Klimaire KSIH024H220SW User Manual

Model Numbers:
KSIH009-H225-IW KSIH012-H222-IW KSIH018-H220-IW KSIH024-H220-IW
KSIH MINI- Split Hyper DC
Inverter Air Conditioner
SERVICE MANUAL
1. Precaution
2. Part Names And Functions
3. Dimension
4. Refrigerant Cycle Diagram
5. Wiring Diagram
6. Installation Details
7. Operation Characteristics
8. Electronic Function
9. Troubleshooting
10. Disassembly Instructions
CONTENTS
1. Precaution .................................................................................................................................................. 1
1.1 Safety Precaution ..................................................................................................................... 1
1.2 Warning .................................................................................................................................... 1
2. Part Names And Functions ....................................................................................................................... 4
2.1 Model Names of Indoor/Outdoor units ...................................................................................... 4
2.2 Part names of Indoor/Outdoor units ................................................................ .......................... 5
3. Dimension ................................................................................................................................................... 6
3.1 Indoor Unit ............................................................................................................................... 6
3.2 Outdoor Unit ............................................................................................................................. 8
4. Refrigerant Cycle Diagram ........................................................................................................................ 9
5. Wiring Diagram......................................................................................................................................... 10
6 Installation Details .................................................................................................................................... 10
6.1 Wrench torque sheet for installation ........................................................................................ 10
6.2 Connecting the cables ............................................................................................................ 10
6.3 Pipe length and the elevation ................................................................................................. 10
6.4 Installation for the first time ..................................................................................................... 10
6.5 Adding the refrigerant after running the system for many years ...............................................11
6.6 Re-installation while the indoor unit need to be repaired ................................ ......................... 12
6.7 Re-installation while the outdoor unit need to be repaired ....................................................... 12
7. Operation Characteristics ....................................................................................................................... 14
8. Electronic Function .................................................................................................................................. 15
8.1 Abbreviation ........................................................................................................................... 15
8.2 Display function ...................................................................................................................... 15
8.3 Main Protection ...................................................................................................................... 16
8.4 Operation Modes and Functions ............................................................................................. 17
9. Troubleshooting ....................................................................................................................................... 22
9.1 Indoor Unit Error Display ........................................................................................................ 23
9.2 Outdoor unit error display ....................................................................................................... 24
9.3 Diagnosis and Solution ........................................................................................................... 28
10 Disassembly Instructions ....................................................................................................................... 57
10.1 Indoor unit ............................................................................................................................ 57
10.2 Outdoor unit ......................................................................................................................... 61
1
1. Precaution
1.1 Safety Precaution
To prevent injury to the user or other
people and property damage, the following
instructions must be followed.
Incorrect operation due to ignoring
instruction will cause harm or damage.
Before service the unit, be sure to
read this service manual at first.
1.2 Warning
Installation
Do not use a defective or underrated
circuit breaker. Use this appliance on a
dedicated circuit.
There is risk of fire or electric shock.
For electrical work, contact the
dealer, seller, a qualified electrician, or an
authorized service center.
Do not disassemble or repair the product, there is risk of fire or electric shock.
Always ground the product.
There is risk of fire or electric shock.
Install the panel and the cover of
control box securely.
There is risk of fire of electric shock.
Always install a dedicated circuit and
breaker.
Improper wiring or installation may cause electric shock.
Use the correctly rated breaker of
fuse.
There is risk of fire or electric shock.
Do not modify or extend the power
cable.
There is risk of fire or electric shock.
Do not install, remove, or reinstall the
unit by yourself (customer).
There is risk of fire, electric shock, explosion, or injury.
Be caution when unpacking and
installing the product.
Sharp edges could cause injury, be especially careful of the case edges and the fins on the condenser and evaporator.
For installation, always contact the
dealer or an authorized service center.
Do not install the product on a
defective installation stand.
Be sure the installation area does not
deteriorate with age.
If the base collapses, the air conditioner could fall with it, causing property damage, product failure, and personal injury.
Do not let the air conditioner run for
a long time when the humidity is very high
and a door or a window is left open.
Take care to ensure that power cable
could not be pulled out or damaged during
operation.
There is risk of fire or electric shock.
Do not place anything on the power
cable.
There is risk of fire or electric shock.
Do not plug or unplug the power
supply plug during operation.
There is risk of fire or electric shock.
Do not touch (operation) the product
with wet hands.
Do not place a heater or other
appliance near the power cable.
There is risk of fire and electric shock.
Do not allow water to run into
electrical parts.
It may cause fire, failure of the product, or electric shock.
Do not store or use flammable gas or
combustible near the product.
There is risk of fire or failure of product.
Do not use the product in a tightly
closed space for a long time.
Oxygen deficiency could occur.
When flammable gas leaks, turn off
the gas and open a window for ventilation
before turn the product on.
If strange sounds or smoke comes
from product, turn the breaker off or
disconnect the power supply cable.
2
There is risk of electric shock or fire.
Stop operation and close the window
in storm or hurricane. If possible, remove the product from the window before the
hurricane arrives.
There is risk of property damage, failure of product, or electric shock.
Do not open the inlet grill of the
product during operation. (Do not touch the electrostatic filter, if the unit is so
equipped.)
There is risk of physical injury, electric shock, or product failure.
When the product is soaked, contact
an authorized service center.
There is risk of fire or electric shock.
Be caution that water could not enter
the product.
There is risk of fire, electric shock, or product damage.
Ventilate the product from time to
time when operating it together with a stove
etc.
There is risk of fire or electric shock.
Turn the main power off when
cleaning or maintaining the product.
There is risk of electric shock.
When the product is not be used for
a long time, disconnect the power supply
plug or turn off the breaker.
There is risk of product damage or failure, or unintended operation.
Take care to ensure that nobody
could step on or fall onto the outdoor unit.
This could result in personal injury and product damage.
CAUTION
Always check for gas (refrigerant)
leakage after installation or repair of
product.
Low refrigerant levels may cause failure of product.
Install the drain hose to ensure that
water is drained away properly.
A bad connection may cause water leakage.
Keep level even when installing the
product.
It can avoid vibration of water leakage.
Do not install the product where the
noise or hot air from the outdoor unit could
damage the neighborhoods.
It may cause a problem for your neighbors.
Use two or more people to lift and
transport the product.
Do not install the product where it
will be exposed to sea wind (salt spray)
directly.
It may cause corrosion on the product. Corrosion, particularly on the condenser and evaporator fins, could cause product malfunction or inefficient operation.
Operational
Do not expose the skin directly to
cool air for long time. (Do not sit in the
draft).
Do not use the product for special
purposes, such as preserving foods, works of art etc. It is a consumer air conditioner,
not a precision refrigerant system.
There is risk of damage or loss of property.
Do not block the inlet or outlet of air
flow.
Use a soft cloth to clean. Do not use
harsh detergents, solvents, etc.
There is risk of fire, electric shock, or damage to the plastic parts of the product.
Do not touch the metal parts of the
product when removing the air filter. They
are very sharp.
Do not step on or put anything on the
product. (outdoor units)
Always insert the filter securely.
Clean the filter every two weeks or more
often if necessary.
A dirty filter reduces the efficiency of the air conditioner and could cause product malfunction or damage.
Do not insert hands or other objects
through air inlet or outlet while the product
is operated.
3
Do not drink the water drained from
the product.
Use a firm stool or ladder when
cleaning or maintaining the product.
Be careful and avoid personal injury.
Replace the all batteries in the
remote control with new ones of the same type. Do not mix old and new batteries or
different types of batteries.
There is risk of fire or explosion.
Do not recharge or disassemble the
batteries. Do not dispose of batteries in a
fire.
They may burn of explode.
If the liquid from the batteries gets
onto your skin or clothes, wash it well with clean water. Do not use the remote of the
batteries have leaked.
4
Series
Capacity
Indoor units
Outdoor units
Inverter
9k
KSIH009-H225-IW
KSIH009-H225-O
12k
KSIH012-H222-IW
KSIH012-H222-O
18k
KSIH018-H220-IW
KSIH018-H220-O
24k
KSIH024-H220-IW
KSIH024-H220-O
2. Part Names and Functions
2.1 Model Names of Indoor/Outdoor units
5
2.2 Part names of Indoor/Outdoor units
6
Model W D
H
KSIH009-H225-IW
32.9 in (835 mm)
7.8 in (198 mm)
11.0 in (280 mm)
KSIH012-H222-IW
39.0 in (990 mm)
8.6 in (218 mm)
12.4 in (315 mm)
KSIH018-H220-IW
KSIH024-H220-IW
46.7 in (1186 mm)
10.2 in (258 mm)
13.5 in (343 mm)
W D
3. Dimension
3.1 Indoor Unit
7
For KSIH009-H225-IW
For KSIH012-H222-IW, KSIH018-H220-IW
For KSIH024-H220-IW
8
Model
W in
(mm)
D in
(mm)
H in (mm)
W1 in (mm)
A in
(mm)
B in
(mm)
KSIH009-H225-O
31.5
(800)
13.11 (333)
21.81 (554)
34.25
(870)
20.24 (514)
13.39 (340)
KSIH012-H222-O
KSIH018-H220-O
33.27 (845)
14.29 (363)
27.64 (702)
35.98 (914)
21.26 (540)
13.78 (350)
KSIH024-H220-O
37.24 (946)
16.14 (410)
31.89 (810)
40.55
(1030)
26.50 (673)
15.87 (403)
More than 60cm(23.6in)
More than 70cm(27.6in)
More than 30cm(11.8in)
More than 60cm(23.6in) (Service space)
Fence or
obstacles
More than 30cm(11.8in)
3.2 Outdoor Unit
Note: The above drawing is only for reference. The appearance of your units may be different.
9
LIQUID SIDE
GAS SIDE
HEAT EXCHANGE (EVAPORATOR)
HEAT EXCHANGE (CONDENSER)
Compressor
2-WAY VALVE
3-WAY VALVE
4-WAY VALVE
COOLING HEATING
T2 Evaporator temp. sensor
T1 Room temp. sensor
T3 Condenser temp. sensor
Accumulator
TP Discharge temp. sensor
T4 Ambient temp. sensor
INDOOR OUTDOOR
Electronic expansion valve
CAPILLARY tube
4. Refrigerant Cycle Diagram
10
Outside diameter
Torque
Additional tightening
torque
Ф6.35mm
1/4in
1500N.cm(153kgf.cm)
1600N.cm(163kgf.cm)
Ф9.52mm
3/8in
2500N.cm(255kgf.cm)
2600N.cm(265kgf.cm)
Ф12.7mm
1/2in
3500N.cm(357kgf.cm)
3600N.cm(367kgf.cm)
Ф15.9mm
5/8in
4500N.cm(459kgf.cm)
4700N.cm(479kgf.cm)
Ф19mm
3/4in
6500N.cm(663kgf.cm)
6700N.cm(683kgf.cm)
Appliance Amps
AWG Wire Size
10
18
13
16
18
14
25
12
30
10
Models
Pipe size
Gas
Liquid
KSIH009-H225-IW + KSIH009-H225-O
3/8in (9.52 mm)
1/4in (6.35 mm)
KSIH012-H222-IW + KSIH012-H222-O
1/2in (12.7 mm)
1/4in (6.35 mm)
KSIH018-H220-IW + KSIH018-H220-O
KSIH024-H220-IW +
5/8in (15.9 mm)
3/8in (9.52 mm)
Models
Standard
Max.
Max.
Additional
Length
Elevation
Length
Refrigerant
KSIH009-H225-IW+ KSIH009-H225-O
24.6 ft
(7.5m)
32.8 ft (10m)
82.0 ft (25m)
0.16 oz/ft
(15g/m)
KSIH012-H222-IW+ KSIH012-H222-O
KSIH018-H220-IW+ KSIH018-H220-O
24.6 ft (7.5m)
65 ft
(20m)
98 ft
(30m)
0.16oz/ft (15g/m)
KSIH024-H220-IW+ KSIH024-H220-O
24.6 ft (7.5m)
82 ft
(25m)
164 ft (50m)
0.32oz/ft (30g/m)
5. Wiring Diagram
(Pls refer the wiring diagram on the unit)
6 Installation Details
6.1 Wrench torque sheet for nstallation
6.2 Connecting the cables
The power cord should be selected according to the following specifications sheet.
The cable size and the current of the fuse or switch is determined by the maximum current indicated on the nameplate which located on the side panel of the unit. Please refer to the nameplate before selecting the cable, fuse and switch.
6.4 Installation for the first time
Air and moisture in the refrigerant system have undesirable effects as below:
Pressure in the system rises.
Operating current rises.
Cooling or heating efficiency drops.
Moisture in the refrigerant circuit may
freeze and block capillary tubing.
Water may lead to corrosion of parts in the refrigerant system.
Therefore, the indoor units and the pipes between indoor and outdoor units must be leak tested and evacuated to remove gas and moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral detergent on the indoor unit connections or outdoor unit connections by a soft brush to check for leakage of the connecting points of the piping. If bubbles come out, the pipes have leakage.
6.3 Pipe length and the elevation
11
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the
indoor and outdoor units, confirm that both the 2-way and 3-way valves are set to the closed position.
2) Connect the charge hose with the push pin
of handle lo to the 3-way valves gas service port.
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check
whether the compound meter indicates -
0.1Mpa(14.5Psi). If the meter does not indicate -0.1Mpa(14.5Psi) after pumping 30 minutes, it should be pumped 20 minutes more. If the pressure can’t achieve -
0.1Mpa(14.5Psi) after pumping 50 minutes, please check if there are some leakage points. Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about
45° counterclockwise for 6 or 7seconds after the gas coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a little higher than the atmosphere pressure. Then remove the charge hose from the 3-way valve.
8) Fully open the 2-way valve and 3-way valve
and securely tighten the cap of the 3-way
valve.
6.5 Adding the refrigerant after
running the system for many years
Procedure
1). Connect the charge hose to the 3-way service port, open the 2-way valve and the 3­way valve. Connect the charge hose to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose. Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4) Operate the air conditioner at the cooling mode.
5) Open the valves (Low side) on the charge set and charge the system with liquid refrigerant.
6). When the electronic scale displays the proper weight (refer to the gauge and the pressure of the low side), disconnect the charge hose from the 3-way valve’s service port immediately and turn off the air conditioner before disconnecting the hose.
7). Mount the valve stem caps and the service port Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
12
6.6 Re-installation while the indoor
unit need to be repaired
1. Collecting the refrigerant into the outdoor
unit
2.Air purging with vacuum pump
Procedure
1). Confirm that both the 2-way and 3-way
valves are set to the opened position Remove the valve stem caps and confirm that the valve stems are in the opened position. Be sure to use a hexagonal wrench to operate the valve stems.
2). Connect the charge hose with the push pin
of handle lo to the 3-way valves gas service port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve slightly to purge air from the charge hose for 5 seconds and then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates
0.1Mpa(14.5psi).
6). Set the 3-way valve to the closed position
immediately Do this quickly so that the gauge ends up indicating 0.3Mpa (43.5Psi) to 0.5 Mpa (72.5psi). Disconnect the charge set and tighten the 2­way and 3-way valve’s stem nuts. Use a torque wrench to tighten the 3-way valves service port cap to a torque of 18N.m. Be sure to check for gas leakage.
1) Completely tighten the flare nuts of the indoor and outdoor units, confirm that both the 2-way and 3-way valves are set to the closed position.
2) Connect the charge hose with the push pin of handle lo to the 3-way valves gas service port.
3) Connect the charge hose of handle hi connection to the vacuum pump.
4) Fully open the handle Lo of the manifold valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check whether the compound meter indicates -0.1Mpa (14.5psi). If the meter does not indicate -
0.1Mpa (14.5psi) after pumping 30 minutes, it should be pumped 20 minutes more. If the pressure can’t achieve -0.1Mpa (14.5psi) after pumping 50 minutes, please check if there are some leakage points. Fully close the handle Lo valve of the manifold valve and stop the operation of the vacuum pump. Confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
7)Turn the flare nut of the 3-way valves about 45° counterclockwise for 6 or 7seconds after the gas coming out, then tighten the flare nut again. Make sure the pressure display in the pressure indicator is a little higher than the atmosphere pressure. Then remove the charge hose from the 3-way valve.
8) Fully open the 2-way valve and 3-way valve
13
and securely tighten the cap of the 3-way valve.
6.7 Re-installation while the outdoor
unit need to be repaired
1. Evacuation for the whole system
Procedure:
1). Confirm that both the 2-way and 3-way valves
are set to the opened position.
2). Connect the vacuum pump to 3-way valve’s
service port.
3). Evacuation for approximately one hour.
Confirm that the compound meter indicates -
0.1Mpa (14.5Psi).
4). Close the valve (Low side) on the charge
set, turn off the vacuum pump, and confirm that the gauge needle does not move (approximately 5 minutes after turning off the vacuum pump).
5). Disconnect the charge hose from the
vacuum pump.
2. Refrigerant charging
Connect the charge hose which you disconnected from the vacuum pump to the valve at the bottom of the cylinder. If the refrigerant is R410A, make the cylinder bottom up to ensure liquid charge.
2). Purge the air from the charge hose Open the valve at the bottom of the cylinder and press the check valve on the charge set to purge the air (be careful of the liquid refrigerant).
3) Put the charging cylinder onto the electronic scale and record the weight.
4). Open the valves (Low side) on the charge set and charge the system with liquid refrigerant If the system cannot be charge with the specified amount of refrigerant or can be charged with a little at a time (approximately 150g each time), operating the air conditioner in the cooling cycle; however, one time is not sufficient, wait approximately 1 minute and then repeat the procedure.
5). When the electronic scale displays the proper weight, disconnect the charge hose from the 3-way valve’s service port immediately If the system has been charged with liquid refrigerant while operating the air conditioner, turn off the air conditioner before disconnecting the hose.
6). Mount the valve stem caps and the service port. Use torque wrench to tighten the service port cap to a torque of 18N.m. Be sure to check for gas leakage.
Procedure:
1). Connect the charge hose to the charging
cylinder, open the 2-way valve and the 3-way valve
14
Temperature
Mode
Cooling operation
Heating operation
Drying operation
Room temperature
17℃~32
(62℉~90)
0℃~30
(32℉~86℉)
10℃~32
(50℉~90℉)
Outdoor temperature
KSIH009-H225-IW KSIH012-H222-IW KSIH018-H220-IW KSIH024-H220-IW
-30°C50°C
(-22°F122°F)
-30°C30°C
(-22°F86°F)
0°C50°C
(32°F122°F)
7. Operation Characteristics
󰇛󰇜
󰇛󰇜 
CAUTION:
1. If the air conditioner is used beyond the above conditions, certain safety protection features may come
into operation and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this figure,
the surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its maximum angle (vertically to the floor) and set HIGH fan mode.
3. The optimum performance will be achieved during this operating temperature zone.
+32
15
ION indication lamp (optional function) This lamp illuminates when Clean Air feature is activated.
DEFROST indication lamp (For cooling & heating models only): Lights up when the air conditioner starts defrosting automatically or when the warm air control feature is activated in heating operation.
OPERATION indication lampThis lamp illuminates when the air conditioner is in operation.
TIMER indication lampLights up during Timer operation.
Temperature indicatorDisplays the temperature settings when the air
conditioner is operational. Displays the malfunction code.
8. Electronic Function
8.1 Abbreviation
T1: Indoor room temperature T2: Coil temperature of evaporator T3: Coil temperature of condenser T4: Outdoor ambient temperature TP: Compressor discharge temperature
8.2 Display function
8.2.1 Icon explanation on indoor display board.
16
8.3 Main Protection
8.3.1 Three minutes delay at restart for
compressor
Less than 1-minute delay for the 1st time stand­up and 3 minutes delay for others.
8.3.2 Temperature protection of compressor
top
The unit will stop working when the compressor top temp. protector cut off and will restart after the compressor top temp. protector restart.
8.3.3 Temperature protection of compressor
discharge
Compressor discharge temp. TP>115 (239°F) for 5s, compressor stops.
8.3.4 Fan speed is out of control
When Indoor fan speed keeps too low (300RPM) or too high(1500RPM) for certain time, the unit will stop and the LED will display the failure
8.3.5 Inverter module protection
The Inverter module has a protection function about current, voltage and temperature. If these protections happen, the corresponding code will display on indoor unit and the unit will stop working.
8.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active immediately and the indoor fan will open 10s later. If the unit runs in heating mode, the indoor fan will be also controlled by anti-cold wind
function.
8.3.7 Compressor preheating functions
Preheating permitting condition: When T4(outdoor ambient temperature) 3°C (37.4°F), the preheating function will be activated
8.3.8 Zero crossing detection error
protection
If AC detects time interval is not correct for continuous 240s, the unit will stop and the LED will display the failure. The correct zero crossing signal time interval should be between 6-13ms.
8.3.9 Sensor protection at open circuit and
breaking disconnection.
When there’s only one temperature sensor in malfunction, the air conditioner will keep working but show the error code, in case of any emergency use. When there’s more than one temperature sensor in malfunction, the air conditioner will stop working
8.3.10 Refrigerant leakage detection
This function is only active in cooling mode. It can better prevent the compressor being damaged by refrigerant leakage or compressor overload. Open condition: When compressor is active, the value of the Coil temperature of evaporator T2 has no change or very little change.
17
Setting fan
speed
Actual fan speed
H+(H+=H+G) A H(=H) B C
M+(M+=M+Z) D M(M=M) E F
L+(L+=L+D) G L(L=L) H I
T1-Td (°F)
L
L-(L-=L-D)
H
H-(H-=H-G)
M
M-(M-=M-Z)
a
b
c
d
T1
e
T4
A+
A
B
C
D E
a
b
c
d
T1
e
T3
Resume
Off
Decrease
Hold
8.4 Operation Modes and Functions
8.4.1 Fan mode
(1) Outdoor fan and compressor stop. (2) Temperature setting function is disabled, and no setting temperature is displayed. (3) Indoor fan can be set to high/med/low/auto. (4) The louver operates same as in cooling mode. (5) Auto fan:
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules
When T1-Ts<-2(28.4°F), the compressor will stop, when T1TS>-0.5(31.1°F),the compressor will be activated. When the AC run in mute mode, the compressor will run with low frequency. When the current is more than setting value, the current protection function will be activated, and the compressor will stop.
8.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4.
For different outdoor units, the fan speeds are different
the speed can be selected as high, medium, low and auto. When the setting temp. is reached, if the compressor stops running, indoor fan motor will run in Minimum speed or setting speed. The indoor fan is controlled as below:
The auto fan acts as below rules:
8.4.2.3 Condenser temperature protection
When condenser temperature temp. is more than setting value, the compressor will stop.
8.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and
8.4.2.5 Evaporator temperature protection
When Evaporator temperature temp.is less than setting value, the compressor will stop
8.4.3 Heating Mode
8.4.3.1 Compressor running rules
When T1-Ts>-ΔT, the compressor will stop, when T1-T
<ΔT-1.5the compressor will be on.
S
ΔT is the programmed parameter of temperature compensation.
18
Setting fan
speed
Actual fan speed
H=H
H+(H+=H+G)
M(M=M)
M+(M+=M+Z)
L(L=L)
L+(L+=L+D)
H-(H-=H-G)
M-(M-=M-Z)
L-(L-=L-D)
T1-Td
LHM
T4
E
D
C
B
A A+
T1-Td+¦ ¤T
Resume
Off
Decrease
Hold
When the AC run in mute mode, the compressor will run with low frequency. When the current is more than setting value, the current protection function will be activated and the compressor will stop.
8.4.3.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed according to T4.
For different outdoor units, the fan speeds are different
8.4.3.3 Indoor fan running rules When the compressor is on, the indoor fan can be set to high/med/low/auto/mute. When indoor unit coil temp. is low, the anti-cold air function will start and indoor fan motor will run at low speed, the speed can’t be changed, when the temp. is lower than setting value, the indoor fan motor will stop. When the indoor temp reaches the setting temp., the compressor will stop, the indoor fan motor will run at the minimum speed or setting speed. (The anti-cold air function is valid). The indoor fan is controlled as below:
8.4.3.4 Defrosting mode
AC will enter the defrosting mode according to the value of temp. of T3 and the value range of temp. change of T3 and also the compressor running time. During the defrosting mode, the compressor keeps running, indoor and outdoor motor will stop, defrost lamp of the indoor unit will be
lighted “ .” Will be displayed.
8.4.3.5 Evaporator coil temperature protection
Auto fan action in heating mode:
When evaporator temperature temp. is more than the setting protection value, the compressor will stop.
8.4.4 Auto-mode
This mode can be chosen with remote controller and the setting temperature can be changed between 17°C(62.6°F) ~30°C(86°F). In auto mode, the machine will choose cooling, heating or fan-only mode according to ΔT (ΔT =T1-Ts).
19
T1-Ts
Cooling
Heating*
Fan only
Heating*: For cooling only models, they will run at fan speed
Indoor fan will run at auto fan of the relevant mode. The louver operates same as in relevant mode. If the machine switches mode between heating and cooling, the compressor will keep stopping for certain time and then choose mode according to T1-Ts. If the setting temperature is modified, the machine will choose running function again.
8.4.5 Drying mode
8.4.5.1 Indoor fan speed is fixed at breeze and can’t be changed. The louver angle is the same as in cooling mode.
8.4.5.2 Low indoor room temperature protection In drying mode, if room temperature is lower than 10°C (50°F), the compressor will stop and not resume until room temperature exceeds 12°C (53.6°F).
8.4.5.3 Evaporator anti-freezing protection, condenser high temperature protection and outdoor unit frequency limit are active and the same as that in cooling mode.
8.4.5.4 The outdoor fan operates the same as in cooling mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function: When the machine is off, pressing the touch button will carry the machine to forced auto mode. If pressing the button once again within 5 seconds, the machine will turn into forced cooling mode. In forced auto, forced cooling or any other operation mode, pressing touch button will turn
off the machine.
8.4.6.2 In forced operation mode, all general protections and remote control are available.
8.4.6.3 Operation rules: Forced cooling mode: The compressor runs at F2 frequency and indoor fan runs as breeze. After running for 30 minutes. the machine will turn to auto mode as 24°C (75.2°F) setting temperature. Forced auto mode: The action of forced auto mode is the same as normal auto mode with 24°C (75.2°F) setting temperature.
8.4.7 Auto-Restart function
The indoor unit is equipped with auto-restart function, which is carried out through an auto­restart module. In case of a sudden power failure, the module memorizes the setting conditions before the power failure. The unit will resume the previous operation setting (not including swing function) automatically after 3 minutes when power returns. If the memorization condition is forced cooling mode, the unit will run in cooling mode for 30 minutes and turn to auto mode as 24°C (75.2°F) setting temp. If AC is off before power off and AC is required to start up now, the compressor will have 1-minute delay when power on. Other conditions, the compressor will have 3 minutes delay when restarts.
8.4.8 Refrigerant Leakage Detection
With this new technology, the display area will show “EC” when the outdoor unit detects refrigerant leakage.
8.4.9 8°C Heating(optional)
When the compressor is running, the indoor fan motor will run without anti-cold air function. When the compressor is off, the indoor fan motor is off
20
Enquiry information
Displaying code
Meaning
T1
T1
T1 temp.
T2
T2
T2 temp.
T3
T3
T3 temp.
T4
T4
T4 temp.
T2B
Tb
T2B temp.
TP
TP
TP temp.
TH
TH
TH temp.
Targeted Frequency
FT
Targeted Frequency
Actual Frequency
Fr
Actual Frequency
Indoor fan speed
IF
Indoor fan speed
Outdoor fan speed
OF
Outdoor fan speed
EXV opening angle
LA
EXV opening angle
Compressor continuous running time
CT
Compressor continuous running time
Causes of compressor stop.
ST
Causes of compressor stop.
Reserve
A0
Reserve
A1 Reserve
0 Reserve
1 Reserve
2
Reserve
3
Reserve
4
Reserve
5
Reserve
6 Reserve
L Reserve
A Reserve
U Reserve
T
8.4.10 Point check function
Press the LED DISPLAY or LED or MUTE button of the remote controller three times, and then press the
AIR DIRECTION or SWING button three times in ten seconds, the buzzer will keep ring for two seconds.
The air conditioner will enter into the information enquiry status. You can press the LED DISPLAY or AIR DIRECTION button to check the next or front item’s information.
When the AC enter the “information enquiry” status, it will display the code name in 2 seconds, the details
are as follows.
When the AC enter into the information enquiry status, it will display the code value in the next 25s, the
details are as follows.
21
Enquiry information
Display value
Meaning
Remark
T1, T2, T3, T4, T2B, TP, TH, Targeted Frequency, Actual Frequency
-1F,-1E,-1d,-1c,­1b,-1A
-25,-24,-23,-22,-21,­20
1. All the displaying temperature is actual
value.
2. All the temperature is °C no matter what kind of remote controller is used.
3. T1, T2, T3, T4, T2B display range : ­25~70, TP display range: -20~130.
4. Frequency display range: 0~159Hz.
5. If the actual value exceeds the range, it will display the maximum value or minimum value.
-1999
-1999
A0,A1,A9
100,101,109
b0,b1,b9
110,111,119
c0,c1,c9
120,121,129
d0,d1,d9
130,131,139
E0,E1,E9
140,141,149
F0,F1,F9
150,151,159
Indoor fan speed /Outdoor fan speed
0
OFF
1,2,3,4
Low speed, Medium speed, High speed, Turbo
For some big capacity motors.
14-FF
Actual fan speed=Display value turns to decimal value and then multiply 10. The unit is RPM.
For some small capacity motors, display value is from 14-FF(hexadecimal), the corresponding fan speed range is from 200-2550RPM.
EXV opening angle
0-FF
Actual EXV opening value=Display value turns to decimal value and then multiply 2.
Compressor continuous running time
0-FF
0-255 minutes
If the actual value exceeds the range, it will display the maximum value or minimum value.
Causes of compressor stop.
0-99
For the detailed meaning, please consult with engineer
Decimal display
Reserve
0-FF
22
9. Troubleshooting
Safety
Electricity power is still kept in capacitors even the power supply is shut off. Do not forget to discharge the electricity power in capacitor.
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
For other models, please connect discharge resistance (approx.100Ω 40W) or soldering iron (plug) between +, ­terminals of the electrolytic capacitor on the contrary side of the outdoor PCB.
Note: The picture above is only for reference. The plug of your side may be different.
Loading...
+ 55 hidden pages