Kimray BK2800 Programming & Installation Manual

Contents
Introduction 1 Specications 2 Programming Mode 2 Additional Input Options 5 Wiring Diagram 6 Troubleshooting 7 Installation Drawing 10 Part Numbering Information 11
BK2800 Flow Monitor
Model 2800
Programming & Installation Manual
Kimray.com
IM:0021 July 2017
Kimray reserves the right to make any changes or
improvements to the product described in this manual at any
Note
time without notice.
Introduction
The BK2800 Flow Monitor is a state-of-the-art, microprocessor
based ow monitor, designed to provide the user with exceptional exibility at a very affordable price. Though designed for use with Kimray Flow Meters, this display can be used with almost any ow meter producing a low amplitude AC output or contact closure signal(s). This ow monitor is capable of accepting a low-level frequency input for calculating ow rate and total. These calculations can then be displayed in the desired units of measurement. All B2800 ow monitors come pre-calibrated, from the factory, if ordered with a Kimray Flow Meter. If required, however, it can easily be re-congured in the eld. The monitor’s large 8 digit by .75” numeric liquid crystal display makes extended range viewing practical. The second 8 digit by .38” alphanumeric display provides for selectable units viewing in run mode and prompts for variables in programming mode. Finally, the user can choose between displaying rate, total, or alternating between both rate and total.
Kimray is an ISO 9001- certied manufacturer. Kimray quality assurance process maintains strict controls of materials
Kimray is an ISO 9001- certied manufacturer. Kimray quality assurance process maintains strict controls of materials
and the certication of parts used in Kimray electronic level switch.
and the certication of parts used in Kimray electronic level switch.
1
BK2800 Flow Monitor
Programming & Installation Manual
Specications Operating the Monitor
The monitor has two modes of operation referred to as the RUN mode and
Power Supply Options:
Battery Powered: 1 “D” size 1.5 Volt alkaline battery Loop Powered: Optional 4-20 mA loop power
Alphanumeric Rate and Total Display:
8 digit, .75” high numeric display 8 character, .38” high alphanumeric display Fixed or toggle modes of operation for ow rate and totalizer display
Accuracy:
±0.1% Temperature Drift = 50ppm/°C (Max)
Mounting Classication:
Meter Mount: NEMA 4X Enclosure Remote Mount: NEMA 4X Enclosure Swivel Mount: NEMA 4X Enclosure
Environmental:
Operating Temperature: -22 ºF to 158 ºF (-30 ºC to 70 ºC) Humidity: 0-90% Non-condensing
Inputs:
Magnetic Pick-up input:
Frequency range = 0 to 3500 Hz Trigger sensitivity = 30 mV p-p Over voltage protected = ±30 VDC
Outputs:
Opto-isolated open collector transistor Max. Voltage: 30 VDC Pulse width: 20mS/Max rate 20Hz Current (ON state): 0.9V drop @ 5.0 mA or 0.7V drop @ 0.1 mA Optional 4-20 mA output
the PROGRAM mode. Both the run mode and the program mode display screen enunciators conrming the state of the monitor. A quick glance at the lower left hand corner of the LCD screen will conrm operating status. Normal operation will be in the RUN mode. To access the programming mode, press the MENU button until the rst programming screen is displayed. After programming the display with the necessary information, a lock out feature can be turned on to prevent unau­thorized access or changing the meter’s setup parameters.
Programming Mode
Keys:
MENU – Switches to Programming mode UP Arrow – Scrolls forward through the parameter choices
and increments numeric variables RIGHT Arrow – Scrolls backward through the parameter choices and moves the active digit to the right ENTER – Used to save programming information, advance to the next programming parameter, and in the reset process
Modes:
RUN – Normal operating mode PROGRAM – Used to program variables into the display
If your monitor was ordered with a Kimray ow meter, the two components ship from the factory, calibrated as a set. If the monitor is a replacement, the turbine’s K-factor has changed, or the monitor is being used with some other pulse generating device, programming will be necessary.
Model 2800
Kimray.com
Certications:
CSA: Class I, Div 1 Groups C, D; Class II, Div 1 Groups E, F, G UL: Class I, II, III Div 1 Groups C, D CE: IEC 61326-1
Kimray is an ISO 9001- certied manufacturer. Kimray quality assurance process maintains strict controls of materials
and the certication of parts used in Kimray electronic level switch.
2
BK2800 Flow Monitor
Model 2800
Programming & Installation Manual
Kimray.com
Programming Using Pulse Output Turbine Flow Meters
Each turbine ow meter is shipped with either a K-factor value or frequency data. If frequency data is provided, the data must be converted to a K-factor before programming the monitor. Kfactor information, when supplied, can usually be found on the neck of the ow meter or stamped on the body. The K-factor represents the number of pulses per unit of volume. The K factor will be needed to program the monitor readout.
Enter Programming Mode
Change to programming mode by pressing the MENU button once. The mode indicator will change from RUN to PROGRAM.
The meter connection size and the bore size are different.
Note
For example, many of the 1” NPT turbines have bore sizes that
range from 3/8” up to 1”. Be sure to use the correct bore size
or the meter will report incorrect ows and totals.
Enter the Meter’s K-Factor Unit
Directly after the METER size is selected, the display’s K-factor unit must be chosen. Use the UP arrow key to select your K-factor unit. For meters calibrated in gallons, use PUL/GAL (pulses per gallon), for meters calibrated in cubic meters, use PUL/ M3 (pulses per cubic meter), etc. Press ENTER to save the Kfactor unit and advance to the next parameter.
Note
Unless otherwise specied, Kimray turbine ow meters
are supplied with K-factors measured in pulses per
gallon (PUL/GAL) which will automatically convert to
your desired units of measure.
Note
The K-factor supplied with the meter or calculated
from calibration data will be needed to complete next step.
Select the Meter Size
At the METER prompt, press the UP or RIGHT arrow keys to select the bore size of your meter. Press ENTER button once to save me­ter size choices and advance to the K-factor units selection.
Kimray is an ISO 9001- certied manufacturer. Kimray quality assurance process maintains strict controls of materials
and the certication of parts used in Kimray electronic level switch.
Enter the Meter’s K-Factor
To change the KFACTOR value, use the RIGHT arrow key and select the position of the number that you wish to change. Using the UP arrow key, increment the display digit until it matches the meter’s K-factor digit. Repeat this process until all K-factor digits have been entered. Press ENTER once to save the K-factor and advance to the RATE/TOTAL Units selection.
Select the Rate/Total Units of Measure
The monitor allows the choice of ve common rate/total units. The monitor shows the rate/total unit that the display is currently set for. If the current selection is current, press the ENTER key once to ad­vance to the next parameter. To change to an alternate unit, use the arrow keys to scroll to the desired rate unit and press ENTER to save the choice.
3
BK2800 Flow Monitor
Programming & Installation Manual
SELECTION RATE TOTAL
GPM/GAL Gallons per Minute Gallons
LPM/LIT Liters per Minute Liters
M3PH/M3 Cubic Meters per Hour Cubic Meters
M3PD/M3 Cubic Meters per Day Cubic Meters
BPD/BBL Oil Barrels per Day Oil Barrels
Model 2800
Kimray.com
The total unit’s output multiplier cannot be modied
in the Simplied program level. This option is reserved
in the Advanced program level.
Note
Select the Display Function
The monitor can display RATE or TOTAL or alternate between BOTH rate and total. If the current selection is correct, press the ENTER key to advance to the next parameter. To change to an alternate display mode, use the arrow keys to scroll to the desired display mode and press ENTER to save the choice.
A TEST function is also available in the Display Function sub
-menu. With the test function selected the display acts like a frequency counter and displays the raw input frequency being supplied to the frequency input terminals. This is very useful when troubleshooting ow problems.
Totalizer Pulse Output
The pulse output parameter can be either enabled or disabled. When enabled this output generates 20mS duration pulse for every time the least signicant digit of the totalizer increments. The amplitude of the pulse is dependent on the voltage level of the supply connected to the pulse output and is limited to a max. 30 VDC.
Password
Password protection prevents unauthorized users from changing programming information. Initially, the password is set to all zeros. To change the password, simply enter any 4 digit code using the arrow keys as previously described, enter the password value. Pressing ENTER once will store the password and take you back to the RST PSWD screen.
Kimray is an ISO 9001- certied manufacturer. Kimray quality assurance process maintains strict controls of materials
and the certication of parts used in Kimray electronic level switch.
4