Killark-Hubbell Electrical Products B7MS SERIES Catalog Page

Page 1
COMPACT MANUAL IEC STARTERS
Class I, Div. 1 & 2, Groups B, C, D Class l, Zones 1 & 2, Groups llB+H2, llA Class II, Div. 1 & 2, Groups E, F, Ga Class III, Div. 1 & 2 NEMA 3, 4, 4X, 7 (B, C, D) 9 (E, F, G)
B7MS SERIES
Certified - File LR11714
T
T
R
E
R
E
R
R
A
A
T
T
S
S
S
S
m
H
H
C
C
A
A
O
O
Z
Z
B7M S1P
Push Button Style
FEATURES-SPECIFICATIONS
Applications
The PRISM
®
B7MS Series of non-reversing, manual line voltage starters and enclosures are suitable for use in applications requiring manual across-the-line starting and stopping of small single and polyphase AC motors, and where overload protection is needed. Manual starters are generally used on small machine tools, fans and blowers, pumps, compressors, and conveyors as well as many other types of electrical equipment.
®
PRISM
enclosures universal design accommodates, as standard, IEC starter manufacturers including Square D, Cutler­Hammer, ABB, Siemens, Moeller, Sprecher + Schuh, Allen-Bradley, Advance Controls, and WEG.
Square D © Schneider Electric Siemens © Siemens AG Moeller © Moeller Electric Corp. See catalog pg. DE8A for copyrights of other brands
referenced.
When ordered with starters, ABB or Square D supplied.
B7MS2R
Rotary Style
Features
Compact size enclosures provide
application flexibility with cost savings over industry standard sizes
NEMA 4, 4X rated – providing protection
from hose directed water and corrosion
Pre-drilled to facilitate easy field
installation of starters
2 operating styles, rotary or push button,
including lock-out provision.
Provisions for drain and breather
Bolt on ductile mounting lugs
Two NPT conduit openings provided
as standard, with custom openings on request
Electrical Rating
Starters rated 600V, 3 phase up to 50HP
DIMENSIONS
Fixed Lug Po sition For B 7MS1
Standard Lug Position For B7MS2
Optional Position For B7MS2
Standard Materials /Finish
Enclosures: Copper-free aluminum (less
than 4/10 of 1% copper content)
Cover Bolts: 316 Stainless Steel
O-ring Gasket: Silicone
Finish: Grey Powder Polyester painted
exterior, electrostatically applied
MODIFICATIONS
SUFFIX
NUMBER
KIT-251 100 amp ground lug
A Auxiliary contacts 1 NO + 1 NC
SU-2 Hinge-9 Installed
SU3B-4X Drain & Breather installed TYPE 4X
SU3B-4XSS Drain & Breather installed TYPE 4X SS
B7SPNPT Change Std. conduit size and location
SU9 Special paint finish
SU14 Fungus proofing of enclosures
DESCRIPTION
Catalog Logic
B7MS 1 R S 1 A
Constant for Series
Enclosure Size
1 = B7EP 2 = B7EQ
Operating Device
R = Rotar y P = Push Buttons
Starter Manufacturer to be supplied
S = Square D A = ABB Blank = Enclosure only
Horsepower (FLA) of starter
Accessories
A = Aux. Contacts NO + NC
ENCLOSURE
OUTSIDE BOX
DIMENSIONS
NOMINAL INSIDE BOX MOUNTING DIMENSIONS
A B C D E F G H I J K
B7MS1 5-3/4 8-1/16 6-5/16 3-5/8 5-13 /16 5-1/16 3-1/ 8 8-1/8 1-1/ 4 1 B7MS2 8-1/ 8 13-1/16 7-13/ 16 4-1/4 9 -13 /16 6-5/16 2-1/ 2 11- 3/8 6-3/8 7-1/2 1-13/ 16 1-1/ 2
CONDUIT
SIZE
Page 2
T
T
R
E
R
E
R
R
A
A
T
T
S
S
S
S
m
H
H
A
A
Z
Z
B7MS SERIES
C
C
O
O
ENCLOSURE
WITHOUT STARTER
B7MS1R B7MS1RA-5 4.0 - 6.3 0.25 0.5 1.5 3 5
ENCLOSURE
WITHOUT STARTER
B7MS2RA
FOR USE WITH
ABB ONLY
ENCLOSURE
WITHOUT STARTER
B7MS1P* B7MS1PS-6 6.0 - 10.0 0.5 1.5 2 3 5 7. 5
ENCLOSURE
WITHOUT STARTER
B7MS2P
ENCLOSURE
WITHOUT STARTER
B7MS1R B7MS1RS-7 9.0 - 14.0 0.75 2 3 3 10 10
ENCLOSURE
WITHOUT STARTER
B7MS2R B7MS2RS-16 30.0 - 40.0 3 5 10 10 30 30
B7MS1R – For use with ABB
MS116, MS325, MS132 Automation Direct BM3 Cutler-Hammer XTPR Moeller PKZMO Seimens 3RV Sprecher + Schuh KTA7 SQ D Telemecanique GV2P WEG MPW25
COMPACT MANUAL IEC STARTERS
B7MS – ROTARY STYLE WITH ABB MS132 & MS450 SERIES
CATALOG NUMBER
ADJUSTMENT
RANGE FLA
B7MS1RA-1 0.63 - 1.0 0.5 0.5 B7MS1RA-2 1.0 - 1. 6 0.1 0.75 0.75 B7MS1RA-3 1.6 - 2.5 0.167 0.5 1 1.5 B7MS1RA-4 2.5 - 4.0 0 .12 5 0.33 1 2 3
B7MS1RA-6 6.3 - 9.0 0.33 1 2.5 5 7. 5 B7MS1RA-7 9.0 - 12.5 0.5 2 3 7.5 10 B7MS1RA-8 12.5 - 16.0 1 2.5 5 10 10
B7MS1RA-9 16.0 - 20.0 1.5 3 5 10 15 B7MS1RA-10 20.0 - 25.0 2 3 7.5 15 20 B7MS1RA-12 11 - 16 1 3 5 5 10 15 B7MS1RA-13 14 - 20 1.5 3 5 7. 5 15 20 B7MS1RA-14 18 - 25 2 5 7.5 10 20 25 B7MS1RA-15 22 - 32 3 5 10 10 25 30 B7MS1RA-16 28 - 40 3 7.5 15 15 30 40 B7MS1RA-17 36 - 45 5 7.5 15 15 30 B7MS1RA-18 40 - 50 5 10 15 20 40 50
B7MS – PUSH BUTTON STYLE SQUARE D GV2 SERIES
B7MS1PS-1 0.63 - 1.0 0.5 0.5
B7MS1PS-2 1.0 - 1.6 0.1 0.75 1
B7MS1PS-3 1.6 - 2.5 0.167 0.5 0.5 1 1.5
B7MS1PS-4 2.5 - 4.0 0.12 5 0.33 0.75 1 2 3
B7MS1PS-5 4.0 - 6.3 0.25 0.5 1.5 1.5 3 5
B7MS1PS-7 9.0 - 14.0 0.75 2 3 3 10 10
B7MS1PS-8 13.0 - 18.0 1 3 5 5 10 15
B7MS1PS-9 17.0 - 23.0 1. 5 3 5 7. 5 15 20 B7MS1PS-10 20.0 - 25.0 2 3 5 7. 5 15 20 B7MS1PS-11 24.0 - 32.0 2 5 10 10 20 30
GV3 SERIES
PUSH BUTTON
STARTER
B7MS – ROTARY STYLE WITH SQUARE D GV2 & GV3 SERIES
B7MS1RS-1 0.63 - 1.0 0.5 0.5
B7MS1RS-2 1.0 - 1.6 0.1 0.75 1
B7MS1RS-3 1.6 - 2.5 0.16 7 0.5 0.5 1 1.5
B7MS1RS-4 2.5 - 4.0 0 .125 0.33 0.75 1 2 3
B7MS1RS-5 4.0 - 6.3 0.25 0.5 1.5 1.5 3 5
B7MS1RS-6 6.0 - 10.0 0.5 1.5 2 3 5 7. 5
B7MS1RS-8 13.0 - 18.0 1 3 5 5 10 15
B7MS1RS-9 17.0 - 23.0 1.5 3 5 7.5 15 20 B7MS1RS-10 20.0 - 25.0 2 3 5 7.5 15 20 B7MS2RS-11 24.0 - 32.0 2 5 10 10 20 30 B7MS2RS-12 9.0 - 13.0 1 2 3 3 7. 5 10 B7MS2RS-13 12.0 - 18.0 1 3 5 5 10 15 B7MS2RS-14 17.0 - 25.0 2 3 7. 5 7. 5 15 20 B7MS2RS-15 23.0 - 32.0 2 5 10 10 20 30
B7MS2RS-17 37.0 - 50.0 3 7. 5 15 B7MS2RS-18 48.0 - 65.0 5 10 20 20 50 50
B7MS2R – For use with
Automation Direct BM3 SQ D Telemecanique GV3P
B7MS2RA – For use with ABB MS450
SINGLE PHASE HP THREE PHASE HP
120V 230V 200V-208V 230V 480V 600V
Discontinued by the manufacturer
15 40 40
B7MS1P – For use with Cutler-Hammer XTPB Moeller PKZMO1 SQ D Telemecanique GV2ME WEG MPW25
B7MS2P – For use with Advance Control MMS25
* B7MS1PRW –
(enclosure without starter) For use with Allen-Bradley 140 Sorecher + Schuh KT4
40
Page 3
COMPACT MANUAL NEMA STARTERS
B7MSN2P Internal View
B7MS SERIES
Class I, Div. 1 & 2, Groups B, C, D Class l, Zones 1 & 2, Groups llB+H2, llA Class II, Div. 1 & 2, Groups E, F, Ga Class III, Div. 1 & 2 NEMA 3, 4, 4X, 7 (B, C, D) 9 (E, F, G)
Certified - File LR11714
T
T
R
E
R
E
R
R
A
A
T
T
S
S
S
S
m
H
H
C
C
A
A
O
O
Z
Z
FEATURES-SPECIFICATIONS
Applications
The PRISM
®
B7MSN Series of nonreversing, manual line voltage starters and enclosures are suitable for use in applications requiring manual across-theline starting and stopping of small single and polyphase AC motors, and where overload protection is needed. Manual starters are generally used on small machine tools, fans and blowers, pumps, compressors, and conveyors as well as many other types of electrical equipment.
®
PRISM
enclosures universal design accommodates, as standard, starter manufacturers including
Allen-Bradley 609 Series
Cutler-Hammer B100M Series
GE CR106 Series
Square D 2510M Series
Allen Bradley © Rockwell Automation Cutler-Hammer © Eaton Corporation GE © General Electric Company Square D © Schneider Electric
SINGLE PHASE
SIZE/
PHASE
120VAC 230VAC 208VAC 230VAC 480VAC** 600VAC 115DC 230VDC
M-0 2P 1 2 1 CH 1.5 C H M-1 2P 2 3 1.5 C H 2 CH
M-1P 2P 3 5
M-0 3P 3 3 5 5 M-1 3P 7.5 7.5 10 10
ENCLOSURE
B7MSN2P
CATALOG NUMBER
W/CUTLER-
W/ SQUARE
HAMMER
B7MSN2PC0B B7MSN2PC1B
B7MSN2PC0C B7MSN2PC1C
B7MSN2PS0B B7MSN2PS1B B7MSN2PSDB B7MSN2PS0C B7MSN2PS1C B7MSN2PS0V B7MSN2PS1V
D
M-0 2P VDC M-1 2P VDC
Features
Compact size enclosures provide
application flexibility with cost savings over industry standard sizes
NEMA 4, 4X rated – providing protection
from hose directed water and corrosion
Pre-drilled to facilitate easy field
installation of starters
Large double green/red start-stop push
buttons
Can be pad locked in “OFF” position
Provisions for drain and breather
Bolt on ductile mounting lugs
Two 1-1/2” NPT conduit openings
provided as standard, with custom openings on request
Electrical Rating
NEMA starter sizes 0, 1, 1-1/2 FVNR; 2 pole single phase = 230 VAC 3 pole three phase = 600 VAC 2 pole VDC = 230 VDC
HP
THREE PHASE DC HP
1 1.5
1.5 2
Overload Heaters
Heaters are not included, see next page.
Standard Materials /Finish
Enclosures: Copper-free aluminum (less
than 4/10 of 1% copper content)
Cover Bolts: 316 Stainless Steel
O-ring Gasket: Silicone
Finish: Grey Powder Polyester painted
exterior, electrostatically applied
MODIFICATIONS
SUFFIX
NUMBER
KIT-251 100 amp ground lug
AO Aux. contact NO only AC Aux. contact NC only
SU-2 Hinge-9 Installed
SU3B-4X Drain & Breather installed TYPE 4X
SU3B-4XSS Drain & Breather installed TYPE 4X SS
B7SPNPT Change Std. conduit size and location
SU9 Special paint finish
SU14 Fungus proofing of enclosures
* NOTE: The installation of a Drain & Breather will void
the NEMA 4-4X rating of enclosure.
DESCRIPTION
Optional Position
Standard Lug Position For B7MSN2P
ENCLOSURE
OUTSIDE BOX
DIMENSIONS
NOMINAL INSIDE BOX MOUNTING DIMENSIONS
A B C D E F G H I J K
B7MSN2P 8-1/8 13-1/16 7-13 /16 4-1/ 4 9- 3/16 6-5/16 2-1/ 2 11- 3/8 6-3/8 7-1/ 2 1-13/16
Loading...