Kingsman HBZDV4224, HBZDV4228, HBZDV4232, HBZDV4224N, HBZDV4224LP Installation Instructions Manual

...
Installation Instructions
Model Numbers HBZDV4224, HBZDV4228, HBZDV4232
Zero Clearance Direct Vent Gas Fireplace
Stock #’s: HBZDV4224N, HBZDV4224LP are
Certified to:
ANSI Z21.50b-2009, CSA 2.22b-2009, CGA 2.17-M91
Stock #’s: HBZDV4228N, HBZDV4228LP, HBZDV4232N and HBZDV4232LP are
are Certified to:
This appliance may be installed in an aftermarket permanently located, manufactured home (USA only) or mobile home, where not prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This appliance is not convertible for use with other gases, unless a certified kit is used.
Printed in Canada January 19, 2010 42HB-MAN
INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.
Read this complete manual before beginning installation.
These instructions must be kept with the unit for future reference.
FOR YOUR SAFETY
WARNING: If the information in these instructions is not followed exactly , a fire or explosion may result
causing property damage, personal injury or loss of life.
WARNING: Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Refer to this manual. Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
What to Do If You Smell Gas
Do not try to light any appliance.
Extinguish any open flame.
Do not touch any electrical switch.
Do not use any phone in your building.
Immediately call your gas supplier from a neighbour’s phone.
If you can not reach your gas supplier, call the fire department.
A Division of R-Co. Inc.
2340 Logan Avenue
Winnipeg, Manitoba, Canada R2R 2V3
Ph: (204) 632-1962
For Propane Horizontal installations the venting must be a minimum of one foot vertical off the flue before going horizontal.
2
Why does my fireplace or stove give off odour?
It is normal for your fireplace to give off some odour. This is due to the curing of the paint, adhesives, silicones and any undetected oil from the manufacturing process as well as the finishing materials used with the installa­tions (e.g. marble, tile and the adhesives used to adhere this product to the walls can react with heat and cause odours).
It is recommended that you burn your gas fireplace or stove for a minimum of four hours at a time with the fan off after the curing of the paint has been completed. These odours can last upward to 40 hours of burn time, keep burning at a minimum of four hours per use until odours dissipate.
About curing of the paint
Your stove or fireplace has been painted with the highest quality silicone stove paint. This paint dries quickly in 15-20 minutes when first applied at the factory. However, due to the high temperature silicone components, the paint will cure when heat is applied to the appliance as it is first used. The following information applies to the curing process to get the paint fully hard and durable.
Fire the appliance four successive times for 10 minutes each firing and a 5 minute cool down between each. Be aware during log and firebox paint curing that a white deposit may be developing on the inside of the glass doors. It is important to remove this white deposit from the glass doors with an appropriate cleaner to prevent build-up (such as Windex or a commercial fireplace glass cleaner).
• Babies, small children, pregnant women and pets should leave the area during the cure phase.
• Ventilate well, open doors and windows.
• Do not touch during curing.
Noise coming from the fireplace?
• Noise caused by metal expanding and contracting as it heats up and cools down, similar to the sound pro­duced by a furnace or heating duct. This noise does not affect the operation or longevity of your fireplace.
• Different types and thicknesses of steel will expand and contract at different rates resulting in “cracking” and “ticking” sounds throughout the heating and cooling periods.
• You should also be aware that as temperatures change within the unit these sounds will likely re-occur. Again this is normal for steel fireboxes, and is not a defect.
Cleaning the Glass
During the first few fires, a white film may develop on the glass front, as part of the curing process. The glass should be cleaned after the unit has cooled down or the film can bake on and become very difficult to remove. Use a non-abrasive cleaner and do not attempt to clean the glass while it is hot.
PRE-INSTALLATION QUESTIONS and ANSWERS
Mobile Home/Manufactured Housing Installation . . . . . . . . . . . . . . . .4
Warnings, Installations & Operations . . . . . . . . . . . . . . . . . . . . . . . . . .5
Operations & Maintenance Instructions . . . . . . . . . . . . . . . . . . . . . . . .6
Installation Requirements for the Commonwealth of Massachusetts . .6
Locating your appliance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Fireplace Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7
Framing your gas fireplace . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8
HBZDV42CVCK Framing and Facing Requirements . . . . . . . . . . . . . .9
Installing Clean View Kit (CVCK) . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Clearances to Combustibles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
MQSW Wall Mount Surround Dimensions . . . . . . . . . . . . . . . . . . . . .11
Installation MQ Wall Mount Surrounds . . . . . . . . . . . . . . . . . . . . . . . .11
Clearances - Mantels & Surrounds . . . . . . . . . . . . . . . . . . . . . . . . . . .12
Mantel Leg Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13
Fan kit installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14
Removing burner system/Access Cover . . . . . . . . . . . . . . . . . . . . . . .15
Brick Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16
Installation of HB Porcelain Liners . . . . . . . . . . . . . . . . . . . . . . . . . . .17
Door and glass information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18
Log Placement Guide . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19-23
Installing MQRSP3 Rock Platform Assembly . . . . . . . . . . . . . . . . . . .24
MQROCK1/MQRSP3 for HBZDV3624/28 & 4224/28 . . . . . . . . . .25-26
Installing LOGC60 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .27
Gas Line Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .28
Millivolt system, lighting, & burner control . . . . . . . . . . . . . . . . . . . . .29
Conversion kit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .30
Installation Instructions - Gas Conversion Kit . . . . . . . . . . . . . . . . . . .31
IPI Electronic Ignition System . . . . . . . . . . . . . . . . . . . . . . . . . . . .32-36
IPI Lighting Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .37
Vent termination . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .38
Venting graph . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .39
General vent installation information . . . . . . . . . . . . . . . . . . . . . . . . .40
Installation of side wall venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .40
Venting vertical . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .41
Kingsman Fireplace part numbers . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Kingsman Log Sets Required . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .42
Kingsman Fireplace Accessories Options . . . . . . . . . . . . . . . . . . . . .42
Kingsman Fireplace Designer Doors . . . . . . . . . . . . . . . . . . . . . . . . .42
Kingsman Burner Assembly and Valve system parts . . . . . . . . . .42-43
Kingsman Miscellaneous parts and Conversion Kits . . . . . . . . . . . . .43
Kingsman Fireplace Venting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .43
Trouble shooting the gas control system . . . . . . . . . . . . . . . . . . . . . .44
Limited Lifetime Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45
Table of Contents
4
Mobile Home/Manufactured Housing Installation
This Direct Vent System Appliance must be installed in accordance with the manufacturer’s installation instructions and the Manufactured Home Construction and Safety Standard Title 24 CFR, Part 3280, or the current Standard for Fire Safety Criteria for Manufactured Home Installations, Sites, and Communities ANSI/NFPA 501A, and with CAN/CSA Z240 MH Mobile Home Standard in Canada.
THE HBZDV4228N, HBZDV4228LP, HBZDV4232N and HBZDV4232LP MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES AFTER FIRST SALE IN THE USA. IN CANADA THE HBZDV4228N, HBZDV4228LP, HBZDV4232N AND HBZDV4232LP MAY BE INSTALLED IN MANUFACTURED (MOBILE) HOMES.
Please follow the current ANSI/NFPA 70 National Electrical Code in the USA and CAN/CSA C22.1 Canadian National Electrical Code in Canada.
An appliance must be grounded to the steel chassis of the home with 8 ga. copper wire using a serrated or star washer to penetrate paint or protective coating to insure grounding.
Use carriage bolt at the attachment point (see diagram above) to secure the appliance to the floor.
For required venting components see venting installation in appropriate section of this manual.
Certified for installation in a bedroom or bed/sitting room. In Canada must be installed with listed milli volt thermostat. In USA see local codes.
Warning: Do not compromise the structural integrity of the manufactured home wall, floor or ceiling, during
installation of appliance or venting.
5
Warnings, Installations, and Operations
Warning
FOR SAFE INSTALLATION AND OPERATION OF YOUR GAS FIREPLACE PLEASE NOTE THE FOLLOWING:
1. Do not clean when the glass is hot.
2. Do not use abrasive cleaners.
3. Using a substitute glass will void all product warranties.
4. For safe operation, glass doors must be closed.
5. When purging the gas line, the glass front must be removed.
6. Do not strike or abuse glass. Take care to avoid breakage.
7. Do not alter gas orifice.
8. No substitute materials may be used other than factory supplied components.
9. This appliance gives off high temperatures and should be located out of heavy traffic areas and away from furniture and draperies.
10. Children and adults should be alerted to the hazards of the high surface temperatures of this appliance and should stay away to avoid burns or ignition of clothing.
11. Young children should be carefully supervised when they are in the same room as the appliance. Toddlers, young children and others may be susceptible to accidental contact burns. A physical barrier is recommended if there are at risk individu­als in the house. To restrict access to a fireplace or stove, install an adjustable safety gate to keep toddlers, young children and other at risk individuals out of the room and away from hot surfaces.
12. Under no circumstances should any solid fuels (wood, paper) be used in this appliance.
13. Under no circumstances should this appliance be modified. Any parts that have to be removed for servicing should be replaced prior to operating this appliance.
14. Installation and repair should be done by a qualified service person. The appliance should be inspected before use and at least annually by a professional service person. More frequent cleaning may be required due to excessive lint from carpet­ing, bedding material, et cetera. It is imperative that control compartments, burners and circulating air passageways of the appliance be kept clean. Make sure that the gas valve and pilot light are turned off before you attempt to clean this unit.
15. Clothing or other flammable material should not be placed on or near the appliance. This appliance should not be used as a drying rack for clothing nor should Christmas stockings or decorations be hung from it.
16. Do not use this heater if any part has been under water. Immediately call a qualified service technician to inspect the heater and to replace any part of the control system and any gas control which has been under water.
17. Do not operate appliance unless completely installed as per installation instructions.
18. Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may result in property damage or personal injury.
19. Do not operate appliance with the glass front removed, cracked or broken. Replacement of the glass should be done by a licensed or qualified service person.
20. The front of the fireplace gives off high temperatures that could ignite combustible material which is kept close to the front of the unit.
21. Ensure that power to the Fireplace is turned off before servicing.
22. Do not operate this Fireplace without the glass front or with a broken glass.
23. Improper installation, adjustment, alteration, service or maintenance can cause injury or property damage. Refer to the owner’s information manual provided with this appliance. For assistance or additional information consult a qualified installer, service agency, or the gas supplier.
24. Operation of this appliance when not connected to a properly installed and maintained venting system or tampering with the blocked vent shutoff system can result in carbon monoxide (CO) poisoning and possible death.
Installation Regulations
This gas appliance must be installed by a qualified installer in accordance with local building codes, or in the absence of local codes, with the current CAN/CGA-B149.1 Installation Code (in Canada) or the current National Fuel Gas Code Z223.1 when installed in the United States.
This appliance, when installed, must be electrically connected and grounded in accordance with local codes, or in the absence of local codes, with the current CSA C22.1 Canadian Electrical Code or with the national Electrical Code; ANSI/NFPA 70-1987 when installed in the United States.
6
• Gas fired appliances may be used only for supplemental heat and/or decorative purposes and under no circumstances shall they provide a primary heat source.
This appliance must not be connected to a chimney flue serving a separate solid-fuel burning appliance.
NOTE: It is recommended that a Carbon Monoxide (CO) Detector be installed in or near bedrooms and on all levels of your home. Place a detector about 15ft [4.5m] outside the room that houses your gas appliance.
Certified for installation in a bedroom or bed/sitting room. In Canada must be installed with listed millivolt thermostat. In USA see local codes.
For safe installation and operation note the following:
The Burner/Log Assembly has been engineered and permanently adjusted for proper flame control.
Periodically remove the logs from the grate assembly and vacuum any loose particles from the grate and burner areas. See Log Placement page to remove logs. Vacuum burner parts and replace logs.
Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation.
Verify proper operation after servicing.
In the Commonwealth of Massachusetts, the installer or service agent shall be a plumber or gas fitter licensed by the Commonwealth. When installed in the Commonwealth of Massachusetts or where applicable codes; the unit shall be installed with a CO detector per the requirements listed below.
1. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment, where the bottom of the vent terminal and the air intake is installed below four feet above grade the following requirements must be satisfied:
A. If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and
alarm shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).
B. A carbon monoxide detector shall be located in the room that houses the appliance or equipment and shall:
• Be powered by the same electrical circuit as the appliance or equipment such that only one service switch services both the appliance and the carbon monoxide detector;
• Have battery back-up power;
• Meet ANSI./UL 2034 Standards and comply with NFPA 720 (2005 Edition); and
Have been approved and listed by a Nationally Recognized Testing Laboratory as recognized under 527 CMR.
C. A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used.
Installation shall be in strict compliance with the manufacturer’s instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
D. A metal or plastic identification plate shall be mounted at the exterior of the building, four feet directly above the loca
tion of vent terminal. The plate shall be of sufficient size to be easily read from a distance of eight feet away, and read “Gas Vent Directly Below”.
2. For direct-vent appliances, mechanical-vent heating appliances or domestic hot water equipment where the bottom of the vent terminal and the air intake is installed above four feet above grade the following requirements must be satisfied:
A . If there is not one already present, on each floor level where there are bedroom(s), a carbon monoxide detector and
alarm shall be placed in the living area outside the bedroom(s). The carbon monoxide detector shall comply with NFPA 720 (2005 Edition).
B. A carbon monoxide detector shall:
• Be located in the room that houses the appliance or equipment;
• Be either hard-wired or battery powered or both; and
• Shall comply with NFPA 720 (2005 Edition).
A Product-approved vent terminal must be used, and if applicable, a Product-approved air intake must be used. Installation shall be in strict compliance with the manufacturer instructions. A copy of the installation instructions shall remain with the appliance or equipment at the completion of the installation.
For the state of Massachusetts a T-handle gas shut-off valve
must be used on a gas appliance. This T-handle gas shut-off valve must be listed and approved by the state of Massachusetts. This is in reference to the state of Massachusetts state code CMR238.
Operations and Maintenance Instructions
Installation Requirements for the Commonwealth of Massachusetts
7
Locating your Appliance
Fireplace Dimensions
(above or below grade)
Installing with Top Vent
Island installation with a top vent is possible as long as the horizontal portion of the vent sys­tem does not exceed 20 feet (6.1 m).
A - Flat on a wall D - As a room divider B - Across the corner E - Flat on wall corner C - As an island F - Exterior wall
HBZDV42 -CVCK (Clean View Circulating Kit)
HBZDV42 louvered
8
Framing for your Gas Fireplace
Framing Specifications
1. Cold climate installation recommendation: When installing this fire­place against non insulated exterior wall or chase, it is recom ­mended that the outer walls be insulated to conform to applicable insulation codes. Drywall must be installed over insulation to prevent contact of insulation and unit.
2. Choose fireplace location and frame in accordance with the fireplace framing dimensions specified (See Framing Diagrams). Bend nailing tabs forward on left and right of unit and place fireplace into framed enclosure. This allows for 1/2” in front of framing tabs for finishing materials.
3. Drywall or other material can extend flush with the appliance on the bottom, sides and top of fireplace. (louvered models only)
HBZDV42 louvered
HBZDV42 WITH CVCK (CLEAN VIEW CIRCULATING KIT)
4. When installing horizontal with a 90 degree bend maintain a minimum of two and a half (2.5”) inches above the bend in enclosures.
5. For HBZDV with louvers combustible floor can raise 1” above the bot­tom of the fireplace. For HBZDV with CVCK (Clean view Circulating Kit) floor or hearth can raise 7” above the bottom of the fireplace with portions being combustible and non combustible. See drawing Below.
6. When installing MQHB42SW surround,the fireplace must be raised a minimum of 3 1/2” above the finished floors, to accommodate the wall surround. The fireplace may be raised higher but the 60” clear­ance measured from the bottom of the fireplace to the ceiling must be maintained at all times. (i.e. For an 8 ft. ceiling the unit can be raised only 36 inches.)
For Propane Horizontal Installations the venting must be a minimum of one foot vertical off the flue before the elbow on any horizontal runs of one foot or greater. This allows for cleaner combustion and greatly reduces carboning and cleaning of glass.
TOP VIEW
11"
11"
821⁄32" DIA.
9
HBZDV42CVCK - Framing and Facing Requirements
HBZDV42 WITH HB42CVCK (CLEAN VIEW CIRCULATING KIT)
HB42CVCK WITH MQHB42SW SURROUND
10
HOW TO INSTALL CLEAN VIEW KIT (CVCK)
Clearance to Combustibles
Clearance to Combustibles
Back (from Standoffs) 0 inches/0 mm Side (from standoffs) 0 inches/0 mm Floor 0 inches/0 mm Ceiling (from bottom of fireplace) 60 inches/150 cm Top (from standoffs) 0 inches/0 mm Top of 90 degree bend in Minimum
Enclosure of 45 to 46 inches 5 inches/128 mm / All Vent Systems Top of 90 degree bend in
Enclosure over 46 inches 2 1/2 inches/64 mm / All Vent Systems Top of Horizontal Pipe 1 1/2 inches/38 mm / All Vent Systems Side & Bottom of Horizontal Pipe 1 inch/25.5mm / All Vent Systems Vertical Vent Pipe 1 inch/25.5mm / Kingsman Vent Systems Vertical Vent Pipe 1 1/4 inch/32mm / Simpson/AmeriVent/Selkirk Direct Temp
Systems
(NOTE -Floor) if installing the appliance directly on carpeting or other combustible materials other than wood flooring, the appliance shall be installed on a metal or wood panel, the full width and depth of the appliance. Carpet may extend 1 inch above the floor of appliance.
For units with CVCK (Clear View Circulating Kit) see framing with CVCK to establish floor heights
CAUTION: When using CVCK DO NOT INSTALL a Louver assembly
1. Install optional Fan Kit (See Fan Instruction)
2. Fold two standoffs up into position & mount with supplied Screws. (Fig. 1)
3. Hang CVCK on top of fireplace retainer tabs and rotate down into position. (Fig. 2)
4. Using the screws provided, fasten the non-combustible header onto the top of the CVCK assembly.
5. Using four supplied #6 screws, fasten CVCK kit to the inside frame of unit
6. Kit is supplied with 2 valve extension knobs. Align the notches and slide the extensions onto the valve knobs.
7. DO NOT brick or tile beyond the inside area of the CVCK kit to allow for removal of door.
8. Install optional pull screen system: First slide curtain onto rods and slide round end of rod into side post Ref: A, using 1/2” DT screws, mount the flattened end of rod to the bottom side of the rod hanger bracket (Ref: B). Repeat this step for the opposite side.
Note: Additional Access
for gasline installation and Fan Electrical installation! When CVCK kit is installed in framing remove 2 screws from the right and left side of bottom panel Ref: C. Once screws are removed, bottom panel can be rotated forward for access to gas valve and
Warning: Failure to position the parts in accordance with these diagrams or failure to use only
parts specifically approved with this appliance may result in property damage or personal injury.
11
MQSW Wall Mount Surround Dimensions
Installation of MQ Wall Mount Surrounds
Remove the old CAP (Control Access Panel), and the Lower CVCK panel by unscrewing the two support screws and drilling out the two rivets.
Remove the two upper CVCK mounting screws located at H2 as shown in the figure below. IMPOR­TANT: KEEP ALL FOUR (4) SCREWS TO REMOUNT THE MODERN SURROUND ASSEMBLY.
Slightly tilt the Modern Surround assembly so that the upper tab will clear the CVCK door opening.
Slide the Modern Surround into the CVCK and align the holes H1 and H2. Please note that the ledge of the Modern Surround should rest on the CVCK Kicker Ledge.
Using the previously removed screws, secure the upper tab of the Modern Surround in to the CVCK frame.
Swing lower portion of the Modern Surround into the CVCK and align the mounting holes on the Lower Tab with the holes on the CVCK Side Frame.
Using the previously removed screws in Step 1, secure the Lower Tab to the CVCK side frame.
Replace the old CAP with the new CAP that accompanied the Modern Surround kit.
Check Installation to make sure the Surround and CVCK is secure.
Concave A B C D E F G H I J L
HB36 40 1/249 1/232 1/221 5/89 1/29 1/28 1/221/25 1/232 7/
16
HB42 42 3/455 7/1636 7/1623 3/49 1/29 1/29 1/221/25 1/236 7/
16
HB47 48 3/461 7/1642 7/1629 3/49 1/29 1/29 1/2316 1/242 7/
16
Convex A B C D E F G H I J L
HB36 41 40 1/232 7/1621 5/89 1/29 1/241 3/162 13/166 1/832 7/
16
HB42 42 15/1644 5/1636 7/1623 3/49 1/29 1/241 3/1631/86 7/1636 7/
16
HB47 48 50 7/1642 7/1629 3/49 1/28 3/441 3/163 3/47 1/842 7/
16
12
CLEARANCES - HBZDV42 - Mantels & Surrounds
Warning:
Combustible objects must not be placed on a non-combustible mantel unless the non-combustible
mantel meets the minimum height and width require ments for a combustible mantel.
*Caution: The CVCK must be flush with the wall.*
Note For the installation of the MQHBSW.
Maintain Minimum 1” Clearance to Top & Sides of the surround.
13
Mantel Leg Clearances
Mantels
Depending on the depth of the fireplace mantel, it may be installed higher or lower from the top of the fireplace opening. See drawings for proper installation height of your combustible mantel. Non-combustible mantels may be installed at any height above the fireplace opening except when using MQHBSW.
Non combustible materials such as brick, tile, etc. can extend up to or over the front face of the fireplace (NO PORTION OF GRILL AREA OR DOOR AREAS CAN BE COVERED) except where designer clean view kit is used.
Combustible material can extend flush to unit up to the top, bottom and sides of fireplace to stand-offs. For COMBUSTIBLE materials extending in front of fireplace consult (Mantel and Mantel Leg Drawings).
Surrounds
If installing wide or slim line surrounds, the finish materials must be flush with the front facing of the fireplace.
Note: When using paint or lacquer to finish the mantel, such paint or lacquer must be heat resistant (250˚F) to prevent discoloration.
14
Fan Installation for HBZDV 36/42/47
Fan Installation instructions for HBZDV36/42/47 with or without CVCK (Clean View Circulating Kit)
1. Slide fan housing into unit and place over 2 Fan Retainer tabs. Tabs are pre punched and bent up. Rubber grommets at the base of the fan should fit snugly over the tabs. *Note: When installing fan, lay the fan on its back and slide into the Fireplace lengthwise. Once inside the fan can be stood upright and slid behind the valve for placement.
2. Note: For Fan Disc installation HBZDV units have been installed with a sliding track system. Install the Thermodisc provided with the Fan Kit. Place thermodisc into sliding assembly, Fig 1, and attach 2 leads exiting right side of fan housing into thermodisc. Now slide disc assembly into thermodisc track, Fig 2. Place swivel handle of disc assembly on track to lock into position. To service disc simply
pull swivel handle slide towards you while rotating handle to access disc.
3. Wire Junction Box to 120v and wall mounted variable speed con­trol. Install a duplex outlet to junction box and plug fan into outlet.
4. Turn the wall switch on (clockwise). Turn fireplace on. Once the sensor in unit reaches operating temperature (approximately 10 to 15 minutes) the fan will turn on. The fan can be switched off if desired by turning the wall switch fully counter clockwise.
5. To set the minimum fan speed. Remove the variable switch from the wall mount. Turn the variable speed wall controller to its mini­mum setting (fully counter clockwise). Use the set screw on the side of variable speed controller to increase or decrease the mini­mum fan speed (lowering minimum fan speed will decrease sound level created by fan)
Reinstall switch into wall mount and cover with face plate.
Parts List:
1 ea. fan comes with 4 ft cord. Two 14’ leads (female ends) 1 ea variable speed control (wall mount type) 1 ea thermodisc 1 thermodisc mount assembly
Electrical Services
All optional fan kits are equipped with a 120V, 60Hz, .4amp blower.
Note: All electric connections are to be made in accordance with CSA Standard C22.1 - Canadian Electrical Code part I or with the National Electrical Code, ANSI/NFPA 70 (latest edition) and/or in accordance with local codes.
Note: INSTALL FAN KIT BEFORE INSTALLING OPTIONAL
CVCK (Clean View Circulating Kit).
If CVCK has been installed into Framing additional access is
provided by removing screws from bottom panel of CVCK. See INSTALLING CLEAN VIEW KIT (CVCK). Page 9 - 10
CAUTION – DO NOT ATTACH 120V FAN ASSEMBLY TO MILLIVOLT GAS VALVE SYSTEM
Note: To service fan with CVCK kit installed see Removing Burner
System in manual.
WARNING:
Label all wires prior to
disconnection when servicing controls. Wiring errors
can cause improper and dangerous operation.
Verify proper operation after servicing.
WARNING:
Electrical Grounding Instructions.
This appliance is equipped with a three-pronged
(grounding) plug for your protection against shock
hazard and should be plugged directly into a properly
grounded three-prong receptacle. Do not cut or remove
the grounding prong from this plug.