Klimaire 13 SEER User Manual

Page 1
INSTALLATION INSTRUCTIONS
13 SEER SERIES
HEAT PUMP & CONDENSING UNITS
1.5-5 Tons
NOTE: Appearance of unit may vary.
RECOGNIZE THIS SYMBOL AS AN INDICATION OF IMPORTANT SAFETY INFORMATION
WARNING
These instructions are intended as an aid to qualified licensed service personnel for proper installation, adjust­ment and operation of this unit. Read these instructions thoroughly before attempting installation or operation. Failure to follow these instructions may result in improper installation, adjustment, service or maintenance possibly resulting in fire, electrical shock, property damage, personal injury or death.
DO NOT DESTROY THIS MANUAL
Please read carefully and keep in a safe place for future reference by a serviceman.
PERFORMANCE
CERT IFIED
ARI Standard 210/240
Unitary Sm allAC
Certification applies onlywhenthe completesystemis listedw ithARI
WWW.aridirectory.org
TM
Page 2
TABLE OF CONTENTS
1.0 SAFETY..................................................................................................................3
1.1 INSPECTION....................................................................................................4
1.2 LIMITATIONS....................................................................................................4
2.0 GENERAL..............................................................................................................4
3.0 UNIT INSTALLATION............................................................................................6
3.1 LOCATION.......................................................................................................6
3.2 GROUND INSTALLATION...............................................................................6
3.3 ROOF INSTALLATION.....................................................................................6
3.4 UNIT PLACEMENT..........................................................................................6
3.5 PRECAUTIONS DURING LINE INSTALLATION.............................................7
3.6 PRECAUTIONS DURING BRAZING OF LINES..............................................8
3.7 PRECAUTIONS DURING BRAZING SERVICE VALVE..................................9
3.8 UNIT MOUNTING...........................................................................................10
3.9 FACTORY-PREFERRED TIE-DOWN METHOD............................................11
3.10 REMOVING THE TOP PANEL AND MOTOR..............................................12
4.0 ELECTRICAL CONNECTIONS...........................................................................13
4.1 GENERAL INFORMATION & GROUNDING .................................................13
4.2 FIELD CONNECTIONS POWER WIRING ....................................................13
5.0 EVACUATION......................................................................................................14
6.0 INTERCONNECTING TUBING............................................................................14
6.1 VAPOR AND LIQUID LINES .........................................................................14
6.2 MAXIMUM LENGTH OF LINES ....................................................................14
6.3 VERTICAL SEPARATION ............................................................................14
7.0 SYSTEM OPERATION........................................................................................16
7.1 COMPRESSOR CRANKCASE HEATER (CCH)...........................................16
7.2 PROTECTION FUNCTION INTRODUCTION...............................................16
8.0 CHECKING REFRIGERANT CHARGE .............................................................16
8.1 CHARGING BY LIQUID PRESSURE............................................................16
8.2 CHARGING BY WEIGHT ..............................................................................17
8.3 FINAL LEAK TESTING .................................................................................17
9.0 INSTRUCTING THE OWNER.............................................................................17
10.0 WIRING DIAGRAM...........................................................................................18
Page 3
CSM18H2P1
M
13 SEER
Page 4
This document is customer property and is to remain with this unit. These instructions do not cover all the different variations of systems nor does it provide for every possible contingency to be met in connection with installa­tion. All phases of this installation must comply with NATIONAL STATE AND LOCAL CODES. If additional information is required please contact your local distribu­tor.
1.0 SAFETY
This is a safety alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
This is an attention alert symbol. When you see this symbol on labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention to the signal words DANGER, WARNING, or CAUTION.
DANGER indicates an imminently hazardous situation, which, if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which, if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if not avoided may result in minor or moderate injury. It is also used to alert against unsafe practices and hazards involving only property damage.
WARNING
Improper installation may create a condition where the operation of the product could cause personal injury or property damage. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to this manual for assistance or for additional information, consult a qualified contractor, installer or service agency.
CAUTION
This product must be installed in strict compliance with the installation instruc­tions and any applicable local, state, and national codes including, but not limited to building, electrical, and mechanical codes.
WARNING
FIRE OR ELECTRICAL HAZARD Failure to follow the safety warnings exactly could result in serious injury, death or property damage. A fire or electrical hazard may result causing property damage, personal injury or loss of life.
3
Page 5
1.1 INSPECTION
As soon as a unit is received, it should be inspected for possible damage during transit. If damage is evident, the extent of the damage should be noted on the carrier's delivery receipt. A separate request for inspection by the carrier's agent should be made in writing. See Local distributor for more information.
Requirements For Installing/Servicing R410A Equipment
Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle the POE or PVE type oils. Manifold sets should be 800 PSIG high side and 250 PSIG low side with 550 PSIG Iow side restart. All hoses must have a 700 PSIG service pressure rating. Leak detectors should be designed to detect refrigerant. Recovery equipment (including refrigerant recovery containers) must be specifi­ cally designed to handle R410A.
Do not use an R-22 TXV.
A liquid-line filter drier is required on every unit. see the Fig.1
NOTE
It will be more convenient to open the Service valve after removing
the Underside Clapboard.
LIQUID SERVICE VALVE
LIQUID-LINE FILTER-DRIER
Fig.1 Filter-Drier insatllation
1.2 LIMITATIONS
The unit should be installed in accordance with all National, State and Local Safety Codes and the limitations listed below:
1.Limitations for the indoor unit, coil and appropriate accessories must also be observed.
2.The outdoor unit must not be installed with any duct work in the air stream. The outdoor fan is the propeller type and is not designed to operate against any additional external static pressure.
3.The maximum and minimum conditions for operation must be observed to assure a system that will give maximum performance with minimum service.
4.This unit is not designed to operate with a low ambient kit. Do not modify the control system to operate with any kind of Iow ambient kit.
5.The maximum allowable line length for this product is 150 feet
Just for Scroll compressor .
2.0 GENERAL
The outdoor units are designed to be connected to a matching indoor coil with sweat connect lines. Sweat connect units are factory charged with refrigerant for a match­ing indoor coil plus 25 feet of field supplied lines.
Matching indoor coils are available with a thermostatic expansion valve or an orifice for the most common usage. The orifice size and/or refrigerant charge may need to be changed for some indoor-outdoor unit combinations, elevation differences or total line lengths.
4
Page 6
]
[
]
[
]
[
]
[
]
L
SERVICE ACCESS
ALLOW 24CLEARANCE
W
AIR DISCHARGE: ALLOW 60 MINIMUM CLEARANCE.
H
AIR INLETS
LOUVERED PANELS ALLOW 18 MINIMUM CLEARANCE
NOTE: GRILL APPEARANCE MAY VARY.
POWER WIRING 1-11/32 (34.5mm)
SERVICE FITTING
LIQUID LINE CONNECTION
FIG.2 DIMENSIONS
VAPOR LINE CONNECTION
DIMENSIONAL DATA
Dimensions (Inches)
Unit Model (Btu/h)
"H" in [mm] "W" in [mm] "L" in[mm
18(cooling unit)
18(heat pump unit) 23-5/8[600] 23-5/8
24 23-5/8[600] 23-5/8 30 28[710] 28[710] 3/8 3/4 36 29-1/8[740] 29-1/8
24-15/16[633] 24-15/16[633]
24-15/16[633] 24-15/16[633] 24-15/16[633]
21-7/8[554] 21-7/8[554] 3/8 3/4
42 29-7/8[759] 28[710] 28[710] 3/8 3/4 48 33-3/16[843] 28[710] 28[710] 3/8 7/8 60 29-1/8[740] 29-1/8
33-3/16[843]
CONTROL WIRING 7/8(22.2mm)
SERVICE FITTING
Refrigerant Connection
Service Valve Size
Liquid in
600 600
740
740
3/8 3/4 3/8 3/4
3/8 3/4
3/8 7/8
Vapor in
5
Page 7
3.0 UNIT INSTALLATION
3.1 LOCATION
Before starting the installation, select and check the suitability of the location for both the indoor and outdoor unit. Observe all limitations and clearance requirements. The outdoor unit must have sufficient clearance for air entrance to the condenser coil, for air discharge and for service access. See Fig.2
NOTE
For multiple unit installations, units must be spaced a minimum of 18 inches apart. (Coil face to coil face.)
If the unit is to be installed on a hot sun exposed roof or a black-topped ground area, the unit should be raised sufficiently above the roof or ground to avoid taking the accumu­lated layer of hot air into the outdoor unit.
Provide an adequate structural support.
3.2 GROUND INSTALLATION
The unit may be installed at ground level on a solid base that will not shift or settle, caus­ing strain on the refrigerant lines and possible leaks. Maintain the clearances shown in Fig.2 and install the unit in a level position.
Normal operating sound levels may be objectionable if the unit is placed directly under windows of certain rooms (bedrooms, study, etc.). Top of unit discharge area must be unrestricted for at least 60 inches above the unit.
WARNING
The outdoor unit should not be installed in an area where mud or ice could cause personal injury.
Elevate the unit sufficiently to prevent any blockage of the air entrances by snow in areas where there will be snow accumulation. Check the local weather bureau for the expected snow accumulation in your area. Isolate the unit from rain gutters to avoid any possible wash out of the foundation.
3.3 ROOF INSTALLATION
When installing units on a roof, the structure must be capable of supporting the total weight of the unit, including a padded frame unit, rails, etc., which should be used to minimize the transmission of sound or vibration into the conditioned space.
3.4 UNIT PLACEMENT
1. Provide a base in the pre-determined location.
2. Remove the shipping carton and inspect for possible damage.
3. Compressor tie-down bolts should remain tightened.
4. Position the unit on the base provided.
6
Page 8
CAUTION
This system uses R410A refrigerant which operates at higher pressure than R-22. No other refrigerant may be used in this system. Gauge sets, hoses, refrigerant containers, and recovery system must be designed to handle R410A. If you are unsure, consult the equipment manufacturer.
The outdoor unit must be connected to the indoor coil using field supplied refrigerant grade copper tubing that is internally clean and dry. Units should be installed only with the tubing sizes for approved system combinations. The charge given is applicable for total tubing lengths up to 25 feet.
NOTE
Using a larger than specified line size could result in oil return problems. Using too small a line will result in loss of capacity and other problems caused by insuf­ficient refrigerant flow. Slope horizontal vapor lines at least 1" every 20 feet toward the outdoor unit to facilitate proper oil return.
3.5 PRECAUTIONS DURING LINE INSTALLATION
1. Install the lines with as few bends as possible. Care must be taken not to damage the couplings or kink the tubing. Use clean hard drawn Copper tubing where no
appreciable amount of bending around obstruction is necessary, if soft copper must be used, care must be taken to avoid sharp bends which may cause a restriction.
2. The lines should be installed so that they will not obstruct service access to the coil,
air handling system or filter.
3. Care must also be taken to isolate the refrigerant lines to minimize noise transmis­sion from the equipment to the structure.
4. The vapor line and liquid line must be insulated with a minimum of 1/2" foam rubber insulation (Armafiex or equivalent). Tape and suspend the refrigerant lines as shown.
DO NOT allow tube metal-to-metal contact. See Fig. 3.
5. Use PVC piping as a conduit for all underground installations as shown in Fig. 4.
Buried lines should be kept as short as possible to minimize the build up of liquid refrigerant in the vapor line during long periods of shutdown.
6. Pack fiberglass insulation and a sealing material such as perma gum around refrig-
erant lines where they penetrate a wall to reduce vibration and to retain some flexi­ bility.
7
Page 9
Sheet Metal Hanger
Insulated Vapor Line
Correct Incorrect
TO POWER SUPPLY
Ta pe
Insulated Liquid Line
Fig.3 Tubing Hanger
Fig.4 Underground Installation
WEATHERPROOF DISCONNECT SWITCH
TO INDOOR BLOWER
TO COIL
Seal opening(s) with permagumor equivalent
NOTE:All outdoor wiring must be weather proof
Fig.5 Typical Installtion
3.6 PRECAUTIONS DURING BRAZING OF LINES
All outdoor unit and evaporator coil connections are copper-to-copper and should be brazed with a phosphorous-copper alloy material such as Silfos-5 or equivalent. DO NOT use soft solder. The outdoor units have reusable service valves on both the liquid and vapor connections. The total system refrigerant charge is retained within the outdoor unit during shipping and installation. The reusable service valves are provided to evacuate and charge per this instruction. Serious service problems can be avoided by taking adequate precautions to assure an internally clean and dry system.
8
Page 10
CAUTION
Dry nitrogen should always be supplied through the tubing while it is being brazed, because the temperature required is high enough to cause oxidation of the copper unless an inert atmosphere is provide. The flow of dry nitrogen should continue until the joint has cooled. Always use a pressure regulator and safety valve to insure that only low pressure dry nitrogen is introduced into the tubing.Only a small flow is necessary to displace air and prevent oxidation.
3.7 PRECAUTIONS DURING BRAZING SERVICE VALVE
Precautions should be taken to prevent heat damage to service valve by wrapping a wet rag around it as shown in Fig. 6. Also, protect all painted surfaces, insulation, during brazing. After brazing cool joint with wet rag.
Valve can be opened by removing the plunger cap and fully inserting a hex wrench into the stem and backing out counter-clockwise until valve stem just touches the cham­fered retaining wall.
Connect the refrigerant lines using the following procedure:
1. Remove the cap and Schrader core from both the liquid and vapor service valve service ports at the outdoor unit. Connect Iow pressure nitrogen to the liquid line service port.
wet rag
2. Braze the liquid line to the liquid valve at the outdoor unit. Be sure to wrap the valve body with a wet rag. Allow the nitrogen to continue flowing. Refer to the Tabular Data Sheet for proper liquid line sizing.
3. Carefully remove the rubber plugs from the evaporator liquid and vapor connections at the indoor coil.
4. Braze the liquid line to the evaporator liquid connection. Nitrogen should be flowing through the evaporator coil.
5. Slide the plastie cap away from the vapor connection at the indoor coil. Braze the vapor line to the evaporator vapor connection. Refer to the Table 1 for proper vapor line sizing.
6. Protect the vapor valve with a wet rag and braze the vapor line connection to the
outdoor unit. The nitrogen flow should be exiting the system from the vapor service port connection. After this connection has cooled, remove the nitrogen source from
the liquid fitting service port.
7. Replace the Schrader core in the liquid and vapor valves.
8. Leak test all refrigerant piping connections including the service port flare caps to be sure they are leak tight. DO NOT OVER TIGHTEN (between 40 and 60 inch -lbs.
maximum).
9. Evacuate the vapor line, evaporator and the liquid line, to 500 microns or less.
service valve
Fig.6 Heat Protection
9
Page 11
Table 1: Refrigerant Connections and Recommended Liquid and Vapor Tube Diameters (ln.)
UNIT LIQUID VAPOR LIQUID (LONG-LINE)
SIZE Tube Diameter Tube Diameter Tube Diameter
18 3/8 3/4 3/8
24 3/8 3/4 3/8
30 3/8 3/4 3/8
36 3/8 3/4 3/8
42 3/8 3/8
48 3/8 3/8
60 3/8 7/8 3/8
10. Replace cap on service ports. Do not remove the flare caps from the service ports except when necessary for servicing the system.
3/4
7/8
CAUTION
Do not connect manifold gauges unless trouble is suspected. Approximately 3/4 ounce of refrigerant will be lost each time a standard manifold gauge is connected.
11. Release the refrigerant charge into the system. Open both the liquid and vapor valves by removing the plunger cap and with an hex wrench back out counter
-clockwise until valve stem just touches the chamfered retaining wall.
12. Replace plunger cap finger tight, then tighten an additional 1/12 turn (1/2 hex flat). Cap must be replaced to prevent leaks.
WARNING
10
Never attempt to repair any brazed connections while the system is under pres­sure. Personal injury could result.
See "System Charge" section for checking and recording system charge.
3.8 UNIT MOUNTING
If elevating the heat pump, either on a flat roof or on a slab, observe the following guidelines.
1.The base pan provided elevates the heat pump 2 above the base pad.
2. If elevating a unit on a flat roof , use 4 ”× 4”(or equivalent) stringers positioned to distribute unit weight evenly and prevent noise and vibration (see fig.7) .
NOTE:Do not block drain openings shown in fig.7.
3. If unit must be elevated because of anticipated snow fall, secure unit and elevating stand such that unit and/or stand will not tip over or fall off. Keep in mind that someone may try to climb on unit. If elevating the heat pump,either on a flat roof or on a slab,observe the following guidelines.
NOTE:Tie down unit if elevated. See in fig.7.
Page 12
BASE PAD (CONCRETE OR OTHER SUITABLE MATERIAL)
BASE PAN (BOTTOM VIEW) DO NOT OBSTRUCT DRAIN HOLES (SHADED)
ELEVATION ABOVE ANTICIPATED SNOW IS NECESSARY
Fig.7 RECOMMENDED ELEVATED INSTALLATION
3.9 FACTORY-PREFERRED TIE-DOWN METHOD
#7 Χ 3/8 screws
1/4”Χ 1-3/4“ Hex Washer Head Concrete Screws (3/16Pilot Hole Needed. Pilot Hole 1/4 deeper
Than The Fastener Embedment)
Fig.8 FACTORY-PREFERRED TIE-DOWN METHOD
REQUIRED PARTS LIST
see detail A
IMPORTANT NOTE:
These instructions are intended as a method to tie-down system to cement slab as a securing procedure for high wind areas. It is recommended to check Local Codes for tie-down methods and protocols.
11
Page 13
Step 1: Prior to installing clear pad of debris. Step 2: Ensure cement pad is level.
IMPORTANT
Then cement pad must be made of HVAC-approved materials and must be the
proper thickness to accommodate fasteners.
Step 3: Center unit onto pad.
Step 4: Fasten (4) L-shaped stainless steel braces onto cabinet base using 1/4” * 1/2”
Hex washer head stainless steel self tapping screws where indicated in detail
Fig.8.
IMPORTANT
Do not use screws longer than indicated 1/4 * 2/3and make sure that the brace
is attached on center of base ban where indicated in Fig.8
Damage will occrue to system. Step 5: Drill 4 holes into cement base ensuring holes are 1//2” dp. Step 6: Assemble unit to cement pad using 1/4* 2 Hex washer head cement
screws make sure not to over tighten.
Step 7:Finish unit assembly process as indicated in installation manual.
DESCRIPTION
1/4”Χ 3/8Hex Washer Head Concrete Screws 1/8”Χ 1-1/2”ΧW(widthofunit+4”) Metal straps 3/8Washers
3.10 REMOVING THE TOP PANEL AND MOTOR
1/2bolt
NOTE:
Dama ge will occur to condenser unit if you remo ve fan bolts prior to cover removal.
QUANTITY
4 4 4
5/16bolts
12
Fig. 9 COVER AND FAN
When motor requires changing follow the steps below: Step 1: Go into electrical panel, disconnect motor power lines.
IMPORTANT NOTE
Disconnect main power to unit. Severe burns and electrical shock will occure if
you do not disconnect main power. Step 2: Remove cover (be careful of motor wires) Step 3: Be sure to place fan cover unit on the ground as indicated in Fig. 9
IMPROTANT NOTE
Do not place or lean fan blades on ground or against surface. Step 4: Remove fan motor by removing 5/16 bolts from cover. Step 5: Remove fan blade from motor by removing 1/2 bolt and place fan on the ground. Step 6: Reverse removal process to reinstall the fan and motor.
IMPROTANT NOTE
When connecting motor wires be sure to check motor direction.
Page 14
4.0 ELECTRICAL CONNECTIONS
4.1 GENERAL INFORMATION & GROUNDING
Check the electrical supply to be sure that it meets the values specified on the unit nameplate and wiring label. Power wiring, control (Iow voltage) wiring, disconnect switches and over current protection must be supplied by the installer. Wire size should be sized per require­ments.
CAUTION
All field wiring must USE COPPER CONDUCTORS ONLY and be in accordance with Local, National Fire, Safety & Electrical Codes. This unit must be grounded with a separate ground wire in accordance with the above codes.
The complete connection diagram and schematic wiring label is located on the inside surface of the unit service access panel and this instruction.
4.2 FIELD CONNECTIONS POWER WIRING
1. Install the proper size weatherproof disconnect switch outdoors and within sight of the unit.
2. Remove the screws at the side of the corner cover. Slide corner cover down and
remove from unit. See Fig. 10.
3. Run power wiring from the disconnect switch to the unit.
4. Route wires from disconnect through power wiring opening provided and into the
unit control box.
CORNER COVER
POWER WIRING
CONTROL
WIRING
Fig.10 Typical Field Wiring
5. Install the proper size time-delay fuses or circuit breaker, and make the power
supply connections.
6. Energize the crankcase heater if equipped to save time by preheating the compres­sor oil while the remaining installation is completed.
NOTE: When changing the motor, remove top cover first.
13
Page 15
5.0 EVACUATION
It will be necessary to evacuate the system to 500 microns or less. If a leak is suspected, leak test with dry nitrogen to locate the leak. Repair the leak and test again. To verify that the system has no leaks, simply close the valve to the vacuum pump suction to isolate the pump and hold the system under vacuum. Watch the micron gauge for a few minutes. If the micron gauge indicates a steady and continuous rise, it's an indication of a leak. If the gauge shows a rise, then levels off after a few minutes and remains fairly constant, its an indication that the system is leak free but still contains moisture and may require further evacuation if the reading is above 500 microns.
6.0 INTERCONNECTING TUBING
6.1 VAPOR AND LIQUID LINES
Keep all lines sealed until connection is made. Make connections at the indoor coil first. Refer to Line Size Information in Tables 2 and 3 for correct size and multipliers to be used to determine capacity for various vapor line diameters and lengths of run. The losses due to the lines being exposed to outdoor conditions are not included. The factory refrigerant charge in the o utdoor unit is sufficient for 25 feet of interconnecting lines. The factory refrigerant charge in the outdoor unit is sufficient for the unit and 25 feet of standard size interconnecting liquid and vapor lines. For different lengths, adjust the charge as indicated below. 1/4”±.3 oz. per foot 5/16”±.4 oz. per foot 3/8”±.6 oz. per foot 1/2”±1.2 oz. per foot
6.2 MAXIMUM LENGTH OF LINES
The maximum length of interconnecting line is 150 feet. Always use the shortest length possible with a minimum number of bends. Additional compressor oil is not required for any length up to 150 feet.
OTE: Excessively long refrigerant lines cause loss of equipment capacity.
N
6.3 VERTICAL SEPARATION
Keep the vertical separation to a minimum. Use the following g installing the unit:
1. DO NOT exceed the vertical separations as indicated on Table 3.
2. It is recommended to use the smallest liquid line size permitted to minimize sys ­em charge which will maximize compressor reliability.
t
3. Table 3
may be used for sizing horizontal runs.
uidelines when
14
Page 16
TABLE 2: SUCTION LINE LENGTH/SIZE VS CAPACITY MULTIPLIER(R410A)
Unit Size
Suction Line Connection Size
Suction Line Run
Feet
1 1/2 Ton 2 Ton 2 1/2 Ton 3 Ton 3 1/2 Ton 4 Ton 5 Ton
3/4" I.D. 3/4" I.D. 3/4" I.D. 3/4" I.D. 3/4" I.D. 7/8" I.D. 7/8" I.D. 5/8 Opt. 5/8 Opt. 5/8 Opt. 5/8 Opt. 5/8 Opt. 3/4 Opt. 7/8 Opt.
3/4* Std. 3/4* Std. 3/4* Std. 3/4* Std. 3/4* Std. 7/8* Std. 1 1/8* Std.
25'
50'
Optional 1.00 1.00 1.00 1.00 1.00 1.00 0.99
Standard 1.00 1.00 1.00 1.00 1.00 1.00 1.00
Optional 0.97 0.97 0.97 0.97 0.98 0.98 0.98
Standard 0.98 0.98 0.98 0.99 0.98 0.98 0.99
100'
150'
Optional 0.94 0.94 0.94 0.94 0.95 0.95 0.94
Standard 0.95 0.95 0.96 0.97 0.97 0.97 0.98
Optional 0.90 0.90 0.90 0.90 0.91 0.92 0.90
Standard 0.92 0.92 0.93 0.96 0.96 0.96 0.97
NOTES:
* Standard size
Using suction line larger than shown in chart will result in poor oil return and is not recommended.
TABLE 3 :LIQUID LINE SIZING (R-410A)
System
Capacity
1 1/2 Ton 3/8"
2 Ton 3/8"
3 Ton
3 1/2 Ton
4 Ton
5 Ton
Line Size
Connection Size
(Inch I.D.)
3/8"2 1/2 Ton
3/8"
3/8"
3/8"
3/8"
Liquid Line Size
Line Size
Compressor
Type
Scroll
Rotary 3/8* 25 30 30 27 24 20
Scroll
Rotary 3/8* 25 30 30 24 20 15
Scroll
Rotary 3/8* 25 30 30 22 17 10
Scroll
Scroll
Scroll
Scroll
Connection And
Line Size
(Inch I.D.)
1/4 25 40 25 9 N/A N/A
5/16 25 50 62 58 53 49
3/8* 25 50 75 72 70 68
1/4 23 N/A N/A N/A N/A N/A
5/16 25 36 29 23 16 9
3/8* 25 50 72 70 68 65
1/4 25 N/A N/A N/A N/A N/A
5/16 25 49 38 27 17 6
3/8* 25 50 68 65 62 58
5/16 25 50 37 22 7 N/A
3/8* 25 50 68 63 58 53
5/16 25 23 4 N/A N/A N/A
3/8* 25 50 43 36 30 24
3/8* 25 46 38 30 22 15
1/2 255056555352
3/8* 25 50 56 44 32 20
1/2 255075817976
25 50 75 100 125 150
Outdoor unit above or below indoor coil
(Heat Pumps Only)
Total Equivalent Length - Feet
Maximum Vertical Separation - Feet
NOTES:
* Standard line size
N/A Application not recommended.
15
Page 17
7.0 SYSTEM OPERATION
7.1 COMPRESSOR CRANKCASE HEATER(CCH)
Refrigerant migration during the off cycle can result in a noisy start up. Add a crank­case heater to minimize refrigeration mirgration, and to help eliminate any start up noise or bearing wash out”.
All heaters are located on the lower half of the compressor shell. Its purpose is to drive refrigerant from the compressor shell during long off cycles, thus preventing damage to the compressor during start-up.
At initial start-up or after extended shutdown periods, make sure the heater is ener­gized for at least 12 hours before the compressor is started. (Disconnect switch on and wall thermostat off.)
7.2 PROTECTION FUNCTION INTRODUCTION
Sensor T3 (condenser pipe temperature) and T4 (outdoor ambient temperature)
When open-circuit, compressor, outdoor fan motor and reverse valve will be OFF. When T4 < 5 ° When T4 > 10.4 °F, compressor will restart.
Discharge temperature protection (Heat pump only)
When discharge temp. > 275 ° When discharge temp. < 194 °F, compressor wi ll restart.
High perssure protection (Heat pump only)
When high pressure > 638 PSIG, compressor and outdoor fan motor will stop. When high pressure < 464 PSIG, compressor and outdoor fan motor will restart (3 minutes delay necessary).
Low pressure protection (Heat pump only)
Low pressure < 21 PSIG, compressor and outdoor fan motor will stop. Low pressure > 44 PSIG, compressor and outdoor fan motor will restart (3 minutes delay necessary).
In stand-by status, the compressor will not start in low pressure protection. Within 30 mins, if 4 protection cycles occurs, system will restore after power cut-down.
F, compressor will stop.
F, compress or will stop.
8.CHECKING REFRIGERANT CHARGE
Charge for all systems should be checked against the Charging Chart inside the access panel cover. IMPORTANT:Do not operate the compressor without charge in system. Addition of R-410A will raise pressures (vapor, liquid and discharge). If adding R-410A raises both vapor pressure and temperature, the unit is over­charged. IMPORTANT: Use industry-approved charging methods to ensure proper system charge.
8.1 CHARGING BY LIQUID PRESSURE
The liquid pressure method is used for charging systems in the cooling and heating mode. The service port on the liquid (small valve) and suction (large valve) is used for this purpose. Verify that the outdoor unit is running and the indoor air mover is delivering the maximum airflow for this system size. Read and record the outdoor ambient tem­perature. Read and record the liquid and suction pressures at the ports on the liquid and suction valves. If refrigerant lines are sized using the nameplate charge, the correct liquid pressure is found at the intersection of the suction pressure and the outdoor ambient.
1. Remove refrigerant charge if the liquid pressure is above the chart value.
2. Add refrigerant charge if the liquid pressure is below the chart value.
16
Page 18
A
8.2 CHARGING BY WEIGHT
For a new installation, evacuation of interconnecting tubing and indoor coil is adequate; otherwise, evacuate the entire system. Note that charge value includes charge required for 15 ft. of standard size interconnecting liquid line. Calculate actual charge required with installed liquid line size and length using: 1/4O.D. = .3 oz./ft. 5/16O.D. = .4 oz./ft 3/8O.D. = .6 oz./ft 1/2O.D. = 1.2 oz./ft With an accurate scale (+/-1 oz.) or volumetric charging device, adjust charge difference between that shown on the unit data plate and that calculated for the new system Installation. if the entire system has been evacuated, add the total calculated charge.
8.3 FINAL LEAK TESTING
After the unit has been properly evacuated and charged, a halogen leak detector should be used to detect leaks in the system. All piping within the condensing unit, evaporator, and interconnecting tubing should be checked for leaks. If a leak is detected, the refrigerant should be recovered before repairing the leak. The Clean Air Act prohibits releasing refrigerant into the atmosphere.
9.0 INSTRUCTING THE OWNER
ssist owner with processing Warranty cards and/or online registration. Review Owners
Guideand providea copytotheowerandguidanceonproperoperationandmainteance.In-
struct the owner or the operator how to start, stop and adjust temperature setting. The installer should instruct the owner on proper operation and maintenance of all other
system components.
9.1 MAINTENANCE
. Dirt should not be allowed to accumulate on the outdoor coils or other parts in the air
1.
circuit. Clean as often as necessary to keep the unit clean. Use a brush, vacuum
cleaner attachment, or other suitable means.
2. The outdoor fan motor is permanently lubricated and does not require periodic oiling.
3. If the coil needs to be cleaned, it should be washed with Calgon Coilclean (mix one
part Coilclean to seven parts water). Allow solution to remain on coil for 30 minutes before rinsing with clean water. Solution should not be permitted to come in contact
with painted surfaces.
4. Refer to the furnace or air handler instructions for filter and blower motor maintenance.
5. The indoor coil and drain pan should be inspected and cleaned regularly to assure
proper drainage.
CAUTION
It is unlawful to knowingly vent, release or discharge refrigerant into the open air during repair, service, maintenance or the final disposal of this unit. When the system is functioning properly and the owner has been fully instructed, secure the owner’s approval.
17
Page 19
10.0 WIRING DIAGRAM
CAUTION
These units must be wired and installed in accordance with all National and
Local Safety Codes.
Lug Plate
CC COMPRESSOR CONTACTOR COMP COMPRESSOR RC 1 RUN CAPACITOR 1 RC 2 RUN CAPACITOR 2
LINE VOLTAGE FACTORY STANDARD FIELD INSTALLED FACTORY
LOW FACTORY STANDARD FIELD INSTALLED FACTORY OPTIONAL USE COPPER CONDUCTORS ONLY WARNING : CABINET MUST BE PERMANMENTLY GROUNDED AND ALL WIRING TO CONFORM TO I.E.C, N.E.C, C.E.C, C.L.C, AND LOCAL CODES AS APPLICABLE REPLACEMENT WIRE MUST BE THE SAME GAUGE AND INSULATION TYPE AS ORIGINALWIRE.
OPTIONAL
VOLTAGE
L1
A1
RC1
T1
CC
A2
L2
BLACK
YELLOW
ORANGE
L1
GND
L1 L2
C Y
THERMOSTAT
C
R
Y
G
Fig.11 Outdoor Unit Wiring Diagram for A/C Systems.
G
R
C
INDOOR UNIT
Fig.12 Control Wiring for A/C Systems.
Y
C
OUTDOOR UNIT
18
Suggestion: When choosing a thermostat, choose K5R-25B or a non-programmable electric thermostat series such as Honeywell (TH5220D). Please refer to thermostat electrical manual for wiring schematic.
Page 20
TABLE 4: Wiring Gauge for A/C Systems
Model(Btu/h)
Input Current Fuse Amps
Outdoor Unit Power Line
Outdoor-Indoor Signal Line
Thermostat Signal Line
Line Quantity
Line Diameter
(AWG )
Line Quantity
Line Diameter
(AWG )
Line Quantity
Line Diameter
(AWG)
18000/24000
15/20
3
2
4
30000/36000 42000 48000/60000
30/30
33
40
3
12
22
2
18
44
4
18
40/50
1014 12
1818 18
1818 18
LINE VOLTAGE FACTORY STANDARD FIELD INSTALLED
OPTIONAL
FACTORY
LOW
VOLTAGE FACTORY STANDARD FIELD INSTALLED FACTORY OPTIONAL USE COPPER CONDUCTORS ONLY WARNING :
CABINET MUST BE PERMANMENTLY GROUNDED AND ALL WIRING TO CONFORM TO
I.E.C, N.E.C, C.E.C, C.L.C, AND LOCAL CODES AS APPLICABLE REPLACEMENT WIRE MUST BE THE SAME GAUGE AND INSULATION TYPE AS ORIGINALWIRE.
CC COMPRESSOR CONTACTOR CCH
CRANKCASE HEATER COMPRESSOR
COMP
DEFROST CONTROL
DFC
AMBIENT TEMPERATURE
T4 T3
PIPE TEMPERATURE
HPC HIGHT PRESSURE CUT-OUT CONTROL
PC LOW PRESSURE CUT-OUT CONTROL
L OFM OUTDOOR FAN MOTOR RC 1 RUN CAPACITOR 1 RC 2 RUN CAPACITOR 2 RV REVER GND GROUND CHASSIS HGS HOT GAS SENSOR
SING VALVE
Lug Plate
21
L1
A1
ORANGE
OFM
CC
YELLOW
A2
22
T1
HPC
HGS
CCH
YELLOW
LPC
CN20
FAN
CN15
L1L2
R
C
C
T4 T3
DFC
C
RV
RV
Y
B
D
Fig.13 Outdoor Unit Wiring Diagram for H/P Systems.
RED
BLACK
YELLOW
BLUE
PURPLE
GND
L1
L2
R
C
Y
B
W2
19
Page 21
W2
B
C
R
Y
G
THERMOSTAT
C
3
w1
RY
C
OUTDOOR UNIT
30000/36000 42000 48000/60000
30/30
33
40
3
12
B
40/50
1014 12
D
R
G
INDOOR UNIT
Fig.14 Control Wiring for H/P Systems.
Suggestion:When choosing a thermostat, choose K5R-25B or a non-programmable electric
thermostat series such as Honeywell (TH5220D). Broken lines means H/P system with electric
heating. Please refer to thermostat electrical manual for wiring schematic.
TABLE 5: Wiring gauge for H/P Systems
Model(Btu/h)
Input Current Fuse Amps
Outdoor Unit Power Line
Line Quantity
Line Diameter
(AWG )
18000/24000
15/20
20
Outdoor-Indoor Signal Line
Thermostat Signal Line
All dimensions are in inches. They are subject to change without notice. Certified dimensions will be provided upon request.
Line Quantity
Line Diameter
(AWG )
Line Quantity
Line Diameter
(AWG)
5
5
55
55
5
18
5
18
1818 18
1818 18
Page 22
TABLE 6:Physical and Electrical Data for A/C Systems.
CRM18C2P13 CSM36C2P13CRM24C2P13 CRM30C2P13
21
Page 23
TABLE 7: Physical and Electrical Data for A/C Systems.
CSM42C2P13 CSM48C2P13 CSM60C2P13
22
Page 24
TABLE 8: Physical and Electrical Data for H/P Systems.
CRM18H2P13 CSM36H2P13CRM24H2P13 CRM30H2P13
23
Page 25
TABLE 9: Physical and Electrical Data for H/P Systems.
CSM42H2P13 CSM48H2P13 CSM60H2P13
24
Page 26
7909 N.W. 54th Street, Miami, FL 33166 USA Phone: +1 (305) 593-8358 - Fax: + 1 (305) 593 8212 e-mail: sales@klimaire.com www.klimaire.com
Loading...