KitchenAid KIRD862VSS0, KIRD861VSS1, KIRD861VSS0, KIRD801VSS0 Owner’s Manual

Kitchen_kid _
30" (76.2 CM) AND 36" (91.4 CM)
RETRACTABLE (POP-UP) DOWNDRAFT VENT
SYSTEM
SYSTEME DE VENTILATION RETRACTABLE
(CLAPET) DE 30"(76,2 CM) ET 36"(91,4 CM) -
ASPIRATION PAR LEBAS
Table of Contents/Table des matieres ............................................................................. 2
FOR RESiDENTiAL USE ONLY.
iMPORTANT : LIRE ET CONSERVER CES iNSTRUCTiONS.
POUR UTILISATION RESIDENTIELLE UNIQUEMENT.
W10187117B
TABLEOF CONTENTS
TABLE DES MATIERES
VENT SYSTEM SAFETY ................................................................. 3
INSTALLATION REQUIREMENTS ................................................ 4
Tools and Parts ............................................................................ 4
Location Requirements ................................................................ 4
Electrical Requirements ............................................................... 7
Venting Requirements .................................................................. 7
INSTALLATION INSTRUCTIONS
INTERIOR-MOUNTED VENT MOTOR .......................................... 8
Venting Methods - Interior Mounted Vent Motor Only ................ 8
Install Vent System ....................................................................... 9
Complete Installation ................................................................. 13
Make Electrical Connections ..................................................... 13
Check Operation ........................................................................ 14
INSTALLATION INSTRUCTIONS
EXTERIOR-MOUNTED VENT MOTOR ....................................... 15
Venting Methods ........................................................................ 15
Install Vent System ..................................................................... 16
Electrical Connection ................................................................. 17
Complete Installation ................................................................. 18
VENT SYSTEM USE ..................................................................... 19
Operating Downdraft Vent ......................................................... 19
VENT SYSTEM CARE .................................................................. 19
Surface of Downdraft Vent ......................................................... 19
Filters .......................................................................................... 19
WIRING DIAGRAM ....................................................................... 20
ASSISTANCE OR SERVICE ......................................................... 21
WAR RANTY .................................................................................. 22
SECURITE DU SYSTEME DE VENTILATION ............................ 23
EXIGENCES D'INSTALLATION ................................................... 25
Outillage et pieces ...................................................................... 25
Exigences d'emplacement ......................................................... 25
Specifications electriques .......................................................... 28
Exigences concernant I'evacuation ........................................... 28
INSTRUCTIONS D'INSTALLATION
VENTILATEUR MONTE .&L'INTERIEUR .................................... 29
M6thodes d'extraction - Seulement pour un
ventilateur monte a I'interieur ..................................................... 29
Installation du systeme d'extraction .......................................... 30
Achever I'installation .................................................................. 34
Raccordements electriques ....................................................... 34
Contr61e du fonctionnement ...................................................... 35
INSTRUCTIONS D'INSTALLATION
VENTILATEUR MONTE .&L'EXTERIEUR ................................... 36
M6thodes d'extraction ............................................................... 36
Installation du systeme d'extraction .......................................... 37
Raccordement electrique ........................................................... 38
Achever I'installation .................................................................. 39
UTILISATION DU SYSTF:ME D'EXTRACTION ........................... 40
Utilisation du systeme d'extraction ............................................ 40
ENTRETIEN DU SYSTF:ME .......................................................... 40
Surface de I'appareil .................................................................. 40
Filtres .......................................................................................... 40
SCHI_MA DE C.&,BLAGE............................................................... 41
ASSISTANCE OU SERVICE ......................................................... 42
GARANTIE ..................................................................................... 43
2
VENT SYSTEM SAFETY
Your safety and the safety of others are very important.
We have provided many important safety messages in this manual and on your appliance. Always read and obey all safety
messages.
This is the safety alert symbol. This symbol alerts you to potential hazards that can kill or hurt you and others.
All safety messages will follow the safety alert symbol and either the word "DANGER" or "WARNING."
These words mean:
You can be killed or seriously injured if you don't immediately
follow instructions.
You can be killed or seriously injured if you don't follow instructions.
All safety messages will tell you what the potential hazard is, tell you how to reduce the chance of injury, and tell you what can happen if the instructions are not followed.
IMPORTANT SAFETY INSTRUCTIONS
WARNING: TO REDUCE THE RISK OF FIRE, ELECTRIC
SHOCK, OR INJURY TO PERSONS, OBSERVE THE FOLLOWING:
m Use this unit only in the manner intended by the
manufacturer. If you have questions, contact the manufacturer.
m Before servicing or cleaning the unit, switch power off at
service panel and lock the service disconnecting means to prevent power from being switched on accidentally. When
the service disconnecting means cannot be locked, securely fasten a prominent warning device, such as a tag,
to the service panel.
m Installation work and electrical wiring must be done by
qualified person(s) in accordance with all applicable codes and standards, including fire-rated construction.
m Sufficient air is needed for proper combustion and
exhausting of gases through the flue (chimney) of fuel burning equipment to prevent backdrafting. Follow the
heating equipment manufacturer's guideline and safety
standards such as those published by the National Fire
Protection Association (NFPA), the American Society for Heating, Refrigeration and Air Conditioning Engineers (ASHRAE), and the local code authorities.
m When cutting or drilling into wall or ceiling; do not damage
electrical wiring and other utilities.
m Ducted fans must always be vented outdoors.
CAUTION: For general ventilating use only. Do not use
to exhaust hazardous or explosive materials and vapors.
CAUTION: To reduce risk of fire and to properly exhaust
air, be sure to duct air outside - do not vent exhaust air into spaces within walls or ceilings, attics or into crawl spaces,
or garages.
WARNING: TO REDUCE THE RISK OF FIRE, USE ONLY
METAL DUCTWORK.
WARNING: TO REDUCE THE RISK OF A RANGE TOP
GREASE FIRE:
m Never leave surface units unattended at high settings.
Boilovers cause smoking and greasy spillovers that may ignite. Heat oils slowly on low or medium settings.
[] Always turn hood ON when cooking at high heat or when
flambeing food (i.e. Crepes Suzette, Cherries Jubilee,
Peppercorn Beef Flamb6).
[] Clean ventilating fans frequently. Grease should not be
allowed to accumulate on fan or filter.
[] Use proper pan size. Always use cookware appropriate for
the size of the surface element.
WARNING: TO REDUCE THE RISK OF INJURY TO
PERSONS IN THE EVENT OF A RANGE TOP GREASE FIRE, OBSERVE THE FOLLOWING: a
[] SMOTHER FLAMES with a close fitting lid, cookie sheet, or
metal tray, then turn off the burner. BE CAREFUL TO PREVENT BURNS. If the flames do not go out immediately, EVACUATE AND CALL THE FIRE
DEPARTMENT.
[] NEVER PICK UP A FLAMING PAN - you may be burned. [] DO NOT USE WATER, including wet dishcloths or towels -
a violent steam explosion will result.
[] Use an extinguisher ONLY if:
- You know you have a class ABC extinguisher, and you already know how to operate it.
- The fire is small and contained in the area where it started.
- The fire department is being called.
- You can fight the fire with your back to an exit.
aBased on "Kitchen Fire Safety Tips" published by NFPA.
SAVE THESE INSTRUCTIONS
INSTALLATION REQUIREMENTS
Gather the required tools and parts before starting installation. Read and follow the instructions provided with any tools listed
here.
Tools Needed
Jigsaw or keyhole saw
Drill
1/8"(3 mm) drill bit for pilot holes
Pencil
Tape measure or ruler
Flat-blade screwdriver
Phillips screwdriver
3/8"(9.5 mm) nut driver or ratchet
Level
Pliers
Metal snips
Wire stripper or utility knife
Caulking gun and weatherproof caulking compound
Vent clamps
Parts Supplied
C E
A. Top trim (1)
B.End caps (2) C. Overcounter support brackets (2) D. Lower support legs (2)
E. Undercounter mounting brackets (2)
Other Parts Supplied
Bag of fasteners (1)
Metal cover (1)
Optional support and 2 screws (36" [91.4 cm] models only)
6" diameter backdraft damper
Parts Needed
Two UL listed or CSA approved 1/2"(12.7 mm) conduit connectors (Three are required if the exterior-mounted vent motor is used.)
Wall cap for interior-mounted motor (1)
Vent system
Home power supply cable
Wiring cable for optional remote blower kit
UL listed wire connectors (4)
NOTE: Downdraft vent is installed directly behind the cooktop. Install the downdraft vent first, then install the cooktop.
IMPORTANT: Observe all governing codes and ordinances.
Have a qualified technician install the downdraft vent. It is the installer's responsibility to comply with installation clearances specified on the model/serial rating plate. The model/serial rating plate is located on the front of the downdraft vent
above the terminal box cover.
Downdraft vent location should be away from strong draft areas, such as windows, doors, and strong heating vents or
fans.
Cabinet opening dimensions that are shown must be used. Given dimensions provide minimum clearance.
Consult the cooktop manufacturer installation instructions before making any cutouts.
Check that the downdraft vent and cooktop location will clear the cabinet walls, backsplash, and rear wall studs
inside the cabinet. Check for the minimum distance between the front edge
of the countertop and the front edge of the cooktop. The minimum horizontal distance between the overhead
cabinets is the same as the width of the installed downdraft vent.
All openings in ceiling and wall where the downdraft vent will be installed must be sealed.
Grounded electrical outlet is required. See "Electrical Requirements" section.
When installing the downdraft vent, the cabinet drawer will need to be removed and the drawer front installed
permanently to the cabinet.
Cabinet Construction:
Downdraft vent is designed for use in a cabinet with a depth of 24" (61 cm). Some installations require a countertop deeper than 25" (63.5 cm). See the Countertop Cutout Dimensions section.
The maximum depth of the overhead cabinet is 13" (33 cm).
Overhead cabinets installed at either side of the downdraft vent must be 18" (45.7 cm) above the cooking surface.
For Mobile Home Installations
The installation of this range hood must conform to the
Manufactured Home Construction Safety Standards, Title 24 CFR, Part 328 (formerly the Federal Standard for Mobile Home Construction and Safety, title 24, HUD, Part 280) or when such standard is not applicable, the standard for Manufactured Home Installation 1982 (Manufactured Home Sites, Communities and Setups) ANSI A225.1/NFPA 501A*, or latest edition, or with local
codes.
Product Dimensions
Interior-mounted blower motor model
_ Top trim widths:
13V2" (34.3 cm)
retractable
vent height
27" (68.6 cm) for 30" (76.2 cm) vent 33" (83.8 cm) for 36" (91.4 m
Terminal box cover
13" (33.0 cm)
13" (33.0 cm)
//
6" (15.2 cm)
diameter
vent collar
30V4" (76.8 cm) for 30" (76.2 cm) vent
36V4" (92.1 cm) for 36" (91.4 cm) vent
11/2" (3.8 cm)
(0.95 cm)
283/4"
(73.0 cm)
(23.5 cm)
Exterior-mounted blower motor model - used with Part Number KPEC992M
Cabinet Dimensions
Interior-mounted blower motor model Exterior-mounted blower motor model
A= 1/2"(12.7 ram)
minimum
21%6"
(54.1 cm)
All cutouts are
for 6" (15.2 cm)
diameter vent system.
Locate power supply junction box aflower
left hand rear corner of the cabinet.
NOTES:
See cooktop manufacturer's instructions for cooktop cutout depth and width.
Use dimensions for vent system cutout location that applies to your installation.
Interior mounted blower systems connect with 6" (15.2 cm) round vent. The cutout locations for this vent system will depend on your specific installation.
Centerline of cooktop cutout
1/2"(12.7 ram)
minimum
/
/
Locate power
supply junction pox afJower
left hand
rear corner of the cabinet.
NOTES:
See cooktop manufacturer's instructions for cooktop cutout depth and width.
Exterior-mounted blower systems connect with 10" (25.4 cm) round vent. The cutout locations for this vent system will depend upon your specific installation.
Countertop Cutout Dimensions
IMPORTANT: Countertops with a bullnosed front edge are not recommended for these installations.
Some models require a countertop deeper than 25" (63.5 cm); see the following Countertop Cutout Dimensions section.
To avoid mistakes, it is recommended that the cooktop and vent cutouts be drawn on the countertop before making any cutouts.
See Cooktop Installation Instructions for complete cutout dimensions, location dimensions and installation details.
B C ---a_
A ....................................|
A. Downdraft vent
B. Cooktop C. Measurement of cooktop rear overhang. D. D = Measurement of eooktop rear overhang (C) +
11_,, [46.2 mm] (E)
Countertop Cutout Dimensions
A. 7/2"(12.7 mm) minimum to backsplash or
rear wall
B. _" (19.1 mm) maximum backsplash depth
I
E. 11_" (46.2 mm)
F. 7/2"(12.7 mm) minimum G. ¼" (6.4 mm) minimum H. Countertop and backsplash
I. 7/2"(12. 7 mm) minimum
B
C. 27½" (69.9 cm) on 30" (76.2 cm) models
33_" (85.9 cm) on 36" (91.4 cm) models
D. D =Measurement of cooktop rear overhang
+ 11_,, (46.2 mm)
6
/iii¸¸ L° i...... .................................
IMPORTANT: Observe all governing codes and ordinances. Save Installation Instructions for electrical inspector's use.
It is the customer's responsibility to contact a qualified electrical installer, and to ensure that the electrical installation is adequate
and in conformance with National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA Standards C22.1-94, Canadian Electrical
Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and ordinances.
If codes permit and a separate ground wire is used, it is recommended that a qualified electrician determine that the ground path is adequate.
A copy of the above code standards can be obtained from:
National Fire Protection Association
One Batterymarch Park, Quincy, MA 02269
CSA International
8501 East Pleasant Valley Road
Cleveland, OH 44131-5575
This fan is suitable for use with solid state speed controls.
A 120 Volt, 60 Hz., AC only 15-amp fused, electrical circuit is required.
Check with a qualified electrician if you are not sure the downdraft vent is properly grounded.
i ts
The downdraft vent must be connected with copper wire only.
The downdraft vent should be connected directly to the circuit breaker (or fused disconnect) box through flexible armored or nonmetallic sheathed copper cable. Allow some
slack in the cable so the downdraft vent can be moved if servicing is ever necessary.
Wire sizes (copper wire only) and connections must conform with the rating of the appliance as specified on the model/ serial rating plate located on the front of the downdraft vent above the wiring box cover.
Wire sizes must conform to the requirements of the National Electrical Code, ANSI/NFPA 70 (latest edition), or CSA
Standards C22.1-94, Canadian Electrical Code, Part 1 and C22.2 No. 0-M91 (latest edition) and all local codes and
ordinances.
Two UL listed or CSA approved 1/2"(12.7 mm) conduit connectors (Three are required if the exterior-mounted vent motor is used.)
A wiring diagram is located on the downdraft vent base above the power control board cover.
IMPORTANT: Make sure there is proper clearance within the wall or floor before making exhaust vent cutouts.
Use heavy (rigid) metal vent.
Venting system must terminate to the outside.
Do not terminate the vent system in an attic or other enclosed area.
Do not use 4" (10.2 cm) laundry-type wall caps.
Do not install 2 elbows together.
Do not use plastic or metal foil vent.
The length of vent system and number of elbows should be kept to a minimum to provide efficient performance.
Use no more than three 90 ° elbows
Make sure there is a minimum of 24" (61 cm) of straight vent between the elbows if more than one elbow is used.
Use clamps to seal all joints in the vent system.
Use caulking tape to seal the exterior wall or floor opening around cap.
Do not cut joist or stud. Ifvent cutout falls over a joist or stud, a supporting frame must be constructed.
Flexible metal vent is not recommended. If it is used, calculate each foot of flexible vent as 2 ft (0.6 m) of rigid metal vent.
Flexible elbows count twice as much as standard elbows. Recommended vent system length:
For either interior-mounted or exterior-mounted blower installations, the vent system length should not exceed the
maximum lengths listed in the Maximum Length of Vent System chart. See "Calculating Vent System Length" in the "Venting Methods - Interior Mounted Vent Motor Only" section.
INSTALLATION INSTRUCTIONS
INTERIOR-MOUNTED VENT MOTOR
_A_ _ _T _1_ _ _ _'_'"__ ',_,_uY_ _,'_ _:_:t1_ ¸¸'_¸_¸'......_¸_'¢¸'¸'¸_¸t_¸
Determine which venting method is best for your application. Island Location Vent system can terminate through either the wall or floor. Vent system installed under a concrete slab using Pro Island location sewer pipe.
B
A
/ ii
C E
A.Down vent K
Built-in cabinet locations
.... II
C
A. Down vent B. Rear vent
I) I............
II II .....D
C.Left vent D.Right vent
........<ii::........
H
/
d I
A. Wall cap B. 6" (15.2 cm) round metal vent C. 16" (40.6 cm) maximum
D. 6" (15.2 cm) round PVC sewer pipe
E. 6" (15.2 cm) round metal vent
F. 6" (15.2 cm) round PVC coupling
G. Concrete slab
H. 6" (15.2 cm) round PVC sewer pipe
I. 6" (15.2 cm) round 90 ° PVC sewer pipe elbow
J. Tightly pack gravel or sand completely around pipe.
K. 6" (15.2 cm) round 90 ° PVC sewer pipe elbow
L. 6" (15.2 cm) round PVC coupling
M. 12" (30.5 cm) minimum
Calculating Vent System Length
It is recommended that you use round vent instead of rectangular vent, especially if elbows are required. If rectangular vent is required, it should be transitioned to 6" (15.2 cm) round vent as soon as possible.
8
Maximum Length of Vent System
Vent Length
6" (15.2 cm) round 35 ft (8.9 m) 31/4'' x 10" (8.3 cm x 25.4 cm) 35 ft (8.9 m)
To calculate the length of the system you need, add the equivalent feet (meters) for each vent piece used in the system.
Vent Piece 6" (15.2 cm) Round
45° elbow 2.5 ft
(0.8m)
90° elbow 5.0 ft
(1.5m)
The following example falls within the maximum vent length of
35 ft (8.9 m).
2 - 90° elbow
1 - wall cap 8 ft (2.4 m) straight
Transition
Length of 6" (15.2 cm)
= 10.0 ft (3 m)
= 0.0 ft (0.0 m) = 8.0 ft (2.4 m) = 4.5 ft (1.4 cm) = 22.5 ft (6.8 m)
system
Excessive Weight Hazard
Use two or more people to move and install downdraft vent.
Failure to do so can result in back or other injury.
6" (15.2 cm) 0.0 ft wall cap (0.0 m)
31/4'' x 10" (8.3 cm x 25.4 cm) 4.5 ft to 6" (15.2 cm) transition (1.4 m)
6" (15.2 cm) to 31/4'' x 10" 1 ft (8.3 cm x 25.4 cm) transition (0.3 m)
31/4"x 10" (8.3 cm x 25.4 cm) 5.0 ft to 6" (15.2 cm) 90° elbow (1.5 m)
transition
6" (15.2 cm) to 31A'' x 10" 5.0 ft (8.3 cm x 25.4 cm) 90° elbow (1.5 m)
transition
Example Vent System
C
1. Place cardboard or similar material on top of a flat surface where you can easily assemble the downdraft vent systm.
2. Remove parts packages, downdraft vent and blower box from the carton.
3. Remove all shipping materials, tape and film from the downdraft vent and blower box.
4. Remove screws from each side of the vent. Attach the left and right side overcounter support brackets to the downdraft
vent and push up to align the screw holes. Use screws to secure the brackets.
_ A
C
A. Qvercounter support bracket B.Blower motor box
C. Qvercounter support bracket screw
5.
Attach the left and right side end caps to the downdraft vent. Place the end cap upon the overcounter support, slide the
tab into the slot and snap into place over the the plastic tabs.
D
A. Blower motor B. Transition C. 90 ° elbows
D. 6" backdraft damper (suppfied)
A. End cap
6. Attach support legs to the side of the downdraft vent with A
2 screws in each leg. Do not tighten screws. ........
A. Blower motor box B. Support leg
®
7. Using 2 or more people, insert the downdraft vent into the countertop cutout. Check that downdraft vent is parallel to side of cutout and that mounting brackets overlap
2.
countertop.
Lift up the blower box from the bottom mounting channel.
8. Move support legs down against cabinet floor. Place a level against the front of the downdraft vent base and adjust until downdraft vent is level vertically. Use a pencil to mark the top of each leg on the downdraft vent and the location of the support leg mounting holes on the cabinet floor.
A
A. Bracket with "Z" slots
B.Hex/slotted head screws (2)
B
A. Level B. Mark locations.
9. Remove downdraft vent from cutout. Drill starter holes at
each mounting screw location on the cabinet floor. Align top of legs with pencil marks on the face of the downdraft vent. Tighten screws in legs.
Determine which direction is best for your installation.
When installed in a cabinet, vent system can exhaust through the bottom, right, left or rear of the cabinet.
Bottom venting:
Downdraft vent is shipped with blower in down venting position so no modification is required. Go to Step 9.
Left or right venting:
1. Loosen the 2 hex/slotted head screws that attach the top bracket that secures the motor to the vent box enough to
slide the bracket into the "Z" slots. This will move the bracket away from the top mounting lip of the blower box and allow it
to tilt away from the vent box panel.
B
A
A. Blower box B. Bottom mounting channel
3. Rotate it 90 degrees to the left or right so that the vent blower damper is repositioned in the direction needed. Do not twist or bind the wires or disconnect the wiring from the blower.
4. Place the bottom tab of the blower box into the bottom mounting channel.
A
A. Blower box B. Bottom mounting channel
10
5. 2. Lift up the blower box from the bottom mounting channel and
Tilt blower box top tab so it is flush with the vent box panel and position it under the top mounting bracket. Slide bracket
set aside.
into the "Z" slots and tighten the 2 hex/slotted head screws to secure.
@
B
A
A.Blower box
NOTE: Optional blower motor mounting position (opposite side). The blower motor box assembly can also be moved to the opposite side of the vent.
1. Remove blower motor box assembly. Follow steps 1 and 2 above.
2. Disconnect the wire connector from the blower motor (see Step 3 of rear venting).
3. Remove panel from the opposite side by loosening the screws in the "Z" slots and sliding the top bracket the same as for the motor box assembly.
4. Install the blower motor box assembly to the opposite side of vent box. Place in the position for the venting method for interior mounted motor, as required.
5. Reconnect wire connector to the blower motor.
6. Install panel cover to the opposite side of the blower motor.
Rear Venting:
1. Remove the vent box. Loosen the 2 hex/slotted head screws that attach the top bracket that secures the motor to the vent
box enough to slide the bracket into the "Z" slots. This will move the bracket away from the top mounting lip of the blower box and allow it to tilt away from the vent box panel.
A
3=
Disconnect the wire connector from the blower motor.
4=
Remove the 2 screws that mount the motor mounting bracket to the vent box. Remove the blower motor and mounting
bracket assembly from the vent box.
B.Bottom mounting channel
\
\
\
\
B
A. Blower motor B. Wire connector
A. Bracket with "Z" slots B. Hex/slo tted head screws (2)
........A
A. Blower motor mounting bracket screws (2)
5=
Remove the 4 screws from the small cover plate on the rear of the vent chamber and set screws and cover plate aside.
11
6,
Install blower motor and mounting bracket assembly to the bracket just below the downdraft tower motor. The blower exhaust opening should fit through the hole in the large cover plate on the opposite side of the vent chamber where the small cover plate was removed. Replace the 2 blower motor mounting bracket screws and tighten.
B
@
_ C
A. Downdraft tower motor B. Large cover plate C. Blower exhaust opening
9. Replace the vent box over the blower motor.
B
i,S
A.Blower motor B. Ventbox
10. Place the bottom tab of the blower box into the bottom mounting channel.
7. Plug in the wire connector to the blower motor.
A B
A. Blower motor B. Wire connector
8,
Place the vent extension for the 6" diameter venting over the vent exhaust and screw into place using the 4 screws.
©
/
B
/
A
A. Blower box B. Bottom mounting channel
11. Tilt blower box top tab so it is flush with the vent box panel and position it under the top mounting bracket.
12. Slide bracket into the "Z" slots.
13. Tighten the 2 hex/slotted head screws to secure.
14. Place the small vent cover over the hole in the vent box and secure in place with the 4 screws.
/
12
\
A. Ventextensionscrews (4)
1=
Attach backdraft damper over 6" vent extension. Secure with vent clamp.
A. 6" vent extension B. Backdraft damper
2. Remove screw attaching the terminal box cover.
B_ C
,/
,/
A. When attaching undercounter bracket to underside
of countertop, make sure that the screw length will
not go through countertop when tightened. B. Backsplash C. Countertop
A
A. Terminal box cover
Determine which direction (rear or bottom) electrical connection will need to run from vent system terminal box.
Remove rear or bottom knockout and install a UL listed or CSA approved conduit connector.
3=
Insert downdraft vent into countertop cutout. Using 2 or more people, position downdraft vent so it is centered in cutout and parallel to edge of cutout. Check that downdraft vent is level vertically. Then fasten lower support legs to the cabinet
floor with screws.
4=
Attach 1 undercounter bracket on front upper right corner of downdraft vent with slot over vent mounting hole and flange against countertop. Attach other bracket to left side of the downdraft vent. Drill starter holes through undercounter mounting brackets into the underside of the countertop. Insert appropriate length screws into holes and tighten brackets to countertop.
Electrical Shock Hazard
Disconnect power before servicing.
Replace all parts and panels before operating. Failure to do so can result in death or electrical shock.
1. Disconnect power.
2. Feed the power supply cable through the conduit connector and into the terminal box.
Fire Hazard
Electrically ground the blower. Use copper wire.
Connect ground wire to green ground screw in terminal box.
Failure to do so can result in death, fire, or
electrical shock.
3. Attach the green (or green and yellow) ground wire to the green ground screw. Tighten the conduit connector clamp
screws.
13
4.
Connect the 2 white wires together using UL listed wire connectors.
1.
Push and hold the button on the top of the downdraft vent for a few seconds. The retractable section of the downdraft vent
will rise, and the blower will start. Position the top trim over the retractable section and snap trim into place.
Trim kits for matching your cooktop color are available from your dealer.
For information on ordering, see the "Assistance or Service" section.
A. Green or green and yellow ground wire B. Green ground screw
C. White wires D. UL listed wire connectors
E.Black wires F UL listed or CSA approved conduit connector
G. Downdraft vent wiring
5.
Connect the 2 black wires together using UL listed wire connectors.
6.
Replace the terminal box cover and secure with screw.
7.
Reconnect power.
E
A. Top trim B. ON/OFF button
C. Blower control sfider D. End cap
E.Filters
2.
Slide the control slider on the side of vent to check the operation and speed of the blower.
3.
If the blower does not operate:
Check that filter or filters are pressed in as far as they will
go.
Check that the circuit breaker has not tripped or a
household fuse blown.
Check downdraft fuse located under power board.
4. Connect vent system to blower. Vent system must end with a wall or roof cap. Use clamps to seal all joints.
5. Install cooktop according to manufacturer's instructions. Check that rear of cooktop overlaps edge of retractable downdraft vent by 3/8"(9.5 mm). See "Countertop Cutout Dimensions" in the "Location Requirements" section.
NOTE: To get the most efficient use from your new retractable downdraft vent, read the "Vent System Use" section.
14
Loading...
+ 30 hidden pages