KING Transformer Silent Relay User Manual

www.king-electric.com
transformer relays
24A01G-3 WIRING
Fig. 1. Diagram of “LEVEL TEMP” wiring
SERIES
Fig. 2. Baseboard heaters with limit
Fig. 3. Typical wiring diagram to “Sequence” two or more loads
King Electrical Manufacturing Company / 9131 10th Avenue South, Seattle, WA 98108 / phone 206.762.0400 / fax 206.763.7738
www.king-electric.com
tranformer relays
Fig. 4. Typical wiring diagram to operate two or more loads simultaneously
SERIES
USING ONE THERMOSTAT AND TWO OR MORE SILENT OPERATORS TO “SEQUENCE” LOADS
Figure 3 shows how several Level-Temp Silent Operators can be used to “sequence on” separate heating loads. This may be accomplished by “jumpering” the thermostat leads of the additional silent operators, and wiring them in careful conformance to the recommended wiring diagram. Note that only one silent operator is in the thermostat circuit. Therefore, set the adjustable heater in thermostat at .2A, or use a thermostat with a .2A fixed heater.
SEQUENCE OF OPERATIONS: A circuit is completed through the bi-metal heater of the first silent operator as the contacts of the low voltage thermostat close. In approximately 45 seconds, the line voltage snap-switch of this operator closes, energizing heating load #1 and the
transformer primary of silent operator #2. Since the thermostat leads of this operator are “jumpered”, its bi-metal heater immediately begins its’ warping action. In approximately 45 seconds the line voltage switch of operator #2 closes to energize heating load #2 and the transformer primary of silent operator #3. This “sequence on” pattern continues until all successive silent operators and heating loads have been energized. When the single Level-Temp room thermostat opens its contacts each separate heating load will be “sequenced off” in intervals of approximately 45 seconds.
OPERATION
King Electrical Manufacturing Company / 9131 10th Avenue South, Seattle, WA 98108 / phone 206.762.0400 / fax 206.763.7738
Loading...
+ 1 hidden pages