Klein Tools MM720 is an automatically ranging true root mean square
(TRMS) digital multimeter that measures AC/DC voltage, AC/DC current,
and resistance. It can also measure temperature, capacitance, frequency,
duty-cycle, test diodes and continuity. It features a high visibility, reverse
contrast LCD display with an optical sensor to automatically optimize
viewability in dark or bright ambient lighting.
• Environment:
• Operating Altitude: 6562 ft. (2000m)
• Relative Humidity: <90% non-condensing
• Operating Temp: 14°F to 122°F (-10°C to 50°C)
• Storage Temp: -4°F to 140°F (-30°C to 60°C)
• Accuracy: Values stated at 65°F to 83°F (18°C to 28°C)
• Temp Coef cient: 0.1 x (Quoted Accuracy) per °C above 28°C
or below 18°C, corrections are required when ambient working
temp is outside of Accuracy Temp range
• Standards: Conforms to: UL STD 61010-1, 61010-2-030,
61010-2-033.
Certified to: CSA STD C22.2 # 61010-1,
61010-2-030, 61010-2-033.
EC EN 61010-1, 61010-2-030,
61010-2-033, 61326-1.
• Pollution degree: 2
• Accuracy: ± (% of reading + # of least significant digits)
• Drop Protection: 6.6 ft. (2m)
• Ingress Protection: IP42 (see WARNINGS)
• Safety Rating:
Double insulation
Indoor. DO NOT expose to moisture, rain, or snow.
CAT IV 600V, CAT III 1000V, Class 2,
CAT III: Measurement category III is applicable to test and
measuring circuits connected to the distribution part of the
building’s low-voltage MAINS installation.
CAT IV: Measurement category IV is applicable to test and
measuring circuits connected at the source of the building’s lowvoltage MAINS installation.
• Electromagnetic Environment: IEC EN 61326-1. This
equipment meets requirements for use in basic and controlled
electromagnetic environments like residential properties,
business premises, and light-industrial locations.
Input Impedance: 10MΩ
Frequency Range: 50 to 400Hz
Maximum Input: 1000V AC RMS or 1000V DC
600.0V100mV
1000V1V
600.0mV0.1mV
60.00V10mV
600.0V100mV
1000V1V
±(1.0% + 3 digits)60.00V10mV
±(1.2% + 5 digits)
±(0.5% + 5 digits)6.000V1mV
±(0.8% + 3 digits)
±(1.0% + 3 digits)
CURRENT (AUTO-RANGING)
600.0μA0.1μA
6000μA1μA
AC Current
(μA and mA)
DC Current
(μA and mA)
Overload Protection: 800mA/1000V and 10A/1000V fuses
Frequency Range: 50 to 400Hz
Maximum Input: µA/mA setting: 600mA AC RMS / DC10A setting: 10A AC RMS / DC
To ensure safe operation and service of the meter, follow these
instructions. Failure to observe these warnings can result in
severe injury or death.
• Before each use verify meter operation by measuring a known
voltage or current.
• Never use the meter on a circuit with voltages that exceed the
category based rating of this meter.
• Do not use the meter during electrical storms or in wet weather.
• Do not use the meter or test leads if they appear to be damaged.
• Use only with CAT IV rated test leads.
• Ensure meter leads are fully seated, and keep fingers away
from the metal probe contacts when making measurements.
• Do not open the meter to replace batteries while the probes
are connected.
• Use caution when working with voltages above 25V AC RMS
or 60V DC. Such voltages pose a shock hazard.
• To avoid false readings that can lead to electrical shock,
replace batteries when a low battery indicator appears.
• Do not attempt to measure resistance or continuity on a live
circuit.
• Always adhere to local and national safety codes. Use personal
protective equipment to prevent shock and arc blast injury
where hazardous live conductors are exposed.
• Meter is IP42 dust & water resistant. Following any contact
with water, thoroughly dry meter and test lead jacks prior to
subsequent use.
To Power ON the meter rotate the Function Selector switch 2 from
the OFF setting to any measurement setting. To Power OFF the meter
rotate the Function Selector switch 2 to the OFF setting. By default
the meter will automatically Power OFF after 5 minutes of inactivity.
Reactivate meter by pressing any button. To deactivate the automatic
Power OFF feature, power the meter ON with the SEL button
depressed. When automatic Power OFF is deactivated, the
symbol will not be visible in the display.
When the Function Selector switch is rotated to a measurement
setting, "LEAD" flashes on the display as a reminder to check that test
leads are inserted into the appropriate jacks.
"SEL" (SELECT) BUTTON (FOR SECONDARY FUNCTIONS)
The "SEL" button11activates the secondary functions for each
setting accessible by the Function Selector switch 2. For Current,
Voltage and Low Z, it toggles between AC and DC. For the other
functions, it switches between Continuity, Resistance, Diode-test,
and Capacitance. The default function for each application is printed
on the meter in white; the secondary functions are printed on the
meter in orange.
"HOLD" (DATA HOLD) / BACKLIGHT BUTTON
Press HOLD 10 to hold the measurement on the display. Press
again to release the display to return to live measuring.
Press and hold the "HOLD" button 10 for more than one second
second to manually adjust the backlight. Meter default is automatic
control of backlight based upon an optical sensor. The long presses
will scroll between high backlight, low backlight, and back to
automatic control. In automatic backlight mode, the "A" and
icons will be displayed. For manual backlight mode, the "M" and
icons will be displayed
11
"RANGE" BUTTON
The meter defaults to auto-ranging measurement mode . This
automatically determines the most appropriate measurement range
for the testing that is being conducted. To manually force the meter
to measure in a different range, use the "RANGE" button 7.
1. Press the "RANGE" button 7 to manually select measurement
range ( is deactivated on the LCD). Repeatedly press
the "RANGE" button 7 to cycle through the available ranges,
stopping once the desired range is reached.
2. To return to auto-ranging mode, press and hold the "RANGE"
button 7 for more than one second ( is reactivated).
Relative measurements are available for Voltage, Current,
Resistance, Temperature, Capacitance and LoZ.
1. Perform first measurement.
2. With test leads connected, press REL 8 to set frame of reference.
3. Perform second measurement. The value displayed is the
difference between first and second measurements.
"MAX/MIN" BUTTON
When the "MAX/MIN" button
of the minimum and maximum value of the measurement as the
meter continues to take samples.
1. When measuring, press MAX/MIN
maximum value. If a new maximum occurs, the display updates
with that new value. Pressing again reveals the minimum value.
If a new minimum occurs, the display updates with the new
value.
Do not test if leads are improperly seated. Results could cause
intermittent display readings. To ensure proper connection, firmly
press leads into the input jack completely.
INCORRECT
CORRECT
TESTING IN CAT III / CAT IV MEASUREMENT LOCATIONS
Ensure the test lead shield is pressed firmly in place. Failure to use
the CAT III / CAT IV shield increases arc-flash risk.
5/32"
(4 mm)
TESTING IN CAT II MEASUREMENT LOCATIONS
CAT III / CAT IV shields may be removed for CAT II locations. This
will allow testing on recessed conductors such as standard wall
outlets. Take care not to lose the shields.
NOTE: The meter defaults to AC measurement. To measure DC, press
the "SEL" button
to toggle between AC and DC modes. The AC or
11
DC icon on the LCD indicates which mode is selected.
Red leadBlack lead
2. Apply test leads to the circuit to be tested to measure voltage.
The meter will auto-range to display the measurement in the
most appropriate range.
NOTE: The hazardous voltage indicator will appear for voltages >30V.
NOTE: If "–" appears on the LCD, the test leads are being applied to
the circuit in reverse. Swap the position of the leads to correct this.
NOTE: When in a voltage setting and the test leads are open,
readings of order mV may appear on the display. This is noise and
is normal. By touching the test leads together to close the circuit
the meter will measure zero volts.
AC/DC LO Z VOLTAGE (LESS THAN 600V)
Voltage measurements in Low Impedance (Lo Z) setting can be used
to identify ghost or stray voltages.
• Follow same procedure for measuring AC/DC Voltage (see above)
with Function Selector switch
in the Lo Z setting.
2
Red leadBlack lead
DO NOT attempt to measure voltages greater than 600V in
2. To measure current: Remove power from circuit, open circuit at
measurement point, connect meter in-series in the circuit using
the test leads, and apply power to circuit.The meter will autorange to display the measurement in the most appropriate range.
Do not attempt to measure more than 10A.
When measuring currents greater than 6A, a measurement
time of 30 seconds followed by 10 minutes of recovery time
is recommended.
CONTINUITY
1. Insert RED test lead into VΩ jack
,
into COM jack
and rotate function selector switch 2 to the
4
Continuity/Resistance/Diode/Capacitance
, and BLACK test lead
5
setting.
NOTE: The meter defaults to Continuity testing in this mode. Ensure
that the Continuity Testing icon
press the "SEL" button
11
is visible on the display. If not,
until the icon appears.
2. Remove power from circuit.
3. Test for continuity by connecting conductor or circuit with test
leads. If resistance is measured less than 50Ω, an audible signal
will sound and display will show a resistance value indicating
continuity. If circuit is open, display will show "OL".
Red leadBlack lead
DO NOT attempt to measure continuity on a live circuit.
RESISTANCE MEASUREMENTS
1. Insert RED test lead into VΩ jack
into COM jack
,
and rotate function selector switch 2 to the
4
Continuity/Resistance/Diode/Capacitance
, and BLACK test lead
5
setting.
NOTE: The meter defaults to Continuity testing in this mode. To
enter Resistance testing mode, press the "SEL" button
once.
11
2. Remove power from circuit.
3. Measure resistance by connecting test leads to circuit. The
meter will auto-range to display the measurement in the most
appropriate range.
NOTE: When in a Resistance setting and the test leads are open
(not connected across a resistor), or when a failed resistor is under
test, the display will indicate O.L. This is normal.
DO NOT attempt to measure resistance on a live circuit.
DIODE TEST
1. Insert RED test lead into VΩ jack
into COM jack
Continuity/Resistance/Diode/Capacitance
,
and rotate function selector switch 2 to the
4
, and BLACK test lead
5
setting.
NOTE: The meter defaults to Continuity testing in this mode. To
enter Diode testing mode, press the "SEL" button
Diode icon
2. Touch test leads to diode. A reading of 200-700mV on display
indicates forward bias, "OL" indicates reverse bias. An open
device will show "OL" in both polarities. A shorted device will
show approximately 0mV.
1. Insert K-type thermocouple with adapter into the VΩ
jacks (observe polarity markings on thermocouple and meter), and
rotate function selector switch 2 to the Temperature setting.
and COM
5
4
NOTE: The meter defaults to Fahrenheit scale in this mode. To enter
Celsius scale, press the "SEL" button 11 once. Ensure that the
appropriate icon (either °F or °C) appears on the display.
2. To measure temperature, make contact between the
thermocouple tip and the object being measured. When
thermocouple tip and object are in thermal equilibrium, the
measurement on the display will stabilize. The meter will auto-
range to display the measurement in the most appropriate range.
K-Type
Thermocouple
Remove thermocouple before switching meter to other
measurement functions.
The thermocouple included with the original purchase
is suitable for temperatures below 356°F / 180°C only. To
measure higher temperatures, a K-type thermocouple
with the appropriate measurement range should be used.
Be sure meter is turned off and wipe with a clean, dry lint-free
cloth.
Do not use abrasive cleaners or solvents.
STORAGE
Remove the batteries when meter is not in use for a prolonged
period of time. Do not expose to high temperatures or
humidity. After a period of storage in extreme conditions
exceeding the limits mentioned in the General Specifications
section, allow the meter to return to normal operating
conditions before using.
FCC & IC COMPLIANCE
for FCC compliance information.
Canada ICES-003 (B) / NMB-003 (B)
WARRANTY
DISPOSAL / RECYCLE
Do not place equipment and its accessories in the trash.
Items must be properly disposed of in accordance with local
regulations. Please see www.epa.gov/recycle for additional
information.