Klockner-Moeller, Div of Eaton Corp. series FAZ branch circuit breakers Catalog Page

Page 1
R
series FAZ branch circuit breakers
Branch circuit protection up to 10kA
M
oeller has just expanded its FAZ line of miniature circuit breakers to include de­vices that are listed and certied as molded case circuit breakers per UL 489 and CSA 22.2, No. 5-02. These new branch circuit breakers, called FAZ-NA, are ideal for the protection of power supplies, control power transformers, HVAC, refrigeration equipment, orescent lighting (to 20A) and many other applications requiring a primary protective device.
See page 43 about…
Applying
FAZ
in North America
>
Molded case circuit breaker per
>
Current limiting device
>
Ring-tongue terminals available
>
Worldwide approvals
(app
photo)
2
Flexible product range
Moeller’s FAZ Branch Circuit Breakers are available in one, two and three pole con­gurations with 20 dierent current ratings ranging from 0.5A to 40A. All breakers are available in both C and D tripping curves, oering protection from 5 to 10 and 10 to 20 x the continuous rating of the device (In). Two and three pole devices can be used in solidly grounded circuits up to 480V AC. The entire line oers short circuit ratings of 10kA regardless of voltage applied.
Many installation options
FAZ Branch Circuit Breakers are available in two terminal congu­rations; standard box terminals that accept multiple conductors and ring-tongue terminals, ideally suited to the demanding re­quirements of the semi-conductor industry. All breakers mount on standard 35mm DIN-rail. Bus Connectors and Feeder Termi­nals facilitate mounting and wiring of multiple miniature circuit breaker arrays in control panel assemblies. Power to the circuit breakers can also be fed from the line or load side.
Standard features enhance safety
As with most products from Moeller, FAZ breaker terminals provide nger and back­of-hand protection to guard against accidental contact with live parts. A color-cod­ed red/green indicator provides immediate visual indication of device status and isolation function (green for OFF, red for ON). All FAZ breakers incorporate a “trip­free” mechanism. This prevents the trip function from being defeated by holding the operator in the ON position. In addition, all FAZ branch circuit breakers are UL listed and CSA certied for fuseless protection of smaller AWG 18 and 16 conductors!
Worldwide acceptance
FAZ-NA (RT) Molded Case Circuit Breakers are UL Listed for use in the United States in accordance with NFPA 70 (NEC). The devices comply with UL 489 and CSA 22.2 No. 5-02, meeting the requirements for Molded Case Circuit Breakers. These de­vices also comply with IEC 60947-2 and are CE compliant.
Page 2
0.0005
Tr
ipping
tim
e t
[sec]
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
acc. to IEC 60898-1
instantaneous tripping
5
4
5
4
3
1
2
N
N
1
2
t
nt
N
N
N
N
4
6
N
3
I = 1.0 I (T=40 °C )
I = 1.35 I : t < 1 h (T=25 °C)
2.0 I : t = 12- 120 s (T=25 °C )
10 I : t < 0.1 s
20 I : t < 0.1 s
conventional non-tr ipping current
conventional tripping current
type C: 5 I : t > 0.1 s
type D: 10 I : t > 0.1 s
tripping characteristic
acc. to UL 489 / CSA 22.2 No. 235
3
D
C
Multiples of I
n
Tripping characteristics
Moeller FAZ-NA(RT) branch circuit breakers are avail­able with “C” and “D” tripping characteristics. C-curve devices are suitable for applications where medium levels of inrush current are expected. Applications in­clude small transformers, lighting, pilot devices, con­trol circuits, and coils. C-curve devices provide a me­dium magnetic trip point.
Devices with a “D” curve are suitable for applications where high levels of inrush current are expected. The high magnetic trip point prevents nuisance tripping in high inductive applications such as motors, transform­ers, and power supplies.
Even though not required by NEC or CEC for Branch Circuit Breakers, Moeller’s FAZ-NA(RT) devices are cur­rent limiting, which means they interrupt fault currents within one half cycle of the fault. Current limiting de­vices oer superior protection by reducing peak let­through current and energy.
This graph shows trip-time versus over-current for Type C and D devices FAZ­NA branch circuit breakers.
Discover these advanced features
Available in one, two and three poles
with “C” & “D” trip charac teristics
Arc Chutes quickly extinguish arcs
generated by the opening of the
contacts under normal or high fault
Arc chutes and switching mechanism
are kept apart for mechanical
Breakers install on standard DIN-rail
Bimetal trip assembly provides reliable
overload protection through a broad
range of ambient temperatures
3
conditions
reliability
Short circuit rating to 10kA (@277V AC and 480Y/277V AC for multi-pole) –
Choose box terminals (AWA #18 to #4 ) or terminals for ring-tongue connectors
Complete bus bar system available for quickly installing breaker arrays
Trip-free design; breaker cannot be defeated by holding the handle in the ON position
Color coded indicator provides breaker status for easy troubleshooting
Breaker information printed on the front of the device for quick identication
Page 3
>
UL Approved (UL489) and CSA Certified (CSA C22.2 No. 5-02) as
Branch Circuit Breakers
>
Interrupting capacity: 10kA UL/CSA; 15kA IEC 60947
>
Trip characteristic C: Response time of instantaneous trip:
5 – 10 x
>
Current limiting device
In current rating
Type C Characteristics
Suitable for applications where medium levels of inrush current are expected. Instantaneous trip is 5 to 10 x rating of device ( tions include small transformers, lighting, pilot devices, control circuits, and coils. Medium magnetic trip point.
Trip Characteristic C – Designed for inductive loads
1 pole 2 poles 3 poles
Rated
Current
I
n
[A]
Catalog Number Price Catalog Number Price Catalog Number Price
0.5 FAZ-CO,5/1-NA 39 FAZ-C0,5/2-NA 90 FAZ-C0,5/3-NA 137
1 FAZ-C1/1-NA 39 FAZ-C1/2-NA 90 FAZ-C1/3-NA 137
1.5 FAZ-C1,5/1-NA 39 FAZ-C1,5/2-NA 90 FAZ-C1,5/3-NA 137
2 FAZ-C2/1-NA 39 FAZ-C2/2-NA 90 FAZ-C2/3-NA 137
3 FAZ-C3/1-NA 39 FAZ-C3/2-NA 90 FAZ-C3/3-NA 137
4 FAZ-C4/1-NA 39 FAZ-C4/2-NA 90 FAZ-C4/3-NA 137
5 FAZ-C5/1-NA 39 FAZ-C5/2-NA 90 FAZ-C5/3-NA 137
6 FAZ-C6/1-NA 34 FAZ-C6/2-NA 78 FAZ-C6/3-NA 120
7 FAZ-C7/1-NA 34 FAZ-C7/2-NA 78 FAZ-C7/3-NA 120
8 FAZ-C8/1-NA 34 FAZ-C8/2-NA 78 FAZ-C8/3-NA 120
10 FAZ-C10/1-NA 34 FAZ-C10/2-NA 78 FAZ-C10/3-NA 120
13 FAZ-C13/1-NA 34 FAZ-C13/2-NA 78 FAZ-C13/3-NA 120
15 FAZ-C15/1-NA 34 FAZ-C15/2-NA 78 FAZ-C15/3-NA 120
16 FAZ-C16/1-NA 34 FAZ-C16/2-NA 78 FAZ-C16/3-NA 120
20 FAZ-C20/1-NA 34 FAZ-C20/2-NA 78 FAZ-C20/3-NA 120
25 FAZ-C25/1-NA 34 FAZ-C25/2-NA 78 FAZ-C25/3-NA 120
30 FAZ-C30/1-NA 34 FAZ-C30/2-NA 78 FAZ-C30/3-NA 120
32 FAZ-C32/1-NA 34 FAZ-C32/2-NA 78 FAZ-C32/3-NA 120
35 FAZ-C35/1-NA 34 FAZ-C35/2-NA 78 FAZ-C35/3-NA 120
40 FAZ-C40/1-NA 34 FAZ-C40/2-NA 78 FAZ-C40/3-NA 120
FAZ Branch Circuit Breakers
Trip Characteristic C
In). Applica-
See Trip Curve chart on page 11
4 moellerNA.com FAZ-CAT-NA-1107 Discount Schedule B23
Page 4
>
UL Approved (UL489) and CSA Certified (CSA C22.2 No. 5-02) as
Branch Circuit Breakers
>
Interrupting capacity: 10kA UL/CSA; 15kA IEC 60947
>
Trip characteristic D: Response time of instantaneous trip:
10 – 20 x
>
Current limiting device
In current rating
Type D Characteristics
Suitable for applications where high levels of inrush current are expected. Instantaneous trip is 10 to 20 x rating of device ( magnetic trip point prevents nuisance tripping in high inductive ap­plications such as motors, transformers, and power supplies.
Trip Characteristic D – Designed for highly inductive loads
1 pole 2 poles 3 poles
Rated
Current
I
n
[A]
Catalog Number Price Catalog Number Price Catalog Number Price
0.5 FAZ-D0,5/1-NA 45 FAZ-D0,5/2-NA 103 FAZ-D0,5/3-NA 158
1 FAZ-D1/1-NA 45 FAZ-D1/2-NA 103 FAZ-D1/3-NA 158
1.5 FAZ-D1,5/1-NA 45 FAZ-D1,5/2-NA 103 FAZ-D1,5/3-NA 158
2 FAZ-D2/1-NA 45 FAZ-D2/2-NA 103 FAZ-D2/3-NA 158
3 FAZ-D3/1-NA 45 FAZ-D3/2-NA 103 FAZ-D3/3-NA 158
4 FAZ-D4/1-NA 45 FAZ-D4/2-NA 103 FAZ-D4/3-NA 158
5 FAZ-D5/1-NA 45 FAZ-D5/2-NA 103 FAZ-D5/3-NA 158
6 FAZ-D6/1-NA 39 FAZ-D6/2-NA 90 FAZ-D6/3-NA 138
7 FAZ-D7/1-NA 39 FAZ-D7/2-NA 90 FAZ-D7/3-NA 138
8 FAZ-D8/1-NA 39 FAZ-D8/2-NA 90 FAZ-D8/3-NA 138
10 FAZ-D10/1-NA 39 FAZ-D10/2-NA 90 FAZ-D10/3-NA 138
13 FAZ-D13/1-NA 39 FAZ-D13/2-NA 90 FAZ-D13/3-NA 138
15 FAZ-D15/1-NA 39 FAZ-D15/2-NA 90 FAZ-D15/3-NA 138
16 FAZ-D16/1-NA 39 FAZ-D16/2-NA 90 FAZ-D16/3-NA 138
20 FAZ-D20/1-NA 39 FAZ-D20/2-NA 90 FAZ-D20/3-NA 138
25 FAZ-D25/1-NA 39 FAZ-D25/2-NA 90 FAZ-D25/3-NA 138
30 FAZ-D30/1-NA 39 FAZ-D30/2-NA 90 FAZ-D30/3-NA 138
32 FAZ-D32/1-NA 39 FAZ-D32/2-NA 90 FAZ-D32/3-NA 138
35 FAZ-D35/1-NA 39 FAZ-D35/2-NA 90 FAZ-D35/3-NA 138
40 FAZ-D40/1-NA 39 FAZ-D40/2-NA 90 FAZ-D40/3-NA 138
FAZ Branch Circuit Breakers
Trip Characteristic D
In). The high
See Trip Curve chart on page 11
FAZ-CAT-NA-1107 moellerNA.com 5 Discount Schedule B23
Page 5
>
UL Approved (UL489) and CSA Certified (CSA C22.2 No. 5-02) as
Branch Circuit Breakers
>
Connections for ring-tongue terminals
>
Trip characteristic C: Response time of instantaneous trip:
5 – 10 x
>
Interrupting capacity: 10kA UL/CSA; 15kA IEC 60947
In current rating
Type C Characteristics
Suitable for applications where medium levels of inrush current are expected. Instantaneous trip is 5 to 10 x rating of device ( tions include small transformers, lighting, pilot devices, control circuits, and coils. Medium magnetic trip point.
Ring Tongue Trip Characteristic C – Designed for inductive loads
Ring Tongue 1 pole Ring Tongue 2 poles Ring Tongue 3 poles
FAZ Branch Circuit Breakers - Ring Tongue
Trip Characteristic C
In). Applica-
Rated
Current
I
n
[A]
0.5 FAZ-CO,5/1-RT 44 FAZ-C0,5/2-RT 100 FAZ-C0,5/3-RT 152
1 FAZ-C1/1-RT 44 FAZ-C1/2-RT 100 FAZ-C1/3-RT 152
1.5 FAZ-C1,5/1-RT 44 FAZ-C1,5/2-RT 100 FAZ-C1,5/3-RT 152
2 FAZ-C2/1-RT 44 FAZ-C2/2-RT 100 FAZ-C2/3-RT 152
3 FAZ-C3/1-RT 44 FAZ-C3/2-RT 100 FAZ-C3/3-RT 152
4 FAZ-C4/1-RT 44 FAZ-C4/2-RT 100 FAZ-C4/3-RT 152
5 FAZ-C5/1-RT 44 FAZ-C5/2-RT 100 FAZ-C5/3-RT 152
6 FAZ-C6/1-RT 38 FAZ-C6/2-RT 86 FAZ-C6/3-RT 132
7 FAZ-C7/1-RT 38 FAZ-C7/2-RT 86 FAZ-C7/3-RT 132
8 FAZ-C8/1-RT 38 FAZ-C8/2-RT 86 FAZ-C8/3-RT 132
10 FAZ-C10/1-RT 38 FAZ-C10/2-RT 86 FAZ-C10/3-RT 132
13 FAZ-C13/1-RT 38 FAZ-C13/2-RT 86 FAZ-C13/3-RT 132
15 FAZ-C15/1-RT 38 FAZ-C15/2-RT 86 FAZ-C15/3-RT 132
16 FAZ-C16/1-RT 38 FAZ-C16/2-RT 86 FAZ-C16/3-RT 132
20 FAZ-C20/1-RT 38 FAZ-C20/2-RT 86 FAZ-C20/3-RT 132
25 FAZ-C25/1-RT 38 FAZ-C25/2-RT 86 FAZ-C25/3-RT 132
30 FAZ-C30/1-RT 38 FAZ-C30/2-RT 86 FAZ-C30/3-RT 132
32 FAZ-C32/1-RT 38 FAZ-C32/2-RT 86 FAZ-C32/3-RT 132
35 FAZ-C35/1-RT 38 FAZ-C35/2-RT 86 FAZ-C35/3-RT 132
40 FAZ-C40/1-RT 38 FAZ-C40/2-RT 86 FAZ-C40/3-RT 132
Catalog Number Price Catalog Number Price Catalog Number Price
All breakers on this page are equipped
with terminals that accommodate
ring-tongue connectors.
See Trip Curve chart on page 11
6 moellerNA.com FAZ-CAT-NA-1107 Discount Schedule B23
Page 6
FAZ Branch Circuit Breakers – Ring Tongue
>
UL Approved (UL489) and CSA Certified (CSA C22.2 No. 5-02) as
Branch Circuit Breakers
>
Connections for ring-tongue terminals
>
Trip characteristic D: Response time of instantaneous trip:
10 – 20 x
>
Interrupting capacity: 10kA UL/CSA; 15kA IEC 60947
In current rating
Type D Characteristics
Suitable for applications where high levels of inrush current are expected. Instantaneous trip is 10 to 20 x rating of device ( magnetic trip point prevents nuisance tripping in high inductive ap­plications such as motors, transformers, and power supplies.
Ring Tongue Trip Characteristic D – Designed for highly inductive loads
Ring Tongue 1 pole Ring Tongue 2 poles Ring Tongue 3 poles
Trip Characteristic D
In). The high
Rated
Current
I
n
[A]
0.5 FAZ-D0,5/1-RT 50 FAZ-D0,5/2-RT 113 FAZ-D0,5/3-RT 172
1 FAZ-D1/1-RT 50 FAZ-D1/2-RT 113 FAZ-D1/3-RT 172
1.5 FAZ-D1,5/1-RT 50 FAZ-D1,5/2-RT 113 FAZ-D1,5/3-RT 172
2 FAZ-D2/1-RT 50 FAZ-D2/2-RT 113 FAZ-D2/3-RT 172
3 FAZ-D3/1-RT 50 FAZ-D3/2-RT 113 FAZ-D3/3-RT 172
4 FAZ-D4/1-RT 50 FAZ-D4/2-RT 113 FAZ-D4/3-RT 172
5 FAZ-D5/1-RT 50 FAZ-D5/2-RT 113 FAZ-D5/3-RT 172
6 FAZ-D6/1-RT 43 FAZ-D6/2-RT 98 FAZ-D6/3-RT 150
7 FAZ-D7/1-RT 43 FAZ-D7/2-RT 98 FAZ-D7/3-RT 150
8 FAZ-D8/1-RT 43 FAZ-D8/2-RT 98 FAZ-D8/3-RT 150
10 FAZ-D10/1-RT 43 FAZ-D10/2-RT 98 FAZ-D10/3-RT 150
13 FAZ-D13/1-RT 43 FAZ-D13/2-RT 98 FAZ-D13/3-RT 150
15 FAZ-D15/1-RT 43 FAZ-D15/2-RT 98 FAZ-D15/3-RT 150
16 FAZ-D16/1-RT 43 FAZ-D16/2-RT 98 FAZ-D16/3-RT 150
20 FAZ-D20/1-RT 43 FAZ-D20/2-RT 98 FAZ-D20/3-RT 150
25 FAZ-D25/1-RT 43 FAZ-D25/2-RT 98 FAZ-D25/3-RT 150
30 FAZ-D30/1-RT 43 FAZ-D30/2-RT 98 FAZ-D30/3-RT 150
32 FAZ-D32/1-RT 43 FAZ-D32/2-RT 98 FAZ-D32/3-RT 150
35 FAZ-D35/1-RT 43 FAZ-D35/2-RT 98 FAZ-D35/3-RT 150
40 FAZ-D40/1-RT 43 FAZ-D40/2-RT 98 FAZ-D40/3-RT 150
Catalog Number Price Catalog Number Price Catalog Number Price
All breakers on this page are equipped
with terminals that accommodate
ring-tongue connectors.
See Trip Curve chart on page 11
FAZ-CAT-NA-1107 moellerNA.com 7 Discount Schedule B23
Page 7
For all FAZ…NA and FAZ…RT Miniature Circuit Breakers
C2
C1
NHK
FAZ
Circuit
Breaker
NHK
FAZ
Circuit Breaker
XAA
Shunt
Trip
Accessory Description Circuit Diagram
Auxiliary / Trip Indicating Contacts
Small selector screw changes mode
• Two Form C (changeover) contacts
• Installs on left side of FAZ or Shunt Trip
Shunt Trip
• Aux. contacts switch when FAZ is tripped electrically or
• manually
Trip indicating contact switches only when FAZ is tripped
• electrically
Test button for electrical tripping function
Allows remote trip of FAZ
• Installs on left side of FAZ
Two-pole auxiliary mode
Trip indicating mode
FAZ Branch Circuit Breakers
Rated
Operational
Voltage Catalog Number Price
230V AC
110 – 415V AC FAZ-XAA-NA110-415VAC 56
Z-NHK
Accessories
39
Padlock Hasp
Prevents reactivation of the device during maintenance
• Holds one padlock
Allowable combinations of accessories
12 – 110V AC FA Z-X AA-NA12-110VAC 56
IS/SPE-1TE 40
Voltage of FAZ-…-NA circuit breaker is limited to 300V with this auxiliary contact
installed.
8 moellerNA.com FAZ-CAT-NA-1107 Discount Schedule B23
Page 8
Bus Bar System
FAZ Branch Circuit Breakers
Accessories
Bus Bar
Number of
Poles per
Device
1
2
3
Number of
Terminals
Fixed Length
12 Z-SV/UL-16/1P-1TE/12 29
18 Z-SV/UL-16/1P-1TE/18 43
12 Z-SV/UL-16/2P-2TE/12 38
18 Z-SV/UL-16/2P-2TE/18 57
12 Z-SV/UL-16/3P-3TE/12 42
18 Z-SV/UL-16/3P-3TE/18 63
Terminal Shroud for unused bus bar terminals
Shroud Description Catalog Number Price
3-pole busbar cover
ZV-BS-UL 3
Rated
Operational
Current (A) Description Catalog Number Price
6
80A
6
80A
6
80A
UL/CSA Max 480V AC, 50/60 HZ; 96V DC
UL/CSA Max 480V AC, 50/60 HZ; 96V DC
UL/CSA Max 480V AC, 50/60 HZ; 96V DC
Z-SV/UL-16/1P-1TE/6 15
Z-SV/UL-16/2P-2TE/6 19
Z-SV/UL-16/3P-3TE/6 21
Incoming Supply Terminal
Terminal Description Catalog Number Price
Extension Terminal
Accommodates conductors up to 25 mm2 (2 – 14 AWG)
Finger-safe connection Max 480V AC, 50/60 HZ; 96V DC
@ 80A
Z-EK/35/UL 13
FAZ-CAT-NA-1107 moellerNA.com 9 Discount Schedule B23
Page 9
0.0005
Tr
ipping
tim
e t
[sec]
7200
3600
1200
600
300
120
60
30
10
5
2
1
0.5
0.2
0.1
0.05
0.02
0.005
0.01
0.002
0.001
5040302015
1098765432
1
acc. to IEC 60898-1
instantaneous tripping
5
4
5
4
3
1
2
N
N
1
2
t
nt
N
N
N
N
4
6
N
3
I = 1.0 I (T=40°C )
I = 1.35 I : t < 1 h (T=25 °C )
2.0 I : t = 12- 120 s (T=25 °C)
10 I : t < 0.1 s
20 I : t < 0.1 s
conventional non-trippingcurrent
conventional trippingcurrent
type C: 5 I : t > 0.1 s
type D: 10 I : t > 0.1 s
tripping characteristic
acc. to UL 489 / CSA 22.2 No. 235
3
D
C
Multiples of I
n
504030
20100-10
-20
0.90
1.40
1.30
1.20
1.10
1.00
Ambient temperature T [°C ]
Maximum load IL at ambient temperature T:
IL (T) = InKT (T)
Load factor
K
T
[I/
I
n
]
FAZ Branch Circuit Breakers
Technical Data
Tripping Characteristics Inuence of ambient temperature T on load
carrying capacity
Power loss at
I
n
Characteristic C
In [A]
0.5 1
1.5 2 3 4 5 6 7 8
10 13 15 16 20 25 30 32 35 40
FAZ-CAT-NA-1107 moellerNA.com 11
P[W]
1.6 3.2 4.7
1.1 2.2 3.4
1.3 2.6 3.9
1.4 2.8 4.3
1.2 2.4 3.6
1.4 2.9 4.3
1.9 3.7 5.6
1.2 2.3 3.5
1.4 2.8 4.3
1.4 2.8 4.2
1.8 3.6 5.3
2.4 4.7 7.1
1.9 3.8 5.6
2.1 4.3 6.4
2.9 5.8 8.7
3.1 6.2 9.3
3.0 6.0 9.0
3.4 6.8 10.2
3.7 7.4 11.0
4.0 8.1 12.1
1p
2p
P[W]
3p
P[W]
Characteristic D
In [A]
0.5 1
1.5 2 3 4 5 6 7 8
10 13 15 16 20 25 30 32 35 40
1p
P[W]
2p
P[W]
1.6 3.2 4.8
0.8 1.5 2.3
1.0 2.1 3.1
1.0 2.1 3.1
1.2 2.4 3.6
1.4 2.9 4.3
1.5 2.9 4.4
1.2 2.3 3.5
1.4 2.8 4.3
1.2 2.4 3.7
1.5 3.0 4.5
2.0 4.1 6.1
1.5 3.1 4.6
1.7 3.5 5.2
1.8 3.7 5.5
2.6 5.1 7.7
2.7 5.4 8.1
3.1 6.2 9.3
3.8 7.6 11.3
3.9 7.8 11.6
3p
P[W]
Page 10
FAZ-NA, FAZ-RT Miniature Circuit Breakers
Electrical
Design according to current test marks as printed onto the device Rated voltage - AC UL/CSA 0.5 – 25A UL/CSA 25 – 40A IEC Rated Voltage - DC UL/CSA - Single Pole UL/CSA - Two Pole Rated frequency Rated breaking capacity - AC UL/CSA IEC Rated breaking capacity - DC UL/CSA Characteristic Endurance Line voltage connection
Mechanical
Frame size Device height Device width Mounting Upper and lower terminals Terminal capacity
Terminal fastening torque
Mounting Calibration temperature UL 489, CSA C22.2 No. 5 IEC 60947-2
FAZ Branch Circuit Breakers
Technical Data
FAZ-NA, FAZ-RT
UL 489, CSA C22.2 No. 5, IEC 60947-2
277/480Y V AC
240 V AC
240/415 V AC
48 V DC 96 V DC
50/60 Hz
10 kA 15 kA
10 kA
C, D
≥ 20,000 operating cycles
operational suitable for reverse feed
45 mm
105 mm
17.7 mm per pole
quick fastening with 2 lock-in positions on DIN rail EN 50022
open mouth/lift terminals
1 Wire AWG 18-6
2 Wires AWG 18-10
1 Wire 21 lb-in
2 Wires 25 lb-in
independent of position
40˚C 30˚C
12 moellerNA.com FAZ-CAT-NA-1107
Page 11
Selectable Aux Contact / Trip Indicating Contact – Z-NHK
Electrical
Can be mounted from the left onto: Contact function Rated voltage [V] Rated frequency [Hz] Rated current [A] Rated thermal current I Utilization category AC13 Rated operational current I Utilization category AC15 Rated operational current I Utilization category DC12 Rated operational current I Rated insulation voltage U Minimum operational voltage per contact U Minimum operational current I Rated peak withstand voltage U Conditional short-circuit current Ik with back-up fuse 6A [kA] Max. back-up fuse, overload and short-circuit
Mechanical
Tripping indicator “electrical tripping” Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity Terminal screws Fastening torque of terminal screws
th
e
e
e
i
min
min
(1.2/50µ)
imp
[A]
[A]
[A]
[A] [VAC] [VDC]
[mA]
[kV]
FAZ Branch Circuit Breakers
Technical Data
Z-NHK
FAZ-NA, FAZ-RT, FAZ-XAA-NA
2 changeover contacts (self cleaning)
230
50/60
2 2
3 / 250V AC
2 / 250V AC
0.5 / 110V DC 250
5
10 mA DC
2.5
1 kA
6A gL
blue/white
45 mm 80 mm
8.8 mm (0.5MU)
Snaps on to side of MCB
IP40
nger and hand-touch safe according to BGV A3, ÖVE-EN 6
lift terminals
18-14 AWG
M3 (Pozidrive Z0)
7 lb-in
FAZ-CAT-NA-1107 moellerNA.com 13
Page 12
Shunt Trip Release FAZ-XAA-NA
Electrical
Can be mounted onto Operational voltage range
Frequency Possible standard auxiliary switch
Mechanical
Frame size Device height Device width Mounting Degree of protection, built-in Terminal protection Terminals Terminal capacity 1 and 2 wires
FAZ Branch Circuit Breakers
Technical Data
FAZ-XAA-NA12-110VAC FAZ-XAA-NA110-415VAC
FAZ-NA, FAZ-RT FAZ-NA, FAZ-RT
12-110V AC
12-60V DC
50/60 Hz 50/60 Hz
Z-NHK Z-NHK
45 mm 45 mm
105 mm 105 mm
17.5 mm (1MU) 17.5 mm (1MJ)
quick fastening with 2 lock-in positions on DIN rail EN 50022 quick fastening with 2 lock-in positions on DIN rail EN 50022
IP40 IP40
nger and hand-touch safe according to BGV A3, ÖVE-EN 6 nger and hand-touch safe according to BGV A3, ÖVE-EN 6
box/lift box/lift
AWG 18-10 AWG 18-10
110-415V AC 110-230V DC
Bus Bar
Electrical
Rated voltage Rated current Short-circuit strength Overvoltage category Impulse voltage strength
Mechanical
Bus bar cross-section Step distance Climatic stability Flame class according to UL Pollution degree
Z-SV/UL-16...
690V
80A
< 25 kA
III
≥ 9.5 kV
16 mm2 Cu
17.6 mm
according to DIN EN 60068
V0/0.4 mm
2
14 moellerNA.com FAZ-CAT-NA-1107