8. Electronic Function .................................................................................................................................. 15
10.1 Indoor unit ............................................................................................................................ 57
10.2 Outdoor unit ......................................................................................................................... 61
1
1. Precaution
1.1 Safety Precaution
◼To prevent injury to the user or other
people and property damage, the following
instructions must be followed.
◼Incorrect operation due to ignoring
instruction will cause harm or damage.
◼Before service the unit, be sure to
read this service manual at first.
1.2 Warning
➢ Installation
◼ Do not use a defective or underrated
circuit breaker. Use this appliance on a
dedicated circuit.
There is risk of fire or electric shock.
◼For electrical work, contact the
dealer, seller, a qualified electrician, or an
authorized service center.
Do not disassemble or repair the product,
there is risk of fire or electric shock.
◼ Always ground the product.
There is risk of fire or electric shock.
◼Install the panel and the cover of
control box securely.
There is risk of fire of electric shock.
◼Always install a dedicated circuit and
breaker.
Improper wiring or installation may cause
electric shock.
◼Use the correctly rated breaker of
fuse.
There is risk of fire or electric shock.
◼Do not modify or extend the power
cable.
There is risk of fire or electric shock.
◼Do not install, remove, or reinstall the
unit by yourself (customer).
There is risk of fire, electric shock, explosion,
or injury.
◼Be caution when unpacking and
installing the product.
Sharp edges could cause injury, be
especially careful of the case edges and the
fins on the condenser and evaporator.
◼For installation, always contact the
dealer or an authorized service center.
◼Do not install the product on a
defective installation stand.
◼Be sure the installation area does not
deteriorate with age.
If the base collapses, the air conditioner
could fall with it, causing property damage,
product failure, and personal injury.
◼Do not let the air conditioner run for
a long time when the humidity is very high
and a door or a window is left open.
◼Take care to ensure that power cable
could not be pulled out or damaged during
operation.
There is risk of fire or electric shock.
◼Do not place anything on the power
cable.
There is risk of fire or electric shock.
◼Do not plug or unplug the power
supply plug during operation.
There is risk of fire or electric shock.
◼Do not touch (operation) the product
with wet hands.
◼Do not place a heater or other
appliance near the power cable.
There is risk of fire and electric shock.
◼Do not allow water to run into
electrical parts.
It may cause fire, failure of the product, or
electric shock.
◼Do not store or use flammable gas or
combustible near the product.
There is risk of fire or failure of product.
◼Do not use the product in a tightly
closed space for a long time.
Oxygen deficiency could occur.
◼When flammable gas leaks, turn off
the gas and open a window for ventilation
before turn the product on.
◼If strange sounds or smoke comes
from product, turn the breaker off or
disconnect the power supply cable.
2
There is risk of electric shock or fire.
◼Stop operation and close the window
in storm or hurricane. If possible, remove
the product from the window before the
hurricane arrives.
There is risk of property damage, failure of
product, or electric shock.
◼Do not open the inlet grill of the
product during operation. (Do not touch the
electrostatic filter, if the unit is so
equipped.)
There is risk of physical injury, electric shock,
or product failure.
◼When the product is soaked, contact
an authorized service center.
There is risk of fire or electric shock.
◼Be caution that water could not enter
the product.
There is risk of fire, electric shock, or product
damage.
◼Ventilate the product from time to
time when operating it together with a stove
etc.
There is risk of fire or electric shock.
◼Turn the main power off when
cleaning or maintaining the product.
There is risk of electric shock.
◼When the product is not be used for
a long time, disconnect the power supply
plug or turn off the breaker.
There is risk of product damage or failure, or
unintended operation.
◼Take care to ensure that nobody
could step on or fall onto the outdoor unit.
This could result in personal injury and
product damage.
➢ CAUTION
◼ Always check for gas (refrigerant)
leakage after installation or repair of
product.
Low refrigerant levels may cause failure of
product.
◼Install the drain hose to ensure that
water is drained away properly.
A bad connection may cause water leakage.
◼Keep level even when installing the
product.
It can avoid vibration of water leakage.
◼Do not install the product where the
noise or hot air from the outdoor unit could
damage the neighborhoods.
It may cause a problem for your neighbors.
◼Use two or more people to lift and
transport the product.
◼Do not install the product where it
will be exposed to sea wind (salt spray)
directly.
It may cause corrosion on the product.
Corrosion, particularly on the condenser and
evaporator fins, could cause product
malfunction or inefficient operation.
➢ Operational
◼ Do not expose the skin directly to
cool air for long time. (Do not sit in the
draft).
◼Do not use the product for special
purposes, such as preserving foods, works
of art etc. It is a consumer air conditioner,
not a precision refrigerant system.
There is risk of damage or loss of property.
◼Do not block the inlet or outlet of air
flow.
◼Use a soft cloth to clean. Do not use
harsh detergents, solvents, etc.
There is risk of fire, electric shock, or
damage to the plastic parts of the product.
◼Do not touch the metal parts of the
product when removing the air filter. They
are very sharp.
◼Do not step on or put anything on the
product. (outdoor units)
◼Always insert the filter securely.
Clean the filter every two weeks or more
often if necessary.
A dirty filter reduces the efficiency of the air
conditioner and could cause product
malfunction or damage.
◼Do not insert hands or other objects
through air inlet or outlet while the product
is operated.
3
◼Do not drink the water drained from
the product.
◼Use a firm stool or ladder when
cleaning or maintaining the product.
Be careful and avoid personal injury.
◼Replace the all batteries in the
remote control with new ones of the same
type. Do not mix old and new batteries or
different types of batteries.
There is risk of fire or explosion.
◼Do not recharge or disassemble the
batteries. Do not dispose of batteries in a
fire.
They may burn of explode.
◼If the liquid from the batteries gets
onto your skin or clothes, wash it well with
clean water. Do not use the remote of the
batteries have leaked.
4
Series
Capacity
Indoor units
Outdoor units
Inverter
9k
KSIH009-H225-IW
KSIH009-H225-O
12k
KSIH012-H222-IW
KSIH012-H222-O
18k
KSIH018-H220-IW
KSIH018-H220-O
24k
KSIH024-H220-IW
KSIH024-H220-O
2. Part Names and Functions
2.1 Model Names of Indoor/Outdoor units
5
2.2 Part names of Indoor/Outdoor units
6
Model W D
H
KSIH009-H225-IW
32.9 in (835 mm)
7.8 in (198 mm)
11.0 in (280 mm)
KSIH012-H222-IW
39.0 in (990 mm)
8.6 in (218 mm)
12.4 in (315 mm)
KSIH018-H220-IW
KSIH024-H220-IW
46.7 in (1186 mm)
10.2 in (258 mm)
13.5 in (343 mm)
WD
3. Dimension
3.1 Indoor Unit
7
For KSIH009-H225-IW
For KSIH012-H222-IW, KSIH018-H220-IW
For KSIH024-H220-IW
8
Model
W in
(mm)
D in
(mm)
H in (mm)
W1 in
(mm)
A in
(mm)
B in
(mm)
KSIH009-H225-O
31.5
(800)
13.11
(333)
21.81
(554)
34.25
(870)
20.24
(514)
13.39
(340)
KSIH012-H222-O
KSIH018-H220-O
33.27
(845)
14.29
(363)
27.64
(702)
35.98
(914)
21.26
(540)
13.78
(350)
KSIH024-H220-O
37.24
(946)
16.14
(410)
31.89
(810)
40.55
(1030)
26.50
(673)
15.87
(403)
More than 60cm(23.6in)
More than 70cm(27.6in)
More than 30cm(11.8in)
More than 60cm(23.6in)
(Service space)
Fence or
obstacles
More than 30cm(11.8in)
3.2 Outdoor Unit
Note: The above drawing is only for reference. The appearance of your units may be different.
9
LIQUID SIDE
GAS SIDE
HEAT
EXCHANGE
(EVAPORATOR)
HEAT
EXCHANGE
(CONDENSER)
Compressor
2-WAY VALVE
3-WAY VALVE
4-WAY VALVE
COOLING
HEATING
T2 Evaporator
temp. sensor
T1 Room temp.
sensor
T3 Condenser
temp. sensor
Accumulator
TP Discharge temp. sensor
T4 Ambient
temp. sensor
INDOOROUTDOOR
Electronic
expansion valve
CAPILLARY
tube
4. Refrigerant Cycle Diagram
10
Outside diameter
Torque
Additional tightening
torque
Ф6.35mm
1/4in
1500N.cm(153kgf.cm)
1600N.cm(163kgf.cm)
Ф9.52mm
3/8in
2500N.cm(255kgf.cm)
2600N.cm(265kgf.cm)
Ф12.7mm
1/2in
3500N.cm(357kgf.cm)
3600N.cm(367kgf.cm)
Ф15.9mm
5/8in
4500N.cm(459kgf.cm)
4700N.cm(479kgf.cm)
Ф19mm
3/4in
6500N.cm(663kgf.cm)
6700N.cm(683kgf.cm)
Appliance Amps
AWG Wire Size
10
18
13
16
18
14
25
12
30
10
Models
Pipe size
Gas
Liquid
KSIH009-H225-IW +
KSIH009-H225-O
3/8in (9.52 mm)
1/4in (6.35 mm)
KSIH012-H222-IW +
KSIH012-H222-O
1/2in (12.7 mm)
1/4in (6.35 mm)
KSIH018-H220-IW +
KSIH018-H220-O
KSIH024-H220-IW +
5/8in (15.9 mm)
3/8in (9.52 mm)
Models
Standard
Max.
Max.
Additional
Length
Elevation
Length
Refrigerant
KSIH009-H225-IW+
KSIH009-H225-O
24.6 ft
(7.5m)
32.8 ft
(10m)
82.0 ft
(25m)
0.16 oz/ft
(15g/m)
KSIH012-H222-IW+
KSIH012-H222-O
KSIH018-H220-IW+
KSIH018-H220-O
24.6 ft
(7.5m)
65 ft
(20m)
98 ft
(30m)
0.16oz/ft
(15g/m)
KSIH024-H220-IW+
KSIH024-H220-O
24.6 ft
(7.5m)
82 ft
(25m)
164 ft
(50m)
0.32oz/ft
(30g/m)
5. Wiring Diagram
(Pls refer the wiring diagram on the unit)
6 Installation Details
6.1 Wrench torque sheet for nstallation
6.2 Connecting the cables
The power cord should be selected according
to the following specifications sheet.
The cable size and the current of the fuse or
switch is determined by the maximum
current indicated on the nameplate which
located on the side panel of the unit. Please
refer to the nameplate before selecting the
cable, fuse and switch.
6.4 Installation for the first time
Air and moisture in the refrigerant system have
undesirable effects as below:
● Pressure in the system rises.
● Operating current rises.
● Cooling or heating efficiency drops.
● Moisture in the refrigerant circuit may
freeze and block capillary tubing.
● Water may lead to corrosion of parts in the
refrigerant system.
Therefore, the indoor units and the pipes
between indoor and outdoor units must be leak
tested and evacuated to remove gas and
moisture from the system.
Gas leak check (Soap water method):
Apply soap water or a liquid neutral
detergent on the indoor unit connections or
outdoor unit connections by a soft brush to
check for leakage of the connecting points of
the piping. If bubbles come out, the pipes have
leakage.
6.3 Pipe length and the elevation
11
1. Air purging with vacuum pump
1) Completely tighten the flare nuts of the
indoor and outdoor units, confirm that both
the 2-way and 3-way valves are set to the
closed position.
2) Connect the charge hose with the push pin
of handle lo to the 3-way valves gas service
port.
3) Connect the charge hose of handle hi
connection to the vacuum pump.
4) Fully open the handle Lo of the manifold
valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check
whether the compound meter indicates -
0.1Mpa(14.5Psi). If the meter does not
indicate -0.1Mpa(14.5Psi) after pumping 30
minutes, it should be pumped 20 minutes
more. If the pressure can’t achieve -
0.1Mpa(14.5Psi) after pumping 50 minutes,
please check if there are some leakage
points. Fully close the handle Lo valve of
the manifold valve and stop the operation of
the vacuum pump. Confirm that the gauge
needle does not move (approximately 5
minutes after turning off the vacuum pump).
7) Turn the flare nut of the 3-way valves about
45° counterclockwise for 6 or 7seconds
after the gas coming out, then tighten the
flare nut again. Make sure the pressure
display in the pressure indicator is a little
higher than the atmosphere pressure. Then
remove the charge hose from the 3-way
valve.
8) Fully open the 2-way valve and 3-way valve
and securely tighten the cap of the 3-way
valve.
6.5 Adding the refrigerant after
running the system for many years
Procedure
1). Connect the charge hose to the 3-way
service port, open the 2-way valve and the 3way valve.
Connect the charge hose to the valve at the
bottom of the cylinder. If the refrigerant is
R410A, make the cylinder bottom up to ensure
liquid charge.
2). Purge the air from the charge hose.
Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air (be careful of the liquid
refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4) Operate the air conditioner at the cooling
mode.
5) Open the valves (Low side) on the charge
set and charge the system with liquid
refrigerant.
6). When the electronic scale displays the
proper weight (refer to the gauge and the
pressure of the low side), disconnect the
charge hose from the 3-way valve’s service port
immediately and turn off the air conditioner
before disconnecting the hose.
7). Mount the valve stem caps and the service
port
Use torque wrench to tighten the service port
cap to a torque of 18N.m.
Be sure to check for gas leakage.
12
6.6 Re-installation while the indoor
unit need to be repaired
1. Collecting the refrigerant into the outdoor
unit
2.Air purging with vacuum pump
Procedure
1). Confirm that both the 2-way and 3-way
valves are set to the opened position
Remove the valve stem caps and confirm that
the valve stems are in the opened position.
Be sure to use a hexagonal wrench to operate
the valve stems.
2). Connect the charge hose with the push pin
of handle lo to the 3-way valves gas service
port.
3). Air purging of the charge hose.
Open the handle Lo valve of the manifold valve
slightly to purge air from the charge hose for 5
seconds and then close it quickly.
4). Set the 2-way valve to the close position.
5). Operate the air conditioner at the cooling
cycle and stop it when the gauge indicates
0.1Mpa(14.5psi).
6). Set the 3-way valve to the closed position
immediately
Do this quickly so that the gauge ends up
indicating 0.3Mpa (43.5Psi) to 0.5 Mpa
(72.5psi).
Disconnect the charge set and tighten the 2way and 3-way valve’s stem nuts.
Use a torque wrench to tighten the 3-way
valves service port cap to a torque of 18N.m.
Be sure to check for gas leakage.
1) Completely tighten the flare nuts of the
indoor and outdoor units, confirm that both the
2-way and 3-way valves are set to the closed
position.
2) Connect the charge hose with the push pin
of handle lo to the 3-way valves gas service
port.
3) Connect the charge hose of handle hi
connection to the vacuum pump.
4) Fully open the handle Lo of the manifold
valve.
5) Operate the vacuum pump to evacuate.
6) Make evacuation for 30 minutes and check
whether the compound meter indicates -0.1Mpa
(14.5psi). If the meter does not indicate -
0.1Mpa (14.5psi) after pumping 30 minutes, it
should be pumped 20 minutes more. If the
pressure can’t achieve -0.1Mpa (14.5psi) after
pumping 50 minutes, please check if there are
some leakage points. Fully close the handle Lo
valve of the manifold valve and stop the
operation of the vacuum pump. Confirm that the
gauge needle does not move (approximately 5
minutes after turning off the vacuum pump).
7)Turn the flare nut of the 3-way valves about
45° counterclockwise for 6 or 7seconds after
the gas coming out, then tighten the flare nut
again. Make sure the pressure display in the
pressure indicator is a little higher than the
atmosphere pressure. Then remove the charge
hose from the 3-way valve.
8) Fully open the 2-way valve and 3-way valve
13
and securely tighten the cap of the 3-way valve.
6.7 Re-installation while the outdoor
unit need to be repaired
1. Evacuation for the whole system
Procedure:
1). Confirm that both the 2-way and 3-way valves
are set to the opened position.
2). Connect the vacuum pump to 3-way valve’s
service port.
3). Evacuation for approximately one hour.
Confirm that the compound meter indicates -
0.1Mpa (14.5Psi).
4). Close the valve (Low side) on the charge
set, turn off the vacuum pump, and confirm that
the gauge needle does not move
(approximately 5 minutes after turning off the
vacuum pump).
5). Disconnect the charge hose from the
vacuum pump.
2. Refrigerant charging
Connect the charge hose which you
disconnected from the vacuum pump to the
valve at the bottom of the cylinder. If the
refrigerant is R410A, make the cylinder bottom
up to ensure liquid charge.
2). Purge the air from the charge hose
Open the valve at the bottom of the cylinder
and press the check valve on the charge set to
purge the air (be careful of the liquid
refrigerant).
3) Put the charging cylinder onto the electronic
scale and record the weight.
4). Open the valves (Low side) on the charge
set and charge the system with liquid
refrigerant
If the system cannot be charge with the
specified amount of refrigerant or can be
charged with a little at a time (approximately
150g each time), operating the air conditioner in
the cooling cycle; however, one time is not
sufficient, wait approximately 1 minute and then
repeat the procedure.
5). When the electronic scale displays the
proper weight, disconnect the charge hose from
the 3-way valve’s service port immediately
If the system has been charged with liquid
refrigerant while operating the air conditioner,
turn off the air conditioner before disconnecting
the hose.
6). Mount the valve stem caps and the service
port. Use torque wrench to tighten the
service port cap to a torque of 18N.m. Be sure
to check for gas leakage.
Procedure:
1). Connect the charge hose to the charging
cylinder, open the 2-way valve and the 3-way
valve
1. If the air conditioner is used beyond the above conditions, certain safety protection features may come
into operation and cause the unit to operate abnormally.
2. The room relative humidity should be less than 80%. If the air conditioner operates beyond this figure,
the surface of the air conditioner may attract condensation. Please set the vertical air flow louver to its
maximum angle (vertically to the floor) and set HIGH fan mode.
3. The optimum performance will be achieved during this operating temperature zone.
+32
15
ION indication lamp (optional function) :This lamp illuminates when Clean
Air feature is activated.
DEFROST indication lamp (For cooling & heating models only): Lights up
when the air conditioner starts defrosting automatically or when the warm air control
feature is activated in heating operation.
OPERATION indication lamp:This lamp illuminates when the air conditioner is in
operation.
TIMER indication lamp:Lights up during Timer operation.
Temperature indicator:Displays the temperature settings when the air
conditioner is operational. Displays the malfunction code.
8. Electronic Function
8.1 Abbreviation
T1: Indoor room temperature
T2: Coil temperature of evaporator
T3: Coil temperature of condenser
T4: Outdoor ambient temperature
TP: Compressor discharge temperature
8.2 Display function
8.2.1 Icon explanation on indoor display board.
16
8.3 Main Protection
8.3.1 Three minutes delay at restart for
compressor
Less than 1-minute delay for the 1st time standup and 3 minutes delay for others.
8.3.2 Temperature protection of compressor
top
The unit will stop working when the compressor
top temp. protector cut off and will restart after
the compressor top temp. protector restart.
8.3.3 Temperature protection of compressor
discharge
Compressor discharge temp. TP>115℃ (239°F)
for 5s, compressor stops.
8.3.4 Fan speed is out of control
When Indoor fan speed keeps too low
(300RPM) or too high(1500RPM) for certain
time, the unit will stop and the LED will display
the failure
8.3.5 Inverter module protection
The Inverter module has a protection function
about current, voltage and temperature. If these
protections happen, the corresponding code will
display on indoor unit and the unit will stop
working.
8.3.6 Indoor fan delayed open function
When the unit starts up, the louver will be active
immediately and the indoor fan will open 10s
later.
If the unit runs in heating mode, the indoor fan
will be also controlled by anti-cold wind
function.
8.3.7 Compressor preheating functions
Preheating permitting condition:
When T4(outdoor ambient temperature) <3°C
(37.4°F), the preheating function will be
activated
8.3.8 Zero crossing detection error
protection
If AC detects time interval is not correct for
continuous 240s, the unit will stop and the LED
will display the failure. The correct zero
crossing signal time interval should be between
6-13ms.
8.3.9 Sensor protection at open circuit and
breaking disconnection.
When there’s only one temperature sensor in
malfunction, the air conditioner will keep
working but show the error code, in case of any
emergency use.
When there’s more than one temperature sensor
in malfunction, the air conditioner will stop
working
8.3.10 Refrigerant leakage detection
This function is only active in cooling mode. It
can better prevent the compressor being
damaged by refrigerant leakage or compressor
overload.
Open condition:
When compressor is active, the value of the Coil
temperature of evaporator T2 has no change or
very little change.
17
Setting fan
speed
Actual fan speed
H+(H+=H+G)
AH(=H)
B
C
M+(M+=M+Z)
DM(M=M)
E
F
L+(L+=L+D)
GL(L=L)
H
I
T1-Td ℃(°F)
L
L-(L-=L-D)
H
H-(H-=H-G)
M
M-(M-=M-Z)
a
b
c
d
T1
e
T4
A+
A
B
C
D
E
a
b
c
d
T1
e
T3
Resume
Off
Decrease
Hold
8.4 Operation Modes and Functions
8.4.1 Fan mode
(1) Outdoor fan and compressor stop.
(2) Temperature setting function is disabled, and
no setting temperature is displayed.
(3) Indoor fan can be set to high/med/low/auto.
(4) The louver operates same as in cooling
mode.
(5) Auto fan:
8.4.2 Cooling Mode
8.4.2.1 Compressor running rules
When T1-Ts<-2℃(28.4°F), the compressor will
stop,
when T1—TS>-0.5℃(31.1°F),the compressor
will be activated.
When the AC run in mute mode, the compressor
will run with low frequency.
When the current is more than setting value, the
current protection function will be activated, and
the compressor will stop.
8.4.2.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed
according to T4.
For different outdoor units, the fan speeds are
different
the speed can be selected as high, medium, low
and auto.
When the setting temp. is reached, if the
compressor stops running, indoor fan motor will
run in Minimum speed or setting speed.
The indoor fan is controlled as below:
The auto fan acts as below rules:
8.4.2.3 Condenser temperature protection
When condenser temperature temp. is more than
setting value, the compressor will stop.
8.4.2.3 Indoor fan running rules
In cooling mode, indoor fan runs all the time and
8.4.2.5 Evaporator temperature protection
When Evaporator temperature temp.is less than
setting value, the compressor will stop
8.4.3 Heating Mode
8.4.3.1 Compressor running rules
When T1-Ts>-ΔT, the compressor will stop,
when T1-T
<ΔT-1.5,the compressor will be on.
S
ΔT is the programmed parameter of temperature
compensation.
18
Setting fan
speed
Actual fan speed
H(=H)
H+(H+=H+G)
M(M=M)
M+(M+=M+Z)
L(L=L)
L+(L+=L+D)
H-(H-=H-G)
M-(M-=M-Z)
L-(L-=L-D)
T1-Td℃
LHM
T4
E
D
C
B
A
A+
T1-Td+¦ ¤T
Resume
Off
Decrease
Hold
When the AC run in mute mode, the compressor
will run with low frequency.
When the current is more than setting value, the
current protection function will be activated and
the compressor will stop.
8.4.3.2 Outdoor fan running rules
The outdoor unit will be run at different fan speed
according to T4.
For different outdoor units, the fan speeds are
different
8.4.3.3 Indoor fan running rules
When the compressor is on, the indoor fan can be
set to high/med/low/auto/mute.
When indoor unit coil temp. is low, the anti-cold air
function will start and indoor fan motor will run at
low speed, the speed can’t be changed, when the
temp. is lower than setting value, the indoor fan
motor will stop.
When the indoor temp reaches the setting temp.,
the compressor will stop, the indoor fan motor will
run at the minimum speed or setting speed. (The
anti-cold air function is valid).
The indoor fan is controlled as below:
8.4.3.4 Defrosting mode
AC will enter the defrosting mode according to the
value of temp. of T3 and the value range of temp.
change of T3 and also the compressor running
time.
During the defrosting mode, the compressor
keeps running, indoor and outdoor motor will
stop, defrost lamp of the indoor unit will be
lighted “.” Will be displayed.
8.4.3.5 Evaporator coil temperature protection
Auto fan action in heating mode:
When evaporator temperature temp. is more than
the setting protection value, the compressor will
stop.
8.4.4 Auto-mode
This mode can be chosen with remote controller
and the setting temperature can be changed
between 17°C(62.6°F) ~30°C(86°F).
In auto mode, the machine will choose cooling,
heating or fan-only mode according to ΔT (ΔT
=T1-Ts).
19
T1-Ts
Cooling
Heating*
Fan only
Heating*: For cooling only models, they will run at
fan speed
Indoor fan will run at auto fan of the relevant mode.
The louver operates same as in relevant mode.
If the machine switches mode between heating
and cooling, the compressor will keep stopping
for certain time and then choose mode according
to T1-Ts.
If the setting temperature is modified, the
machine will choose running function again.
8.4.5 Drying mode
8.4.5.1 Indoor fan speed is fixed at breeze and
can’t be changed. The louver angle is the same
as in cooling mode.
8.4.5.2 Low indoor room temperature protection
In drying mode, if room temperature is lower than
10°C (50°F), the compressor will stop and not
resume until room temperature exceeds 12°C
(53.6°F).
8.4.5.3 Evaporator anti-freezing protection,
condenser high temperature protection and
outdoor unit frequency limit are active and the
same as that in cooling mode.
8.4.5.4 The outdoor fan operates the same as in
cooling mode.
8.4.6 Forced operation function
8.4.6.1 Enter forced operation function:
When the machine is off, pressing the touch
button will carry the machine to forced auto
mode. If pressing the button once again within 5
seconds, the machine will turn into forced cooling
mode.
In forced auto, forced cooling or any other
operation mode, pressing touch button will turn
off the machine.
8.4.6.2 In forced operation mode, all general
protections and remote control are available.
8.4.6.3 Operation rules:
Forced cooling mode:
The compressor runs at F2 frequency and indoor
fan runs as breeze. After running for 30 minutes.
the machine will turn to auto mode as 24°C
(75.2°F) setting temperature.
Forced auto mode:
The action of forced auto mode is the same as
normal auto mode with 24°C (75.2°F) setting
temperature.
8.4.7 Auto-Restart function
The indoor unit is equipped with auto-restart
function, which is carried out through an autorestart module. In case of a sudden power
failure, the module memorizes the setting
conditions before the power failure. The unit will
resume the previous operation setting (not
including swing function) automatically after 3
minutes when power returns.
If the memorization condition is forced cooling
mode, the unit will run in cooling mode for 30
minutes and turn to auto mode as 24°C (75.2°F)
setting temp.
If AC is off before power off and AC is required to
start up now, the compressor will have 1-minute
delay when power on. Other conditions, the
compressor will have 3 minutes delay when
restarts.
8.4.8 Refrigerant Leakage Detection
With this new technology, the display area will
show “EC” when the outdoor unit detects
refrigerant leakage.
8.4.9 8°C Heating(optional)
When the compressor is running, the indoor fan
motor will run without anti-cold air function.
When the compressor is off, the indoor fan motor
is off
20
Enquiry information
Displaying code
Meaning
T1
T1
T1 temp.
T2
T2
T2 temp.
T3
T3
T3 temp.
T4
T4
T4 temp.
T2B
Tb
T2B temp.
TP
TP
TP temp.
TH
TH
TH temp.
Targeted Frequency
FT
Targeted Frequency
Actual Frequency
Fr
Actual Frequency
Indoor fan speed
IF
Indoor fan speed
Outdoor fan speed
OF
Outdoor fan speed
EXV opening angle
LA
EXV opening angle
Compressor continuous running time
CT
Compressor continuous
running time
Causes of compressor stop.
ST
Causes of compressor
stop.
Reserve
A0
Reserve
A1 Reserve
0 Reserve
1 Reserve
2
Reserve
3
Reserve
4
Reserve
5
Reserve
6 Reserve
L Reserve
A Reserve
U Reserve
T
8.4.10 Point check function
Press the LED DISPLAY or LED or MUTE button of the remote controller three times, and then press the
AIR DIRECTION or SWING button three times in ten seconds, the buzzer will keep ring for two seconds.
The air conditioner will enter into the information enquiry status. You can press the LED DISPLAY or AIR
DIRECTION button to check the next or front item’s information.
When the AC enter the “information enquiry” status, it will display the code name in 2 seconds, the details
are as follows.
When the AC enter into the information enquiry status, it will display the code value in the next 25s, the
details are as follows.
21
Enquiry
information
Display value
Meaning
Remark
T1, T2, T3,
T4, T2B, TP,
TH, Targeted
Frequency,
Actual
Frequency
-1F,-1E,-1d,-1c,1b,-1A
-25,-24,-23,-22,-21,20
1. All the displaying temperature is actual
value.
2. All the temperature is °C no matter
what kind of remote controller is used.
5. If the actual value exceeds the range, it
will display the maximum value or minimum
value.
-19—99
-19—99
A0,A1,…A9
100,101,…109
b0,b1,…b9
110,111,…119
c0,c1,…c9
120,121,…129
d0,d1,…d9
130,131,…139
E0,E1,…E9
140,141,…149
F0,F1,…F9
150,151,…159
Indoor fan
speed
/Outdoor fan
speed
0
OFF
1,2,3,4
Low speed, Medium
speed, High speed,
Turbo
For some big capacity motors.
14-FF
Actual fan
speed=Display value
turns to decimal
value and then
multiply 10. The unit
is RPM.
For some small capacity motors,
display value is from 14-FF(hexadecimal),
the corresponding fan speed range is from
200-2550RPM.
EXV opening
angle
0-FF
Actual EXV opening
value=Display value
turns to decimal
value and then
multiply 2.
Compressor
continuous
running time
0-FF
0-255 minutes
If the actual value exceeds the
range, it will display the maximum
value or minimum value.
Causes of
compressor
stop.
0-99
For the detailed
meaning, please
consult with engineer
Decimal display
Reserve
0-FF
22
9. Troubleshooting
Safety
Electricity power is still kept in capacitors even the power supply is shut off. Do not forget to discharge the electricity
power in capacitor.
Electrolytic Capacitors
(HIGH VOLTAGE! CAUTION!)
For other models, please connect discharge resistance (approx.100Ω 40W) or soldering iron (plug) between +, terminals of the electrolytic capacitor on the contrary side of the outdoor PCB.
Note: The picture above is only for reference. The plug of your side may be different.
Loading...
+ 55 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.