Kinetico 2025s, 2020CHF, 2060s, 2060s OD Installation Instructions Manual

Page 1
Installation Instructions
Softening Systems
Block Salt Softeners
Check your local building and sanitation codes for installation compliance. Installation must meet all state and local codes.
Check your water quality first. This system is not intended to be used for treating water that is microbiologically unsafe or of
unknown quality without adequate disinfection before or after the system.
Standard Softeners
2025s 2060s
Commercial Softeners
4060s OD
Page 2
Parts Identification
Brine Tank
Brine Line Tubing
Drain Line Tubing
Brine Valve
Chemical Care
Soldering
Eye Protection
prevent potential eye injury that could be caused
Grounding
Natural Reach Read / Review
Owners Manual
Installation Instructions
Softener Assembly
Includes: control module main and remote tanks tank connectors connector bracket connector bracket pins located inside cabinet models: 2020CHF
Included with these systems:
Mach Control Valve
2025s 2060s 2060s OD
Cabinet, standard, commercial
Inlet / Outlet Adapters
Adapter E-clips
Inlet / Outlet O-rings
Safety
Read all steps, guides and rules carefully before installing and using the Kinetico Softening System
Use a scorch pad to protect any surface that may be exposed to a torch flame or excessive heat.
Use only LEAD FREE solder.
Close or remove PVC containers and other flammable materials to prevent fire or explosions.
Provide proper ventilation when using PVC cleaner or glue.
When installing a plastic component, install grounding straps BEFORE the lines are actually cut to ensure that the ground is never broken.
Wear protective eyewear while installing to
by splattering soldering materials or metal/plastic shavings.
Use a ladder for all work overhead beyond your natural reach. If working continuously at a height of six feet or more, employ the appropriate safety devices.
R ev . 11/ 20 10 P ag e 2 P ro duc t No. 14 197
Page 3
Procedure
5
5
Connect Adapters for
Connect Adapters for
2
Test Water Quality
Cabinet / Brine Tank
Softener Assembly
Instructions
1
Unpack Equipment
Locate and identify parts shown in parts section.
3
Parts Pack
Brine Line
Drain Line
Assemble Softener
Larger units requir
Assemble Mach Head (if applicable)
Lube O-rings
Connect tanks
e tank connection.
Confirm water quality to determine proper setup
Total Hardness pH Ferrous Iron Ferric Iron
4
Position Softener
Position softener and brine
ank on a level surface.
t
If within 3 meters of hot water tank, make sure an expansion tank is used.
Environmental conditions:
50º C Max., protect from freezing
Water conditions:
Temperature 1 – 50º C Pressure: 1 – 8.5 Bar
a
Classic Control Valve Systems
Lube O-rings Insert adapters Insert adapter bracket Insert adapter pin
Rev. 11/2010 Page 3 Product No. 14197
b
Mach Control Valve Systems
Install O-rings Lube O-rings Insert adapters Insert E-clips
Page 4
Remove existing use
Make sure pawls and springs are back before inserting new meter disc
6
7
Install By-pass Set Meter Disc
Connect Softener
Remove cap screws
Remove cap and actuator
Insert new meter disc
Gently turn disc clockwise until
Tighten cap screws
8
Use of an external 3-valve by-pass or equivalent is recommended.
Connect softener to main plumbing via by-pass.
Do not solder brass adapters while they are inserted in the control module.
Take care during the installation process to assure that solder and flux do not come in contact with: media tanks control module E-clips related plastic components
Set number of gallons between regenerations based on your system size and inlet water quality (see step 10).
meter disc
R ev . 11/ 20 10 Pag e 4 P rod uc t No. 14 19 7
pawls fall in place
Replace oring, spring, actuator and cap
Page 5
Set Brine Valve
9
Meter Disc and Brine Valve Chart
Select disc based on inlet compensated hardness.
Meter Disc
Number Denotes Compensated Hardness in mg/L
Model Salt Setting (adjuster) Float 1 2 3 4 5 6 7 8
2020c HF 0.22 Kg -- -- 34 68 86 120 154 188 222 257
0.34 Kg -- 114mm 34 86 120 171 222 257 308 342
2025s 0.45 Kg 1.5 184mm 68 137 205
0.6 Kg 1.5 191mm 86 188 274 359 428
2060s 1.22 Kg N 153mm 137 257 376 479 581 684 770 855
1.63 Kg L 185mm 154 308 462 581 701 821 923 1026
1.81 Kg N 172mm 171 325 479 616 752 872 975 1077
2.00 Kg N 178mm 188 342 496 650 787 906 1026 1129
2060s OD 1.22 Kg N 152mm 51 103 154 188 239 291 325 376
1.81 Kg N 172mm 68 120 188 257 308 359 428 479
2.00 Kg N 178mm 68 137 205 274 325 393 445 513
10
Float Cup Setting (all units) Remove the brine valve assembly and rest it on a flat surface.
Remove rubber band.
Height is measured from the base of the brine valve assembly to the top of the float cup (see drawing at right).
Adjuster Tube Setting (standard and commercial units)
Cut and remove tabs on both sides of the tube.
Remaining number or letter imprinted on the tab determines the correct setting. The drawing at right shows an adjuster tube at setting "M".
Float Cup Setting
Rev. 11/2010 Page 5 Product No. 14197
Page 6
11
12
Connect Brine Tank
Install Drain Line
13 14
Install Brine Tank Overflow
15
16
Flush System
Start-Up System
Confirm Drain Air Gap
Apply 2 – 3 wraps of Teflon control valve. Locate tube elbow. Hand tighten elbow, then turn once with wrench. Attach tube from elbow to brine valve – hand Make sure tubing is not kinked.
Waste connections or drain outlets shall be designed and constructed to provide for connection to the sanitary waste system through an air gap of 2 pipe diameters or 25 mm, whichever is larger.
tighten tube side nuts.
®
tape to nipple on
Apply 2 – 3 wraps of Teflon
control valve. Locate ½” x tube elbow. Hand tighten elbow, then turn once with wrench. Attach drain line from elbow to drain. Make sure line is not kinked. Drain lines must not travel more than 2.4 meters up
from module head. On lines traveling more than 10 meters, increase diameter of the drain line.
Install drain line on the barbed overflow fitting on the drum
and connect it to a drain.
Make sure the drain is not higher than the barbed fitting.
FOLLOW PLUMBING CODES.
®
tape to ½” nipple on
Flush both the inlet and outlet lines by opening the by-pass valve and allowing water to rinse out any debris in the lines.
Flush lines for 10 minutes.
R ev . 11/ 20 10 P ag e 6 P ro du ct N o. 14 197
Put by-pass into service position.
Using #2 Philips screwdriver, depress and turn actuator clockwise into backwash position.
Brine tank will begin to fill.
After 5 minutes, turn actuator until alternate tank is in backwash.
Page 7
17
18
Add Salt
Purge Air from Plumbing
Sanitize Softener
19
Using #2 Philips screwdriver,
brine position.
Add a clean grade of salt at this time.
DO NOT USE ROCK SALT OR SOLAR SALT.
Regenerate both tanks.
turn actuator clockwise into
Use a clean grade of salt appropriate for use with water treatment equipment. DO NOT USE ROCK SALT OR SOLAR SALT.
Mix 29.6 mL of unscented household bleach in 15.1 liters of clean/soft water. This should make a 100 ppm solution. Use 22.7 liters for commercial units.
Put the system into by-pass.
Disconnect the brine line and put the 3/8” tube into the container holding the bleach mixture from the step above.
Note: Do not add bleach to brine tank. Salts containing red-out additives will create hazardous fumes.
Put the system into service.
Put the unit into brine draw on one tank.
Draw the mixture until a strong bleach odor is detected (smelled or tested) in the drain line. This procedure should produce approximately 20 ppm in the mixed solution.
Switch quickly to the other tank and repeat the procedure.
Advance the control disc to the service position and allow the unit to stand water, the longer the stand time should be.
Put unit into by-pass.
Reconnect the brine line (3/8” tube) to the brine tank and backwash each tank of the softener two times.
Put unit into service.
After the unit is fully pressurized, open a faucet in the house to purge air from lines.
Check all other house faucets, and purge air by manually cycling unit from one tank to the other.
After regeneration time, initiate regeneration on second tank.
for 30-60 minutes. The colder the
R ev. 11/ 20 10 P a g e 7 P r oduc t No . 14 197