Filled Connectors for Outdoor/Irrigation Use
INSTALLATION INSTRUCTIONS
IMPORTANT: Turn off power before
installing or removing connector.
Product to be used in accordance with
local and national codes.
1. Strip #22 - 18 wires 1/2” (12.7mm)
and #16-12 wires 3/8” (9.5mm).
2. Align any frayed strands or
conductors.
3. Pre-twisting unnecessary. Place
stripped wires together with ends of
insulation even.
4. Twist connector onto wires pushing
firmly until hand-tight. Do not over
torque.
5. Wipe sealant in and around
conductors and connector opening
while tightening. Do not reuse.
DryConn® Black/White
Catalog # Selling Unit
61135 Bag of 25
61145 Bag of 100
61146 Canister of 150
61148 Canister of 500
PRODUCT SPECIFICATIONS
& MEASUREMENTS
Max. Voltage: 600V max. building wire
(1000V max. signs or luminaries)
Connector Size: 27/32” x 7/16”
Wire Type: Copper/Copper
Wire Range: Min #22/Max #12
Temperature Rating: 105°C (221°F)
Silicone Sealant Temperature: -45°F to 400°F
UL Designation: SWP*
Measurements (Inches):
A - 0.85
B - 0.44
C - 0.31
U.S. Pat. 5,771,578 and additional Patents
Pending apply. All other trademarks, U.S. and
Foreign Patents apply. All Rights Reserved.
Selected 600V Wire Combinations
• UL 486D listed as a sealed wire
connector system. For use in damp,
wet, raintight, direct bury, and
submersible locations. Not to be
used in continuous submersion
applications.
For use with solid and/or stranded combinations.
2 #14 1 #14 w/1-3 #18 or #20 3 #16 w/1 #18, #20 or #22
2-5 #18 2 #14 w/1 #18 1 #18 w/1-4 #20
3-5 #20 1 #16 w/1 #18 4 #18 w/1 #20
1 #14 w/1 or 2 #16 2 #16 w/1-2 #18 or #20 4 #20 w/1 #22
50100-22 REV H 03/15