Kimo Class 300 User Manual

User Manual
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
Configuration of TransmittersClass 300
N
e
e
w
w
Keypad Keypad
TH300 >
Remote probe
Remote controlRemote control
Temperature
Humidity
TH300 >
Standard probe
Modbus networkModbus network
Air velocity
CTV310 >
Standard probe
Temperature
< TT300
Remote probe
CP300 >
Pressure
TT300 >
Standard probe
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
Summary
TRONIC
1. Prerequesite.......................................................................................P 1
1.a - Working principle
1.b - Output signal selection
1.c - Protection tip of the sensor
2. Modbus parameters ............................................................................P 3
2.a - Configuration parameters
2.b - Modbus functions
2.c - Register access security key
3. Activation code and access to functions...............................................P 5
4. Display and keypad configuration • F100 ...........................................P 6
4.a - Transmitter channel for infrared remote control
4.b - Backlight
4.c - Display contrast control
4.d - Keypad locking
4.e - Slave addressing (Modbus)
5. Configuring channels and units of measurement • F200......................P 9
6. Analogue output management • F300...............................................P 10
6.a - Output diagnostics
6.b - Analogue outputs setting
........................................................................P 1
..................................................................P 2
.............................................................P 2
...............................................................P 3
........................................................................P 3
...........................................................P 3
.......................................P 6
.................................................................................P 6
.................................................................P 7
..........................................................................P 7
.............................................................P 8
.....................................................................P 11
..............................................................P 12
SEN
7. Alarm / Relay settings • F400 ...........................................................P 14
7.a - Activation / Deactivation of BEEP alarm
7.b - Relay security
..........................................................................P 14
7.c - Alarm / relay functions and LED colour codes
7.d - Channel selection for alarms / relays
7.e - Alarm mode details
7.f - Alarm mode selection
.....................................................................P 17
..................................................................P 19
7.g - Set points and time-delay setting
..............................................P 14
.......................................P 15
.................................................P 16
.....................................................P 20
8. Pressure measurement configuration • F500 ....................................P 22
8.a - Pressure measurement integration (CP 300)
8.b - Time-delay between 2 self-calibrations (CP 300)
........................................P 22
....................................P 22
9. Humidity measurement configuration • F500 ....................................P 23
9.a - Humidity and temperature offset adjustment (TH 300)
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
..............................P 23
mailbox@sentronic.com
www.sentronic.com
Summary
TRONIC
10. Air velocity measurement configuration (CP300 + SQR) • F600 ........P 24
10.a - Temperature compensation
10.b - Air velocity coefficient selection
10.c - Air velocity correction coefficient input
11. Airflow measurement configuration • F600 .....................................P 28
12. Other functions................................................................................P 31
12.a - Activation / Deactivation of the RS 232 and home bus
12.b - Serial number display
12.c - Modification of Modbus communication speed
12.d - Purge Mode
...........................................................................P 33
13. Error codes .....................................................................................P 36
14. Functions recap...............................................................................P 37
.........................................................P 24
......................................................P 26
..............................................P 27
............................P 31
................................................................P 31
.....................................P 32
SEN
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
1. Prerequisite
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
1.a - Working principle
Using keypad / remote control / Modbus configuration, you can activate (or deactivate) a channel, change the measuring range, set the set points and time-delay...
Principle: the configuration options are accessed via folders and sub-folders (similar to Windows ). Access is
®
made via a numerical code (full details in this manual).
Visual alarm LED
AL1 AL2
Graphic display
R
CODE:
0000
Infrared receiver
Keypad
1.a.1 - Keypad
R
AL1 AL2
CODE:
0000
Meaning of the keys
To increment a value or a level
To decrement a value or a level
To validate an input
To cancel an input or to return to the previous step
Class 300 transmitter configuration via keypad / remote control / Modbus
Page 1
1. Prerequesite
TRONIC
1.a.2 - Infrared remote control
The remote control works like the keypad and the configuration method remains exactly the same whichever you use (keypad or remote control).
=
Meaning of the remote control keys
To increment a value or a level
To decrement a value or a level
To validate an input
To cancel an input or to return to the previous step
Channel selector
With this selector, you can swap the transmission channel so that it matchs with the transmitter reception channel. See page 6 to configure the transmitter reception channel.
1.b - Output signal selection
Voltage or Current ?
The Class 300 can output either a voltage or a current signal.
Page 2
SEN
1.c - Protection tip of the sensor
It's extremely unwise to remove the protection tip of our hygrometry probes as the sensitive element is very fragile even to light contacts. However, if you have to remove the protection tip, take all possible precautions and avoid any contact with the sensitive element.
!
To remove the protection tip, unscrew it or unclip it.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
With the on-off switch located on the left top of the transmitter (when open), you can choose analogue output 0-10V (voltage) or 4-20 mA (current)
Protection tip to unscrew
Protection tip to unscrew
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
Down
0-10 V
Up
4-20 mA
Sensitive element
Sensitive element
mailbox@sentronic.com
www.sentronic.com
2. Modbus parameters
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
2.a - Configuration parameters
Communication speed. . . . . . . . . . . . . . . . . . . . . 19200 Bauds (see page 33 to configure the speed)
Data bits. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 bits
Stop bit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 bit
Parity. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . None
Flow control. . . . . . . . . . . . . . . . . . . . . . . . . . . . . None
Transmitter addressing. . . . . . . . . . . . . . . . . between 1 and 255
default address “0” for single ended bus configuration
to change the addressing, see page 8.
2.b - Functions
Register reading . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function 03
Register writing. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Function 16
Communication loop test . . . . . . . . . . . . . . . . . . . . . Function 08
2.c - Access codes to Registers
Registers type . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . Signed long integer (32 bits), permuted (LSB, MSB)
• Alarms status - Modbus code : 1436
Ex. The value sent by the transmitter is 5 Alarm condition 1 and relay 1 excited
• Values - Modbus code : 1438 (channel 1)
1442 (channel 2) 1446 (channel 3 or value 1 of the external transmitter) 1450 (channel 4 or value 2 of the external transmitter)
Ex. the value sent by the transmitter is 6321
b31
Relay 2
Relay 1
...
b4 b3 b2 b1 b0
0 1 0 1
Alarm 1
Alarm 2
• Values formatting - Modbus code :
1440 (channel 1) 1444 (channel 2) 1448 (channel 3 or value 1 of the external transmitter) 1452 (channel 4 or value 2 of the external transmitter)
...
b31
Units of measurement
1 m/s 12 mmH O
2 fpm 13 inWg
3 m3/h 14 Kpa
4 L/s 15 mmHg
5 cfm 16 mbar
6 m3/s 17 g/kg (absolute humidity.
7 °C 18 °C (dew temp. Td)
8 °F 19 °F (dew temp. Td)
9 %RH 20 °C (wet temp. Tw)
10 PSI 21 °F (wet temp. Tw)
11 Pa 22 KJ/Kg (Enthalpy i)
Class 300 transmitter configuration via keypad / remote control / Modbus
2
ñ)
b12 b11 b10 b9 b8 b7
0 0 0 1 0 0 0 0 1 1 0 0
Nr of digits after the comma
Value sign (0=>+, 1=> -)
Ex. The formatting displayed is 268.
Unit of measurement => 12 (see chart) Figure(s) after the comma => 1 Sign => positive
If the value measured is equal to 6231 :
Result => 623,1 mmH O
b5 b4 b3 b2 b1 b0
b6
Unit of measurement (see chart)
2
Page 3
2.c - Access code to Registers (sequel)
TRONIC
• Serial number of sensing element (SPI - CP300 / Humidity - TH300)
Modbus code: 1402
2. Modbus parameters
Other access codes to different registers are indicated on each function at stage n°2.
Shown as this pictogram:
b
d
u
o
s
M
202
Page 4
SEN
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
3. Activation code and access to functions
TRONIC
This step is COMPULSORY for each configuration.
!
To access the transmitter functions, and for safety, you have to first enter a safety code.
• Please check that the transmitter is powered on.
• If the transmitter displays an error code, please see “Errors Code” section on page 35
Step 1
Press on to get this screen
CODE:
0000
Step 2
Enter the CODE “0101” with the keypad and validate with
CODE:
0101
Step 3
This screen appears:
100
The first “0” blinks, which means that this column is activated and you can enter data from the keypad.
The code must be entered from left to right. To increment a value or a level, press
To decrement a value or a level, press To validate a value (level) or to validate the code, press To return to the previous status or to cancel, press
This screen confirms that the code was correctly entered, and that you can
configure the transmitter.
If the code was wrongly entered, the transmitter initializes and returns to the
starting display.
100
Configuration folder number
The transmitter includes 6 folders maximum::
• 100 • 400
• 200 • 500
• 300 • 600
Ex. In the folder 400, you can configure the alarms and relays. See page 14.
SEN
Step 4
Configuration folder selection
100
F 102
>
05
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
To select your configuration folder, press to increment 100 or press to decrement 100.
Once the folder is selected, press to validate.
On the top left of each page of this manual, you can find a reminder of the configuration folder where the function is available.
F400
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
Page 5
www.sentronic.com
F100
TRONIC
4. Display and keypad configuration
4.a - Transmitter channel for infrared remote control
You can change the channel number for receiving the signal from the infrared remote control.
The advantage is that only one remote control is required to drive several transmitters, and that there
is no interference if 2 transmitters are located side by side.
By default, the channel number is 0.
Step
Step
2
Step
3
Step
4
1
100
100
F 100
>
>
>
00
F 100
03
F 100
03
Go into the configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “100” and validate with .
Select the sub-folder “100” and validate with . The cursor
> goes to the line of available choices.
With and keys, select the channel number (from 00 to 09). Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode
• press once to select another folder.
• with and keys, you can choose another sub-folder from the folder 100.
4.b - Backlight
With the backlight, the reading is easier with more contrast, if the ambient light is weak. You can activate or deactivate it.
Step
Step
2
100
1
100
F 101
>
01
Go into the configuration mode (see page 5). The folder number displayed corresponds to the last folder used.
Select the folder “100” and validate with .
Select the sub-folfer “101” and validate with . The cursor
> goes to the line of available choices.
o
M
200
o
M
202
b
d
u
s
b
d
u
s
Page 6
SEN
Step
3
Step
4
F 101
>
>
01
F 101
01
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
With and keys, select 00 to deactivate the backlit or 01 to activate. Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to select another folder.
• with and keys, you can choose another sub-folder from the folder 100.
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
F100
TRONIC
4.c - Display contrast control
Step
100
1
Go into configuration mode (see page 5). The folder number which appears corresponds to the last configuration folder used.
4. Display and keypad configuration
Step
2
Step
3
Step
4
100
F 102
>
>
>
05
F 102
08
F 102
08
Select the folder “100” and validate with .
Select the sub-folder “102” and validate with . The cursor
> goes to the line of available choices.
With and keys, set the contrast required (from 0 to 10). Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from folder 100.
4.d - Keypad locking
For safety, you can lock the keypad access. Like on a mobile phone, the keys will be disabled after having been locked.
Step
Step
2
1
100
100
F 104
>
01
Go into configuration mode (see page 5). corresponds to the last folder used.
Select the folder “100” and validate with .
Select the sub-folder “104” and validate . The cursor
> goes to the different choices available.
The folder number which appears
o
M
204
o
M
208
b
d
u
s
b
d
u
s
SEN
Step
Step
3
4
F 104
>
>
01
F 104
01
With and keys, select 01 to lock the keypad access or 00 if you do not want to lock the keypad. Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys to choose another sub-folder from the folder 100
To unlock keypad access, press and hold the key for 10 seconds.
!
After 10 seconds, an audible signal confirms that the keypad is unlocked.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
Page 7
www.sentronic.com
F100
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
4. Display and keypad configuration
4.e - Slave addressing (Modbus)
Step
100
1
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Step
2
Step
3
Step
4
100
F 106
>
F 106
>
>
23
F 106
23
01
Select the folder “100” and validate with .
Select the sub-folder “106” and validate with .
o
M
212
b
d
u
s
The cursor > goes to available choices.
With and keys, set the slave addressing number (from 1 to 255). Validate with .
The cursor > goes to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys to choose another sub-folder from the folder 100.
Page 8
Class 300 transmitter configuration via keypad / remote control / Modbus
F200
TRONIC
5. Configuring channels and units of measurement
Class 300 transmitters have 4 measuring channels. You can activate 1, 2, 3 or 4 channels and select each unit of measurement.
Step
200
1
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Step
2
Step
3
200
F 200
>
04
F 201
>
06
Select the folder “200” and validate with .
Channel 1 Channel 2 Channel 3 Channel 4
Select sub-folder 200 201 202 203 and validate with . The
cursor
> goes to choices line.
o
M
400
b
d
u
s
b
d
u
o
s
M
b
d
u
o
M
402 404 406
With and keys, select the unit of measurement (see chart below). Validate with .
CP 301, 302 et 303 CP 304 TH 300
00 Inactive channel
01 Pa Pa °C °C m/s
02 mmH O mmH O °F °F fpm
03 inWg inWg %HR °C
04 mbar mbar g/Kg (Hygro. absolue °F
05 °C mmHg °C (Temp. de rosée Td) m /h
06
07
08 fpm m/s °F (Temp. humide Tw) m /s
09 m /h fpm KJ/Kg (Enthalpie i)
10 L/s m /h
11 cfm L/s
12 m /s cfm
13 m /s
2
°F °C °F (Temp. de rosée Td) L/s
m/s °F °C (Temp. humide Tw) cfm
3
3
Inactive channel Inactive channel Inactive channel Inactive channel
2
3
3
TT 300 CTV 310
ñ)
b
d
u
s
o
s
M
3
3
SEN
For a CP 300 transmitter (301, 302, 303 and 304),the SQR option is required in order to activate the units of air velocity and airflow.
Step
4
F 201
>
06
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys to choose another sub-folder from the folder 200.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
Page 9
www.sentronic.com
F300
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
6. Analogue output management
6.a - Output diagnostics
With this function, you can check with a multimeter (or a regulator/display, or a PLC/BMS) if the transmitter outputs are working properly. The transmitter generates a voltage of 0 V, 5 V and 10 V or a current of 4 mA, 12 mA and 20 mA.
6.a.1 - Multimeter connection configuration
Before carrying out the output diagnostics, all connections and configurations of the transmitter must be
enabled, to avoid any damage on the transmitter and the multimeter !
Step
Selection of the channel
1
to be checked
First, select a channel for the output diagnostics.
The channel numbers are indicated on the board located below the terminal block.
Step
2
Example of connection
On the photo alongside, the multimeter is connected to the 0-10 V output and channel n°1.
Analogue output 1
Analogue output 2
Channel n°1
Relay 1
Channel n°2
Relay 2
Page 10
..............voltage
0-10 V
GND.................ground
4-20 mA ...........current
B-A
+
0-10 V ..............voltage
GND.................ground
4-20 mA ...........current
NO .............normally open
COM ..........common
NC .............normally closed
Class 300 transmitter configuration via keypad / remote control / Modbus
NO .............normally open
COM ..........common
NC .............normally closed
24 Vdc / ac
[
230 Vac 115 Vac
The ticked box shows the power supply type of the transmitter (230 Vac shown above).
F300
TRONIC
6. Analogue output management
6.a.2 - Output diagnostics
Once the connection of the transmitter to the multimeter (or regulator or PLC/BMS is complete, (see page
6), you can carry out the analogue output diagnostics on several check points.
Step
100
1
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Step
2
Step
3
>
>
!
300
F 300
00
Select the folder “300” and validate with .
b
d
u
o
s
Channel n° 1 output
Select sub-folder “300
M
600
Channel n° 2 output
Select sub-folder “303
and validate with .
F 300
01
The cursor
With and keys, select the signal that the transmitter must output (see chart below). Note : no need to validate with .
> goes to available choices.
Diagnostic Output
00 0 V
01 5 V
02 10 V
03 4 mA
04 12 mA
05 20 mA
If the deviations are too big (>0,05V or >0,05mA) between the signal issued and the value displayed on the multimeter, we recommend that you return the transmitter to
our factory.
o
M
606
b
d
u
s
SEN
Step
4
F 300
>
01
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys to choose another sub-folder from the folder 300.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
Page 11
www.sentronic.com
F300
TRONIC
6. Analogue output management
6.b - Analogue output settings
With this function, you can modify the measuring range of the transmitter, and you can equate the new limits to the analogue output (0-10V or 4-20mA).
You can enter the measuring range required on your own !
You must enter the values according to the units of measurement selected, not
!
according to the measuring range of the transmitter.
Eg. on a CP 303 pressure transmitter (0 to ±1000 Pa) with a reading in mmH2O, the minimum and maximum ranges must be configured on measuring range of 0 to ±102 mmH2O. See conversion chart on following page.
Step
Step
2
1
100
300
F 301
>
-100
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “300” and validate with .
b
d
u
o
s
M
Minimum
Minimum of Channel n°1
output Select sub-folder “301
of Channel n°2
602
output Select sub-folder “304
and validate with . The cursor > returns to the input line.
Step
Step
3
4
F 301
>
-000100
F 302
>
+500
With and keys, select the value sign: negative or positive, validate with
. Then, enter the minimum limit value and validate with .
b
d
u
o
s
Maximum of Channel
output
Select sub-folder “302
n°1
M
Maximum of Channel n°2
604
Select sub-folder “305
output
and validate with . The cursor > goes to the input line.
Step
5
F 302
>
+000500
With and keys, select the value sign: negative or positive, validate with
.
Then, enter the maximum limit value and validate with .
We recommend that the interval between the minimum and maximum is > 5% of the measuring range.
!
Etape
Step
6
>
F 302
+500
The cursor > goes to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys you can choose another sub-folder from the folder
300.
After an analogue output setting, if the unit of measurement is modified (see page 5), you have to reconfigure the outputs according to the new unit of measurement.
M
608
o
M
610
b
d
u
o
s
b
d
u
s
Page 12
SEN
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
F300
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
6. Analogue output management
6.b.1 - Units of measurement conversion chart
Pressure
Pa mmH2O inWg mbar mmHg
CP 301 0 to ±100 0 to ±10,2 0 to ±0,401 0 to ±1,00 -
CP 302 0 to ±500 0 to ±51,0 0 to ±2,005 0 to ±5,00 -
CP 303 0 to ±1000 0 to ±102,0 0 to ±4,015 0 to ±10,00 -
CP 304 0 to ±10000 0 to ±1020,0 0 to ±40,01 0 to ±100,00 0 to ±75,00
Temperature
°C °F
TH 300 - Stainless steel probe -40,0 to +180,0 -40,0 to +356,0
TH 300 - PC probe -20,0 to +120,0 -4,0 to +248,0
TT 300 - Stainless steel probe -40,0 to +180,0 -40,0 to +356,0
TT 300 - PC probe -20,0 to +120,0 -4,0 to +248,0
CTV 310 0,0 to +50,0 32,0 to 122,0
Air velocity (CTV 310)
m/s fpm
CTV310 from 0,0 to 30,0 from 0 to 5905
Class 300 transmitter configuration via keypad / remote control / Modbus
Page 13
F400
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
7.a - Activation / Deactivation of BEEP alarm
The beep alarm (audible alarm) is activated when a set point is reached. For more details on the setpoint settings, see page 20.
7. Alarm / relay settings
Step
Step
2
Step
3
Step
4
1
100
400
F 400
>
>
>
01
F 400
01
F 400
01
Go into configuration mode (page 5). The folder number displayed corresponds to the last configuration folder used.
b
d
Select the folder “400” and validate with .
Select sub-folder “400” and validate with .
o
M
800
u
s
The cursor > goes to available choices.
With and keys, select 01 to activate the BEEP alarm or 00 to disactivate. Validate with .
The cursor > goes to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys you can choose another sub-folder from the folder 400.
7.b - Relay security
The relay outputs are by default, in negative security: the relay is energized when a set point is reached. With the keypad, you can swap the relays in positive security : then, the relay is de-energized when a set point is reached or during a power outage.
Step
Step
2
1
100
400
F 401
>
01
Enter in configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select folder “400” and validate with .
Select sub-folder “401” and validate with .
o
M
802
b
d
u
s
The cursor > goes to available choices.
Page 14
Step
3
Step
4
F 401
>
>
01
F 401
01
Class 300 transmitter configuration via keypad / remote control / Modbus
With the keys and , select 01 for a positive security or 00 for a negative security. Validate with .
The cursor > returns to sub-folders line.
• press twice on to return to reading mode.
• press once on to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder 400.
F400
TRONIC
7. Alarm / relay settings
7.c - Alarm / relay functions and LED colour codes
7.c.1 - Visual / audible alarms
Class 300 transmitters have 2 visual / audible alarms located in front of the transmitter, allowing to know the
condition of the setpoints.
Alarm n°2Alarm n°1
Green The alarm function is activated and
Red The alarm function is activated and
None The alarm function is not activated
Alarm LED colour codes
the set point is not reached
the setpoint is reached
The red LED appears when the setpoint is reached, taking into account the time-delay and the action type (falling or rising). See page 17 for more details.
Audible alarm
Once the alarm is activated, an alarm sounds whilst the setpoint is reached.
The BEEP alarm function must be activated to use the audible alarm. See page 14.
7.c.2 - The relays
Class 300 transmitters have 2 relays visible on the transmitter board. These 2 relays each have one LED to
allow real-time checking.
Relay n°1 LED
Relay n°1
Relay n°2
Relay n°2
LED
SEN
Red The relay is
None The relay
The relay is energized when the setpoint is reached, taking into account the time-delay, the action type and also the alarms security mode. Set points, time-delay and action type setting: see page 20 Alarm security settings : see page 14
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
Relay LED colour codes
energized
or has not been configured
is not energized
mailbox@sentronic.com
Page 15
www.sentronic.com
F400
TRONIC
7. Alarm / relay settings
7.d - Selection of the channel for visual and relays alarms
Class 300 transmitters have 4 alarms: 2 visual (LED) and audible alarms and 2 relay alarms. The transmitter can be
configured with 4 different alarms setups.
Before any alarm setup, check that the corresponding channel(s) is activated.
!
Step
Step
2
Step
3
Step
4
1
100
400
F 402
>
>
01
F 402
01
>
F 402
01
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “400” and validate with .
Select sub-folder
b
d
u
b
d
u
o
s
“402” “407” “412” “417”
Alarm 1 Alarm 2 Relay 1 Relay 2
M
804
o
M
814
s
o
M
824
b
d
u
s
b
d
u
o
M
834
(LED 1) (LED 2)
and validate with .
With and keys, select the channel number for which you want to configure an alarm. Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder 400 (i.e. for example to configure another alarm / relay)
s
Page 16
SEN
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
F400
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
7. Alarm / relay settings
7.e - Alarm mode details
7.e.1 - Definitions
Setpoint
The setpoint is a limit which, on being reached and/or exceeded , activates an alarm or energizes a relay (in negative security, see page 14 for more details).
Time-delay
Once the setpoint is reached and/or exceeded, the time-delay postpones the alarm activation (or relay excitation) for a short period (in seconds). Once this period is elapsed, and if the setpoint is still exceeded, then the alarm is activated or the relay is energized (in negative security).
Action type
For alarm activation or relay excitation, you can choose the action type: rising or falling action.
• Rising action: the alarm is activated once the measurement goes over the setpoint
• Falling action: the alarm is activated once the measurement goes below the setpoint
7.e.2 - Available configurations
Configuration N°1 : 2 setpoints and time-delay activated (Control Mode)
Measurement
Energized
Not energized
Energized
Not energized
<T> <T> <T>
Setpoint 1 > Setpoint 2
Relay status
Negative security
Relay status
Positive security
Setpoint 1
Setpoint 2
Time
Alarm set
Time-delay
<T>
Co ntro l mode (or regulation mode)
=>you can regulate the measurement within a range determined by 2 setpoints.
Setpoint 2 > Setpoint 1
Measurement
<T> <T> <T>
Energized
Not energized
Energized
Not energized
Class 300 transmitter configuration via keypad / remote control / Modbus
Relay status
Negative security
Status relay
Positive security
Setpoint 2
Setpoint 1
Time
Alarm set
Time-delay
<T>
Page 17
F400
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
Measurement
7. Alarm / relay settings
Configuration N°2 : 1 setpoint, time-delay and rising action activated
Setpoint 1
<T>
Alarm set
Time-delay
Energized
Not energized
Energized
Not energized
Measurement
Energized
Not energized
Energized
Not energized
<T> <T> <T>
Relay status
Negative security
Relay status
Positive security
Time
Configuration N°3 : 1 setpoint, time-delay and falling action activated
Setpoint 1
<T> <T> <T>
Relay status
Negative security
Relay status
Positive security
Time
<T>
Alarm set
Time-delay
Page 18
Class 300 transmitter configuration via keypad / remote control / Modbus
F400
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
7.f - Alarm mode selection
7. Alarm / relay settings
Step
Step
2
Step
3
Step
4
1
100
400
F 403
>
01
F 403
>
>
01
F 403
01
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “400” and validate with .
Select sub-folder
b
d
u
o
s
“403” “408” “413” “418”
Alarm 1 Alarm 2 Relay 1 Relay 2
M
806
o
M
816
b
d
u
s
o
M
826
b
d
u
s
d
o
M
836
and validate with .
With and keys, select the code relative to the alarm mode (see chart below). Validate with .
Code Alarm mode Drawing
00 No alarm
01 2 setpoints with time-delay (control mode) N° 1 page 17
02 1 setpoint with time-delay and rising action
03 1 setpoint with time-delay and falling action N° 3 page 18
N° 2 page 18
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder
400.
b
u
s
Class 300 transmitter configuration via keypad / remote control / Modbus
Page 19
F400
TRONIC
7.g - Setpoints and time-delay setting
7.g.1 - Setpoints
Step
100
1
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
7. Alarm / relay settings
Step
2
400
F 404
>
02
Select the folder “400” and validate with .
To configure the
b
d
u
o
s
“404” “409” “414” “419”
Alarm 1 Alarm 2 Relay 1 Relay 2
M
808
setpoint 1, select sub-folder
o
M
818
b
d
u
s
o
M
828
b
d
u
s
d
o
M
838
and validate with .
(alarm in control mode, see p17)
b-folder
select su
o
M
820
b
d
u
s
o
M
830
b
d
u
,
d
s
o
M
840
b
d
u
setpoint 2
s
To configure the
o
“405” “410” “415” “420”
Alarm 1 Alarm 2 Relay 1 Relay 2
M
810
and validate with .
Step
3
F 404
>
-00100
With and keys, select the value sign: negative or positive. Validate with
.
Then, enter the setpoint value and validate with .
You must enter values according to the units of measurement selected, not
!
according to the measuring range of the transmitter.
Ex. on a CP 303 pressure transmitter (0 to ±1000 Pa) with a reading in mmH2O, the minimum and maximum ranges must be configured on measuring range of 0 to ±102 mmH2O. See conversion chart on page 13.
Step
4
F 404
>
-100
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder
400.
b
u
s
b
u
s
Page 20
SEN
If after having set up a setpoint, the unit of measurement is modified (see page 9), then you have to reconfigure the setpoints according to this new unit of measurement.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
F400
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
7.g.2 - Time-delay
7. Alarm / relay settings
Step
Step
2
Step
3
Step
4
1
100
400
F 406
>
02
F 406
>
>
15
F 406
15
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “400” and validate with .
Select sub-folder
b
d
u
o
s
“406” “411” “416” “421”
Alarm 1 Alarm 2 Relay 1 Relay 2
M
812
o
M
822
b
d
u
s
o
M
832
b
d
u
s
d
o
M
842
and validate with .
With and keys, set the required time-delay: from 00 to 60 seconds. If you do not need the time-delay, enter 00.
Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys , you can choose another sub-folder from the folder 400.
b
u
s
Class 300 transmitter configuration via keypad / remote control / Modbus
Page 21
F500
TRONIC
8. Pressure measurement configuration
8.a - Pressure measurement integration (CP 300)
The integration coefficient makes an average of the measurements: this helps to avoid any excessive variations and guarantees a stable measurement.
[((10 - Coef.) x N Value) + (Coef. x former value)]New value displayed = /10
This value is applicable when the variation is less than Coef. x 10 Pa)+/- (
Example : CP303 (0-1000 Pa) - First measurement: 120 Pa - New measurement : 125 Pa
The pressure source is stable, the user applied a low integration. Integration : 1, maximum variation allowed +/-10 Pa. Since the variation is less than 10 Pa, we apply the integration calculation formula. Next measurement displayed ((9 * 125) + (1 *120 ))/10 = 124.5 soit 124 Pa. If the new value had been 131 Pa, the next value displayed would have been 100% of the new value, i.e 131 Pa.
Step
100
1
ew
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Step
2
Step
3
500
F 500
>
>
03
F 500
08
Select the folder “500” and validate with .
Select the sub-folder “500” and validate with . The cursor
> returns to available choices.
With and keys, you can set the integration value: from 00 to 09.
Validate with .
Coefficient 0 : no integration, large variation of the measurement displayed. Coefficient 9 : maximum integration, more stable measurement display.
Step
4
F 500
>
08
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys , you can choose another sub-folder from the folder 500.
8.a - Time-delay between 2 self-calibrations
Step
Step
2
Step
3
Step
4
1
100
500
F 501
>
F 501
>
30
F 501
>
30
15
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “500” and validate with .
Select the sub-folder “501” and validate with . The cursor
> goes to available choices.
With and keys, you can set the time-delay values between 2 self­calibrations: from
0 t o 60 minutes. Validate with .
Nota : if the value is equal to 0, the transmitter will not carry out any self-calibration.
The cursor > returns to sub-folder line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys , you can choose another sub-folder from the folder 500
d
o
M
1000
d
o
M
1002
b
u
s
b
u
s
Page 22
SEN
Whenever you want, in reading mode, you can carry out a self-calibration by keeping “ESC” pressed for 5 seconds.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
F500
TRONIC
9. Humidity measurement configuration
9.a - Offset setting in humidity and temperature
In order to compensate for any longterm drift of the transmitter, you can add an offset to the value displayed by the TH 200 with the EHK 500 reference portable instrument or via the keypad.
Function only available on humidity transmitters: TH 300
!
The EHK 500 is a reference portable instrument (optional) which enables you to adjust at one point the humidity and temperature reading, via the RS 232 connection cable. Thanks to this new time-saving system, no need to return the transmitter to our factory. Your transmitter is always available on site.
EHK 500.
9.a.1 - Offset in hygrometry (TH300)
Etape
1
100
Go into the configuration mode (see page 2). The folder number displayed corresponds to the last folder used.
For more details, see technical datasheet and user manual of
Etape
2
Etape
3
Etape
4
500
F 500
+0010,0
>
F 500
>
+0010,0
F 500
>
10
Select folder “500” and validate with .
Select sub-folder “500” and validate with . The cursor
With keys and , enter the offset value: from -50,0 to +50,0. Validate with .
The cursor > returns to sub-folders line.
• press once on to return to reading mode.
• or choose another folder to access other functions.
9.a.2 - Offset in temperature (TH300)
Etape
1
Etape
2
Etape
3
Etape
4
100
500
F 501
+0003,2
>
F 501
>
+0003,2
F 501
>
3,2
Go into the configuration mode (see page 2). The folder number displayed corresponds to the last folder used.
Select folder “500” and validate with .
Select sub-folder “501” for an offset in °C or “502” for an offset in °F and validate with . The cursor
With keys and , enter the offset value: from -50,0 to +50,0 (in °C) or from
The cursor > returns to folders line.
• press once on to return to reading mode.
• or choose another folder to access other functions.
> goes to the line of available choices.
> goes to the line of available choices.
-90 to +90 (in °F). Validate with .
SEN
If you activate the offset in temperature in °C (function 501), the value entered is automatically converted into °F (function 502) and vice versa.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
Page 23
www.sentronic.com
F600
TRONIC
10. Air velocity measurement configuration
10.a - Temperature compensation
You can modify the temperature compensation value. The air velocity and airflow measured with a differential probe (such as Pitot tube, Debimo blade,orifice plate...) depends on the working temperature. Then, it is required to enter the working temperature to get more accurate results. You can enter the value either manually or using a thermocouple K probe which offers the automatic temperature compensation.
Function only available on pressure transmitter type CP 300 with SQR option
!
10.a.1 - Manual compensation
Step
Step
2
Step
3
Step
4
Step
5
1
100
600
F 600
>
>
>
>
23
F 600
+00020
F 602
00
F 602
00
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “600” and validate with .
b
d
u
o
s
M
Select the sub-folder “600” to enter a value in °C
b
d
u
o
s
or "601" to enter a value in °F
validate with . The cursor
M
1202
> returns to available choices.
1200
With and keys, enter the temperature compensation (Celsius degree shown alongside, sub-folder "600"). Validate with .
Select the folder “602” and validate with . The cursor
With and keys, choose
> returns to available choices.
00. Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder 600
Page 24
SEN
If you make a temperature compensation in Celsius degree (sub-folder "600"), the transmitter will automatically make the conversion into Farenheit degree (sub-folder "601") and vice versa.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
F600
TRONIC
10. Air velocity measurement configuration
10.a.1 - Automatic compensation
Before configuring the automatic compensation in temperature, you must connect the thermocouple K probe on the transmitter.
!
Step
1
Step
2
Step
3
Step
4
100
600
>
F 602
01
F 602
>
>
01
F 602
01
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
b
d
u
o
s
Select the folder “600” and validate with .
Select the sub-folder “602” , validate with . The cursor
> returns to available choices.
M
1204
With and keys, choose 01. Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder 500
SEN
Once the automatic temperature compensation configuration is complete, check carefully
!
the connection of the thermocouple K probe.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
Page 25
www.sentronic.com
F600
TRONIC
10. Air velocity measurement configuration
10.b - Air velocity coefficient selection (CP 300)
Since the air velocity is calculated from the pressure (on a CP 300) and from a differential probe, you must enter the coefficient value of the differential probe. For Pitot tubes and Debimo blades, the coefficient is already included
in the transmitter.
Function only available on the pressure transmitters: CP 300 + SQR option
!
Step
Step
2
Step
3
1
100
600
F 603
>
>
00
F 603
01
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “600” and validate with .
Select the sub-folder “603” and validate with . The cursor
> goes to available choices.
With and keys, select the differential probe type. Validate with .
Code Differential probe Coef.
00 Pitot tube L (ISO 3966) 1
01 DEBIMO blade 0.8165
02 Other differential probe To be entered
Step
4
F 603
>
01
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder
600.
If you use “Other differential probe” please carefully follow the instructions below.
10.b.1 - Manual coefficient input
Step
1
600
F 604
>
00
Select the folder “600” and validate with .
Select the sub-folder “604” and validate with . The cursor
> goes to available choices.
o
M
1208
d
o
M
1206
b
d
u
b
u
s
s
Page 26
SEN
Step
2
Step
3
F 604
>
0.8165
F 604
>
0.8165
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
With and keys, enter the coefficient relative to your differential probe. This coefficient is given by the manufacturer (from 0.0001 to 9.9999).
Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys , you can choose another sub-folder from the folder 600.
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
F600
TRONIC
10. Air velocity measurement configuration
10.c- Air velocity coefficient input
With this correction coefficient, you can adjust the transmitter according to the air velocity in your installation.
Function only available on the transmitter : CP 300 + SQR option and CTV 310.
!
10.c.1 - How to calculate it ?
If the air velocity in your duct is equal to 17 m/s, and if the transmitter indicates 16.6 m/s, then the
coefficient to apply is 17 / 16,6, ie 1.024
10.c.2 - Coefficient input
Step
100
1
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Step
2
Step
3
Step
4
600
F 605
>
>
>
00
F 605
1.024
F 605
1.024
b
d
u
o
Select the folder “600” and validate with .
Select the sub-folder “605” and validate with . The cursor
> goes to available choices.
M
1210
s
With and keys, enter the coefficient value calculated (from 0.200 to
2.000). Validate with .
The cursor > returns to the sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with et keys, you can choose another sub-folder from the folder 600.
SEN
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
Page 27
www.sentronic.com
F600
TRONIC
11. Airflow measurement configuration
11.a - Selection of duct section type or airflow coefficient
11.a.1 - Working from the section type
Function only available on transmitters: CP 300 + SQR option and CTV 310
!
Step
100
1
Step
600
2
F 606
>
Step
Step
3
4
F 606
>
F 606
>
Section sizes input
Step
100
1
00
00
00
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
b
d
u
o
s
Select the folder “600” and validate with . Select the sub-folder “606” and validate with .
The cursor
> goes to available choices.
M
1212
With and keys, select the section type (00 or 01). Validate with .
Code Section type
00 Rectangular
01 Circular
02 Airflow coefficient (to be entered, see p 29)
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys to choose another sub-folder from the folder 600.
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Page 28
SEN
Step
2
600
F 607
>
1500
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Select the folder “600” and validate with .
Select sub-folder
Rectangular section Circular section
Length Width Diameter
b
d
u
o
s
mm “607” “608” “609”
inch “610” “611” “612”
M
1214
d
o
M
1220
b
u
s
d
o
M
1216
d
o
M
1222
b
u
s
b
u
s
and validate with .
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
d
o
M
1218
d
o
M
1224
b
u
s
b
u
s
F600
TRONIC
10. Airflow measurement configuration
Step
Step
3
4
F 607
>
1500
F 607
>
1500
With and keys, enter the value (from 0 to 3000mm or 0 to 118.11 inch). Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder 600.
If you enter a length, width or diameter in mm, the transmitter will automatically calculate the conversion in Inch (vice versa)
10.a.2 - Working from a airflow coefficient
With this coefficient, you can calculate the airflow from the pressure. This coefficient is given by the manufacturer of the devices supplied with pressure connections (+ and -). From the square root of the pressure measured (Delta P),and from this coefficient, you get the airflow.
Function only available for the pressure transmitter: CP 300 + SQR option. In this calculation mode, you
!
have no access to reading of air velocity. If you activate this calculation mode and also a channel in
air velocity, the transmitter will display an error code “4”.
Go back to procedure page 28 / step 3:
!
With and keys, select
Step
100
1
Airflow = C x Pressure
02 and validate with .
D
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
SEN
Step
2
Step
3
Step
4
600
F 613
>
F 613
>
40.25
F 614
>
00
01
Select the folder “600” and validate with . Select the sub-folder “613” and validate with .
The cursor
> goes to available choices.
With and keys, enter the airflow coefficient value (from 0.1 to 9999.9). Validate with .
The cursor > returns to sub-folders line. Select the sub-folder “614” to select the unit of measurement in
pressure for the airflow calculation and validate with . The cursor
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
> returns to available choices.
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
b
d
u
o
s
M
1226
b
d
u
o
s
M
1228
mailbox@sentronic.com
Page 29
www.sentronic.com
F600
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
11. Airflow measurement configuration
Step
5
Step
6
F 614
>
F 614
>
01
01
With and keys, select the unit of measurement (see chart below). Validate with .
CP301/302/303 CP304
01 Pa Pa
02 mmH O
03 inWg inWg
04 mbar mbar
05 - mmHg
2
mmH O
2
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys to choose another sub-folder from the folder 600.
Page 30
Class 300 transmitter configuration via keypad / remote control / Modbus
12. Other functions
TRONIC
12.a- Activation / deactivation of the RS232 and home bus
Class 300 transmitters have one RS232 and one RS 485 digital output (Modbus protocol) - optional. With the RS 232, you can display 1 or 2 parameters which are measured by other Class 200 and 300 transmitters, or you can send measurements to be displayed on another Class 300 transmitters.
If you set up your transmitter to send measurements to another transmitter via RS 232, then you will
!
not be able to use the RS 485 digital output anymore (Modbus - optional).
Step
100
1
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Step
2
Step
3
100
F 103
>
>
00
F 103
00
Select the folder “100” and validate with . Select the sub-folder “103” and validate with
.
With and keys, select 00 to receive data from another
transmitter or select
CAUTION !!
When the transmitter is configured to receive data, then the RS 485 Modbus is active). When the transmitter is configured to
send data via RS 232, then the RS 485 Modbus is inactive.
Step
4
F 103
>
00
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder 100.
12.b- Serial number display
Step
Step
100
1
2
>
03.12.2004
100
F 105
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “100” and validate with . Select the sub-folder “105
01 to send data via RS 232. Validate with
b
d
u
o
s
M
210
o
M
206
b
d
u
s
SEN
Step
3
F 105
>
03.12.2004
The serial number of the transmitter is displayed. The cursor
> returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys to choose another sub-folder from the folder 100.
Class 300 transmitter configuration via keypad / remote control / Modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
Page 31
mailbox@sentronic.com
www.sentronic.com
12. Other functions
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
12.c- Modification of Modbus communication speed
Step
Step
2
Step
3
Step
4
1
100
100
F 107
>
>
>
03
F 107
05
F 107
05
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “100” and validate with .
Select the sub-folder “107” and validate with .
b
d
u
o
s
With and keys, select a communication speed
(see chart below). Validate with .
00 2400 bauds 03 19200 bauds (speed by default)
01 4800 bauds 04 38400 bauds
02 9600 bauds 05 115200 bauds
M
214
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, you can choose another sub-folder from the folder 100.
Page 32
Class 300 transmitter configuration via keypad / remote control / Modbus
12. Other functions
TRONIC
12.d- Purge mode
The purge mode enables to freeze the measurement when being displayed, enables to lock the analogue outputs, and to activate the relay 1, in order to actuate a de-dust system of an air movement conditions system and to activate the relay 2 in order to isolate the transmitter.
Here is the detailed process of purge mode : 1 - Measurement is frozen. 2 - Wait for three seconds. 3 - Activation of relay 2 (isolation of the transmitter) 4 - Wait for time-delay (e.g : 10 seconds).
- Activation of relay 1
5 (sending compressed air
into the network to clean the installation)
6 - Purge duration (
This function is only available on CP 300 pressure transmitters.
!
(e.g : 30 seconds)
Frozen measurement Relay 1 : Command of purge electro-valve
3 seconds of time delay
7 - Deactivation of relay 1 (stop sending
compressed air).
8 - Wait for time-delay .
(e.g : 10 seconds) 9 - Deactivation of relay 2 10 - Wait for three second. 11 - Recovery of measurement
SEN
Relay 2 : Command of isolation electro-valve
Protection duration of
the transmitter
Purge time : 30 seconds by default
Time-delay of advance of triggering of the relay 2 corresponding :
Temporisation of 10 seconds by
Time-delay of triggering of the relay 2 corresponding : Temporisation of 10
seconds by default
default
To modify purge time and temporisation delay, see page 34-35.
Class 300 transmitters configuration via keypad / remote control / modbus
Produkte, Support und Service
AG
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
Page 33
www.sentronic.com
12.d.1 -Activation / deactivation of Purge Mode
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
12. Other functions
Step
Step
2
Step
3
Step
4
1
100
300
F 306
>
>
>
00
F 306
01
F 306
01
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “300” and validate with .
Select the sub-folder “306” and validate with .
With and keys, activate (01) or deactivate (00) the purge mode. Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, choose another sub-folder from the folder 300
12.d.2 -Working duration of purge mode
Step
Step
2
Step
3
1
100
300
F 307
>
>
00
F 307
25
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder displayed.
Select the folder “300” and validate with .
Select the sub-folder “307” and validate with .
With and keys, enter the value in seconds of the required working duration of each purge (from 01 to 60). Validate with
.
M
M
o
614
o
612
d
b
d
u
s
b
u
s
Page 34
Step
4
F 307
>
25
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• press and to choose another sub-folder from the folder 300
Class 300 transmitters configuration via keypad / remote control / modbus
12.d- Mode Purge
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
12.d.3 -Frequency
12. Other functions
Step
Step
Step
Step
1
2
3
4
100
300
F 308
>
>
>
00
F 308
60
F 308
60
12.d.4 - Time-delay
Time-delay corresponds to the advanced and retardation lead time of triggering of the relay 2 relative to the relay 1.
Step
Step
Step
1
2
3
100
300
F 309
>
>
00
F 309
10
Go into configuration mode (see page 5). The folder number displayed corresponds to the last configuration folder used.
Select the folder “300” and validate with .
Select the sub-folder “308” and validate with .
b
d
u
o
s
With keys and , enter the value in minutes of the frequency
M
616
of each purge (from 01 to 9999). Validate with .
The cursor > returns to sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and , choose another sub-folder from the folder 300.
Go into configuration mode (see page 5).
The folder number displayed
corresponds to the last configuration folder used.
Select the folder “300” and validate with .
Select the sub-folder “309” and validate with .
b
d
u
o
s
With and keys, enter the value in seconds of the time-delay
M
618
required (from 00 to 60). Validate with .
Step
4
F 309
>
10
The cursor > returns to the sub-folders line.
• press twice to return to reading mode.
• press once to return to another folder selection.
• with and keys, choose another sub-folder from the folder 300.
Class 300 transmitters configuration via keypad / remote control / modbus
Page 35
Code Problem Solution
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
Configuration error (alarm(s) set on a non
01
displayed/activated channel)
No channel activated
02
• Check status of the 4 alarms and 4 channels.
Ex. : the error appears if an alarm is configured on a channel (1,2,3 or 4) which is not active. Then, you must activate the channel on which you want to configure an alarm.
Activation of a channel :see page 5
Alarm and relay configurations: see page 14
• Activate one channel (at least).
Activation of a channel: see page 5
13. Error codes
Humidity probe (TH300) or SPI (CP 300) not
03
connected
Only on CP 300.
04
A channel is configured in air velocity (see page
5) and the airflow calculation function (page 23) is set to 02 (airflow coefficient). This combination is impossible.
• Connect the probe / SPI (see user manual SPI)
• Select a unit in airflow for the channel 1, 2, 3 or 4 (see channels configuration, page 5)
• Instead of airflow coefficient, select a circular or rectangular section in function 606 (see page 28)
Page 36
Class 300 transmitters configuration via keypad / remote control / modbus
14. Functions recap
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
b
d
u
o
s
M
Code Description Available settings
100 Channel n° for IR remote control 0 to 9 101 Backlight 0 or 1 102 Display contrast control from 0 to 10 103 Sending data via RS232 0 or 1 104 Keypad locking 0 or 1 105 Serial number display 106 Modbus slave number 1 to 255 107 Modbus communication speed
Code Description
200 Unit of channel 1 201 Unit of channel 2 202 Unit of channel 3 203 Unit of channel 4
xxx
200 202 204 206 208 210 212
214
d
o
M
xxx
400 402 404 406
b
u
s
F100
00 2400 bds 02 9600 bds 04 38400 bds
01 4800 bds 03 19200 bds 05 115200 bds
F200
Available settings
CP301, 302 et 303 CP 304 TH300 CTV310
00 I
Inactive channel Inactive channel nactive channel Inactive channel
01 Pa Pa °C m/s 02 mmH O mmH O °F fpm 03 inWg inWg %HR °C 04 mbar mbar g/Kg (absolute humd. °F 05 °C mmHg °C (dew temperature Td) m /h 06 °F °C °F (dew temperature Td) L/s 07 m/s °F °C (wet temperature Tw) cfm 08 fpm m/s °F (wet temperature Tw) m /s 09 m /h fpm KJ/Kg (Enthalpy i) 10 L/s m /h 11 cfm L/s 12 m /s cfm 13 m /s
2
3
3
2
ñ)
3
3
3
3
Class 300 transmitters configuration via keypad / remote control / modbus
Page 37
14. Functions recap
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
b
d
u
o
s
M
Code Description
300 Analogue output setting on channel 1 0=>0V, 1=>5V, 2=>10V
xxx
600
F300
Available settings
3=>4mA, 4=>12mA, 5=>20mA
301 Analogue output minimum on channel 1
c ha n ne l 1
302 Analogue output maximum on channel 1
303 Analogue output setting on channel 1 0=>0V, 1=>5V, 2=>10V
602 604
606
3=>4mA, 4=>12mA, 5=>20mA
304 Analogue output minimum on channel 2
c ha n ne l 2
305 Analogue output maximum on channel 2
306 Activation / Deactivation of purge mode 00 or 01 307 Working time of each purge from 01 to 60 seconds 308 Frequency of each purge from 01 to 9999 minutes
CP 300
309 Time-delay before and after purge from 00 to 60 seconds
Code Model Description
500 CP300 Measurement integration from 0 to 9 500 TH300 Offset in humidity -50,0 to +50,0 501 CP300 Self-calibration for time-delay from 0 to 60 minutes 501 TH200 Offset in temperature (°C) from -50,0 to +50,0 502 TH200 Offset in temperature (°F) from -90,0 to +90,0
608 610
612 614 616 618
b
d
o
M
xxx
1000 1000 1002 1002 1004
u
s
F500
Available settings
Page 38
Class 300 transmitters configuration via keypad / remote control / modbus
14. Functions recap
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
b
d
u
o
s
M
Code Description
400 Audible alarm 0 or 1 401 Relays security 0 (negative) or 1 (positive)
402 Channel selection for alarm 1 1=> channel 1, 2=> 2, 3 403 Channel selection for alarm 1 => inactive
xxx
800 802
804 806
F400
Available settings
channel =>channel 3, 4=> channel 4
0 1=> setpoint 1, setpoint 2 and time-delay 2=> setpoint 1, time-delay and rising action 3=> setpoint 1, time-delay and falling action
404 Setpoint 1 of alarm 1
A L A R M 1A L A R M 2R E L AY 1R E L AY 2
405 Setpoint 2 of alarm 1 406 Time-delay on alarm 1 from 0 to 60 seconds
407 Channel selection for alarm 2 1=> channel 1, 2=> channel 2, 3=>channel 3, 4=> channel 4 408 Alarm 2 type selection 0=> inactive
808 810 812
814 816
1=> setpoint 1, setpoint 2 and time-delay 2=> setpoint 1, time-delay and rising action 3=> setpoint 1, time-delay, and falling action
409 Setpoint 1 of alarm 2 410 Setpoint 2 of alarm 2 411 Time-delay on alarm 2 from 0 to 60 seconds
412 Channel selection for Relay 1 1=> channel 1, 2=> channel 2, 3=>channel 3, 4=> channel 4 413 Alarm type selection for Relay 1 0=> inactive
818 820 822
824 826
1=> setpoint 1, setpoint 2 and time-delay 2=> setpoint 1, time-delay and rising action 3=> setpoint 1, time-delay and falling action
414 Setpoint 1 of Relay 1 415 Setpoint 2 of Relay 1 416 Time-delay of Relay 1 from 0 to 60 seconds
828 830 832
417 Channel selection for Relay 2 1=> channel 1, 2=> channel 2, 3=>channel 3, 4=> channel 4 418 Alarm type selection for Relay 1 0=> inactive
834 836
1=> setpoint 1, setpoint 2 and time-delay 2=> setpoint 1, time-delay and rising action 3=> setpoint 1, time-delay and falling action
419 Setpoint 1 of Relay 2 420 Setpoint 2 of Relay 2 421 Time-delay of Relay 2 from 0 to 60 seconds
Class 300 transmitters configuration via keypad / remote control / modbus
838 840 842
Page 39
14. Functions recap
Rugghölzli 2 CH - 5453 Busslingen
Tel. +41 (0)56 222 38 18 Fax +41 (0)56 222 10 12
mailbox@sentronic.com
www.sentronic.com
Produkte, Support und Service
SEN
TRONIC
AG
b
d
u
o
s
M
Code Description
600 Compensation temperature in °C* - 601 Compensation temperature in °F* - 602 Compensation type* manual =>00 or automatic=>01 603 Air velocity measurement mean*
604 Air velocity coefficient value* from 0.0001 to 9.9999 605 Air velocity correction coefficient from 0.200 to 2.000 606 Section type selection
CP 300 - CTV 310
607 Section length in mm from 0 to 3000 mm 608 Section width in mm from 0 to 3000 mm 609 Section diameter in mm from 0 to 3000 mm
610 Section length in inch from 0 to 118.11 inch 611 Section width in inch from 0 to 118.11 inch 612 Section diameter in inch from 0 to 118.11 inch
xxx
1200 1202 1204 1206
1208 1210 1212
1214 1216 1218
1220 1222 1224
F600
Available settings
Code Differential probe
00 Pitot tube
01 DEBIMO blade
02 Other differential probe
Code Section type
00 Rectangular
01 Circular
02 Airflow coefficient
613 Airflow coefficient* from 0.1 to 9999.9 614 Units of pressure
* : only for CP300 transmitter
1226 1228
for the pressure calculation*
01 Pa Pa
02 mmH O
03 inWg inWg
04 mbar mbar
05 - mmHg
CP301/302/303 CP304
2
mmH O
2
Ref. NT Ang - Classe 300 - 13/07/10 - RCS (24) 349 282 095 Non-contractual document - We reserve the right to modify the characteristics of our products without prior notice.
Loading...