Klimaire KTHM015-E5H2 Service Manual

Page 1
.
KLIMAIRE 60Hz .
Page 2
CONTENTS
1. Precaution ........................................................................................................................................... 1
1.1 Safety Precaution. ............................................................................................................................. 1
1.2 Warning .............................................................................................................................................. 1
2. Function and control panel. ............................................................................................................... 5
3. Dimension. ........................................................................................................................................... 7
4. Refrigerant Cycle Diagram. ................................................................................................................ 7
5. Wiring Diagram. .................................................................................................................................. 8
6 Electronic function .............................................................................................................................. 9
6.1 Terms and definitions ....................................................................................................................... 9
6.2 Electric Control working environment ............................................................................................ 9
6.3 Protection function ........................................................................................................................... 9
6.4 Operation of fan motor ..................................................................................................................... 9
6.5 Operation of compressor ............................................................................................................... 11
6.6 Sensor malfunction......................................................................................................................... 12
7 Installation details .............................................................................................................................. 13
7.1 How to install the unit ..................................................................................................................... 13
7.2 Care and cleaning ........................................................................................................................... 16
8 Operation characteristics .................................................................................................................. 18
8.1 Cooling operation. .......................................................................................................................... 18
8.2 Characteristic of temperature sensor............................................................................................ 18
9 Troubleshooting ................................................................................................................................. 19
Page 3
1. Precaution
1.1 Safety Precaution.
To prevent injury to the user or other people and property damage, the following instructions must
be followed.
Incorrect operation due to ignoring instruction will cause harm or damage.
Before service unit, be sure to read this service manual at first.
1.2 Warning
Installation
Do not use a defective or underrated circuit breaker. Use this appliance on a dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the dealer, seller, a qualified electrician, or an Authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of control box securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and breaker.
Improper wiring or installation may cause fore or electric shock.
Use the correctly rated breaker of fuse.
There is risk of fire or electric shock.
Do not modify or extend the power cable.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the unit by yourself(customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the dealer or an Authorized service center.
There is risk of fire, electric shock, explosion, or injury.
1
Page 4
Do not install the product on a defective installation stand.
It may cause injury, accident, or damage to the product.
Be sure the installation area does not deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for a long time when the humidity is very high and a door or a
window is left open.
Moisture may condense and wet or damage furniture.
Take care to ensure that power cable could not be pulled out or damaged during operation.
There is risk of fire or electric shock.
Do not place anything on the power cable.
There is risk of fire or electric shock.
Do not plug or unplug the power supply plug during operation.
There is risk of fire or electric shock.
Do not touch (operation) the product with wet hands.
There is risk of fire or electric shock.
Do not place a heater or other appliance near the power cable.
There is risk of fire and electric shock.
Do not allow water to run into electric parts.
It may cause fire, failure of the product, or electric shock.
Do not store or use flammable gas or combustible near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly closed space for a long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off the gas and open a window for ventilation before turn the
product on.
Do not use the telephone or turn switches on or off. There is risk of explosion or fire.
If strange sounds, or small or smoke comes from product. Turn the breaker off or disconnect the
power supply cable.
There is risk of electric shock or fire.
Stop operation and close the window in storm or hurricane. If possible, remove the product from the
window before the hurricane arrives.
2
Page 5
There is risk of property damage, failure of product, or electric shock.
Do not open the inlet grill of the product during operation. (Do not touch the electrostatic filter, if the
unit is so equipped.)
There is risk of physical injury, electric shock, or product failure.
When the product is soaked (flooded or submerged), contact an Authorized service center.
There is risk of fire or electric shock.
Be caution that water could not enter the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to time when operating it together with a stove, etc.
There is risk of fire or electric shock.
Turn the main power off when cleaning or maintaining the product.
There is risk of electric shock.
When the product is not be used for a long time, disconnect the power supply plug or turn off the
breaker.
There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
CAUTION.
Always check for gas (refrigerant) leakage after installation or repair of product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that water is drained away properly.
A bad connection may cause water leakage.
Keep level even when installing the product.
To avoid vibration of water leakage
Do not install the product where the noise or hot air from the outdoor unit could damage the
neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and transport the product.
Avoid personal injury.
Do not install the product where it will be exposed to sea wind (salt spray) directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins,
3
Page 6
could cause product malfunction or inefficient operation.
Operational.
Do not expose the skin directly to cool air for long periods of time. (Do not sit in the draft).
This could harm to your health.
Do not use the product for special purposes, such as preserving foods, works of art, etc. It is a
consumer air conditioner, not a precision refrigerant system
There is risk of damage or loss of property.
Do not block the inlet or outlet of air flow.
It may cause product failure.
Use a soft cloth to clean. Do not use harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the product when removing the air filter. They are very sharp.
There is risk of personal injury.
Do not step on or put anything on the product. (outdoor units)
There is risk of personal injury and failure of product.
Always insert the filter securely. Clean the filter every two weeks or more often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other object through air inlet or outlet while the product is operated.
There are sharp and moving parts that could cause personal injury.
Do not drink the water drained from the product.
It is not sanitary could cause serious health issues.
Use a firm stool or ladder when cleaning or maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the remote control with new ones of the same type. Do not mix old and
new batteries or different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the batteries. Do not dispose of batteries in a fire.
They may burn of explode.
If the liquid from the batteries gets onto your skin or clothes, wash it well with clean water. Do not
use the remote of the batteries have leaked.
The chemical in batteries could cause burns or other health hazards
4
Page 7
202021890236
2. Function and control panel.
KTHM009-E3C2 KTHM012-E3C2 KTHM015-E5C2 KTHM009-E3H2 KTHM012-E3H2 KTHM015-E5C2
The controls featured in this manual are representative of many available models. Your model may offer slightly different features.
POWER
- Press the POWER button to turn the unit on or off. When the unit is on, the power indicator light will be green.When the unit is off, the light will go out.
MODE
- Push this button to cycle through the modes from COOL-HEAT-FAN-COOL.The green indicator light beside the "MODE" option will illuminate, identifying the mode selected.
- COOL:The range of set temperature is 17/62~30/86.Cooling begins automatically when the room temperature is above the set point,and stops when the room temperature is 2(4) below the
set point. But the compressor will run 5 minutes at least in COOL mode before stoping. The fan runs in continuous mode.
- HEAT:The range of set temperature is 17OC/62OF ~29OC/84OF.For heat pump models,the unit can alternate to run between in reverse cycle heat mode and electric heater mode according to the difference between the setting temperature and the room temperature.The fan motor cycles on and off with the compressor and electric heater. NOTE: The reverse cycle and electric heater can not be run at the same time.
5
Page 8
- FAN:Fan operation only without heating and cooling.
UP/DOWN BUTTONS ( / )
- Push the UP (or DOWN) button to increase (or decrease) the set temperature of the unit in cooling or heating mode.The temperature can be set by increments of 1 (1).The setting temperature
appears in the display. NOTE:Press and hold and buttons together for 3 seconds will alternate the temperature display between & scale.
FAN (FAN SPEED)
- Every time you push this button,the fan speed cycles through the settings as follows:HIGH-MED­ LOW-HIGH.
DISPLAYS:
- Shows the set temperature in or . While on Fan only mode,it shows the room temperature.
Control code: LC-Pads on the control panel is not available.The unit can be setted by using wire cotroller only. Error codes: AS-Room temperature sensor error; ES-Evaporator temperature sensor error; CS-Condenser temperature sensor error; OS-Outside temperature sensor error; HS-Exhaust temperature sensor error; NOTE:When error occurs,unplug the unit and plug it back in.If error repeats, call for service. Other codes: LO-Room temperature is lower than 0/32; HI-Room temperature is higher than 37/99.
6
Page 9
Dimension Mode
W(mm)
H(mm)
D(mm)
PTAC
1067
408
606
3. Dimension.
4. Refrigerant Cycle Diagram.
The figure below is a brief description of the important components and their function in what is called the refrigeration system. This will help to understand the refrigeration cycle and the flow of the refrigerant in the cooling cycle.
7
Page 10
5. Wiring Diagram.
KTHM009-E3C2 KTHM012-E3C2 KTHM015-E5C2 KTHM009-E3H2 KTHM012-E3H2 KTHM015-E5C2
8
Page 11
6 Electronic function
6.1 Terms and definitions
T1: Temperature of indoor ambient (TA) T2: Temperature of evaporator (TC). T3: Temperature of condenser (TE) T4: Temperature of outdoor ambient (T0) TS: The set temperature. DAHT: Temperature of discharge (T5) DAHT: Temperature of discharge (T6)
6.2 Electric Control working environment
Input voltage: 187~264V for 50Hz models and 97~127V for 60Hz models;
208~230V or 238~291V for 60Hz models
6.3 Protection function
6.3.1 The compressor functions protection with a delay of three minutes.
6.3.2 Sensor protection at open or short circuit.
6.3.3 Evaporator anti-icing protection at cooling mode.
6.4 Operation of fan motor
6.4.1. Fan motor is on when compressor is on, Fan motor is off when compressor is off. (except theT2 high Temp. protection).
If theres only one speed of the fan motor, use the high speed instead of the low speed.
6.4.2. The fan motor operates at the cooling only mode as below:
9
Page 12
T4
T01
Operate on high speed
T02
Operate on low speed
T4
T03
Operate on high speed
T04
Operate on low speed
When T4T01 and lasts for 1 minute, the fan motor will operates at high speed.
When T4T02 and lasts for 1 minute, the fan motor will operates at low speed.
When T02T4T01: A) If fan motor is off originally, it will operate at high speed. B) If fan motor is on originally, it will keep on working at the original speed.
6.4.3. The fan motor operates at the heat pump and cooling mode as below:
A) If fan motor is off originally, it will operate at high speed.
B) If fan motor is on originally, it will keep on working at the original speed.
6.4.4. The high temperature protection of evaporator at the heat pump and cooling mode as below:
When T4T03 and lasts for 1 minute, the fan motor will operates at low speed.
When T4T04 and lasts for 1 minute, the fan motor will operates at high speed.
When T04T4﹤T03:
10
Page 13
(T1-Ts)
+0
-4
Compressor on
Operation conditon
Compressor off
TE7
TE8
TE15
TE9
Compressor
Fan motor
Fan motor (low speed)
Compressor on Fan motor on
(High/low speed is determined by T4)
Compressor
Fan motor
Compressor on Fan motor on (High/low speed is determined by T4)
If T2TE7, this unit turns into the protection of compressor off , and quits this protection when T2TE9. If T2TE8,it turns into the protection of fan motor off , and quits this protection when T2TE9. If T2TE15, fan motor operates at low speed by force, then quits the operation and determines the high
or low speed by T4.
6.4.5. At the fan only mode, the fan always keeps on working, and the compressor/fan motor/heater stop working.
6.5 Operation of compressor
6.5.1. The compressor operates at cooling mode as below:
T1≥Ts compressor on
T1Ts-4 compressor off
6.5.2. The compressor operates at heating mode: (There are two ways of heating mode: Heat pump and cooling/Electric heater and cooling)
The electrical heater or compressor will be activated by sensing the difference between setting temperature and the actual ambient room temperature.
11
Page 14
(T1-Ts)
2
-2
Operation conditon for heater or compressor
Heater(compressor) off
Heater(compressor) on
LED display
Stand for
AS
Room temperature sensor error(T1)
Es
Room temperature sensor error(T2)
CS
Condenser temperature sensor error(T3)
OS
Outside temperature sensor error(T4)
HS
Exhaust temperature sensor error(T5,T6)
6.5.2.1 The Electric heater operates as below: a. When T1Ts-2, the fan motor operates, and 3 seconds later, the heater is on and
operates at low speed within 30 seconds. After 30 seconds, it will change to the setting speed. If the DAHT temperature checked is higher than the protection temperature, when the heater operating, the fan motor will be off automatically.
b. When T1Ts+2, the heater is off, and the fan motor keeps on working at setting speed. If
the DAHT temperature checked is low than the protection temperature, and the operation time of fan motor is more than 15 seconds, then the fan motor will be off. If the T2 protection gets started, the fan motor also does not work.
6.5.2.2 The Heat pump operates as below:
The Heat pumps operation mode is in accordance with the way of compressors working.
The compressor is on (electric heater is off), the fan motor operates according to the anti-cold wind of heat pump. The four-way valve always keeps on. When T1Ts-2, the compressor is on, and when T1Ts+2,it will be off. The fan motor works according to the operation of compressor. If T2TE7, the compressor is off by force. When the DAHT protection gets started, it is not allowed that the compressor operates.
6.6 Sensor malfunction
12
Page 15
CAUTION: There are sharp edges that can cause serious cuts.
When lifting the air conditioner, it is HEAVY. Use 2 people to lift.
7 Installation details
7.1 How to install the unit
Dimension of air conditioner
Dimension of sleeve assembly (optional)
13
Page 16
- For existing sleeve, you should measure the wall sleeve dimensions.
- Install the new air conditioner according to these installation instructions to achieve the best performance. All wall sleeves used to mount the new air conditioner must be in good structural condition and have a rear grille that securely attaches to the sleeve or the flange of the sleeve to secure the new air conditioner.
- To avoid vibration and noise, make sure the unit is installed securely and firmly.
- When installing the sleeve, make certain there is nothing within 20 of the back that would interfere with heat radiation and exhaust air flow. (See Fig.2)
PREPARATION OF SLEEVE ASSEMBLY (optional)
- Refer to the installation instruction of sleeve assembly for details.
UNIT INSTALLATION
- Carefully remove shipping tape from the front panel. (See Fig.3)
- Remove the front panel. (See Fig.4)
- Remove the shipping screw from the vent door.(See Fig.5)
14
Page 17
- Rotate the vent control lever to either open or close the vent door.(See Fig.6) NOTE: When vent control lever set at CLOSE, only the air inside the room is circulated and filtered. When set at OPEN, some outdoor air will be drawn into room. This will reduce heating or cooling efficiency.
- Lift unit level and slide unit into wall sleeve until firmly against front of wall sleeve and secure with 4 screws and washers (supplied) through the unit flange holes. (See Fig.7 and Fig.8)
- Reinstall front panel.(See Fig.9)
15
Page 18
CAUTION: UNIT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or improper operation. Airflow
restriction may cause damage to the unit.
CAUTION: UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation. Do not operate unit without filters in place. If a filter becomes torn or damaged, it should be
replaced immediately. Operating without filters in place or with damaged filter will allow dirt and dust to reach indoor
coil and reduce cooling, heating, airflow and efficiency of unit. Airflow restriction may cause damage to unit.
7.2 Care and cleaning
FRONT PANEL AND CARE
- Turn unit off and disconnect power supply. To clean, use water and a mild detergent. DO NOT use bleach and abrasive. Some commercial cleaners may damage the plastic parts.
OUTDOOR COIL
- Coil on outdoor side of unit should be checked regularly. Unit will need to be removed to inspect dirt build-up that will occur on the inside of the coil. If clogged with dirt and soot, coil should be professionally cleaned. Clean inside and outside of outdoor coils regularly. NOTE: Never use a high-pressure spray on coil.
AIR FILTERS IMPORTANT:TURN UNIT OFF BEFORE CLEANING.
- The most important thing you can do to maintain unit efficiency is to clean the filters at least every 30 days (or sooner depending on application). Clogged filters reduce cooling, heating and airflow.
- Keeping filters clean will:
Decrease cost of operation.
Save energy.
16
Page 19
Prevent clogged indoor coil. Reduce risk of premature component failure.
- To Clean Air Filters:
Vacuum off heavy soil. Run water through filter. Dry thoroughly before replacing.
- Removing Air Filter (See.Fig.10)
- Replacing Air Filter (See.Fig.11)
VENT DOOR FILTER IMPORTANT:TURN UNIT OFF BEFORE CLEANING.
- Make sure to remove the shipping screw from the vent door.(See.Fig.5)
- Rotate the vent control lever to open the vent door. (See. Fig.6)
- Remove four screws from the vent door filter. (See.Fig.12)
- First pull out the vent door steel wire from the hole of the vent door, then take off the vent door and filter. (See.Fig.12)
- Clean the filter. Dry thoroughly before replacing.
- Replace the vent door and filter, reinstall the four screws.
- Reinsert the vent door steel wire into the hole of the vent door.
17
Page 20
Temp.
Resistance KΩ
Temp.
Resistance KΩ
Temp.
Resistance KΩ
-10
62.2756
17
14.6181
44
4.3874
-9
58.7079
18
13.918
45
4.2126
-8
56.3694
19
13.2631
46
4.0459
-7
52.2438
20
12.6431
47
3.8867
-6
49.3161
21
12.0561
48
3.7348
-5
46.5725
22
11.5
49
3.5896
-4
44
23
10.9731
50
3.451
-3
41.5878
24
10.4736
51
3.3185
-2
39.8239
25
10
52
3.1918
-1
37.1988
26
9.5507
53
3.0707
0
35.2024
27
9.1245
54
2.959
1
33.3269
28
8.7198
55
2.8442
8 Operation characteristics
8.1 Cooling operation.
Outdoor air temp. DB
8.2 Characteristic of temperature sensor.
Indoor air temp. DB
18
Page 21
2
31.5635
29
8.3357
56
2.7382
3
29.9058
30
7.9708
57
2.6368
4
28.3459
31
7.6241
58
2.5397
5
26.8778
32
7.2946
59
2.4468
6
25.4954
33
6.9814
60
2.3577
7
24.1932
34
6.6835
61
2.2725
8
22.5662
35
6.4002
62
2.1907
9
21.8094
36
6.1306
63
2.1124
10
20.7184
37
5.8736
64
2.0373
11
19.6891
38
5.6296
65
1.9653
12
18.7177
39
5.3969
66
1.8963
13
17.8005
40
5.1752
67
1.830
14
16.9341
41
4.9639
68
1.7665
15
16.1156
42
4.7625
69
1.7055
16
15.3418
43
4.5705
70
1.6469
POSSIBLE CAUSES
Solution
UNIT DOES NOT START
Unit may have become unplugged Fuse may have blown Circuit breaker may have been tripped Unit may be off Unit may be in a protection mode.
Check that plug is plugged securely in wall receptacle.
Note: Plug has a test/reset button on it. Make sure that the plug has not tripped.
Replace the fuse. See Note 1.  Reset circuit breaker. See Note 1.  Turn unit on (bottom right button on keypad).
9 Troubleshooting
In general, possible trouble is classified in three kinds. One is called Starting Failure which is caused from an electrical defect, another is ineffective Air Conditioning caused by a defect in the refrigeration circuit and improper application, and the other is called the Structure Damage.
19
Page 22
UNIT NOT COOLING/HEATING ROOM
Unit air discharge section is blocked Temperature setting is not high or low
enough. Note: Set point limits may not allow the unit to heat or cool the room to the temperature desired. Check section on dip switch settings.
Unit air filters are dirty. Room is excessively hot or cold when
unit is started.
Vent door left open. Unit may be in a protection mode. Compressor is in time delay.
Make sure that curtains, blinds or furniture are not restricting
or blocking unit airflow.
Reset to a lower or higher temperature setting. Remove and clean filters. Allow sufficient amount of time for unit to heat or cool the room.
Start heating or cooling early before outdoor temperature, cooking heat or gatherings of people make room uncomfortable.
Close vent door. Check dipswitch settings for desired comfort. Wait approximately 3 minutes for compressor to start.
DISPLAY HAS STRANGE NUMBERS/CHARACTERS ON IT
The unit may be in a protection mode. The unit may be set for (instead of ).
UNIT MAKING NOISES
Clicking, gurgling and whooshing noises are normal during
operation of unit.
WATER DRIPPING OUTSIDE
If a drain kit has not been installed, condensation runoff during
very hot and humid weather is normal. See Note 2. If a drain kit has been installed and is connected to a drain system, check gaskets and fittings around drain for leaks and plugs.
WATER DRIPPING INSIDE
Wall sleeve is not installed level
Wall sleeve must be installed level for proper drainage of
condensation. Check that installation is level and make any necessary adjustments.
ICE OR FROST FORMS ON INDOOR COIL
Low outdoor temperature Dirty filters
When outdoor temperature is approximately 55 or below, frost
may form on the indoor coil when unit is in Cooling mode. Switch unit
to FAN operation until ice or frost melts. Remove and clean filters.
COMPRESSOR PROTECTION
Power may have cycled, so
compressor is in a restart protection.
Random Compressor restart-Whenever the unit is plugged in, or
power has been restarted, a random compressor restart will occur. After a power outage, the compressor will restart after approximately 3 minutes.
Compressor Protection-To prevent short cycling of the compressor,
there is a random startup delay of 3 minutes and a minimum compressor run time of 3 minutes.
NOTES:
1. If circuit breaker is tripped or fuse is blown more than once, contact a qualified electrician.
2. If unit is installed where condensation drainage could drip in an undesirable location, an accessory drain kit should be
installed and connected to drain system.
20
Page 23
2190 NW 89 Place, Doral, FL 33172 - USA
The Klimaire logo is a registered Trademark of Klimaire Products inc.
Copyright 2010 Klimaire Products Inc.
21