KING SRK10 User Manual

SRK10 Splice and Tee Kit with End Seal
Installation, Operation and Maintenance Instructions
IMPORTANT: Save These Instructions!
DESCRIPTION
SRK10 SPLICE AND TEE KIT The SRK10 kit is to be used with King SR heating cables to make a splice, tee connection and one end seal.
Item Qty Description
A 1 B 2 C 3 D 1 E 6 F 2 G 5 H 1
I 1
J 3 K 1 X 1 Y 1 Z 1
Black heat shrink tube for ground Insulated buss wire crimp connectors Black heat shrink tube (1/2” dia. x 1” length) Un-insulated ground crimp connector
Black heat shrink tube (1/8” dia. x 1” length) Heat shrink cap (1/2” dia. x 2” length) Mastic strips (1” width x 1-1/2” length) Black cloth tape (1” width x 6” length)
Cable tie with mounting hole Cable ties
Black heat shrink tube (1” dia. x 8” length) Black heat shrink tube (3/4” dia. x 5” length) Woven braid sleeve ( ½” dia. x 4” length) Black heat shrink cap ( ½” dia. x 1-1/4” length)
WARNING: ELECTRIC SHOCK HAZARD
Disconnect all power before installing or servicing the heating cable and accessories. SR heating cable must be grounded properly in accordance with the National Electrical Code (NEC). Failure to comply can result in personal injury or property damage. Only a qualified licensed electrical contractor shall install and service of SR heating cable and accessories, otherwise the warranty is voided.
Note:·All electrical wiring, including Ground Fault Circuit Interrupters (GFCI), must be done according to the NEC and local codes by a qualified installer. Article 426 of ANSI/NFPA 70 of National Electrical Code (NEC section 62 of CAN/CSA-C22.1, Canadian Electrical Code, Part I (CEC) governs the installation of this heat systems
www.king-electric.com 1
Rev 9.15.12
WARNING:
The SRK10 kit components are electrical devices and they must be installed correctly to ensure proper operation and to prevent shock or fire. Carefully follow all of the installation instructions and read these important warnings.
1. Heating cables must be installed in compliance with the national electric code (NEC) in addition to state, provincial and local codes. Check with your local inspector for specific code requirements (or regulations or standards) in your area.
2. To minimize the danger of fire from electrical arcing if the heating cable is damaged or improperly installed ground fault equipment protection (GFEP) must be used on each heating cable branch circuit. Arcing may not be stopped by conventional circuit protection.
3. Bus wires will short if they make contact each other, keep bus wire separated.
4. Keep ends of heating cable and kit components dry before and during installation.
5. The black heating cable core is conductive and can short. It must be properly insulated and kept dry.
6. UL listing approvals and performance are based on the use of the specified components in this kit only. Do not substituted parts or use vinyl electrical tape.
7. Damaged heating cable can cause arcing or fire. Do not energize damaged heating cable. Repair or replace damaged heating cable prior to applying power.
8. Do not twist cables during installation or embed in thermal insulation.
The SR heating cable is comprised of several layers as shown above, use the illustration to gain a clear understanding of the
1
cable components.
Cut the braid and push it back to loosen it as shown. Bend the cable and gently pull it through the braid.
Lightly score completely around and then down
outer jacket a distance of 7”. Do not cut braid or inner
2
jacket. Bend heating cable to break jacket at score, then peel off outer jacket!.
Twist and position the braid to one side of heating
4 3
cable and then cut the insulating jacket back 4-1/2”. Lightly score the inner insulating jacket and then bend the cable to break the jacket and peel it off.
www.king-electric.com 2
Rev 9.15.12
Notch the conductive core at the end and twist it back
5 6
to peel the bus wires from the core.
Score between the bus wires and bend the core to break it free and peel the core material away from the bus wires.
Cut and remove the remaining center core, leaving the
7
bare conductors.
Center the 1/2” x 1” heat shrink tube over the cable core
9
and bus wires as shown.
Slide the 1/8” dis. X 1” heat shrink tube over the bus wires.
Apply heat to shrink the tubes, approximately 2 minutes at
8
600ºF (315ºC). Keep tubes up against the core while heat shrinking.
10
Heat evenly for approximately 3 minutes at 600ºF (315ºC) until it shrinks completely.
www.king-electric.com 3
Rev 9.15.12
Loading...
+ 5 hidden pages