KitchenAid 30” (76.2cm) Installation Instructions Manual

HOME APPLIANCES
Part No. 9751595 Rev. A
1 A
WARNING
l
ALL RANGES CAN
TIP
l
INJURY TO PERSONS
l
INSTALL ANTI-TIP DEVICE PACKED
WITH RANGE
l
SEE INSTALLATION INSTRUCTIONS
IMPORTANT: Read and save
these instructions. &F%
\
Installer-
Leave Installation Instructions
Homeowner:
Keep lnstallatibn Instructions and anti-tip bracket template for future reference.
Save
Installation Instructions for local
electrical inspector’s use.
30”
(76.2cm) Sealed Burner= Slide-in Range
with self-cleaning thermal/convection
oven
G?5
/
Cabinet opening dimensions
25” (63.5 cm) countertop (with or without backsplash) 24” (61 cm) base cabinet island installation: countertop cutout depth 25” (63.5 cm)
Before you start...
Read electrical and carpentry instructions. Proper installation
is your responsibility. A qualified technician must install this range. Make sure you have everything necessary for correct installation. It is the customer’s responsibility to make sure that the countertop has been properly prepared and that the installation clearances specified on the model/serial rating plate are met. The model/serial rating plate is located on the frame
behind the storage drawer.
Check location
where range will be installed. The range should be located for convenient use in the kitchen. Recessed installations must provide complete enclosure of the sides and rear of range.
ALL OPENINGS IN THE WALL OR FLOOR WHERE RANGE IS TO BE INSTALLED MUST BE SEALED.
Cutout shown
is for a 25-inch (63.5 cm)
countertop with a 24-inch (61 cm) base cabinet.
Cabinet construction:
This appliance is
designed for use in a base cabinet with a depth
of 24 inches (61 cm). The maximum depth for overhead cabinets is 13 inches (33 cm). For the minimum vertical clearance between the cooking surface and the overhead cabinets, see Note.‘*** Overhead cabinets installed at either side of the appliance must be a minimum of 18 inches (45.7 cm) above the cooking surface. The minimum horizontal distance between the overhead cabinets is 30 inches (76.2 cm).
Important: Observe all governing codes and ordinances.
Grounded electrical outlet
is required. See “Electrical requirements,” Panel B.
30-3/8” (77.2 cm)
r
opening width
1
cookto see
P,
Note ***
Cabinet opening dimensions
that are shown must be used.
Do Not pinch the power cord between the range and the wall.
4” (10.2 cm) min.
4 clearance to side wall or other
combustible material - bot
y &i.2 cm) ,lO”
(25.4 cm)
I
min. required between cabinet opening and door or hinge opening.
Do Not seal range to side cabinets.
36” (91.4 cm)
countertop
height
**** Note: 30” (76.2 cm) min. when
bottom of wood or metal cabinet is protected by not less than 114” flame retardant milfboard covered with not less than No. 28 MSG sheet steel, 0.015” (0.4 mm) stainless steel, 0.024” (0.6 mm) aluminum or 0.020” (0.5 mm) copper.
36” (91.4 cm) min. clearance between the top of the cooking platform and the bottom of an un rotected wood or metal
1. ca met.
Countertop preparation
WARNING: If the information in this manual is not followed exactly, a fire or explosion may
result causing property damage, personal injury or death.
- Do Not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
-WHAT TO DO IF YOU SMELL GAS
l
Do Not try to light any appliance.
l
Do Not touch any electrical switch; Do Not use any phone in your building.
l
Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
l
If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the
gas supplier.
Personal Injury Hazard
To eliminate the risk of burns or fire, avoid
installing cabinet storage above the
cooking surface. If cabinets are already
installed, reduce the hazard of reaching over a heated cooking surface by installing a range hood.The range hood should extend a minimum of 5 inches out from the bottom front of the cabinets.
Reaching over a heated cooking surface could result in a serious burn or other personal injury.
Electrical Shock Hazard It is the customer’s responsibility: *To contact a qualified electrical installer. *To assure that the electrical installation is
adequate and in conformance with National Electrical Code, ANWNFPA 70 - latest edition* or CSA Standard C22.1, Canadian Electrical Code, Part 1
- latest edition”*, and all local
codes and ordinances.
Failure to do so could result in death or serious injury.
ides of ver edges top
The cooktop sides of the slide-in range fit over the cutout edge of your countertop.
If you have a square finish (flat) countertop and the opening width is 30-3/a” (77.2 cm),
no countertop preparation is required.
30-3/8” (77.2 cm)
;ydet”h’ng /
ormed or tiled
30-7&I”
(78.4 cm)
countertop trimmed l/4” (0.64 cm) back at front corners of countertop
-1
opening.
Formed front-edged countertops:
Must have molded edge shaved flat l/4” (0.64 cm) from each front corner of opening.
Tile countertops
may need trim cut back l/4” (0.64 cm) from each front corner and/or rounded edge flattened.
If countertop opening width is greater than
30-3/8” (77.2
cm),
adjust the l/4” (0.64 cm)
dimension.
Countertop must
be
level.
Place level on countertop, first side to side; then front to back. If countertop is not level, range will not be level. Oven must be level for satisfactory baking conditions.
Product dimensions
Mobile home installation
The installation of this range must conform to the Manufactured Home Construction and Safety Standards, Title 24 CFR, Part 3280 (formerly the Federal Standard for Mobile Home Construction and Safety, Title 24, HUD, Part
280); or when such standard is not applicable, the Standard for Manufactured Homes Installations 1982 (Manufactured Home Sites, Communities and Setups), ANSI A225.1INFPA 501A*, or with local codes.
In Canada, the installation of this ranae must conform with the current standards CAN/CSA­2240 - latest edition***, or with local codes.
When this range is installed in a mobile home, it must be secured to the floor during transit. Any method of securing the range is adequate as long as it conforms to the standards listed
30-718”
(78.4 cm)
cooktop width
Fr /A- above.
Note:
The
metal chassis of the range MUST be
earth-grounded in order for the con&o1 panel to
work. If the metal chassis of the range is not earth-grounded, NO keypads will operate. Check with a qualified electrician if you are in
.
;;-~u~$l~;,rJ~Or
doubt as to whether the metal chassis of range
(4-s cm) beyond
24”
is earth-grounded.
(61 cm) base cabinet.
Copies of the standards listed may be obtained from: * National Fire Protection Association
Batterymarch Park Quincy, Massachusetts 02269
** American Gas Association
1515 Wilson Boulevard Arlington, Virginia 22209
***Canadian Standard Association
176 Rexdale, Boulevard Rexdale (Toronto), Ontario M9W 1 R3
Anti-tip bracket:
The floor anti-tip bracket MUST be
installed. To install the anti-ti
shipped with the range, see
F
bracket
anel C and
the anti-tip bracket template.
Panel
A
Tools needed for
installation:
flat-blade screwdriver or 5/l 6”
hand or electric drill
wood floor:
l/S” (3 mm) drill bit
concrete/ceramic floor:
3/16” (4.5 mm)
carbide-tipped
masonry drill bit
L.P. gas conversion requires:
pin pick up (claw
attachment)
5/16” nut driver
Parts
supplied for
installation:
L 2-plastic
anchors
l
burner grates and caps
l
vent cap
l
L.P. conversion orifice spuds kit: 2 x #64 cooktop 2 x #69 cooktop 1 x #65 broil burner
(Bracket must be securely mounted to sub-floor. Thickness of flooring may require longer screws to anchor the bracket to sub-floor.)
Gas supply requirements
Observe all governing codes and
ordinances.
Fire Hazard
l
Range must be connected to a regulated
gas supply.
l
L.P. gas supply must Not exceed a pressure of 14 inch water column. This must be checked by a qualified
technician before installing the range.
L.P. gas must not be used unless L.P.
conversion kit has been installed.
l
Do Not use an open flame to test for leaks from gas connections.
l
New, A.G.AJC.G.A.-design-certified, flexible metal gas line connector should be used when codes permit.
Failure to follow these instructions could result in a fire, explosion or personal injury.
IA
This installation must conform with local codes and ordinances. In the
. absence of local codes installations
must conform with American National Standard, National Fuel Gas Code ANSI Z223.1- latest edition (**,
see Panel A) or CAN/CGA-B1 49
latest edition (***,
see Panel A) installation
codes.
le
Input ratings shown on the
. serial/rating plate are for elevations up
to 2,000 feet (609.6 m). For elevations above 2,000 feet (609.6 m), ratings are reduced at a rate of 4% for each 1,000 feet (304.8 cm) above sea level. (Not applicable for Canada.)
El
This range is equipped for use with
n
Natural gas. It is design-certified by
A.G.A./C.G.A. for Natural and L.P. gas with appropriate conversion. The model/serial rating plate, located on the oven frame behind the drawer, has information on the type of gas that can be used. If this information does not agree with the type of gas available, check with your KitchenAid dealer. Conversion to L.P. gas requires installation of the kit included in the parts package. This conversion must be done by a qualified technician.
ID.I
Provide a gas supply line of 3/4” (1.9 cm) rigid pipe to the range location. A smaller size pipe on long
runs may result in insufficient gas supply. Pipe-
joint compounds appropriate for use with L.P.
gas must be used. With L.P. gas, piping or
tubing size can be l/2” (1.3 cm) minimum. L.P.
gas suppliers usually determine the size and materials used on the system.
El
If local codes permit, a new A.G.A./C.G.A. design-certified, 4-5 foot (122 -152.4 cm) long. l/2”
(1.3 cm) or 3/4” (1.9 cm) I.D.,‘flexible metal appliance connector is recommended for connecting this range to the gas supply line. Do
Not kink or damage the flexible tubing when moving the range. A l/2” (1.3 cm) male pipe thread is needed for connection to pressure regulator female pipe threads.
El
The supply line shall be equipped with an approved shutoff valve. This valve
should be located in the same room. but external to the range, and should be in a ’ location that allows ease of opening and closing. Do Not block access to shutoff valve.
El
If rigid pipe is used line, a combination of pipe fittings must be used to obtain an in-line
connection to the range. All strains must be
removed from the supply and fuel lines so range will be level and in line.
IH
The regulator setting must be checked
n
at a minimum of 1 inch water column
above the manifold oressure. The inlet pressure to the regulator should be as follows for operation:
Natural gas: Manifold pressure - 5 inches
Maximum pressure - 14 inches L.P. gas: Manifold pressure - 10 inches
Maximum pressure - 14 inches
(1.
Line pressure testing:
Testing above l/2 psi (gauge)
The range and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures greater than l/2 psig (3.5 kPa).
Testing at l/2 psi (gauge) or lower
The range must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than l/2 psig (3.5 kPa).
Electrical requirements
Electrical Shock Hazard
l
Electrical ground is required on this appliance.
l
Do Not ground to a gas supply pipe.
l
Do Not modify the power supply cord plug. If it does not fit the outlet, have a proper outlet installed by a qualified
electrician.
. Do Not use an extension cord with this
appliance.
l
Do Not have a fuse in the neutral or grounding circuit. A fuse in the neutral or grounding circuit could result in an electrical shock.
l
Check with a qualified electrician if you are in doubt as to whether the appliance is properly grounded.
Failure to follow these instructions could result in death or serious injury.
If codes permit and a separate grounding wire is used, it is recommended that a qualified electrician determine that the grounding path is adequate.
A 120-volt, 60-Hz, AC-only, 15-ampere, fused electrical circuit is required. A time-delay fuse or circuit breaker is recommended. It is recommended that a separate circuit serving only this appliance be provided.
Electronic ignition systems operate within wide voltage limits, but proper grounding and polarity are necessary. In addition to checking that the outlet provides 120-volt power and is correctly grounded, the outlet must be checked by a qualified electrician to see if it is wired with correct polarity.
The wiring diagram is included in the literature package. The wiring diagram can also be found on the back of the range.
Note:
The metal chassis of the range MUST be earth-grounded in order for the control panel to work. If the metal chassis of the range is not earth-grounded, NO keypads will operate. Check with a qualified electrician if you are in doubt as to whether the metal chassis of range is earth-grounded.
Recommended grounding method
For personal safety, this appliance is equipped with a power supply cord having a 3-prong grounding plug. To minimize possible shock hazard, the cord must be plugged into a mating 3-prong, grounding-type wall receptacle, grounded in accordance with the National Electrical Code, ANSVNFPA 70 - latest edition(*, see Panel A) or CSA Standard C22.1, Canadian Electrical Code, Part 1, - latest
edition( ***, see Panel A), and all local codes and ordinances. If a mating wall receptacle is not available, it is the personal responsibility and obligation of the customer to have a properly grounded, 3-prong wall receptacle installed by a qualified electrician.
power
plug
grounding prong
3-prong grounding-type wall receptacle
J
Panel B
Loading...
+ 4 hidden pages