KING U-SS User Manual

electrical mfg. company
UTILITY HEATER
Protect your equipment from destructive freezing by install-
ing this unit where protective warmth is required. This versatile utility heater will save you time and money by preventing the costly inconve­nience of frozen pipes and equipment in your pump room, valve room, utility room, etc. With the automatic thermostat you set the required temperature to be maintained. Low wattage units can be used in electri­cal cabinets for moisture control and to maintain a minimum operating temperature to provide high reliability of electronic equipment.
WATTAGE
62 U2425** N/A 5*
125 U2450** N/A 10*
187 U2475** N/A 15*
250 U24100** U2425 20
500 U1250 U2450 38
750 U1275 U2475 50
1000 U12100 U24100 75
* cubic foot cabinet ** 240 Volt unit run at 120 Volts
Model for
120V
Model for
240V
ROOM SIZE
(cubic feet)
• Thermostat has range of 40º to 90ºF
• Steel sheath long life element
• Expanded metal element shield
• 4 mounting feet
• Capillary tube safety high limit
• Steel case and grille
• Optional stainless steel case and grille
• Baked enamel ivory finish
½" knockout for electrical hookup
• 1-year warranty
Clearances from combustible surfaces
Low Wattage Clearances from combustible surfaces - for 62 Watts to 187 Watts
Maximum wattage for vertical installation is 250 Watts. Do not exceed 250 Watts with this installation.
VERTICAL
ON WALL
(Thermostat Up)
DO NOT INSTALL THIS WAY
9131 10th Avenue South, Seattle WA 98108 (206) 762-0400 fax (206)763-7738
U.indd : 1/10
Installation Instructions
It is extremely important to verify the electrical power supply is the same voltage as the heater you are installing. 120 Volt heaters are usually not interchangeable with 240 Volt power supply. Powering a 240 Volt unit with 120 Volt supply wires will reduce the heater output by approximately 75% which may be undesirable for your application. Powering a 120 Volt unit with 240 Volt supply wires will destroy the heater and void all warranties if the heater is not made to be connected to 120 and 240 Volts. The 240V pumphouse can be run on 120V for reduced wattage.
CAUTION: Turn off power source supplying the heater before attempting installation, maintenance or repairs. Lock or tag circuit breaker or fuse panel door. Failure to do so could result in serious electrical shock, burns or possible death.
WARNING : RISK OF ELECTRIC SHOCK. CAN CAUSE INJURY OR DEATH : DISCONNECT ALL REMO TE ELECTRIC POWER SUPPLIES BEFORE SERVICING.
WARNING: Risk of fire, do not use as residential or household heater.
CAUTION: Source of possible ignition - high temperatures, keep combustible material away from front of heater. Do not operate heater with cover removed.
Note: Not for use in explosive gas environments similar to boat gasoline engine rooms. Thermostat is a snap action
type and creates an arc when opening.
Installation Instructions
• Remove heater from box. Check contents received for damage from shipping.
• Attach unit to wall or flat surface following dimensional clearances from page one.
• Unit cannot be installed vertically with thermostat at
the top.
• Remove junction box cover and connect power wire with
appropriate strain relief device.
• Attach power wires to lead wires in unit.
• Replace junction box cover and turn thermostat off.
• Apply power.
• Turn thermostat on and test to insure that unit and
thermostat are working properly.
• Set thermostat for desired temperature.
Dimensions
Wire
Diagram
Exploded view shown for detail. Unit is one-piece.
9131 10th Avenue South, Seattle WA 98108 (206) 762-0400 fax (206)763-7738
Parts List
When ordering parts you must specify if you are replacing Stainless Steel Parts by adding -SS to the end of the model number. The model
numbers below are for standard utility heaters.
1 64 UTILITY SM CASE Pump House Case (1 piece) 2 64-08 Reflector Pan 3 & 4 64-02 Wiring Compartment Cover & Element Screen (1 piece) 5 500xxxx Element - Specify Voltage & Wattage 6 10H11-221445 High Temperature Capillary Tube Limit 7 58T1S-302861 Optional Single Pole Thermostat Kit 8 PT-2-P-S Optional Thermostat Knob
U.indd : 1/10