FTang – transmitter_CP111-112-113 – 12/11/13 – RCS (24) Périgueux 349 282 095 Non-contractual document – We reserve the right to modify the characteristics of our products without prior notice.
MOUNTING
To mount the transmitter, mount the ABS plate on the wall (drilling : Ø6 mm, screws and pins are
supplied).
Insert the transmitter on the fixing plate (see A on the drawing beside). Rotate the housing in
clockwise direction until you hear a “click” which confirms that the transmitter is correctly installed.
Once the transmitter is installed and powered up, please make an autozero to
guarantee the correct working of the transmitter in any position.
MAINTENANCE
Please avoid any aggressive solvent. Please protect the transmitter and its probes from any cleaning product containing formalin, that may be used for cleaning
rooms or ducts.
OPTIONS AND ACCESSORIES
●
KIAL-100A : Power supply class 2, 230 Vac input, 24 Vac output
●
KIAL-100C : Power supply class 2, 230 Vac input, 24 Vdc output
●
LCC-S : configuration software with USB cable
●
Connection tube
●
Connection fittings
●
Through-connections
●
Straight connections
●
Spherical coupling nut
➢
Standard range / central zero setting – left DIP switch
To set the type of measuring range, put the on-off switch 4 as indicated beside :
Configurations Full scale Central zero
Combinations
Example 0-100 Pa: Full scale / 0
Central zero
(0 / 100 Pa)
(-50 Pa / 0 / +50 Pa)
➢
Output setting – right DIP switch (CP111/112/113 – AO and CP111/112/113 – AN models)
To set the type of analogue output, please put the on-off switch of the output as shown
beside.
➢
Units setting – right DIP switch
To set a measurement unit, put the on-off switches 2, 3 and 4 of the units as shown in the table below .
Please follow carefully the combinations beside with the DIP switch. If the combination is wrongly done, the following message will appear
on the display of the transmitter “CONF ERROR”. In that case, you will have to unplug the transmitter, place the DIP switches correctly, and
then power the transmitter up.
Configurations Pa
mmH2O
mbar InWG mmHG daPa kPa hPa
Combinations
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
1
2
3
4
An easy and friendly configuration with the software !
You can configure your own intermediary ranges.
Caution : the minimum difference between the high range and the low range is 20.
For example, it is possible to set the instrument from -20 to 0 Pa, from 0 to +20 Pa, or from -10 to +10 Pa...
• To access the configuration via software :
- Set the DIP switches as shown beside. Nota : the on-off switch 1 of the right DIP switch can be in
any position (selection of the analogue output 0-10 V or 4-20 mA)
- Connect the cable of the LCC-S to the connection of the transmitter.
• Please refer to the user manual of the LCC-S to make the configuration.
CONFIGURATION VIA LCC-S SOFTWARE (option)
1
2
3
4
Left DIP switch
1
2
3
4
Right DIP switch
The configuration of the parameters can be done either with the DIP switch or via software (you can not combine both solutions).
Configurations 4-20 mA 0-10 V
Combinations
2
3
4
1
2
3
4
1
Configuration via PC
7.5 mm
8 mm
4.5 mm
40 mm
50 mm
68 mm
75 mm
37.5 mm
23.75 mm
14 mm
A
A