SERIES
Klimaire Indoor Unit Model Number KSIR030-H215-I KSIR036-H215-I
Klimaire Outdoor Unit Model Number KSIR030-H215-O KSIR036-H215-O
Power supply V-ph-Hz 208-230/1/60 208-230/1/60
Capacity Btu/h 30000 36000
Power input W 2857 4235
Cooling Rated current A 12,5 18,5
EER Btu/w 10,5 8,5
SEER 18 16
Capacity Btu/h 30000 36000
Power input W 3110 3835
Heating Rated current A 13,5 16,7
COP W/W 2,8 2,8
HSPF 9,6 10
Minimum circuit ampacity (MCA) A 20 25
Max. fuse size A 30 35
Capacity Btu/h 25760 25760
Compressor Input W 2070 2070
Rated current (RLA) A 15 17
Power input W 58 58
Indoor fan motor RLA A 0,5 0,5
Speed (Hi/Med/Lo) rpm 1200/1050/950 1200/1050/750
Indoor air flow (Hi/Med/Lo) cfm 795/618/471 853/647/471
Indoor noise level (Hi/Med/Lo) dB(A) 52/44/35 52/44/36
Dimension (W*D*H) in 49.57x11.10x14.25 49.57x11.10x14.25
Indoor unit Packing (W*D*H) in 52.76x17.72x14.96 52.76x17.72x14.96
SYSTEM
Outdoor fan motor RLA A 0,6 0,6
Outdoor air flow cfm 2530 2943
Outdoor noise level dB(A) 62 63
Outdoor unit Packing (W*D*H) in 42.91x19.69x34.06 42.91x19.69x34.06
Refrigerant type oz R-410A/97.0 R-410A/119.9
Refrigerant precharge ft 25 25
Additional charge for each ft oz 0,322 0,322
Design pressure psig 550/340 550/340
Refrigerant piping Max. refrigerant pipe length ft 164 213
Connection wiring (Stranded, unshielded) AWG 16*4 16*4
Thermostat type Remote Control Remote Control
Operation temperature Outdoor (cooling/heating) - W / O, low ambient cooling ºF 32~122/5~86
Application area (cooling standard) sq ft 1400-1900 1650-2400
Net/Gross weight lb 43.2/55.6 43.2/55.6
Input W 150 150
Speed rpm 810 810
Dimension(W*D*H) in 37.24x16.54x31.89 37.24x16.54x31.89
Net/Gross weight lb 137.79/147.71 143.3/153.22
Liquid side/ Gas side in 3/8"/5/8" 3/8"/5/8"
Max. difference in level ft 82 98
Indoor (cooling/ heating) ºF 62~90/32~86
Outdoor (cooling/heating) - W, low ambient cooling ºF 5~122/5~86
62~90/32~86
32~122/5~86
5~122/5~86
6 in
D
W
H
W
Continued product improvement is our goal at
Klimaire Products, Inc. Hence, specifications and
data listed herein are subject to change without
notice and without obligation on our part. Allways
comply with local, state, and national electrical
codes.
1 - Minimum 10 ft line set recommended.
2 - Outdoor unit being elevated than the indoor
unit oil trap should be installed every 17 ft to 23 ft (
5 to 7 m)
3 - Factory installed only, not field option. Units
may operate in heating and cooling mode until the
ambient conditions reach 5º F
D
H
Eco Friendly
Product Code
K
Brand
K: Klimaire
Product Type
M: Multi-zone Outdoor
Unit Type
I : DC Inverter
S I
Product Series
R
Nominal Capacity
036: 36,000 Btu/h
048: 48,000 Btu/h
H 2 15 A1–036 I
Power Supply
1 : 115 / 60
2 : 208-230 / 1 / 60
Operational Function
H: Heat Pump
C: Cooling Only
–
O: Outdoor Dedicated
I: Indoor Unit
Nominal Efficiency
SEER
Revision & Design
(If any)