Klemsan POWYS 1110, POWYS 1012, POWYS 1023, POWYS 1120, POWYS 1022 User Manual

1
USER
MANUAL
Energy Analyzer
2
SECTION 1 GENERAL INFORMATION ....................................................... 5
1.1 General Features ................................................................................................... 5
1.2 Poper Use and Safety Conditions ................................................................... 6
1.4 General View&Definitions.................................................................................. 7
1.5 Icons&Leds .............................................................................................................. 8
1.6 Buttons&Their Functions ................................................................................... 8
1.7 Menu Structure ..................................................................................................... 9
1.8 Four Quadrant Representation ......................................................................13
SECTION 2 INSTALLATION .......................................................................14
2.1 Preparation for Installation .............................................................................15
2.2 Mounting ............................................................................................................... 15
2.3 Connection Diagrams ....................................................................................... 15
2.3.1 Connections .........................................................................................................15
2.3.2 Digital Output Connection Diagram .......................................................... .16
2.4 Dimensions (mm) .............................................................................................. 17
SECTION 3 MENUS ....................................................................................18
3.1 Instantaneous Measurements .......................................................................19
3.2 Maximum, Minimum and Demand Values ...............................................19
3.3 Energy Meters (Energy Menu) ......................................................................20
3.4 Prevalue Assignme ............................................................................................21
3.5 Saving Procedure ................................................................................................21
3.6 Counters Menu ....................................................................................................22
3.7 Settings Menu ......................................................................................................23
3.8 Value Changing ...................................................................................................28
3.9 Main Settings (Basic) .........................................................................................28
3.10 Alarm Settings (Alarms)....................................................................................28
3.11 Demand Time Setting (Demand) .................................................................29
3.12 RS485 Setting (RS485) .......................................................................................29
3.13 Digital Output Settings (Dig Out) ................................................................. 30
3.14 Pulse Output Settings (Pulse) .........................................................................30
3.15 Password Settings (Security) ..........................................................................31
3.16 Display Settings (Display) ................................................................................ 31
3.17 Clear Menu (Clear) .............................................................................................. 32
3.18 Confirmation Procedure ..................................................................................33
SECTION 4 RS485 COMMUNICATION ....................................................34
4.1 Applying Multiple Option Settings With Modbus ..................................40
4.2 Status Flags ...........................................................................................................41
SECTION 5 FACTORY PREVALUES AND SETTİNG RANGES ................42
SECTION 6 TECHNICAL SPECIFICATIONS ..............................................47
TABLE OF CONTENTS
3
FIGURES
Fig. 1-1 Connections ........................................................................................................... 7
Fig. 1-2 General view of the device ................................................................................ 7
Fig. 1-3 LCD icon descriptions ......................................................................................... 8
Fig. 1-4 Segment display LED descriptions ................................................................. 8
Fig. 1-5 Four Quadrant Representation ......................................................................13
Fig. 2-1 Connection Diagram ......................................................................................... 16
Fig. 2-2 Digital Output Connection Diagram ( POWYS 10xx ) ............................16
Fig. 2-3 Dimensions ........................................................................................................... 17
Fig. 3-1 Example of instantaneous measurement page (Reactive power) ....19
Fig. 3-2 Example of demand page (Active power) .................................................20
Fig. 3-3 Example of Import Active Energy Meter Display .................................... 21
Fig. 3-4 Save Prosedure ....................................................................................................22
Fig. 3-5 Counters Menu ....................................................................................................23
Fig. 3-6 Alarm Example(Alarm delay is set to be zero) ..........................................29
Fig. 3-7 Confirmation Prosedure ...................................................................................33
TABLES
Table 1-1 Button functions ................................................................................................... 9
Table 1-2 Instantaneous measurements and submenus (LCD devices) ...........10
Table 1-3 Instantaneous measurements and submenus (7-Segment devices) ....11
Table 1-4 Energy, counter, harmonics and settings menus ....................................12
Table 3-1 SETTINGS Menu tree .........................................................................................28
Table 4-1 MODBUS table .................................................................................................... 40
Table 5-1 Factory Prevalu ....................................................................................................46
Table 6-1 Measurement Accuracy....................................................................................49
4
SECTION 1
GENERAL
INFORMATION
Enerji Analizörü
5
SECTION 1 GENERAL INFORMATION
1.1 General Features
POWYS 1xxx series is an energy analyzer designed for single phase systems, measuring the following parametres:
• Voltage
• Current
• Network frequency
• CosØ value
• Power factor
• Active power
• Reactive power
• Apparent power
• THDV
• THDI
• Voltage and current harmonics between 1-31
In addition to the measurement features, it also executes the following functions:
• Import active, export active, import reactive, export reactive energy meters
• Demand values for current, active power, reactive power and apparent power are calculated and stored in its memory.
• Establishes and stores in its memory the maximum and minimum values reached by current, voltage, frequency, cosØ, power factor, THDV, THDI, active, reactive and apparent powers
• Assigns alarms for current, voltage, frequency, cosØ and power factor parameters
• Keeps the on hour, run hour and number of power interruption
• CTR setting that may be entered from 1 to 5000
• VTR setting that may be entered from 0.1 to 5000
• RS485 communication that may be adjusted from 1200 to 57600 baud (POWYS 11xx)
• Communication with MODBUS RTU (POWYS 11xx)
• 2 pulse outputs can be used for high and low alarm outputs(POWYS 10xx)
• Pulse outputs that may be assigned to the energy values as output parametre (POWYS 10xx)
• Unauthorized access protection with 4 digit user password
• Adjustable automatic menu browsing feature
SECTION 1 GENERAL INFORMATION
6
• Adjustable LCD backlight on duration
• Sealable cover
• Low power consumption
• A wide range of feeding and operating temperature
Device model POWYS 1110 POWYS 1012 POWYS 1120 POWYS 1022 POWYS 1023 Order number 606 351 606 354 606 352 606 355 606 356 Connection Rail mount Rail mount Rail mount Rail mount Rail mount Basic
measurements
Minimum­maximum value storage
Demand measurements
LCD - -
7-segment displays and leds
- -
Alarm definition
RS485 communication
-
- -
Digital output that may be assigned to pulse or alarms
- 2 pcs
2 pcs 2 pcs
1.2 Poper Use and Safety Conditions
• Installation and connections should be established in accordance with the instructions set out in the manual by authorized persons. Unless the connection is built properly,
device should not be operated.
• Before wiring the device up, make sure that energy is cut o
• Do not disconnect the POWYS current transformer connection before short circuiting the k-1 tips of the current transformer somewhere else. Otherwise, dangerous high voltages may emerge at the secondary tips of the current transformer.
• Use a dry cloth to remove the dust from the device/clean the device. Avoid using alcohol, thinner or a corrosive material.
• Device should be engaged only after all the connections are made.
• Do not open the inside of the device. There are no parts which the users can intervene inside.
SECTION 1 GENERAL INFORMATION
7
• Device should be kept away from humid, wet, vibrant and dusty environments.
• It is recommended to connect a breaker or automatic fuse (2 amper) between the voltage inputs of the device and the network.
The manufacturing company may not be kept responsible for unfavorable incidents that arise out of the failure to follow the above cautions.
1.3 Connection Types
POWYS 1110 POWYS 1120
POWYS 1012 POWYS 1022
POWYS 1023
Fig. 1-1 Connections
1.4 General View&Definitions
Supply terminal
Output terminals
RS485 terminals or
Digital output terminals
Display
LCD or 7-Segment
Display group
Status LEDs
(Vaild for 7-Segment models
Buons
Current input terminals Voltage input terminals
Fig. 1-2 General view of the device
SECTION 1 GENERAL INFORMATION
8
1.5 Icons&Leds
The descriptions of the icons appearing on the display of the devices with LCD are provided as follows:
Imp
activated when the import meters are shown
Exp
activated when the reactive meters are shown
act
activated when the active meters are shown
rea
activated when the reactive meters are shown
run
activated when the total run hour is shown
on
activated when the total on hour is shown
int
activated when the total number of power interruptions is shown
max
activated when the maximum values are shown
min
activated when the minimum values are shown
demand
activated when the demand values are shown
kVArh
unit of the reactive meters
kWh
unit of the active meters
activated when giving pulse from the 1st pulse output
activated when giving pulse from the 2nd pulse output
activated during RS485 communication
activated if the value shown is inductive
activated if the value shown is capacitive
1
2
Fig. 1-3 LCD icon descriptions
For 7-segment display devices, the ash status of LEDs located in the upper part of the display is described as below:
k
shows that value written on the display is divided into 1000
M
shows that value written on the display is divided into 1000000
if the value shown is capacitive, it gets activated
shows that at least 1 alarm is present
activated when giving a pulse from any one of the pulse outputs
activated during RS485 communication
Fig. 1-4 Segment display LED descriptions
1.6 Buttons&Their Functions
The buttons valid on the front panel and their functions are described on the following table:
SECTION 1 GENERAL INFORMATION
9
In the MEASUREMENTS
menus
In the ENERGY, COUNTER,
HARMONICS, SETTINGS
menus
ASSIGNING PRE VALUES TO THE
METERS
CHANGE SETTINGS
SHORT PRESSING ( t < 2sec )
LONG PRESSING ( t > 2sec )
SHORT PRESSING ( t < 2sec )
LONG PRESSING
( t > 2sec )
SHORT PRESSING ( t < 2sec )
LONG PRESSING ( t > 2sec )
SHORT PRESSING ( t < 2sec )
LONG PRESSING ( t > 2sec )
RIGHT
Switches between
menus
Skips
to the
"ENERGY"
menu
Switches
to the
submenu
Skips to the
menu at the
bottom
Changes
the active
digit
Activates changing
value
Activates changing
value or
changes
the
active
step
No eect
DOWN
Switches between
menus
No eect
Switches between
menus
No eect
Changes
value
No eect
Changes
value
No eect
UP
Switches between
menus
No eect
Switches between
menus
No eect
Changes
value
No eect
Changes
value
No eect
LEFT
Switches between
menus
Skips
to the
homepage
Switches between
menus
Skips to the most recent menu in the
measurements
menu
Stops changing value and
confirms
the value
entered
No eect
Stops
changing
value
and
confirms
the value
entered
No eect
Table 1-1 Button functions
1.7 Menu Structure
Instantaneous measurement menus and the menus showing their related maximum, minimum and demand values are provided in the following table. As provided in the table, down, up, right and left handside buttons provide menu switches.
SECTION 1 GENERAL INFORMATION
10
menu max min demand
VOLTAGE max min
CURRENT max min demand
FREQ max min
COSQ max min
PF max min
POWER P max min demand
POWER Q max min demand
POWER S max min demand
THD V max min
THD I max min
Table 1-2 Instantaneous measurements and submenus (LCD devices)
SECTION 1 GENERAL INFORMATION
11
menu max min demand
Uolt H - U L - U
Curr H - I L - I d - I
FrEq H - F L - F
coSQ H - co. L - co.
PF H - PF L - PF
Act H - Ac. L - Ac. d - Ac.
rEA H - rE. L - rE. d - rE.
APr H - AP L - AP d - AP
tHdU H - t.U L - t.U
tHdI H - t.I L - t.I
Table 1-3 Instantaneous measurements and submenus (7-Segment devices)
Energy meters, counters, odd harmonics between 1-31 and menus showing the settings
are provided in the following table. As provided in the table, down, up, right and left
handside buttons provide menu switches.
SECTION 1 GENERAL INFORMATION
12
ENERGY
IMPORT ACTIVE
EXPORT ACTIVE
IMPORT REACTIVE
EXPORT REACTIVE
COUNTERS
RUN HOUR
ON HOUR
POWER INT. COUNTER
HARMONICS
V HARM
V HARM 1
V HARM 3
.
.
V HARM 31
I HARM
I HARM 1
I HARM 3
.
.
I HARM 31
SETTINGS (SETTINGS MENU TREE)
Table 1-4 Energy, counter, harmonics and settings menus
SECTION 1 GENERAL INFORMATION
13
1.8 Four Quadrant Representation
The angle(Ø) between voltage and current provides us information about the direction of energy ow. A positive sign for active/reactive power indicates that active/reactive power is consumed. And also a negative sign for active/reactive power indicates that active/reactive power is generated.
Meters
Imp. Active & Imp. Reactive
Active Power
Reactive Power
Meters
Exp. Active & Imp. Reactive
QUADRANT -1
P => positive Q => positive & inductive CosØ => inductive PF => positive
QUADRANT -2
P => negative Q => positive & capacitive CosØ => capacitive PF => negative
Meters
Imp. Active & Exp. Reactive
Meters
Exp. Active & Exp. Reactive
QUADRANT -4
P => positive Q => negative & capacitive CosØ => capacitive PF => positive
QUADRANT -3
P => negative Q => negative & inductive CosØ => inductive PF => negative
S
P
Q
Fig. 1-5 Four Quadrant Representation
NOTE: If the signs of active and reactive power are examined, it can be defined the quadrant that POWYS measures.
In order to understand P and Q signs in POWYS 10xx and POWYS 11xx, instantaneous displays for P and Q must be checked. If active power display is seem constantly, it means active power(P) is positive. If it is blinked, it means active power(P) is negative. If reactive power(Q) display is seem constantly, it means reactive power(Q) is positive. If it is blinked, it means reactive power(Q) is negative.
NOTE: Signs of P and Q can be reached through modbus communication.
e.g.; P= +10kW, Q= +5kVAr => Quadrant-1
P= -10kW, Q= +5kVAr => Quadrant
-2
P= -10kW, Q= -5kVAr => Quadrant
-3
P= +10kW, Q= -5kVAr => Quadrant
-4
SECTION 1 GENERAL INFORMATION
14
SECTION 2
INSTALLATION
Energy Analyzer
15
SECTION 2 INSTALLATION
SECTION 2 INSTALLATION
2.1 Preparing for Installation
The purchased product may not include all hardware options referred in this document. This situation does not constitute an impediment to the electrical installation.
Assembly and related connections of the product, must be implemented by authorized persons in accordance with the instructions of user manual.
The device must not be put into service if the operator is not sure that all connections are correctly accomplished.
2.2 Mounting
POWYS 10xx and POWYS 11xx are replaced onto 35mm standart rail.
Before wiring up voltage and current ends to POWYS, you must be sure that the power is cut.
The product is connected to current transformer(s). Before disconnecting current transformer leads, be sure that they are short circuited elsewhere or connected to a parallel load which has suiciently low impedance. Otherwise dangerously high voltages will be induced at the current transformer leads. Same phenomena also apply for putting into service.
2.3 Connection Diagrams
2.3.1 Connections
POWYS 10xx and POWYS 11xx are replaced onto 35mm standart rail.
Loading...
+ 35 hidden pages