIDITY SETUP
DEHUMIDIFICATION
HUMIDIFICATION
DEHUMIDIFICATION
DEHUM:
ALLOW HTG DEHUM: NO DEHUM SETPT: 60%RH DEHUM DEADBAND: 5%RH
ENABLE
4. Up/Down to increment/decrement value.
The type of application (as well as the model of FlexStat) aects the context-sensitive options under Additional Setup.
NOTE: If a dehumidication option is enabled, the
Space Humidity Alarm will also be enabled. See Alarms on page 11.
BAC-10000 Series 5 Operation Guide, Rev. J
Sensor Setup

(Advanced) CB (Control Basic) Programs

SENSOR SETUP
IN 2:
DISCH AIR TEMP
The Input 2 sensor (AI2) can be congured for discharge air temperature (Type III thermistor is the default), fan status (dry contact), or unused.
• If set for discharge air temperature, the sensor can be calibrated and changed from the default Type III thermistor to a Type II. See (Advanced)
Inputs on page 8.
• If set for discharge air temperature, Trend Log #2 is automatically created and monitors the discharge air temperature, but it has no eect on operation.
• If set for fan status and no closed contact is detected when there is a call for fan operation, a Fan Fail Alarm is created. See Alarms on page 11.
• If set for unused, built-in applications will not use AI2, but the input would be available to custom programming.
Staging Setup
STAGING
STG DELAY (MINS):
3
Valve Setup
VALVE SETUP
TYPE:
ACTION: NRM OPEN
2–POSITION
CB PROGRAMS
PROG1:
PROG2: RUNNING PROG3: RUNNING PROG4: RUNNING PROG5: RUNNING PROG6: HALTED PROG7: IDLE
RUNNING
PROGRAM #1 SETPOINTS & MODES AUTO-RUN: TRUE CHANGE: READY STATE: RUNNING HALT REASON: NORMAL HALT DESC: OUT OF SERVICE: FALSE
To halt or load/run the built-in (1–5) and custom (6–10) Control Basic programs, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
NOTE: If custom Control Basic programs are
installed and a restore to factory seings
is performed, all factory programs are restarted but all custom Control Basic programs are halted. Change the state
of each program by loading/running the program from the CB Programs menu (or BACstage).
NOTE: If custom Control Basic programs are
installed and set to autorun, whenever the
rmware is updated, ALL (factory and custom) programs are halted.
If custom Control Basic programs are
installed but NOT set to autorun,
whenever the rmware is updated, factory programs are restarted but any (manual) running custom programs are halted at restart.
Change the state of each custom program
by using the Update Manager or loading/ running each program from the CB Programs menu (or BACstage).
UPDATE MANAGER PROGRAM CONFIG ERROR
ENABLE FACTORY:
ENABLE CUSTOM: NO EDIT CB PROGRAMS DONE
NO
NOTE: Customized programs are the responsibility
of the user. KMC Controls does not provide
support for such programs.
BAC-10000 Series 6 Operation Guide, Rev. J

(Advanced) BACnet Communications

Sample Time Zones Oset to Equal UTC
COMMUNICATIONS
MAC ADDRESS:
BAUD RATE: 38400 MAX MASTER: 127
1
To set parameters for BACnet MS/TP EIA-485 communications, press:
1. Up/Down to move among entries.
2. Enter to select.
NOTE: The Max Master is the highest MAC
address a device will aempt to locate when polling for master devices on the local network. To avoid possible communication issues with the network or a computer connected through a KMD­5576 USB Communicator, the Max Master
number should be the lowest number needed for that network.

(Advanced) Date/Time

DATE/TIME
DATE:
TIME: 1:43:59 PM UTC OFFSET: 300 DST ENABLE: TRUE DST AUTO: TRUE DST START: >2ND SUN MAR 2:00 AM
APRIL 11 2009
Alaska 9 hours = 540 minutes
USA/Canada Pacic
8 hours = 480 minutes
Standard Time
USA/Canada Mountain
7 hours = 420 minutes
Standard Time
USA/Canada Central
6 hours = 360 minutes
Standard Time
USA/Canada Eastern
5 hours = 300 minutes
Standard Time Bolivia, Chile 4 hours = 240 minutes Argentina, Uruguay 3 hours = 180 minutes
United Kingdom,
0 hours = 0 minutes
Portugal Europe (most countries) –1 hours = –60 minutes Egypt, Israel, Turkey –2 hours = –120 minutes Kuwait, Saudi Arabia –3 hours = –180 minutes United Arab Emirates –4 hours = –240 minutes India, Sri Lanka –5.5 hours = –330 minutes China, Mongolia –8 hours = –480 minutes Korea, Japan –9 hours = –540 minutes New Zealand –12 hours = –720 minutes
NOTE: The BACnet standard for this oset value
is: “The time zones to the west of the zero degree meridian shall be positive values, and those to the east shall be negative values.” The value is in minutes, not hours.
To enter date and time information, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
For areas that observe Daylight Saving Time, select True/On for DST ENABLE.
If the FlexStat is used in a BACnet network with UTC (Coordinated Universal Time) synchronization (via broadcasting or addressing a single thermostat) set the UTC Oset value. The UTC Oset value is in minutes and corresponds to the distance of the local time zone to the zero degree meridian. In stand-alone operation or networks that do not have UTC broad­casts, seing this value is not necessary.
BAC-10000 Series 7 Operation Guide, Rev. J

(Advanced) BACnet Device Properties

(Advanced) Temp. Setpoint Limits

DEVICE
INSTANCE:
NAME: FlexStat_101 LOCATION: KMC Controls
RESTART: NO RESTORE FACTORY: NO
1
To set the BACnet device instance, name, and location, press:
1. Up/Down to move among entries.
2. Enter to select.
The FlexStat can also be restarted or restored to factory defaults from this menu. See Reseing the
FlexStat on page 14 for more information about that
function.

(Advanced) Inputs

INPUTS 1: SPACE TEMP
2:
DISCH AIR TEMP 3: MIXED AIR TEMP 4: OUTSIDE AIR TEMP 4: SPACE HUMIDITY
Inputs vary according to model, selected application, and selected application options. See (Advanced) Ap-
plication Options on page 5.
To change sensor type and calibration oset, press:
1. Up/Down to move among entries.
2. Enter to select.
INPUT #2 DISCH AIR TEMP VALUE: 60.0° F CAL. OFFSET: 0.0 OUT-OF-SERVICE: FALSE
SENSOR:
10K TYPE III
LIMITS
OCC MIN CLG:
OCC MAX HTG: 76° F UNOCC MIN CLG: 77° F UNOCC MAX HTG: 65° F
71° F
To set the minimum and maximum allowed user/ operator setpoint values, press:
1. Up/Down to move among entries.
2. Enter to select.
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.

(Advanced) Motion Sensor

MOTION SENSOR
MOTION OCC:
STATE: OCCUPIED
In BAC-11xxx models, a motion/occupancy sensor may be enabled to trigger occupancy override. During scheduled “o” times, the motion sensor will start occupancy override (for 1 hour as a default) when it detects motion. Occupancy override will end (with the default seing) 1 hour aer motion was last detected. The length of occupancy override is congurable in the System menu. See System Setup
on page 13.
To enable/disable or monitor the motion/occupancy sensor (if installed), press:
ENABLE
3. Right/Le to move among value elds.
4. Up/Down to increment/decrement value.
Value will show a temperature reading or a voltage (0.0 to 3.0), depending on the sensor. Analog sensors can be calibrated using the Calibration Oset option.
1. Enter to select.
2. Right/Le to move among value elds.
3. Up/Down to increment/decrement value.
The State eld monitors whether motion has been detected during the last scan of the motion sensor input (BI6). Detected motion will show an “occu­pied” state. This can be used during troubleshooting to determine if motion is being detected.
BAC-10000 Series 8 Operation Guide, Rev. J

(Advanced) Security Levels and Passwords

SECURITY
ACCESS LEVELS
PASSWORDS
ACCESS LEVELS
SETPOINT ADJ:
MAIN MENU: ADMIN SYSTEM MODE: OPER OCC OVERRIDE: USER FAN OCC/UNOCC: OPER
NONE
Access to the Main Menu, Setpoint Adjust, and System/Occupancy/Fan seings have a default password level of User. This level can be changed for each function to None, Operator, or Administrator through the Access Levels menu. Passwords are set in the Passwords menu.
Any person can view the display but might not be able to change any seings without logging in with one of the three levels of passwords:
• None (Level “0”): No password is required (everyone has access).
• User (Level 1): See the Menu Items Access Levels chart.
• Operator (Level 2): See the Menu Items Access Levels chart.
• Administrator (Level 3): Can access all menus and change all editable values. DO NOT
FORGET THIS PASSWORD!
NOTE: Seing a password to (the default) 0000
eliminates the password prompt and allows full access for that level. If no password is set for ADMIN, no password prompt will occur. If any password is set for ADMIN, the menu items accessible at the various levels are shown in the following chart.
NOTE: Changes in security levels and/or
passwords take eect when the current Administrator log-in has timed out. Log-
ins last until 60 seconds (default) aer the last buon press. Desired length of inactivity time-out can be changed in the Systems submenu.
NOTE: When seing a password, the Up buon
increases the alphanumeric value (0 through 9 and then A through Z). The
Down buon decreases the value. DO NOT FORGET THE ADMIN PASSWORD!
PASSWORDS
USER:
OPERATOR: ADMIN:
1 0 0 0 1 2 3 4 5 6 7 8
To enter an alphanumeric password at the prompt:
1. Up/Down to move.
2. Enter to select.
3. Up/Down to increment/decrement value.
The required password level is specied in the prompt.
For additional security and protection from vandalism, install the FlexStat inside a third-party locking thermostat guard/cover (but proper airow must be maintained).
Menu Items Access Levels
Menus User Operator Administrator
Home Screen * = Selectable, Default is User
Setpoint Adjust (Up/Down) x* x* x*
System Mode (Auto/Heat/Cool/Off) x* x* x*
Occupancy Override (On/Off) x* x* x*
Fan Modes (Auto/On/Off) x* x* x*
Main Menu* (Default is User)
About x x x
Advanced x x
Alarm x x
Date/Time x x
Schedule x x
Setpoints x x
System x x
Trend Viewer x x x
Advanced Menu
Application x
Additional Setup x
Control Basic Programs x x
Communication x
Date/Time x x
Device x
Inputs x x
Limits x x
Motion Sensor x x
Security x
Trend Logs x x
Test x x
This chart shows conditions in which an administrator password is set (is not 0000) and default password levels are used.
BAC-10000 Series 9 Operation Guide, Rev. J
Loading...
+ 19 hidden pages