Kinder Kalahari SC Powerflue, KPFC00SN, KPFC00SP Installation And Maintenance Instructions Manual

Kalahari SC
Powerflue
DECORATIVE FUEL EFFECT
POWERFLUE GAS FIRES
Installation and Maintenance Instructions
Hand these instructions to the user
Model No. KPFC00SN is for use on Natural Gas (G20) at a supply pressure of 20 mbar in G.B. / I.E. Model No. KPFC00SP is for use on Propane Gas (G31) at a supply pressure of 37 mbar in G.B. / I.E.
CONTENTS
Section 1 Information and Requirements PAGE
1.0 Appliance Information 3
1.1 Conditions of Installation 4
1.2 Flue Terminal Position 4
1.3 Fireplace / Surround Suitability 5
1.4 Fireplace Opening 6
1.5 Shelf Position 6
1.6 Installation Types 6-7
1.7 Hearths 7-9
1.8 Spillage Monitoring System 10
Section 2 Installation of Fire
2.1 Unpacking the fire 11
2.2 Marking the Firebox Recess 11
2.3 Fitting the Fan Unit / Firebox 12-20
2.4 Making the Electrical Connection 21
2.5 Making the Gas Connection 21
2.6 Making the Solenoid / Wiring Loom Connection 22
2.7 Final Fitting of the Fan Unit 22-23
2.8 Gas Tightness & Inlet Pressure 24
Section 3 Assembling Fuel Bed and Commissioning
3.1A Assembling the ceramics and fuel bed (Pebble Fuelbed) 24-27
3.1B Assembling the ceramics and fuel bed (Coal Fuelbed) 28-31
3.2 Lighting the appliance 32
3.3 Checking for clearance of combustion 33 products
Section 4 Maintenance
4.1 Removal of the Burner Assembly 34-35
4.2 Removal of the Battery Ignitor 35
4.3 Replacement of the Battery 35
4.4 Removal of the Pilot Assembly 35
4.5 Replacement of the Control Cable 36-37
Parts Shortlist 37
This appliance is manufactured by:­BFM Europe Ltd, Trentham Lakes, Stoke-on-Trent, ST4 4TJ
2
SECTION 1
INFORMATION AND REQUIREMENTS
1.0 APPLIANCE INFORMATION
Model KPFC00SN KPFC00SP
Gas Type G20 G31 Main injectors (2 off) Size 260 Size 85 Pilot Type Copreci Copreci
Single Flame Single Flame 21100 / 162 21100 / 167
Max. Gross Heat Input : 6.9 kW Min. Gross Heat Input : 4.2 kW
Cold Pressure : 19.0 +/-1.0 mbar 36.0 +/-1.0 mbar Ignition : 1.5V Battery Generator
Supply Voltage : 230V a.c. Supply Frequency : 50Hz Supply Fuse : 3 Amp to BS 1362 Power Input : 90W IP Rating : IP23 Electrode Spark Gap 4.5mm Packed Weight (without fender) 24kg
Fire box Dimensions (with trim’s fitted)
Kalahari Models
Width : (with standard trim, no spacer) 470mm Height : (with standard trim, no spacer) 586mm Depth : (overall-without fender) 170mm Depth : (overall-with spacer fitted) 120mm
Gas Connection : 8mm Compression (Supplied with fire)
3
INSTALLATION REQUIREMENTS
1.1 CONDITIONS OF INSTALLATION
It is the law that all gas appliances are installed in accordance with the rules in force only by a CORGI Registered Installer in G.B, in accordance with these installation instructions and the Gas Safety (Installation and Use) Regulations 1998 as amended. Failure to install appliances correctly could lead to prosecution. It is in your own interest and that of safety to comply with the law.
The installation must also be in accordance with all relevant parts of the Local and National Building Regulations where appropriate, the Building Regulations (Scotland Consolidation) issued by the Scottish Development Department, and all applicable requirements of the following British Standard Code of Practice.
1. B.S. 5871 Part 3 Installation of Decorative Fuel Effect Gas Fires
2. B.S. 6891 Installation of Gas Pipework
3. B.S. 5440 Parts 1 & 2 Installation of Flues and Ventilation
4. B.S. 1251 Open fire place components
5. B.S. 715 Metal flue pipes for gas appliances
6. B.S. 6461 Part 1 Installation of Chimneys and flues
7. I.S. 813 : 1996 Domestic Gas Installation (Republic of Ireland)
No purpose made additional ventilation is normally required for this appliance, when installed in G.B. When Installing in I.E. please consult document I.S. 813 : 1996 Domestic Gas Installation, which is issued by the National Standards Authority of Ireland. If installing in Northern Ireland, please consult local building regulations. Any purpose made ventilation must be checked periodically to ensure that it is free from obstruction.
4
1.2 FLUE TERMINAL POSITION
The minimum acceptable dimensions from the flue terminal to obstructions and ventilation openings are shown below in fig. 1 and listed in the table (Fig. 2 below)
IT IS IMPORTANT THAT THE POSITION OF THE FLUE ALLOWS THE FREE PASSAGE OF AIR ACROSS IT AT ALL TIMES.
DIMENSION TERMINAL POSITION MINIMUM DIMENSION
A Directly below an opening, air brick, 300mm (12 in.)
opening window
B Above an opening, air brick, 300mm (12 in.)
opening window
C Horizontally to an opening, air brick, 300mm (12 in.)
opening window etc. D Below gutters, soil pipes or drain pipes 75mm (3 in.) E Below eaves 200mm (8 in.) F Below balconies or car port roof 200mm (8 in.) G From a vertical drain pipe or soil pipe 150mm (6 in.) H From an internal or external corner 200mm (8 in.) I Above ground roof or balcony level 300mm (12 in.) J From a surface facing the terminal 600mm (24 in.) K From a terminal facing the terminal 1200m (48 in.) L From an opening in the car port 1200m (48 in.) M Vertically from a terminal on the same wall 1500mm (59 in.) N Horizontally from a terminal on the 300mm (12 in.)
same Wall O From the wall on which the terminal is mounted 50mm (2 in.) P From a vertical structure on the roof N/A Q Above intersection with roof 150mm
5
Fig. 1
Fig. 2
1.3 FIREPLACE / SURROUND SUITABILITY
The fire must only be installed on a hearth it must not be installed directly onto carpet or other combustible floor materials.
The fire is suitable for fitting to non-combustible fire place surrounds and propri-
etary fire place surrounds with a temperature rating of at least 150oc.
If a heating appliance is fitted directly against a wall without the use of a fire surround or fire place all combustible material must be removed from behind the trim. Soft wall coverings such as blown vinyl, wall paper etc. could be affected by the rising hot air and scorching and/or discoloration may result. Due consideration should be made to this when installing or decorating.
1.4 FIRE PLACE OPENING
The front opening of the fire place must be between 375 and 440 mm wide, and between 550 and 570mm high. If the opening exceeds these dimensions then a surround must be constructed from suitable non-combustible material to produce a correct size opening. Any surround must be suitably sealed to the fire place to prevent leakage. See below in fig.3
1.5 SHELF POSITION
The fire may be fitted below a combustible shelf providing there is a minimum distance of 200mm above the top of the fire and the shelf does not project more than 150mm. If the shelf overhangs more than 150mm the distance between the fire and the shelf must be increased by 15mm for every 25mm of additional over­hang over 150mm.
Fire Opening
375mm Minimum 440mm Maximum
610mm Minimum
520mm Minimum
Fig. 3
550mm Minimum 570mm Maximum
Minimum Flat Sealing Area
6
1.6 INSTALLATION TYPES
This fire can be fitted against an outside facing facing flat wall surface or into a fireplace opening cut into the wall.
When fitting the fire in front of the inner cavity wall, the distance between the mounting face of the fire and the rear face of the firebox (170mm nominally), a false chimney breast or fireplace surround should be constructed. The firebox must then be secured into the fireplace using the method described in section 2. Any combustible material must be removed from the the area around the firebox flange. In all installations, ensure that there is no structural damage to the property or the damp course. See fig. 4 below
When fitting the fire into a cavity wall, this requires the opening of the inner leaf of brickwork, to recess the firebox into. The opening needs to be sufficient to accomodate the firebox. To support the wall above the hole, a suitable lintel must be inserted across the top of the opening. If fitting the appliance into a cavity wall, a lintel 750mm long having a thickness of 75mm with a height of the inner wall should be used. The lintel could be either pre-cast concrete or steel - Catnic CN52 or CN 46 could be used, depending upon the inner wall thickness. Before proceeding with the installation of the fire, an assessment of the area immediately above the fire is required, see Fig. 5 overpage. If there is no existing openings within either triangle, proceed with forming the opening. However, if opening or beams occur within either triangle, then you should seek specialist advice from a structural engineer or consider relocating the proposed position of the firebox.
7
170mm
Fan Unit
Outer Cavity Wall
Inner Cavity Wall
False Chimney / Fireplace
Maximum Installation Depth From Mounting Face of Fire Surround to Outer Face of Cavity Wall = 870mm Minimum Installation Depth From Mounting Face of Fire Surround to Outer Face of Cavity Wall = 320mm
Minimum Hearth Forward Projection 300mm
Fig. 4
Fig. 5
To proceed with the installation when the above stated criteria have been satisfied :-
Mark out where possible, centrally beneath a block joint where the lintel is to be fitted. Unless lime mortar has been used it will be necessary to drill four holes with a masonary drill, then use a mechanical cutter such as a “shark saw” to cut out the correct size of slot in the inner leaf of brickwork for the lintel you have chosen to install. See fig. 6 below.
Fig. 6
Fit the lintel, ensure that it is bedded on mortar. Do not bed on a dry bed. Then remove all debris from the cavity and construct the opening to the minimum / maximum opening sizes as shown overpage (fig. 8) and in section 1.4, (fig. 3)
8
The Load Triangle - No Beam or opening permissible in this area
600mm load t
riangle
400mm interactive area
50mm Minimum Hearth Height
Opening Width 375mm Minimum 440mm Maximum
Opening Height 550mm Minimum 570mm Maximum
Lintel e.g. 750mm x 75mm
T
he Interactive Zone - Openings, beams or joists within this area n
eed to be assessed.
Firebox recess in wall
Remove any combustible material from within the area of the opening. No combustible material can be allowed to come into contact with any area of the appliance.
Fig. 7
1.7 HEARTHS
This appliance must only be installed on to a concrete or non-combustible hearth. The hearth material must be a minimum thickness of 12mm with the top surface at least 50mm above the floor. The hearth must be fitted symmetrically about the fire opening and have a minimum width of 760mm and a minimum projection of 300mm forwards from the fire opening. If the black spacer frame is used, the hearth projection forward from the fireplace opening will require to be 350mm.
9
Opening Sizes Width :­375mm Minimum 440mm Maximum
Opening Sizes Height 550mm Minimum 570mm Maximum
Lintel must project Minimum 150mm each side of opening
Ensure that the recess of the fire­box is screed level so the firebox will sit level within the recess
1.8 SPILLAGE MONITORING SYSTEM
This appliance is fitted with an atmosphere sensing spillage monitoring system in the form of an oxygen sensing pilot. This is designed to shut the fire off in the event of a partial or complete blockage of the flue pipe causing a build up of combustion products in the room in which the fire is operated. The following are important warnings relating to this spillage monitoring system :-
1) The spillage monitoring system must not be adjusted by the installer.
2) The spillage monitoring system must not be put out of operation.
3) When the spillage monitoring system is exchanged only a complete original manufacturers part may be fitted. It is not possible to replace individual parts on the pilot system on this appliance, only a complete
pilot assembly (including the thermocouple) may be fitted.
10
SECTION 2
INSTALLATION OF FIRE
2.1 UNPACKING THE FIRE
Carefully lift the fire out of the carton. Remove the loose item packaging carefully from the front of the appliance. Check the contents as listed :-
Packing Check List
1off Fire box / burner assembly 1off Boxed fuelbed base, ceramic front rail and 18 synthetic coals 1off Loose items bag. 1off Flue Tube 1off Fan Unit 1off Flue Collar & Seal 1off Cable Fixing Kit 1off each User instruction book and Installation book
2.2 MARKING THE FIREBOX RECESS
Drill a pilot hole into the outer leaf of brickwork at a height of 482mm from the hearth level, centrally about the firebox, then using a core drill, drill a hole of 150mm (6 inch) diameter, centrally about the horizontal line drawn above the level of the hearth, and vertically central to the centre line of the appliance. See fig. 8 below.
NOTE : If the fire is to be fitted against the inner cavity wall, the inner and
outer cavity walls will require drilling.
Fig. 8
11
482mm to CRS
Hearth
Diameter 150mm (6 inch)
2 off diameter 25mm holes
IIIIMMMMPPPPOOOORRRRTTTTAAAANNNNTTTTNNNNOOOOTTTTEE
EE
::
DO NOT FIT THIS APPLIANCE FAN UNIT ABOVE A HEIGHT OF 1.4M FROM GROUND LEVEL
2.3 FITTING THE FAN UNIT / FIREBOX
a) Remove the 7 outer case fixing screws which hold the fan unit cover in
place. See fig. 9 below.
Fig. 9
b) Remove the fan mounting plate from the main body of the fan unit by
removing the four screws from the fan unit as indicated below in fig. 10
Fig. 10
7 off Outer Case Fixing Screws
4 screws to remove fan unit from mounting plate
12
Loading...
+ 28 hidden pages