KING CKL User Manual

Electric CK Plenum Heater
Plenum Heater
The Model CK Series is a special ap­plication heater that is approved for use in concealed areas of a building. This heater may be installed in areas that are not readily available for a person to see, such as the area between a concrete ceiling and a drop-tile ceiling, in plenum open or ducted system and can be used for constant environmental temperature control and freeze protection for sprinkler systems in concealed areas.
It is also suitable for use as a special purpose unit heater where the environmental requirements are dirty, dusty, moist or mildly corrosive.
CK heater installed inside a plenum area for inline ducted air and heat boost in large commercial HVAC systems.
Access opening must be provided to the heater.
OPTIONS
2-Stage Control for Single or Three Phase Models
Modulating Thermostat for SSR Control
In-Built Thermostat - N.E.M.A. 4X
Duct Sensor for Modulating Thermostat
Motor Substitution To Increase Or Decrease CFM, Standard ¼ and ½ HP
Disconnect Switches - 30 through 100 Amp, 3-Pole
Solid State Relays - 25, 45 and 75 Amp
Duct Sensor for Modulating Thermostat
Outside Wall
Large building ventilation system air heater for preheat or stand alone heating system.
No Diffuser For In-Line Duct Installation
2007 CK.indd : 12/07
King Electrical Mfg. Co. 9131 10th Ave South, Seattle WA 98108 ph: 206-762-0400 fax: 206-763-7738
1
MODEL CK PLENUM INSTALLATION INSTRUCTIONS
TESTED AND APPROVED BY ETL TESTING LABORATORIES No 500505
CAUTION: Turn off power source for the heater before attempting installation, maintenance or
repairs. Lock, tape or tag circuit breaker or fuse so that power cannot be turned on by accident. Failure to do so could result in personal injury or shock.
INSPECT HEATER: Remove heater from carton and check to be sure blower wheel is free-turning, and that element assemblies are in place. Be sure filter is in proper position and not torn or dam­aged.
Control Wiring: Connect thermostat to terminals R and W for heating, and to R and G for cool air only. This can be done with a single stage heat-cool ther­mostat or a single stage heat only thermostat and a separate fan only switch to control the fan-relay (optional). Some models have two stage operation (optional) and are provided with terminals W1 and W2. If a single stage thermostat is used it should be connected to terminals R and W1 and a jumper wire installed from terminals W1 to W2; see enclosed control circuit wiring diagram.
The model CK Air Heater plenum installation is a special application heater for use in the space cre­ated between a finished concrete ceiling and a drop type t-bar ceiling, an area normally hidden from view.
The heater is mounted horizontally with the integral suspension bracket provided in an area where service access can be readily maintained.
Safety screens are provided at both the air intake and discharge aperture. Fixed air directional louvers are standard.
A 24 volt control thermostat with a maximum temperature setting of 100º F will prevent operation of the unit should the ambient rise above 100º F. - the maximum ambient for which the heater is intended to operate.