LINEAR FLUORESCENT EMERGENCY LIGHTING
FEATURES-SPECIFICATIONS
Applications
LINEARLITE DBFE Emergency Lighting
fixtures provide continuous illumination
under normal power and switch to
emergency battery backup during power
outages. Units contain a battery unit that
provides the OSHA required 90 minutes of
illumination for egress.
Units are designed for general and task
lighting in areas where flammable gases
or vapors or combustible dusts may exist
due to abnormal conditions, and create a
Division 2 hazardous location, as defined by
the NEC.
Features
• Sheet steel 20 ga. housing with
continuous weld prevents foreign matter
from entering enclosure
• Lens frame assembly has silicon rubber
gasketing and heat tempered glass lens
• Electrostatically applied polyester finish
• NEMA 4 construction for wet locations
• LED charging indicator light visible
through lens
• Push-To-Test Button mounted on sloping
side of fixture - allows end-to-end
mounting of fixtures
KILLARK LIGHTING
DBFE SERIES
Class I, Div. 2, Groups A,B,C,D
Class I, Zone 2, Groups IIC, IIB, IIA
Class ll, Div. 2 Groups F,G
NEMA 3, 4
UL Listed
Compliances: UL 4 4; UL 81570, UL9 24
UL Wet Location Listed (Indoor & Outdoor)
DBFE FLUORESCENT EMERGENCY LIGHTING
CATALOG
NUMBER
DBFE232302
DBFE 24012
DBFE24042
DBFE16012
DBFE16042
DBFE232303
DBFE 24013
DBFE24043
KFBP7 (32/40 or 60 Watt) Replacement bat ter y unit
Notes: Emergency unit will start lamps at 0ºF
32W T8 Electronic ballast minimum start is 0ºF;
40W ballast is electronic with 50º F star t (add CW for electromagnetic 0º F);
60W electromagnetic ballast start -20ºF
32W & 40W units operate 2 Lamps in emergency mode for maximum illumination
60W units operate a single lamp. 3 Lamp 60W emergency units not available.
For dimensional data and mounting accessories, see DBF series page L162.
Digit af ter E is number of lamps energized during power loss.
LAMPS
2 32W Lamps 625 455
2 40W Lamps 610 420
1 60W Lamp 780 460
CONDUIT
SIZE
3/4” 2
3/4” 3
NUMBER
OF LAMPS
EMERGENCY LUMEN CHART
INITIAL
LUMENS
AFTER 90
MINUTES
LINE
VOLTAGE
120-277 V 50/60 Hz
120V 60 Hz
277V 60 Hz
120V 60 Hz
277V 60 Hz
120-277 V 50/60 Hz
120V 60 Hz
277V 60 Hz
32W T8 electronic ballast OºF star t
Medium bi-pin base
32W T8 electronic ballast OºF star t
Medium bi-pin base
32W T8 electronic ballast OºF star t
Medium bi-pin base
32W T8 electronic ballast OºF star t
Medium bi-pin base
32W T8 electronic ballast OºF star t
Medium bi-pin base
DESCRIPTION
T
T
I
I
H
H
N
N
G
G
G
G
I
I
L
L
H
H
C
C
A
A
O
O
Z
Z
L
L
DBFE HAZARDOUS LOCATION APPLICATION DATA
NO.
OF
LAMPS
2 32/40 40 90 T6 (85°C/185°F) T6 (85°C/185°F) YES YES
3 32/40 40 90 T5 (100°C/212°F) T6 (85°C/185°F) YES YES
2 60 40 90 T4A (120°C/248°F) T6 (85°C/185°F) YES YES
LAMP
WATTS
RATED
AMBIENT
°C
SUPPLY WIRE
SUITA BLE
FOR °C MIN
CLASS I, DIV. 2,
GROUPS A,B,C,D
MAX. LAMP TEMP.°C
UL/CSA TEMP./I.D.
CLASS II, DIV. 2,
GROUPS E.F,G
MAX. SURF. TEMP.°C
UL/CSA TEMP./I.D.
NEMA
TYPE 3
(RAINTIGHT)
NEMA
TYPE 4
(HOSEDOWN)