cЙ~нмкЙл
• Compact size enclosures provide
application flexibility with cost savings
over industry standard sizes
• Fewer cover bolts reduces installation
and maintenance time
• Gasketed flange with O-ring located in
side bolt circle to seal out moisture
• Rotary handle style operating mechanism with lockout provision as standard
• Removable ductile mounting lugs
adjust to irregular mounting surfaces
• Bodies have top and bottom drilled and
tapped conduit entrances for power connection, with custom openings available
• ABB UL98 certified switch supplied for
30-100 Amp units
^a^mqbo=hfq
• Required for Allen-Bradley and
Sprecher + Schuh disconnects
Order separately
B7KIT - NRW
cбсЙЗ=iмЦ=mзлбнбзе=cзк=_TkcaN
lйнбзе~д=mзлбнбзе=cзк=_TkcaO
pн~еЗ~кЗ=iмЦ=mзлбнбзе=cзк=_TkcaO
_T=`ljm^`q=
pbofbp
DISCONNECT SWITCHES
cb^qrobpJpmb`fcf`^qflkp
Class I, Div. 1 & 2, Groups B,C,D
Class l, Zones 1 & 2, Groups llB+ H2, llA
Class II, Div. 1 & 2, Groups E,F,G
①
Class III
NEMA 3, 4, 4X, 7(B,C,D) 9(E,F,G)
B7NFD1 B7NFD2
C
Certified - File LR11714
US
^ййдбЕ~нбзел
The PRISM
®
B7 Series of non-fused dis-
connect switches are used:
• In locations made hazardous due to the
presence of flammable gasses or vapors
or ignitable dusts, fibers and flyings.
• Outdoors or indoors in damp, wet and
dirty locations, or in areas where frequent
washdowns, heavy rain or water spray
routinely occurs.
• Use as motor circuit disconnect.
PRISM
®
enclosures universal design
accomodates the following manufacturers
switches as standard:
• Advance Controls 14046 Series
• Allen-Bradley 194E Series (B7NFD1 only)
• ABB OT Series
• Cutler-Hammer C362N Series
• Sprecher + Schuh LA7
Advance Controls © Advance Controls Inc.
Allen-Bradley © Rockwell Automation
ABB © Tne ABB Group
Cutler-Hammer © Eaton Corporation
Sprecher + Schuh © Sprecher + Schuh
pн~еЗ~кЗ=j~нЙкб~дл=LcбеблЬ
• Enclosures: Copper-free aluminum
(less than 4/10 of 1% copper content)
• Cover Bolts: 316 Stainless Steel
• O-ring Gasket: Silicone
• Finish: Grey Powder Polyester painted
exterior, electrostatically applied.
• Electrical rating: 600VAC, 30 - 100 Amp
KIT-251 100 amp ground lug
SU-2 Hinge-9 Installed
SU3* Drain & Breather installed (NEMA 7CD)
SU3B* Drain & Breather installed (NEMA 7BCD)
SU9 Special paint finish
A 1 NC+1NO Auxiliary
B7SPNPT Change std. conduit size and location
SU14 Fungus proofing of enclosures
SUFFIX DESCRIPTION
NUMBER
*NOTE: The installation of a Drain & Breather will void the NEMA
4-4X ratings of enclosure.
MODIFICATIONS
** Use MN. 75çC wire
CATALOG NUMBER SWITCH SINGLE PHASE HP THREE PHASE HP DC HP WIRE CONDUIT
ENCLOSURE ONLY W/ABB AMPS / PHASE 120VAC 230VAC 208VAC 230VAC 480VAC 600VAC 230VDC SIZE** SIZES
B7NFD1 B7NFD13A 30 / 3P 2 5 10 10 20 30 1 #14-10 1 NPT
B7NFD2 B7NFD26A 60 / 3P 3 7.5 20 20 40 40 10 #14-4 1-1/2 NPT
B7NFD2 B7NFD21A 100 / 3P 5 15 25 30 50 50 20 #8-1 1-1/2 NPT
Enclosure OUTSIDE BOX NOMINAL MOUNTING
DIMENSIONS INSIDE BOX DIMENSIONS
ABCD EFGHIJK
B7NFD1 5-3/4 8-1/16 6-5/16 3-5/8 5-13/16 5-1/16 3-1/8 8-1/8 - - 1-1/4
B7NFD2 8-1/8 13-1/16 7-13/16 4-1/4 9-3/16 6-5/16 2-1/2 11-3/8 6-3/8 7-1/2 1-13/16
afjbkpflkp