Pressure • Temperature • Humidity • Air Velocity • Airflow • Sound level
TG 100
duct mount
TG 100
Pt 100 on terminal block
(probe in option)
Part number
To order, just add the codes to complete the part number :
Transmitter / power supply / output
VActive • 24 Vac/Vdc • 0-10V
A Passive • 18/30 Vdc • 4-20 mA
Display
OWith display
NWithout display
Mounting
ADuct mount
BTerminal block
w
w
e
Temperature transmitter
N
N
e
TG 100
• Duct temperature transmitter, TG100 type
• Measuring ranges from 0 to +50°C, -20 to +80°C, -50 to +50°C, 0 to +100°C,
0 to 200°C, 0 to +300°C, 0 to +400°C (according to model, see “Configuration”)
• 0-10 V output , active sensor, power supply 24 Vac/Vdc (3-4 wires) or
4-20 mA output , passive loop, power supply 18 to 30 Vdc (2 wires)
• ABS IP 65 housing, with or without display
• Quick and easy mounting “1/4 turn” system with wall-mount plate
Features of the transmitter
Temperature
Working principle : Pt100 is a resistance with a positive
coefficient which varies according to the temperature. The higher the
temperature is, the more the value of the resistance increases.
Example : for 0°C 100 - for 100°C 138,5
Measuring range ......................see chart ”Configuration”
Units of measurement .............°C, °F
Accuracy * ................................±0,5% of reading ±0,4°C (duct mount probe)
according to the probe (Pt 100 on terminal block)
Response time .........................1/e (63%) 5 sec. (duct mount probe)
according to the probe (Pt 100 on terminal block)
Resolution ................................0,1°C
Type of sensor..........................Pt 100 class A as per DIN IEC751
Type of fluid............................ air et neutral gases
WITH or WITHOUT display
e temperatur
TG100
Example : TG100-VOA
Model : temperature transmitter TG 100 active sensor 0-10 V output, with
display and duct mount probe.
Output / power supply....active transmitter 0-10 V (power supply 24 Vac/Vdc ±10%), 3-4 wires
..........................................
..........................................
..........................................
Consumption ....................................2 VA (0-10V) or max. 22 mA (4-20mA)
Electro-magnetical compatibility.......EN 61326
Electrical connection .......................
Communication to PC ...................... Kimo RS 232 cable
Working temperature (housing)..........0 to +50°C
Working temperature (probe).............-20 to +80°C (duct mount probe)
Storage temperature ........................-10 to +70°C
Environment .....................................air and neutral gases
passive loop 4-20 mA (power supply. 18/30 Vdc), 2 wires
maximum load : 500 Ohms (4-20 mA)
minimum load : 1 K Ohms (0-10 V)
screw terminal block for cables Ø 1.5 mm² max
according to the probe (Pt100 on terminal block)
*All the accuracies indicated in this technical datasheet were stated in laboratories conditions, and can be guaranted for
measurements carried out in the same conditions, or carried out with calibration compensation.
Connection
For the models
TG 100 - VOA, TG 100 - VNA • Output
active sensor
Connection
to PC
LCC 100
software
c
Power supply
b
e
Cable tubing
Vdc...........direct voltage
GND.........ground
a
OR
Vac...........alternative voltage (phase)
b
Vac...........alternative voltage (neutral)
For the models
TG 100 - AOA, TG 100 - ANA
Output 4-20 mA - passive loop
Vdc...........direct voltage
a
IT ..............direct current (temperature)
0-10 V
Power supply
terminal block
Output
GND .................ground
Vdc T................direct voltage (temperature)
Cable grip : to insert the cable, it is required to
c
slightly cut the rubber.
a
Terminal block
d
DIP switch
a
Output
terminal block
b
For the models
TG 100 - VOB, TG 100 - VNB • Output 0-10 V - active sensor
Connection
to PC
e
LCC 100
software
Cable grip
c
Output
a
GND .................ground
Vdc T................direct voltage
For the models
TG 100 - AOB, TG 100 - ANB
Output 4-20 mA - passive loop
Vdc...........direct voltage
a
IT ..............direct current (temperature)
2’ 2 1
f
(temperature).........................
terminal block
a
Pt100
b
b
Terminal
block
Power supply
Vdc...........direct voltage
GND.........ground
OR
Vac...........alternative voltage (phase)
Vac...........alternative (neutral)
2’ 2 1
f
d
DIP switch
a
Output
terminal block
b
Power supply
terminal block
f
Pt100
terminal block
Electrical connection - as per norm NFC15-100
This connection must be made by a qualified technician. To make the connection, the transmitter must not be energized.
It is possible to configure the measuring ranges, the units, the output of the transmitter (according to the model) either by DIP switch
e
and/or via software (connections and on drawing “connection)
d
Configuration by DIP switch
To configure the transmitter, please unscrew the 2 screws from the housing,
and then open it.
Electronic
board
d
DIP
switch
On-off switch
• Units setting
To set the measuring unit, please put the on-off switch 4 of
units, as shown beside.
Identification of
DIP switch on the board
1
2
}
Measuring range
setting
3
4
DIP switch
Units setting
To configure the transmitter, it must not be
energized. Then, you can make the settings
required, with the DIP switches (as shown on the
drawing beside). When the transmitter is
configured, you can power it up.
!
Caution !
Please follow carefully the combinations beside with the
DIP switch.
If the combinations are wrong, the following message will
appear on the display of the transmitter “CONF ERROR”.
In that case, you will have to unplug the transmitter, place the
DIP switches correctly, and then power the transmitter up.
Configurations
Combinations
°C°F
1
2
3
4
1
2
3
4
Pt 100 on terminal block
0 to 200 °C
1
2
3
4
• Measuring range setting
To set the measuring range, please
put the on-off switches 1, 2 and 3 of
the measuring range, as shown
beside.
Configurations
Combinations
Measuring range
duct mount
0 to 50 °C -20 to 80 °C -50 to 50 °C 0 to 100 °C
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
Initialization the transmitter
When the transmitter is powered up, it initializes and displays the digits and then its configuration including :
- the measuring range- the analog output.
1- The measuring range
The following message is displayed : . This is the low value of the measuring range, and its digit value : ex :.
The following message is displayed : . This is the high value of the measuring range and its digit value : ex :.
The arrow displayed (at the bottom or on the right of the screen) is relative to the unit of measurement : ex : from 0 to 400 °C.
2 - The analog output
If the analog output is in 4-20mA, then the following message will appear .
If the analog output is 0-10 V, then the following message will appear .
L
H.
0.0.0.0.0
0. .0.- 0
,
0
4 0 0. .
4 - 2 0 A. . . .
Measuring range
0 to 300 °C
1
2
3
4
0 to 400 °C
1
2
3
4
After the display of the configuration, the transmitter displays , which confirms that the initialization is finished and you can start the measurements.
An easy and friendly configuration with the software !
You can configure your own intermediary ranges.
Example : for a transmitter with a range of -100 to +400°C, the minimum configurable range is 20°C.
For example, you can configure your transmitter with a range from -20 to +380°C, or from +300 to
+320°C...
• To access the configuration via software, you must first position the DIP switches as per the
following picture (shown beside), and then connect the cable to the transmitter (see beside and see
“Connection”).
• Please refer to the user manual of the LCC 100 to make the configuration.
!
Caution !
The configuration of the parameters can be done either with the DIP switch, or via software (you
cannot combine both solutions).
1
2
3
4
DIP switch
Mounting
Installation : mount the ABS plate on the wall (this plate is supplied
with the transmitter). Drilling : Ø 6 mm (with the screws and pins
supplied with the transmitter). Insert the transmitter on the plate (see
A on the drawing beside) and rotate its housing in clockwise direction
until you hear a “click” which confirms that the transmitter is correctly
installed.
For the model with duct mount, an additional drilling of Ø14mm must
be done before mounting the ABS plate.
Maintenance
Please avoid any aggressive solvent.
Please protect the transmitter and its probes from any
cleaning product containing formol, that may be used
for cleaning rooms or ducts.
Options
Power supply class 2, input 230 Vac,
output 24 Vac, ref.KIAL-100A
Configuration LCC 100 software with RS
232 cable
Temperature probes Pt100 3 wires (for
model TG 100 on terminal block)