SML133 Operating Manual
SML 133 Instrument Parameters
# parameter group range default comment
00 lock LOC / OPN OPN
see Instrument Setup
Locking / Unlocking
01 CT – ratio, multiplier
screen 1 : row 2 : nominal primary current
row 3 : nom. secondary current
(for models “X/100mA”,“X/333mV” fixed)
screen 2 : MUL – current multiplier
primary : 1A ÷ 10 kA
sec. : 5A / 1A (0.1A)
(0.1 A, 0.333 V)
0.001 ÷ 999
5 / 5 A
1
secondary current selection
with the key
par. placed in side branch
if the current multiplier
different from 1 the ▲/
▼flashes
02 connection type 3Y / 3D / 3A 3Y
04 conn. mode: direct (---) or VT–ratio, mult.
screen 1 : row 2 : primary U [ kV ]
row 3 : secondary U [ kV ]
screen 2 : MUL – voltage multiplier
0.001 ÷ 65 kV
0.001 ÷ 0.999 kV
0.001 ÷ 999
direct
(- - -)
1
parameters placed in side
branch
if the voltage multiplier
different from 1 the ▲/
▼flashes
05 fNOM, UNOM
row 2 : fNOM [ Hz ]
row 3 : UNOM [ V / kV ]
50 / 60 Hz
50 V ÷ 1MV
50
230
UNOM specification
depending on connection
mode :
- direct : line-to-neutral
- via VT : line-to-line
06 ΣPNOM [ kVA / MVA ] 1 kVA ÷ 999 MVA
-
07 averaging period
row 2 : for U/I group
row 3 : for P/Q/S group
0.01 ÷ 60
(1 sec÷ 60 mins) 1 min
15 min
floating window type
averaging method applied
as default; thermal method
indicated with symbol ▲
08 avg period for ΣPavgmaxE,, El-meter d. mode
line 2 : averaging period for ΣPavgmaxE,
line 3 : Electricity meter display mode
0.01 ÷ 60
(1 sec÷ 60 mins)
“4E+Pmax” / “8E”
15 min
“4E+ Pmax”
floating window type
averaging method applied
09 fund. harmonic PF display format cos / tan / fi cos
10 backlight AUT / ON ON
AUT-mode : the backlight is
switched off automatically
after app. 5 mins if no key is
pressed
11 output setup
row 2 : output O1
row 3 : output O2
standard type : “-O-”
pulse type : pulses / kWh(kvarh)
control energy symbol :
• none … ΣEP+
• - … ΣEP-
• … ΣEQL
• … ΣEQC
“ - - -” = off
“-O-” = standard
output
0.001 ÷ 999000 =
pulse output
- - -
( off )
control energy selection with
the key
Standard type output can be
set via communication line
only, not from instrument
panel. Symbol ▲indicates
different setup of the alarm
light A1 from the O1 and the
A2 from the O2
If pulse type output set from
instrument panel, the A1
and the A2 alarm lights are
set identically as the O1 and
the O2, respectively.
15
(16)
communication interface 1 (and 2, opt.)
for RS-485 / M-Bus :
screen 1: row 2 : address
row 3 : rate [ kBd ]
screen 2: Prt (protocol) – databits & parity
for Ethernet:
screen 1 : DHCP
screen 2÷5 : IP1÷ IP4 (IP)
screen 6÷9 : MA1÷ MA4 (Subnet Mask)
screen 10÷13 : Gt1÷ Gt4 (Gateway)
1 ÷ 255
2.4 ÷ 460
8 / 9-n / 9-E / 9-0
ON / OFF
0 ÷ 255
0 ÷ 255
0 ÷ 255
1
9.6
8
OFF
10.0.0.1
255.255.255.0
10.0.0.138
parameters placed in side
branch
19 instrument status (read only)
row 2 : failure specification
row 3 : serial no. & instr. version (scroll)
0 ÷ 255
-
0
-
r. 2 : 0 = failure-free
r. 3 : S...serial no.
F... firmware version
b...bootloader version
H...hardware version
11