KSIO Outdoor Unit
Klimaire Model No. KSIO012-H223-O KSIO018-H221-O KSIO024-H218-OC
Power supply V- Ph-Hz 230-1-60 230-1-60 230-1-60
Max. fuse A 15 20 25
Minimum circuit ampacity A 8 13 15
Ourdoor fan motor Qty 1 1 1
Speed r/min 850/580 750/500 850
Outdoor air flow cfm 1295 1471 2060
Outdoor noise level dB(A) 55 60,5 61
Throttle type Capillary Capillary Capillary + EXV
Dimension (W×D×H) in 30"-1/8 x 11"-1/8 x 23"-1/4 33"-1/4 x 13"-3/16 x 27"-13/32 35"-3/16 x 12"-3/16 x 33"-7/8
Outdoor unit
Refrigerant type/Quantity
Design pressure psig 340 340 340
Refrigerant piping
Ambient temperature
Remarks:1.The above design and specifications are subject to change without prior notice for product improvement.
2.The values given in the table for the noise level reflect the levels in anechoic chamber.
Packing (W×D×H) in 35" x 14" x 25"-3/8 38" x 15"-5/8 x 29"-11/16 41" x 15"-5/8 x 36"
Net/ Gross weight lb 87 /92.4 104.5 / 112.2 159 /168
Type R410A R410A R410A
Charged volume oz 56,53 61,83 89,6
Liquid side/ Gas side in 1/4" / 1/2" 3/8" / 5/8" 3/8" / 5/8"
Max. pipe length ft 35 98 160
Max. difference in level ft 33 65 80
Cooling ºF
Heating ºF
0~50 5~122 5~122
5~75 5~75 5~75