King Pigeon GSM 3G M2M RTU User Manual

GSM 3G IOT M2M
Solution
Ver 1.0
S27x
Date Issued: 2015-04-20
All rights reserved by
King Pigeon Comm.Co.,Limited.
www.GSM-M2M.com
GSM 3G M2M RTU
Page 2 of 15 Ver 1.0 File No.:S27x10
GSM 3G M2M RTU
Automation solution
Table of contents
1. Brief introduction -------------------------------------------------------------------------------------------------4
2. Safety Directions ---------------------------------------------------------------------------------------------------6
3. Physical Layout ----------------------------------------------------------------------------------------------------7
4. Settings ---------------------------------------------------------------------------------------------------------------8
5. SMS commands & APP-------------------------------------------------------------------------------------------9
6. Communication Protocol--------------------------------------------------------------------------------------13
7. Registers Assignment Table----------------------------------------------------------------------------------14
8. Upgrade Firmware ----------------------------------------------------------------------------------------------15
9. Warranty -----------------------------------------------------------------------------------------------------------15
GSM/3G
Precision
DIN
AIN
DO
Register
Record
Port
S270
V
12bit
2 2 2 X 1000
USB
S271
V
12bit
4 4 4 X 1000
S272
V
12bit
8 6 4 X TF Card
USB/RS232/RS485
S273
V
12bit
8 6 4
64
TF Card
S275
V
16bit
8 6 4
64
TF Card
USB/RS232/RS485/RJ45
Notice
1. For 3G Version, the model should plus C or W, C stands for inbuilt module is CDMA2000. W stands
for inbuilt module is WCDMA;
2. All of them support 1 temperature and 1 humidity inputs for environment monitoring.
3. The standard package:
1x RTU, 1x GSM Antenna, 1x AC/DC Adaptor,1x Android APP, 1x PC Configuration Software, 1x USB cable, 1x User Manual, 1x Backup battery inside, 1x TF card inside, Terminals for Connection.
4. The standard package not includes: SIMCard , Temperature+Humidity sensor TH100
Warning Tips:
This User manual is for S275, for other models please refer to this user
manual and note abovementioned differences.
This handbook has been designed as a guide to the installation and operation of RTU S27x. Statements contained in the handbook are general guidelines only and in no way are designed to supersede the instructions contained with other products. We recommend that the advice of a registered electrician be sought before any Installation work commences. King Pigeon Communication.Co.,Limited. its employees and distributors, accept no liability for any loss or damage including consequential damage due to reliance on any material contained in this handbook. King Pigeon Communication.Co.,Limited. its employees and distributors, accept no liability for GSM Network
upgrading or SIMCard upgrading due to the technology specifications contained in this handbook.
Page 3 of 15 Ver 1.0 File No.:S27x10
GSM 3G M2M RTU
Automation solution
1. Brief Introduction
The GSM 3G M2M RTU inbuilts ARM® Cortex™ 32 Bit RISC Core, 168 MHz inside, RTOS system. It is a multi I/O port remote terminal unit, through the RS232/485 port can extend up to 64 additional I/O or connect intelligent meters or PLC. It is special for BTS monitoring, remote data acquisition, telemetry, BTS monitoring, access control, ATM, generator monitoring, Pump station monitoring, weather satiation monitoring and other applications. It supports voice communication, SMS, GPRS, 3G and RJ45 LAN IP communications.
The GSM 3G M2M RTU can be used as remote access control. The authorized users can open the gate or turn on the machine with a free charge call at specified time.
The GSM 3G M2M RTU supports Modbus RTU, Modbus TCP, TCP/UDP protocol, transparent data transmission over GPRS/3G, RS232, RS485, RJ45, performs as Modbus Master or Modbus Slave. It can integrate into present SCADA or DCS or HMI directly.
The GSM 3G M2M RTU can be used as Modbus RTU SMS Alert Alarm, when the data acquisition from RS232/485 exceeds threshold value, it also can send pre-definition SMS to users.
The GSM 3G M2M RTU can be used as:
A Switch with SMS Remote Control. SMS texts for switching particular terminals on/off are
configurable.
A Modbus RTU SMS Alarm. It can be used as Modbus RTU SMS Alarm, when the data/value
acquisition from RS232/485 exceed the threshold, it can send SMS to alert the users immediately.
A Timer-Switch which can be activated automatically. It can be used as preset time when the GSM
3G M2M RTU need work and when it needn‘t work.
An Access Control unit. Up to 10 tel. numbers can be authorized for dial to access control and open
the electricity door directly with free charge.
An automation system. Each input can link to output actions, this is very useful when the temperature
upto appointed value, need switch on the air-conditioning immediately, or when water overflow and need switch on the dryer, or when somebody broken into the door or windows need to start the CCTV and Siren.
A SMS reporter. The GSM 3G M2M RTU can setup daily automatically report its current status to users. A SMS Alarm Controller. The IO activations or deactivations can be reported by SMS and optionally
confirmed by phone calls. Each input can have its own message texts and the message can be programmed by users.
A Pulse Counter. The digital inputs can be used as the pulse counter, the user can setup both of interval
value activated alarm and total value activated alarm.
A Data Logger. The unit can save the all of the acquisition data in internal memory storage and upload
to internet by GPRS /3G/RJ45/RS232/RS485 network according to schedue, no distance limitation.
A Wireless Data Acquisition to SCADA or HMI or Monitoring Center. The unit can acquisition the
varity data(E.g.: Pressure, Level, Current, Voltage, digital input status, pulse counter, digital relay output status, temperature value, humidity value and other) and upload to the SCADA(Real time dynamic data) or HMI or Monitoring Center by SMS/GPRS/3G/RJ45/RS232/RS485, no distance limitation.
A Wireless Intelligent Meter Reader. The GSM 3G M2M RTU can be used to read remotely intelligent
meter data to SCADA or monitoring center by RS232 port or RS485 Port.
Page 4 of 15 Ver 1.0 File No.:S27x10
GSM 3G M2M RTU
Automation solution
A GSM 3G DTU(GPRS 3G Data Transfer Unit). It can work with the supervisioning center, in the
supervisioning center, the own can remote monitoring and control the remotely terminals by GPRS/3G/RJ45 LAN Network.This is very useful to Fuel tank monitoring, Oxygen in hospital, Flood level, street light control, wellhead control, BTS environment monitoring, power transmission system monitoring and other applications.
1.1 Typically Applications
Typically BTS Solution Diagram:
Page 5 of 15 Ver 1.0 File No.:S27x10
GSM 3G M2M RTU
Automation solution
A:I/O port connections, RS232/RS485 extend I/O ports, RS232/RS485 connects Air-Conditioners, intelligent
meters, Diesel Generator, Power System, and Battery Groups via transparent protocol or Modbus RTU protocol. Under this condition, the RTU performs Modbus RTU Master;
B:Through RJ45 LAN cable or GPRS or 3G to HMI, OMC, the protocol is defined by user of personal. C: Through RJ45 LAN cable or GPRS or 3G to SCADA,HMI, DCS, OPC Server, Under this condition, the RTU
performs Modbus Slave.
Through RS232 or RS485 to SCADA, HMI, DCS, OPC Server, under this condition, the RTU performs
Modbus Slave.
D:Through SMS to control RTU, or receive SMS alarm alert, or through voice communication to open the door
or receive alarm calling.
1.2 Mainly Features
1) ARM® Cortex™-M4 32 Bit RISC Core, 168 MHz inside, RTOS system;
2) Widely Rated voltage range, 9~36VDC, Inbuilt large capacity rechargeable backup battery;
3) 2G TF card for save historical data, USB port for configuration and upgrade firmware;
4) 6 analog inputs, 16bits, supports 0-5V, 0-20mA, 4-20mA;
5) 4 Relay outputs, 5A/30VDC,5A/250VAC;
6) 8 digital inputs, dry contact or level input. One of the input can be used as counter;
7) 1 temperature probe input, 1 humidity transducer input;
8) I/O ports with opto-isolated, RS232/485 with 15KV ESD protection;
9) 2 IP data centers, supports Modbus TCP,TCP/IP protocol over GPRS/3G/RJ45 LAN network;
10) RS232/RS485 can performs Modbus RTU Master, Modbus RTU Slave, supports 01,02,03,04,05 code, up to 64 registers, the register arise alarm also can send SMS to alert;
11) RS232/485 can be used as data transparent transmission for different intelligent meters or PLC;
12) Automatically resend the data while communication failure, GPRS failure will alert by SMS text;
13) Supports remotely restart the RTU, and configure it by SMS commands remotely;
14) Supports over voltage protection and phase-reversal protection;
15) 10 SMS Alert and auto dial numbers, can program to receive specified alarm message.
16) 10 access control authorized numbers, can open the BTS door or turn on/off machine with a free charge call at the specified time.
1.3 Specifications
Item
Reference Scope
DC Power supply
Standard adapter: DC 12V/1.5A Range 9-36VDC
Power consumption
Standby:12V/70mA; Working Max.: 12V/300mA
GSM/3G Frequency
850/900/1800/1900Mhz/3G(WCDMA or CDMA2000)