KING KFUH User Manual

SAVE THESE INSTRUCTIONS
KFUH Electric Unit Heater
Installation Instructions
WARNING: RISK OF ELECTRIC SHOCK. CAN CAUSE INJURY OR DEATH. DISCONNECT ALL REMOTE ELEC­TRIC POWER SUPPLIES BEFORE SERVICING.”
CAUTION: Turn off power source supplying the heater before attempting installation, maintenance or repairs. Lock or tag circuit breaker or fuse panel door. Failure to do so could result in serious electrical shock, burns, or possible death.
It is extremely important you verify the electrical power supply is the same voltage as the heater being installed. 240 and 480 Volt heaters are not interchangeable. Powering a 480 Volt unit with 240 Volt supply wires will reduce the heater output by approximately 75% and is never recommended. Powering a 240 Volt unit with 480 Volt supply wires will destroy the heater and voids all warranties.
CHECK: Ensure blower wheel is free-turning and that element assemblies are in place. Be sure filter is in proper position and not torn or damaged. Check that blower housing and motor have not separated from element compartment during shipment.
FIELD WIRING
208 and 240 Volt heaters are equipped with circuit breakers over 48 Amps to provide internal circuit protection and a field disconnect on the unit. A terminal block provides a single strike for field wiring. 480 Volt units do not have circuit breakers but are fused when internal protection is required and are also supplied with terminal blocks for field wiring. Consult the National Electric Code for proper wire size and service circuit breaker protection.
Ter m in a l B lo c k
1 Phase and 3 Phase
240VAC
L6
L5
240VAC
L4
L3
240VAC
L2
L1
60 Amp
Circuit Breaker
60 Amp
Circuit Breaker
60 Amp
Circuit Breaker
To L im i t C on t ro l s
and
Heater Elements
Low Voltage Thermostat
R
W
G
Y
Furnace Low Voltage
Ter m in a l B lo c k
C
R
W
G
Thermostat Control Wiring diagram
for use with electric furnaces and showing cooling coil relay hook-up
Transformer
24VAC
Heat Relays
Fan Only Relays
Cooling Coil Relay*
(*provided by others)
Electronic Air Cleaner Wiring diagram
for use with electric furnaces and utilizing an airflow interlock switch
D
I M E N S
I O N
AIR FLOW AIR FLOW
S
2007 KFUH.indd : 3/08
King Electrical Mfg. Company • 9131 10th Avenue South • Seattle WA 98108 • phone (206) 762-0400 • fax (206) 763-7738
1
Mounting
KFUH heaters can be mounted vertically or horizontally as shown. 3/8" weldnuts are weld­ed into brackets and will accept 3/8 threaded rod. A minimum of 6 inches clearance to vertical and horizontal surfaces and 6 feet minimum above floor are required. Louvers can be adjusted for desired airflow.
Application Tips
First, calculate the heating loads in the con­ventional way using the N.E.M.A. handbook or ASHRAE guide. Next, determine quantity and size of heaters to be used. In instances where large groups of people are normally settled in the same location, use a large number of smaller kW unit heaters. (Example: people on a production line or skilled machine opera­tions.) By utilizing heaters in this manner one can best distribute uniform heat, prevent hot drafts, reduce potential noise levels and bal­ance the electrical operating demand. When considering warehouse areas or storage rooms (where heat distribution and constant temperatures are less important) use fewer heaters of higher capacity. To maintain uniform heat and reduce strati­fied air it is recommended that the total CFM of the units turn the air over approximately 3 times per hour.
Horizontal Mount
Smaller rooms can be heated by one unit heater. Where two walls are exposed heaters should be mounted as shown. In larger rooms, units should be located so their air streams wipe exposed walls without
Ceilings under 12 feet
6" Minimum
Clearance
Adustable
Louvers
blowing at them. Units should be located so that the air stream of one supports that of another thus setting up a circulatory air move­ment. (Distance between units to be approxi­mately 1½ times published air throw). Units should not be mounted horizontally in areas having ceiling heights in excess of 10 to 12 feet.
Vertical Mount
Units should be mounted vertically where they may otherwise interfere with assorted material, handling equipment and in high bay areas. Heaters should be situated to provide free air circulation. Size and selection of units should be based on recommended mounting height. Unit heaters are frequently used to combat cold air inrush when loading dock doors are opened. For such applications, one or more units should be arranged to blow warm air vertically in front of opening.
Ceilings over 12 feet
Motor HP
Dual Mounting
Where square footage is large and comfort essential, both horizontal and vertical installa­tions may best serve your requirements.
Mounting Limitations
KFUH unit heaters should not be used in potentially explosive atmospheres. The finish is not intended for direct salt spray exposure in marine applications or the highly corrosive atmospheres of swimming pools, chemical storage bins, etc. Please refer to the factory for explosion proof or marine application heater information. Do not install unit heaters above recom­mended maximum mounting height. Obstruc­tions must not block unit heater air inlet or discharge. To prevent possible injury heaters must be mounted at least 6 feet above the floor to prevent accidental contact with the heating element or fan blade.
AIR DELIVERY CHART @ .2 static
MOTOR SPEED
Motor Load
230
230
230
Amps
3.4
1.7
3.2
1.7
3.8
1.9
Voltage
1/5
380/460
1/3
380/460
1/2
380/460
Wire Color
Air Volume = Cubic Feet per Minute (CFM) Air Velocity = Feet per Minute (FPM)
Low Med
CFM FPM
775 570 860 630
1100 810 1250 920 1100 810 1250 920 1540 1130
Red
CFM
Blue
FPM
CFM
1000 1000 1540 1540 1750 1750
High
FPM
735
735 1130 1130
1285 1285
Black
The following accessories and/or options
may have been ordered with your unit.
Model
1E30-910
KFUH-90D
KFUH-RD
KFUH-90RD
KFUH-PTBL
2
Description
24V Wall Thermostat, range 50°- 90°
90 Degree Elbow w/ adjustable louver diffuser
Radial Diffuser
90 Degree Elbow w/ radial diffuser
Kit includes casters and mounting bracket to create a Portable KFUH (no power cord)
Add Suffi x
-T
-2TS
-SF
-BR
-2S1
-2S3
-DS40
-DS60
-DS80
-DS100
-ND
Description
1-Pole thermostat - factory installed
2-Stage thermostat - factory installed
Summer fan switch - factory installed
Blower relay for remote fan only operation
2-Stage control, 1-Phase models
2-Stage control, 3-Phase models
40 Amp 3-Pole non-fused disconnect switch
60 Amp 3-Pole non-fused disconnect switch 80 Amp 3-Pole non-fused disconnect switch
100 Amp 3-Pole non-fused disconnect switch
No diffuser - 1" duct collar provided on discharge side for connection to 14" x 14" duct
2007 KFUH.indd : 3/08
Loading...
+ 2 hidden pages