Killark-Hubbell Electrical Products KFL SERIES Catalog Page

C1D2 FLOOD – INTRODUCTION & LOGIC
LED
FEATURES-SPECIFICATIONS
Applications
LED Floods are designed for installations where moisture, dirt, dust, corrosion and vibration may be present, or NEMA 3 and 4X areas where wind, water, snow or high ambients can be expected. They can be used in locations made hazardous by the presence of flammable vapors or gases or combustible dusts as defined by the NEC.
Typical applications include manufacturing plants, and certain chemical and petrochemical processing facilities, sewage treatment plants, off-shore and dockside installations, garages and storage facilities.
Compliances
UL-8750 for LED lighting
ANSI/UL 1598(A)
UL-844 Standard for lighting fixtures for
hazardous locations, Class I, Division 2; Class II, Divisions 1 and 2; Class III
CSA C22.2 no. 137-M1981 electric
luminairies for use in hazardous locations
Enclosed and gasketed
NEMA 3, 4X
IP66
IEX suffix Zone 2/21 to IEC 60079-0,
60079-15, 60079-31 Standards
Materials
Body, end caps and lens frame corrosion
resistant copper-free aluminum alloy with baked powder epoxy/polyester finish, electrostatically applied for complete, uniform corrosion protection
All external hardware - stainless steel
Thermal shock and impact resistant glass lens
High temperature silicone gasketing
Trunnion heavy gauge galvanized steel
with painted finish
LED Flood Features and Standards
Crisp White Light for Excellent Color
Rendering - Chromaticity 5000K (CCT); approx. 70 CRI
Energy Savings - High lumens per watt
Long Life - to 100,000+ maintenance free
hours to 70% initial lumens
Ambient suitability -50°C to 55°C up to 125Wk
Instant On - Including after power interruption
World Voltage 120 - 277VAC 50/60Hz
Solder-LESS LED Board Connections -
Vibration Resistant
LM80-08* Measurement of lumen
maintenance for LED light sources
LM79-08* Certified “Absolute” Photometry,
including Chromaticity Color for Solid State Lighting
L70 Values - Industry Nomenclature for
Hours of use to 70% of initial Lumens ­TM-21* & Calculated
Supplemental surge protection included as standard for AC models only
Catalog Number Logic
KFL - Series Constant
Fixture Wattage 060
- 60W
070
- 70W
075
- 75W
085
- 85W
090
- 90W
105
- 105W
110
- 110W
125
- 125W
150
- 150W
165
- 165W
195
- 195W
Consult website for current list of approved luminaires
Voltage 30 33 34 Options
PL
F FF TBL P1 P2 P3 QD D20 D25 D75 SY IEX
– 120 - 277VAC 50/60Hz – 347 - 48 0VAC 60Hz (85W to 125W models)k – 120 - 250VDC (85W to 125W models)
- Polycarbonate Lens
- Single Fusej
- Double Fusej
- Terminal Blocks
- 120V Photocell, factory installed
- 208V-277V Photocell, factory installed
- 347V Photocell, factory installed
- Quick Disconnect
- 2x M20 entries
- 2x M25 entries
- 2 x 3/4” NPT
- 316 SS Yoke
- IECEx & ATEX includes TBL and External Ground (to 125W)
KFL 125 30 XX
Looping
KILLARK LIGHTING
KFL SERIES
Class I, Div. 2, Groups A,B,C,D Class II, Div. 1&2, Groups EFG Class III Suitable for wet locations Marine Rated (US Only) NEMA 3, 4X IP66
File LR 11713
IEC Ex Rated model (w/IE X suffix) Zone 2 and Zone 21 areas Ex nA IIC T6…T3, Gc Ex tb IIIC T160°C Db Tamb -50°C <Ta<+55°C, IP66 IECE x Cer tificate CSA 14.000 2X ATEX CML 14ATEX3087/4088
PATENTED LUMINAIRE DESIGN
KFL with KFS-6
Sliptter mount on 2” pipe
Dark Sky Visor
KFL-DARK
* LM-xx & TM-xx are illumination Engineering Society
Standards designed to promote uniformity in testing procedures among test labs and manufacturers. For more information go to www.ies.org
IEX Units include Qty. 3 6mm terminals plus external ground as standard
Construction Note:
Models with dual metric entries are tapped with one plugged and the standard 3/4” NPT entry will be plugged.
j Fusing not for Canadian or Marine
Installations
(Std. w/IEX)
k 347V-480V +40°C Max
H
H
T
T
I
I
H
H
N
N
G
G
G
G
I
I
L
L
C
C
A
A
O
O
Z
Z
L
L
KILLARK LIGHTING
T
T
I
I
H
H
N
N
G
G
G
G
I
I
L
L
H
H
A
A
Z
Z
KFL SERIES
C
C
O
O
L
L
C1D2 FLOOD – ORDERING INFORMATION & TECHNICAL DATA
ORDERING INFORMATION AND AMBIENT SUITABILITY
CATALOG
NO.j
KFL06030
WEIGHT LBS./KG
WATTS VOLTAGE
60 120-27 7VAC 0.50-0.20 6 111 T6 T5 T3C T3C T3C (EFG) T3C (EFG) T6 T5 145-7 0 160-85 60100 270000
AMPS
jk
LUMENSl
C1D2m
40°C 55°C 40°C 55°C 40°C 55°C 40°C 55°C 40°C 55°C TM-21 CALCULATED
C1D2m
SIMULTANEOUS
C2D1m
KFL07030 70 120 -277VAC 0.60-0.30 9742 T6 T5 T3C T3C T3C (EFG) T3C (EFG) T6 T5 145-7 0 160-85 72600 278000 KFL07530 75 120 -277VAC 0.60-0.30 7454 T6 T5 T3C T3C T3C (EFG) T3C (EFG) T6 T5 145-7 0 160-85 60100 270000 KFL08530
120-27 7VAC 0.70-0.30
85
10840 T6 T5 T3C T3C T3C (EFG) T3C (EFG) T6 T5 145-70 160-85 72600 278000KFL08533 347-480VAC 0.24-0.17
KFL08534 120-250VDC 0.70-0.27 KFL09030
120-27 7VAC 0.80-0.40
90
9023 T6 T5 T3C T3C T3C (EFG) T3C (EFG) T6 T5 145-70 160-85 60100 270000KFL09033 347-480VAC 0.28-0.23
KFL09034 120-250VDC 0.80-0.36 KF L10 530
KFL10534 120-250VDC 0.90-0.36
30.00 /
13.61
KF L110 30 KFL11033 347-480VAC 0.31-0.23
120-27 7VAC 0.90-0.40
105
120-27 7VAC 0.90-0.40
110
1037 0 T4A T4A T3C T3C T3C (EFG) T3C (EFG) T4 T4 145-70 160-85 60100 270000KFL105 33 347-480VAC 0.31-0.23
1378 0 T6 T5 T3C T3C T3C (EFG) T3C (EFG) T6 T5 145-70 160-85 72600 278000
KF L110 34 120-250VDC 0.90-0.36 KF L12 530 KF L12 533 347-480VAC 0.35-0.29
120-27 7VAC 1.00- 0. 50
125
15340 T6 T5 T3C T3C T3C (EFG) T3C (EFG) T6 T5 145-70 160-85 72600 278000
KFL12534 120-250VDC 1.00-0.45 KF L15 030 150 120 -277 VAC 1.25-0.54 18550 T5 - T3C - T3C (EFG) - - - - - 60300 190000 KF L16 530 165 120 -277 VAC 1.38-0.60 19 22 0 T5 - T3C - T3C (EFG) - - - - - 72600 278000 KF L19 530 195 120 -277 VAC 1.63-0.70 2194 0 T5 - T3C - T3C (EFG) - - - - - 72600 278000
j Cat. nos. are 120-277VAC models, see logic for 347-480V. k Amperage measured at 120VAC; 277VAC calculated l Extra high Lumens per Watt LED models m Use 75° minimum Supply Wire @40 °C Ambient; 90 @55°C Ambient n First number is lens temperature under 25mm layer of dust; Second number is lens temp. for dust cloud.
IEC ZONE 2
m
IEC ZONE 21n
Dimensions
17.75
[450.9]
14.88
[377.8]
L70
KFS-6
Sliptter
KFCB
Cross Arm Mount
KFWB
Wall/Pipe Bracket
K4040
Wall Bracket
4041
Tenon Fitting
KFL MOUNTS AND ACCESSORIESj
CATALOG NUMBER DESCRIPTION
KFS-6 Steel Slipfitter for 2” Pipe (2-3/ 8” o.d.) Tenon. Slips 3.75” Over Pipe. KFCB Heav y Dut y Cast-Iron Crossarm Fitting for Horizontal Trunnion KFWB Heav y Dut y Wall Mount and/or Pipe Clamp Fit ting Clamps 2” Pipe (2-3/8” o.d.) Through
K4040 Heav y Dut y Steel Wall Bracket. (Must be with 4041 Heav y Dut y Steel Wall Bracket 2” Pipe (2-3/8” o.d.) Tenon Fitting. Uses with KFS-6. KFLGo VMSC10k KFL-DARKlo KFL-DOOR Replacement Door and Lens A ssembly (for units w/o internal reflectors) KFL-DOOR2mn
j Fittings available to adapt trunnion mount  oodlights to crossarms, poles and walls. Must be ordered separately. k Drop limit 1’. Attaches to luminaire cable provision and to mounting structure. l Designed to eliminate uplight when aimed at 45°. m Only for models factory supplied with internal reector. n Not backward compatible with units originally shipped without internal reector. o KFLG and KFL-DARK cannot be used together.
2-1/2” Pipe (2-7/8” o.d.)
KFCB
Crossarm Fitting).
Wire Guard, 316 Stainless Steel (not used with KFL-DARK) 10’ Stainless Steel Safety Cable with loop grip Dark Sk y Visor, White Painted Aluminum (not used with KFLG)
Replacement Internal Reflector and Lens Assembl y
11.32
[287.6]
.531 DIA.
(13)
Trunnion Mounting
3-1/8”
(79)
Detail
Front
5.22
[132.7]
2.00
[50.8]
Side
8.41
[213.5]
14.07
[357.3]
Loading...