Klimaire KSIR036H218 Specifications

Klimaire Model No. KSIR036-H218 KSIR048-H218
Power supply V- Ph-Hz 208-230 / 1 / 60 208-230 / 1 / 60
Max. fuse size A 50 50
Minimum circuit ampacity A 30 35
Type Type ROTARY ROTARY
Compressor Capacity Btu/h 32823 44697
Input W 2570 3420
Rated current (RLA) A 22,00 23,5
Input W 120 (Output) 85 (Output)
Speed
Outdoor air flow (Max.)
Outdoor noise level
Throttle device
rpm 950 900
cfm 2530 4470
dB(A) 66 62,5
Type Capillary +EXV Capillary +EXV
Dimension (W×D×H) in 37.24x16.14x31.89 37.48x16.34x52.48
Outdoor unit Packing (W×D×H) in 42.91x19.69x34.06 43.11x19.49x58.27
Net/ Gross weight lb 148.59/160.94 217.4/246.0
Refrigerant Type / Charge
Refrigerant pre-charge
Additional charge for each ft
oz R410A/108 R410A/148.2
ft 25 25
oz 0,32 0,32
Design pressure psig 550/340 550/340
Liquid side/ Gas side in 3/8" / 5/8" 3/8" / 5/8"
Refrigerant piping
Max. pipe length
ft 213 213
Max. difference in level ft 98 98
Ambient temperature Cooling 5~122 5~122
Heating
ºF
ºF
5~86 5~86
Continued product improvement is our goal at Klimaire Products, Inc. Hence, specifications and data listed herein are subject to change without notice and without obligation on our part. Allways comply with local, state, and national electrical codes.