Killark-Hubbell Electrical Products XMSW SERIES Catalog Page

C
XMSW SERIES • CONTROLS
MANUAL LINE STARTERS
C73
FEATURES-SPECIFICATIONS
Heaters not included. If heaters are required order as separate item by catalog number, three phase starters require three heaters. Single phase starters require two heaters.
Three pole starters may be used on two-phase four-wire circuits by running one wire direct to motor.
XMSW MANUAL LINE STARTERS

HEATER TABLE FOR XMSW SERIES MANUAL LINE STARTERS
WESTINGHOUSE B100 STARTERS FULL VOLTAGE, NON-REVERSING SINGLE AND POLYPHASE
Listed - File E12379
See files for details or call Killark.
Applications
XMSW Series, non-reversing, manual line voltage starters and enclosures are suitable for use in applications requir­ing manual across-the-line starting and stopping of small single and polyphase AC motors, and where overload pro­tection is needed. Manual starters are generally used on small machine tools, fans and blowers, pumps, compres­sors, and conveyors as well as many other types of electrical machinery.
Features
Rectangular bolted cover design
provides for attractive, compact, uniform installations
Enclosure and external handle are
diecast copper-free (less than 0.4%) aluminum alloy
Cast “ON,” “OFF,” “TRIPPED” mark-
ings on cover align with external handle and provide clear indication of enclosed starter condition
External handle is a vault type with
standard provisions for locking in the ”OFF” position with up to three pad­locks. Provision for locking in “ON” position is available as factory modi­fication (add suffix SU-40 to catalog number).
Two cast 1" NPT conduit hubs with
integral pipe stop, one top and one bottom, are standard on all assemblies
Electrical Rating
Starter sizes 0, 1, 11/2 Two pole, single phase; three pole,
polyphase Maximum 10 HP, 600 Volts AC
Class I, Div. 1 & 2, Groups C,D Class l, Zones 1 & 2, Groups llB, llA Class II, Div. 1 & 2, Groups E,F,G Class Ill NEMA 3R, 7(C,D) 9(E,F,G)
7
/16"
(11)
11
7
/8"
(302)
10
1
/4"
(260)
8
3
/8"
(213)
1
3
/8"
(35)
8
5
/16"
(211)
7
/8"
(22)
7
1
/8"
(181)
6"
(152)
NEMA NUMBER OF
MAXIMUM HORSEPOWER
SIZE POLE SIZE
120 VAC 208-240 VAC 480-600 VAC
0 2-POLE; 1Ø, A C 1 2
0 3-POLE; 3Ø, A C 2 3 5
1 2-POLE; 1Ø, A C 2 3
1 3-POLE; 3Ø, A C 3 7-1/2 10
1-1/2 2-POLE; 1Ø, A C 3 5
CATALOG NUMBER WITH ENCLOSURE STARTER ONLY
XMSW-0BT XMSW-0CT XMSW-1BT XMSW-00T XMSW-1CT XMSW-DBT
MOTOR FULL-LOAD AMPS @ 40˚C
WESTING-
CATALOG
SINGLE THREE
HOUSE
NUMBER
PHASE PHASE
CODEMARK
YOWEA200-FH03 .28-.29 .25-.26 FH03 YOWEA200-FH04 .30-.33 .27-.29 FH04 YOWEA200-FH05 .34-.36 .30 .32 FH05 YOWEA200-FH06 .37-.40 .33-.35 FH07 YOWEA200-FH07 .41-.45 .36-.39- FH07 YOWEA200-FH08 .46-.50 .40-.44 FH08 YOWEA200-FH09 .51-.56 .45-.49 FH09 YOWEA200-FH10 .57-.63 .50-.55 FH10 YOWEA200-FH11 .64-.70 .56-.61 FH11 YOWEA200-FH12 .71-.78 .62-.68 FH12 YOWEA200-FH13 .79-.86 .69-.75 FH13 YOWEA200-FH14 .87-.95 .76-.83 FH14 YOWEA200-FH15 .96-1.04 .84-.91 FH15 YOWEA200-FH16 1.05-1.14 .92-1.00 FH16 YOWEA200-FH17 1.15-1.25 1.01-1.10 FH17 YOWEA200-FH18 1.26-1.39 1.11-1.22 FH18 YOWEA200-FH19 1.40-1.54 1.23-1.35 FH19 YOWEA200-FH20 1.55-1.71 1.36-1.50 FH20 YOWEA200-FH21 1.72-1.89 1.51-1.66 FH21 YOWEA200-FH22 1.90-2.10 1.67-1.84 FH22 YOWEA200-FH23 2.11-2.32 1.85-2.03 FH23 YOWEA200-FH24 2.33-2.54 2.04-2.23 FH24 YOWEA200-FH25 2.55-2.79 2.24-2.45 FH25 YOWEA200-FH26 2.80-3.07 2.46-2.69 FH26 YOWEA200-FH27 3.08-3.36 2.70-2.95 FH27 YOWEA200-FH28 3.37-3.68 2.96-3.23 FH28 YOWEA200-FH29 3.69-4.03 3.24-3.53 FH29
MOTOR FULL-LOAD AMPS @ 40˚C
WESTING-
CATALOG
SINGLE THREE
HOUSE
NUMBER
PHASE PHASE
CODEMARK
YOWEA200-FH30
4.04-4.40 3.54-3.86 FH30
YOWEA200-FH31 4.41-4.81 3.87-4.22 FH31 YOWEA200-FH32 4.82 -5.26 4.23 -4.61 FH32 YOWEA200-FH33 5.27-5.74 4.62-5.03 FH33 YOWEA200-FH34 5.75-6.25 5.04-5.49 FH34 YOWEA200-FH35 6.27-6.83 5.50-5.99 FH35 YOWEA200-FH36 6.84-7.45 6.00-6.53 FH36 YOWEA200-FH37 7.46-8.11 6.54-7.11 FH37 YOWEA200-FH38 8.12 -8.81 7.12 -7.73 FH38 YOWEA200-FH39 8.82-9.58 7.74-8.40 FH39 YOWEA200-FH40 9.59-10.40 8.41-9.12 FH40 YOWEA200-FH41 10.41-11.3 9.13-9.89 FH41 YOWEA200-FH42 11.4-12.2 9.9-10.7 FH42 YOWEA200-FH43 12.3-13.5 10.8-11.8 FH43 YOWEA200-FH44 13.6-14.9 11.9-13.0 FH44 YOWEA200-FH45 15.0-16.0 13.1-14.0 FH45 YOWEA200-FH46 16.1-17.1 14.1-15.0 FH46 YOWEA200-FH47 17.2-18.3 15.1-16.1 FH47 YOWEA200-FH48 18.4-19.7 16.2-17.3 FH48 YOWEA200-FH49 19.8-21.2 17.4-18.6 FH49 YOWEA200-FH50 21.3-22.8 18.7-20.0 FH50 YOWEA200-FH51 22.9-24.5 20.1-21.5 FH51 YOWEA200-FH52 24.6-26.4 21.6-23.2 FH52 YOWEA200-FH53 26.5-28.5 23.2-25.0 FH53 YOWEA200-FH54 28.6-30.8 25.1-26.8 FH54 YOWEA200-FH55 30.9-33.3 — — FH55 YOWEA200-FH56 33.4-36.0 — — FH56 YOWEA200-FH57 36.1-38.9 — — FH57
Select heater element based on motor
nameplate listed. Full-load amps. Trip rating of element is 125% of motor minimum F.L.A. listed for the element.
Dimensions
®
Loading...