WITHSTANDING VOLTAGE/
INSULATION RESISTANCE TESTER
TOS9200 Series
TOS9200
TOS9201
GPIB/RS-232C INTERFACE
DANGER
This Tester generates high voltage.
Any incorrect handling may cause death.
Read Chapter 2 “
in TOS9200/9201 manual to prevent accident.
Keep this manual together with the manual for
TOS9200/9201, near the tester for easy accsse
of the operator.
PRECAUTIONS ON HANDLING
”
Use of Operation Manual
Please read through and understand this Operation Manual before operating the product. After reading, always
keep the manual nearby so that you may refer to it as needed. When moving the product to another location,
be sure to bring the manual as well.
If you find any incorrectly arranged or missing pages in this manual, they will be replaced. If the manual gets
lost or soiled, a new copy can be provided for a fee. In either case, please contact Kikusui distributor/agent,
and provide the “Kikusui Part No.” given on the cover.
This manual has been prepared with the utmost care; however, if you have any questions, or note any errors or
omissions, please contact Kikusui distrib
utor/agent.
Reproduction and reprinting of this operation manual, whole or partially, without our permission is prohibited.
cations and manual contents are subject to change without notice.
Saf ety Symbols
For the saf e use and saf e maintenance of this pr oduct, the f ollo wing sym -
OR
Indicates that a high v oltage (o v er 1 000 V) is used here . T ouch ing the par t causes a possib ly f atal electr ic shoc k. If ph ysical
contact is required b y y our w or k, star t w or k only after y ou mak e
sure that no v oltage is output here .
oducts).
D
bols are used thr oughout this man ual and on the pr oduct. Under stand
the meanings of the symbols and obser ve the instructions the y indicate
(the c hoice of symbols used depends on the pr
ANGER
WARNING
CAUTION
Indicates an imminently hazardous situation which, if ignored,
will result in death or ser ious injur y .
Indicates a potentially hazardous situation which, if ignored,
could result in death or ser ious injur y .
Indicates a potentially hazardous situation which, if ignored, ma y
result in damage to the product and other proper ty .
Sho ws that the act indicated is prohibited.
Is placed bef ore the sign “D ANGER, ” “W ARNING, ” or “CA U TION” to emphasiz e these . When this symbol is mar k ed on the
product, see the rele v ant sections in this man ual.
TOS9200 GPIB/RS232C
Indicates a protectiv e conductor ter minal.
Indicates a chassis(fr ame) ter
minal.
Safety Symbols I
Description of Contents
This manual is composed of the follo wing chapters.
Chapter 1 TOS9200 GPIB/RS-232CSetup
This chapter describes the preparations to be made for remote control using the
GPIB/RS-232C interface.
Chapter 2 GPIB and RS-232C
This chapter describes the GPIB/RS-232C interf ace and device messages.
Chapter 3 Messa ges and Registers
This chapter describes the de vice messages and registers.
This is the operation manual designed to remotely control the TOS9200 Series withstanding voltage/insulation resistance tester using the GPIB or RS-232C interface.
Attention is focused on the device message used in remote control.
Before starting remote control, prepare the Operation Manual for the TOS9200
Series and gain a full understanding of the instructions given in the manual.
WARNING
NOTE
• In remote control, an external signal is used to turn a high voltage on/off,
resulting in serious potential danger. To avoid the accidental generation of
a high voltage and prevent workers from touching the device under testing
(hereinafter referred to as a “DUT”), the high-voltage test leadwire, the
high-voltage probe, and the output terminals when a high voltage is being
output, provide full safety measures. Never conduct remote control without
taking proper safety measures.
• When an abnormal voltage occurs on the power line while a remote control operation using GPIB or RS-232C interface, the tester returns PROTECTION (line
voltage monitoring) message. However, when the power of the tester is turned on
while an abnormal voltage occurs already on the power line, the tester cannot
return a message.
Personal computer
GPIB/RS-232C
Withstand-voltage/
insulation-resistance tester
TOS9200/9201
H.V
SCAN I/F
Scanner
TOS9220/9221
CH1CH2CH3CH4
H.V
Scanner
TOS9220/9221
CH5CH6CH7CH8
H.V
Scanner
TOS9220/9221
CH9 CH10 CH11 CH12
H.V
Scanner
TOS9220/9221
CH13 CH14 CH15 CH16
SCAN I/F
SCAN I/F
SCAN I/F
Fig.1-1System configuration (example)
TOS9200 GPIB/RS-232CTOS9200 GPIB/RS-232CSetup 1-1
1.1Preparing for GPIB Control
INTERFACE
NOTE
• If settings are made so that the tester controls the earth continuity tester TOS6200,
the GPIB interface cannot be used for remote control. For details, see “Controlling
the TOS6200” in the Operation Manual for the Tester.
1.1.1Connecting the GPIB cable
Turn off all POWER switches on the TOS9200 and other devices that are part of the
GPIB system.
Connect the GPIB cable to the GPIB connector on the rear panel of the TOS9200/
OS9201.
T
1.1.2Setting the GPIB address
To conduct remote control using the GPIB interface, a GPIB address must be set on
the TOS9200/TOS9201. Do not use an address already set in the system.
To set a GPIB address, use the Interface Settings screen.
To display the Interface Settings screen (INTERFACE), press the SHIFT + SYSTEM(I/F) keys. The SYSTEM(I/F) key then lights up.
NOTE
INTERFACE
GPIB ADDRESS : 4
SPEED : 19200 PARITY :
DATA : 8bit STOP : 2bit
GPIB SPEED DATA PARITY STOP
F1 F2 F3 F4 F5
NONE
Set the GPIB address on the TOS9200/TOS9201 to 0 through 30.
• The set GPIB address becomes valid after the TOS9200/9201 is restarted.
1. Using the F1 key (GPIB) or the keys, move the cursor to the GPIB
ADDRESS.
2. Using the rotary knob, set a GPIB address.
3. On the TOS9200/TOS9201, turn off the POWER switch and then turn it on
ain.
ag
1-2 TOS9200 GPIB/RS-232CSetupTOS9200 GPIB/RS-232C
1.2Preparing for RS-232C Control
INTERFACE
1.2.1Connecting the RS-232C cable
Turn off all POWER switches on the TOS9200 and other devices that are part of the
RS-232C system.
Connect the RS-232C cable to the RS-232C connector on the rear panel of the
OS9200/TOS9201.
T
1.2.2RS-232C settings
To make settings, use the Interface Settings screen.
To display the Interface Settings screen (INTERFACE), press the SHIFT + SYSTEM(I/F) keys. The SYSTEM(I/F) key will then light up.
INTERFACE
GPIB ADDRESS : 4
SPEED : 19200 PARITY :
DATA : 8bit STOP : 2bit
GPIB SPEED DATA PARITY STOP
NONE
NOTE
F1 F2 F3 F4 F5
• When the interface settings are changed, they become valid after the TOS9200/
9201 is restarted.
Setting the communication speed of the RS-232C interface
Three communication speeds are available for the RS-232C interface:
38,400 bps
19,200 bps
9,600 bps
1. Using the F2 key (SPEED) or the keys, move the cursor to SPEED.
2. Using the rotary knob, select 38,400, 19,200, or 9,600 bps.
Setting the data length of the RS-232C interface
The following two data lengths are available for the RS-232C interface:
7 bits
8 bits
1. Using the F3 key (DATA) or the keys, move the cursor to DATA.
2. Using the rotary knob, select 7 or 8.
TOS9200 GPIB/RS-232CTOS9200 GPIB/RS-232CSetup 1-3
Setting the parity of the RS-232C interface
The following three parities are available for the RS-232C interface:
NONE
ODD
EVEN
1. Using the F4 key (PARITY) or the keys, move the cursor to PARITY.
2. Using the rotary knob, select NONE, ODD, or EVEN.
Setting the stop bit of the RS-232C interface
The following two stop bits are available for the RS-232C interface:
1 bit
2 bits
1. Using the F5 key (STOP) or the keys, move the cursor to STOP.
2. Using the rotary knob, select 1 or 2.
1-4 TOS9200 GPIB/RS-232CSetupTOS9200 GPIB/RS-232C
Chapter 2GPIB and RS-232C
This chapter describes the GPIB/RS-232C interface and device messages.
2.1Interface
The tester is provided with a GPIB and RS-232C interface. Either can be selected.
2.1.1GPIB interface
List of GPIB functions
Function SubsetDescription
Source handshaking SH1All functions provided
Acceptor handshakingAH1All functions provided
TalkerT6All functions provided except for the talk-only function
Expansion talkerTE0No function
ListenerL4All functions provided except for the listen-only function
Expansion listenerLE0No function
Service requestSR1All functions provided
Remote localRL1All functions provided
Parallel pollingPP0No function
Device clearDC1All functions provided
Device triggerDT0No function
ControllerC0No function
Electrical interfaceE1
Open collector
GPIB cables are available from Kikusui. Contact the supplier or your Kikusui agent.
GPIB cable: 1 m (Product No. 92080)
GPIB cable: 2 m (Product No. 92070)
GPIB cable: 4 m (Product No. 92090)
2.1.2RS-232C interface
To use an RS-232C interface, the settings specified below must be made. For the
setting procedure, see "1.2.2 RS-232C settings".
•RS-232C interface communication speed
•RS-232C interface data
•RS-232C interface parity
•RS-232C interface stop bit
Communication with the RS-232C must be regulated by flo
acknowledge message. One-w
ay transmission may make proper communication
difficult. For details on acknowledge messages, see "2.2.1 Messages".
As the RS-232C cable, use an AT-type 9-pin D-SUB female-female cross cable.
TOS9200 GPIB/RS-232CGPIB and RS-232C 2-1
w control or using an
RS-232C pin assignment
1: CD (carrier detection)
2: RXD (received data)
3: TXD (transmitted data)
4: DTR (data terminal ready)
5: GND (signal ground)
9: RI (ring indicator)
8: CTS: (clear to send)
7: RTS: (request to send)
6: DSR (data set ready)
1
2
3
4
5
6
7
8
9
9-pin D-SUB female
1
2
3
4
5
6
7
8
9
9-pin D-SUB female
On the tester
Fig.2-1AT-type 9-pin connector
RS-232C flow control
Communication among tester controllers can be controlled by executing Xon and
Xoff. These control codes are controlled by DC (Device Control) codes.
DC1Send request11h
DC3Send Stop request13h
Controlling transmission from the RS-232C terminal to the tester
RXD
TXD
Example of a cross cable
Function ASCII code
DC3
The tester suspends transmission within three characters following the
receipt of DC3.
Up to three
characters
Suspend
DC1
Restart transmission
Controlling transmission from the tester to the RS-232C terminal
TXD
RXD
DC3
Have the RS-232C terminal suspend transmission within 10 characters
following the receipt of DC3.
Up to ten
characters
Suspend
DC1
Restart transmission
Fig.2-2Controlling transmission between the RS-232C terminal and
the tester
2-2 GPIB and RS-232CTOS9200 GPIB/RS-232C
2.2Messages and Terminators
This section explains the terms used for communication between the computer
(controller) and the tester (device). See Fig. 2-3.
Program message
Controller
Command
message
Query
message
Command
program
header
Query
program
header
Program
data
Program
-message
terminator
Response
message
Device
Fig.2-3Messages and terminators
2.2.1Messages
Commands sent from the computer to the tester are referred to as “program messages.” Responses sent from the tester to the computer are referred to as “response
messages.”
Each message is composed of a program-header block and a data block.
Program messages
Program messages are either “command messages” or “query messages.”
Command messages are used to execute specific functions of the tester and to
change settings.
Query messages are used to inquire about the settings and status of the tester.
Program
header
Response
program
header
Data
Response
data
Response
-message
terminator
ControllerDevice
Describing a program message
•A space (ASCII: 20h) must be inserted between the program header and the
data.
Program headerSpace (ASCII: 20h)Data
TOS9200 GPIB/RS-232CGPIB and RS-232C 2-3
•If there are two or more pieces of data, connect them using “ , ” (ASCII: 2Ch).
,
Program headerSpace (ASCII: 20h)Data
•To connect program messages, use “ ; ” (ASCII: 3Bh).
;
Program message
NOTE
• To describe data using hexadecimals, add “#H.”
(Example) The decimal 10 is expressed as “#H0A” in hexadecimal.
• With the GPIB interface, add “@” to the end of a program message to maintain
the HOLD OFF status until the message has been executed. However, in the event
of a command message terminator with only EOI, use "@@".
Acknowledge message (RS-232C)
Acknowledge messages are used only with the RS-232C interface. They are sent
from the tester to the controller, and are used to confirm that the handling of a program message has been completed.
Acknowledge header
Acknowledge messages contain only a header composed of character strings in
ASCII codes. The following two acknowledge messages are used:
• OK: Normal termination
• ERROR: Abnormality such as a syntax error
Using the SILENT command message, settings can be made to specify whether to
return an ackno
2-4 GPIB and RS-232CTOS9200 GPIB/RS-232C
wledge message.
2.2.2Terminators
A program-message terminator is used to end a program message. A response-message terminator is used to end a response message.
•Program-message terminators
Any of the following can be used as a program-message terminator. No settings necessary:
CR+LF+EOI, LF, LF+EOI, CR+EOI
•Response-message terminators
By default, CR+LF+EOI is used. It can be changed to one of the following in
accordance with the
CR+LF+EOI, LF+EOI, EOI, CR+EOI
TRM command message. EOI is used only for GPIB.
NOTE
• EOI is exclusively used for GPIB as a program-message terminator and a
response-message terminator.
TOS9200 GPIB/RS-232CGPIB and RS-232C 2-5
2-6 GPIB and RS-232CTOS9200 GPIB/RS-232C
Chapter 3Messages and Registers
Program messages and response messages supported by the tester are referred to as
“device messages.”
The following describes each device message supported by the tester.
The symbol in parentheses following the device-message name is the abbreviation
of the message name.
Special symbols and characters
The symbols and characters used to describe program messages and response messages are given below, along with their definitions.
Symbols and characterDescription
< >
{ }
_Represents a space
The parentheses indicate program data. In actual programming,
do not use these parentheses.
Choose one from among the characters and numerals enclosed
in parentheses and separated by “ : ”. In actual programming,
do not use these parentheses.
3.1Register-Related Messages and General
Purpose Messages
Below, general purpose device messages and messages common to all modes are
explained. general purpose device messages are used to set and reset each register,
make inquiries, and specify a terminator.
*CLS
Resets the status byte register, event status register, device status register, protection
register 1, protection register 2, fail register, invalid-setting register, and error register.
For each register, see "3.9 Registers".
Program message
• Syntax
Command message:
*CLS
TOS9200 GPIB/RS-232CMessages and Registers 3-1
*ESR
*IDN
The event status register is reset when it is read by the *ESR? Message.
For details on the event status register, see "3.9 Registers".
Program message
• Syntax
Query message:
Response message
To reset, the contents of the event status register are returned to *ESR?.
(Example) When Bit 5 of the event status register is set,
Inquires about the model name and ROM version of the tester
Program message
• Syntax
Query message:
*ESR?
32 is returned.
*IDN?
*RST
Response message
The model name of the tester is returned to *IDN?, as follows:
KIKUSUI ELECTRONICS CORP., TOS9200, 0, 1.00
Company name
Initializes the tester (to original factory-set settings). Note the settings made in the
INTERFACE screen will not be initialized.
For details on initialization, see the relevant section of the operation manual for the
.
tester
Program message
• Syntax
Command message:
*RST
Model name
Version No.
Not used
3-2 Messages and RegistersTOS9200 GPIB/RS-232C
*SRE
Sets or resets each bit of the service-request enable register, or inquires about the
contents of the register.
For details on the service-request enable register, see "3.9 Registers".
Program message
• Syntax
Command message:
Query message:*SRE?
• Program data
Data format:Hexadecimal or decimal
Set value:00H to FFH (0 to 255)
Resolution:1H (1)
(Example) To set the service-request enable register to #50H,
*SRE #H50
Response message
To *SRE?, the contents of the service-request enable register are returned.
(Example) When Bit 5 and Bit 6 of the service-request enable register are set,
returned.
*SRE_<value>
96 is
*STB
Used to inquires about the contents of the status byte register.
For details on the status byte register, see "3.9 Registers".
Program message
• Syntax
Query message:
Response message
To *STB?, the contents of the status byte register are returned.
(Example) When Bit 5 and Bit 6 of the status byte register are set,
*STB?
96 is returned.
TOS9200 GPIB/RS-232CMessages and Registers 3-3
CLR
DSE
Resets all registers exclusive of enable register and sets the STOP flag.
The same procedure is performed as when the GPIB bus line message DCL or SDC
has been received.
Also used to perform the same processing as is performed by a DCL message from
the RS-232C.
Program message
• Syntax
Command message:
Sets or resets each bit of the device-status enable register, or inquires about the contents of the register.
For details on the device-status enable register, see "3.9 Registers".
Program message
• Syntax
Command message:
Query message:DSE?
CLR
DSE_<value>
DSR
• Program data
Data format:Hexadecimal or decimal
Set value:00H to FFH (0 to 255)
Resolution:1H (1)
(Example) To set the device-status enable register to 01H,
DSE #H01
Response message
To DSE?, the contents of the device-status enable register are returned.
(Example) When Bit 5 of the device-status enable register is set,
Used to inquires about the contents of the device status register.
For details on the device status register, see "3.9 Registers".
Program message
• Syntax
Query message:
DSR?
32 is returned.
3-4 Messages and RegistersTOS9200 GPIB/RS-232C
ERR
FAIL
Response message
To DSR?, the contents of the device status register are returned.
(Example) When Bit 5 of the device-status enable register is set,
The error register is reset when read by the ERR? Message.
For details on the error register, see "3.9 Registers".
Program message
• Syntax
Query message:
Response message
To ERR?, the contents of the error register are returned.
(Example) When Bit 3 of the error register is set,
ERR?
8 is returned.
32 is returned.
Inquires about the contents of the fail register.
For details on the fail register, see "3.9 Registers".
Program message
• Syntax
Query message:
Response message
To FAIL?, the contents of the fail register are returned.
(Example) When Bit 4 of the fail register is set,
FUNCTION (FUN)
Shifts the LCD to each mode (setting screen) and Inquires about the current mode
(displayed screen).
Program message
• Syntax
Command message:
Query message:FUNCTION?
FAIL?
16 is returned.
FUNCTION_<value>
FUN_<
FUN?
value>
TOS9200 GPIB/RS-232CMessages and Registers 3-5
• Program data
(Example) To change the contents of the program (to shift to AUTO EDIT)
Response message
To FUN?, the current mode is returned.
(Example) If the current mode is the AC withstanding voltage test,
INVALID (INV)
Used to inquires about the contents of the invalid-setting register.
For details on the invalid-setting register, see "3.9 Registers".
Program message
• Syntax
Data format:Integer
Set value:0: ACW; 1: DCW; 2: IR; 3: AUTO TEST; 4: AUTO EDIT;
5: SYSTEM; 6: OFFSET ADJ; 7: INTERFACE
FUN 4
0 is returned.
Query message:
INVALID?
INV?
Response message
To INV?, the contents of the invalid-setting register are returned.
(Example) When Bit 3 of the invalid-setting register is set,
LOCAL (LOC)
Return to the LOCAL from the REMOTE state.
Program message
• Syntax
Query message:
8 is returned.
LOCAL
LOC
3-6 Messages and RegistersTOS9200 GPIB/RS-232C
PROTECTION (PROT)
Inquires about the contents of protection registers 1 and 2.
For details on the protection registers, see "3.9 Registers".
Program message
• Syntax
Query message:
Response message
To PROT?, the contents of protection registers 1 and 2 are returned.
(Example) When Bit 3 and Bit 5 are set in protection registers 1 and 2, 8 and 32 are
returned, respectively
SILENT (SIL)
Used in control via RS-232C to specify whether to return an acknowledgment message to a message divided by the response message terminator. The SILENT? message is used to inquire about the set value that specifies whether to return an
acknowledgment message.
As an acknowledgment message, either “OK” or “ERR
If an acknowledgment message is to be received, the RS-232C must be set at full
x communication.
duple
Full duple
x communication: The transmission of data in two directions simulta-
PROTECTION?
PROT?
.
OR.” is returned.
neously. For full duplex settings, see the manual for
your PC.
Program message
• Syntax
Command message:
Query message:SILENT?
• Program data
Data format:Integer
Set value:0: Return an acknowledge message.
(Example) To set “Do not return an acknowledge message,”
SIL 1
Response message
To SIL?, the set value for an acknowledge message is returned.
(Example) If the current settings are made to “Do not return an acknowledge mes-
1 is returned.
sage,”
TOS9200 GPIB/RS-232CMessages and Registers 3-7
SILENT_<{0|1}>
SIL_<{0|1}>
SIL?
1: Do not return an acknowledge message.
START
STOP
Starts testing.
While a test program is running, it shifts the program from the step suspended due
to a HOLD setting in the interval to the next step.
This command message is valid only in the test conditions set up (ACW, DCW, IR),
fset measurement (OFFSET), or program (AUT
of
the FUNCTION message.
Program message
• Syntax
Command message:
Stops a test. Also cancels FAIL, PASS (HOLD), and PROTECTION.
Program message
• Syntax
Command message:
START
STOP
O) screens. Switch screens using
TRM
Used to set the response-message terminator, then inquire about the set value it.
Note that the GPIB uni-line message “EOI” is effective only in GPIB communication.
Program message
• Syntax
Command message:
Query message:TRM?
• Program data
Data format:Integer
Set value:0: CR/LF+EOI; 1: LF+EOI; 2: EOI; 3: CR+EOI
(Example) To set the response-message terminator to LF+EOI,
TRM 1
Response message
To TRM?, the preset response-message terminator is returned.
(Example) If the response-message terminator is set to LF+EOI,
TRM_<{0|1|2|3}>
1 is returned.
3-8 Messages and RegistersTOS9200 GPIB/RS-232C
3.2Messages Exclusively Used for AC
Withstanding Voltage Testing
This section explains the messages used to check the test conditions and settings for
AC withstanding voltage testing.
ACW:TESTV (A:TES)
Sets the test voltage for an AC withstanding voltage test, or inquires about the set or
setting test voltage
NOTE
• This message is valid even during a test. However, make only fine voltage adjustment instead of making a large change to the voltage. A substantial change may
activate the protective circuit to shift the tester to the protection status.
Program message
• Syntax
Command message:
Query message:ACW:TESTV?
• Program data
Data format:Real number
Set value:0.00 to 5.20 E3 (or 0 to 5 200)
Resolution:0.01
Unit:V
(Example) To set the test voltage to 5.00 kV,
A:TES 5.00E3
Response message
To A:TES?, the currently set test voltage is returned.
(Example) If the currently set test voltage is 2.50 kV,
ACW:TESTV_<voltage>
A:TES_<voltage>
A:TES?
2.50E3 is returned.
TOS9200 GPIB/RS-232CMessages and Registers 3-9
ACW:FREQUENCY (A:FREQ)
Sets the test frequency for an AC withstanding voltage test, or inquires about the set
or setting test frequency.
Program message
• Syntax
Command message:
Query message:ACW:FREQUENCY?
• Program data
Data format:Character
Set value:50, 60
Unit:Hz
(Example) To set the test frequency to 50 Hz,
A:FREQ 50
Response message
To A:FREQ?, the currently set test frequency is returned.
(Example) If the current test frequency is 60 Hz,
60 is returned.
ACW:FREQUENCY_<{50|60}>
A:FREQ_<{50|60}>
A:FREQ?
ACW:LOWER (A:LOW)
Sets the lower current (LOWER) and ON/OFF of the lower judgment function for
an AC withstanding voltage test. Also inquires about the lower current and the ON/
OFF status of the lower judgment function.
Program message
• Syntax
Command message:
Query message:ACW:LOWER?
• Program data <lower current>
Data format:Real number
Set value:0.01 E-3 to 110 E-3
Resolution:0.01 E-3 (0.01 E-3 to 9.99 E-3)
Unit:A
ACW:LOWER_<lower current, {ON|OFF}>
A:LOW_<
A:LOW?
0.1 E-3 (10.0 E-3 to 99.9 E-3)
1 E-3 (100 E-3 to 110 E-3)
lower current, {ON|OFF}>
3-10 Messages and RegistersTOS9200 GPIB/RS-232C
• Program data <{ON|OFF}>
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the lower current (LOWER) to 10.0 mA,
A: LOW 10.0E-3,ON
Response message
To A:LOW?, the currently set lower current and the ON/OFF status of the lower
judgment function are returned as “lower current, 1/0.”
(Example) If the present lower current is 5.00 mA and the lower judgment function
is OFF
ACW:UPPER (A:UPP)
Sets the upper current (UPPER) for an AC withstanding voltage test. Also inquires
about the present upper current.
,
5.00E-3,0 is returned.
CAUTION
• If the upper current is set above 50 mA, the protective circuit may be activated. To prevent this, set the output time below 30 minutes and the pause
to longer than the output time.
Program message
• Syntax
Command message:
Query message:ACW:UPPER?
• Program data
Data format:Real number
Set value:0.01 E-3 to 110 E-3
Resolution:0.01 E-3 (0.01 E-3 to 9.99 E-3)
Unit:A
(Example) To set the upper current to 50.0 mA,
A:UPP 50.0E-3
ACW:UPPER_<upper current>
A:UPP_<
A:UPP?
0.1 E-3 (10.0 E-3 to 99.9 E-3)
1 E-3 (100 E-3 to 110 E-3)
upper current>
Response message
To A:UPP?, the present upper current is returned.
(Example) If the present upper current is 80.0 mA,
80.0E-3 is returned.
TOS9200 GPIB/RS-232CMessages and Registers 3-11
ACW:TIMER (A:TIM)
Sets the test time (TEST TIME) and ON/OFF of the timer function for an AC withstanding voltage test. Also inquires about the current test time and the ON/OFF status of the timer function.
CAUTION
• If the upper current is set above 50 mA, the protective circuit may be activated. To prevent this, set the output time below 30 minutes and the pause
to longer than the output time.
Program message
• Syntax
Command message:
Query message:ACW:TIMER?
• Program data <test time>
Data format:Real number
Set value:0.3 to 999
Resolution:0.1 for 0.3 to 99.9, 1 for 100 to 999
Unit:s
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the test time to 5 s,
<{ON|OFF}>
A:TIM 5,ON
ACW:TIMER_<test time, {ON|OFF}>
A:TIM_<
A:TIM?
test time, {ON|OFF}>
Response message
To A:TIM?, the current test time and the ON/OFF status of the timer function are
returned as “test time, ON/OFF.”
(Example) If the current test time is 2.0 s and the timer function is set to OFF,
2.0,0 is returned.
3-12 Messages and RegistersTOS9200 GPIB/RS-232C
ACW:OFFSET (A:OFF)
Sets ON/OFF of the offset function for an AC withstanding voltage test. Also
inquires about the ON/OFF status of the offset function.
Program message
• Syntax
Command message:
Query message:ACW:OFFSET?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the offset function to ON,
A:OFF 1
Response message
To A:OFF?, the ON/OFF status of the offset function is returned.
(Example) If the offset function is currently set to OFF,
0 is returned.
ACW:OFFSET_<{ON|OFF}>
A:OFF_<{ON|OFF}>
A:OFF?
ACW:STARTV (A:STAR)
Sets the start voltage for an AC withstanding voltage test. Also inquires about the set
or setting start voltage.
Program message
• Syntax
Command message:
Query message:ACW:STARTV?
• Program data
Data format:Integer
Set value:0 to 99
Resolution:1
Unit:%
(Example) To set the start voltage to 10% of the test voltage,
A:STAR 10
Response message
To A:STAR?, the current start voltage is returned.
(Example) If the start voltage is currently set to 0%,
0 is returned.
ACW:STARTV_<start voltage>
A:STAR_<
A:STAR?
start voltage>
TOS9200 GPIB/RS-232CMessages and Registers 3-13
ACW:RISETIME (A:RTIM)
Sets the voltage rise time (RISE TIME) for an AC withstanding voltage test. Also
inquires about the set or setting voltage rise time.
Program message
• Syntax
Command message:
Query message:ACW:RISETIME?
• Program data
Data format:Real number
Set value:0.1 to 200
Resolution:0.1 for 0.1 to 99.9, 1 for 100 to 200
Unit:s
(Example) To set the voltage rise time to 1 s,
A:RTIM 1
Response message
To A:RTIM?, the current voltage rise time is returned.
(Example) If the voltage rise time is currently set to 2.0 s,
2.0 is returned.
ACW:RISETIME_<voltage rise time>
A:RTIM_<
A:RTIM?
voltage rise time>
ACW:FALLTIME (A:FTIM)
Sets the voltage fall time (FALL TIME) for an AC withstanding voltage test. Also
inquires about the set or setting voltage fall time.
Program message
• Syntax
Command message:
Query message:ACW:FALLTIME?
• Program data
Data format:Real number
Set value:0.0 to 200
Resolution:0.1 for 0.0 to 99.9, 1 for 100 to 200
Unit:s
(Example) To set the voltage fall time to 1 s,
A:FTIM 1
ACW:FALLTIME_<voltage fall time>
A:FTIM_<
A:FTIM?
voltage fall time>
3-14 Messages and RegistersTOS9200 GPIB/RS-232C
Response message
To A:FTIM?, the current voltage fall time is returned.
(Example) If the voltage fall time is currently set to 2.0 s,
2.0 is returned.
ACW:VRANGE (A:VRAN)
Sets the output-voltage range for an AC withstanding voltage test. Also inquires
about the set or setting output range.
Program message
• Syntax
Command message:
Query message:ACW:VRANGE?
• Program data
Data format:Integer
Set value:0: AUTO; 1: 5 kV
(Example) To set the output range to AUTO,
A:VRAN 0
ACW:VRANGE_<{0|1}>
A:VRAN_<{0|1}>
A:VRAN?
Response message
To A:VRAN?, the output-voltage range is returned.
(Example) If the current output-voltage range is 5 kV,
1 is returned.
ACW:RESPONSE (A:RES)
Sets the current detection response speed (RESPONSE) for an AC withstanding
voltage test.
Also inquires about the set or setting current detection response speed.
Program message
• Syntax
Command message:
Query message:ACW:RESPONSE?
• Program data
Data format:Integer
Set value:0: SLOW; 1: MID; 2: FAST
ACW:RESPONSE_<{0|1|2}>
A:RES_<{0|1|2}>
A:RES?
TOS9200 GPIB/RS-232CMessages and Registers 3-15
(Example) To set the current detection response speed to FAST,
Response message
To A:RES?, the preset current detection response speed is returned.
(Example) If the detection response speed is currently set to MID,
ACW:GND (A:GND)
Sets LOW/GUARD of the GND for an AC withstanding voltage test. Also inquires
about the set or setting value of the GND.
A:RES 2
1 is returned.
WARNING
• If it is not known whether a DUT or jig is grounded, never select GUARD.
If GUARD is selected with a DUT grounded, the ammeter will be short-cir-
cuited, disabling measurement and posing grave danger. See Fig. 3-1 (B).
• When GUARD is selected, do not connect the tester to devices grounded
on a single side
, such as Kikusui’s high-v
oltage digital voltmeter 149-10A
and the current calibrator TOS1200. Otherwise, the ammeter will be shortcircuited. See Fig. 3-1 (A).
HIGH VOLTAGE terminal
D
U
T
Ammeter
LOW
terminal
TOS9200/9201
Setting to GUARD
149-10A
(A) Connecting the 149-10A
HIGH VOLTAGE terminal
D
U
T
Ammeter
Stray capacity
and insulation
resistance of
the test lead
wire and jig
LOW
terminal
TOS9200/9201
Setting to GUARD
(B) Selecting GUARD when the DUT is grounded
Fig.3-1Dangerous connections
3-16 Messages and RegistersTOS9200 GPIB/RS-232C
CAUTION
• When the tester’s LOW terminal is connected to the HIGH or LOW terminal on the earth continuity tester TOS6200, the ammeter will make measurement errors if GUARD is selected. This is due to the fact that the
resistor in the TOS6200 is connected in parallel with the tester’s ammeter.
To use the TOS6200, do not connect one terminal to another, or set the
LOW terminal to LOW.
Program message
• Syntax
Command message:
Query message:ACW:GND?
• Program data
Data format:Character
Set value:LOW (0), GUARD (1)
(Example) To set the GND to GUARD,
A:GND 1
Response message
To A:GND?, the current GND setting is returned.
(Example) If the GND is currently set to LOW,
0 is returned.
ACW:GND_<{GUARD|LOW}>
A:GND_<{GUARD|LOW}>
A:GND?
ACW:SCAN (A:SCAN)
Sets HIGH/LOW/OPEN for the scanner channel for an AC withstanding voltage
test.
Also inquires about the set or setting value of the high-voltage scanner channel.
Program message
• Syntax
Command message:
Query message:ACW:SCAN?_<channel>
• Program data <channel>
Data format:Integer
Set value:1 to 16
Resolution:1
• Program data
Data format:Character
ACW:SCAN_<channel, {H|L|O}>
A:SCAN_<
A:SCAN?_<
<{H|L|O}>
channel, {H|L|O}>
channel>
TOS9200 GPIB/RS-232CMessages and Registers 3-17
Set value:O (0): OPEN; L (1): LOW; H (2): HIGH
(Example) To set scanner channel 1 to HIGH,
A:SCAN 1,H
Response message
To A:SCAN?2, the preset value for scanner channel 2 is returned.
(Example) If scanner channel 2 is currently set to OPEN,
0 is returned.
ACW:SCANW (A:SCANW)
Sets HIGH/LOW/OPEN for 16 scanner channels at a time using 16 bits for an AC
withstanding voltage test. Also inquires about the current settings for all 16 channels.
Program message
• Syntax
Command message:
Query message:ACW:SCANW?
ACW:SCANW_<setting 1, setting 2>
A:SCANW_<
A:SCANW?
setting 1, setting 2>
• Program data <setting 1>
Data format:Integer
Set value:0 to 65535 (#HFFFF)
Resolution:1
LOW is represented by 0 and HIGH by 1.
• Program data
Data format:Integer
Set value:0 to 65535 (#HFFFF)
Resolution:1
OPEN is represented by 1 and NOT OPEN by 0.
(Example) To set scanner channels 1 through 4 to LOW, scanner channels 5 through
Response message
To A:SCANW?, the settings for all 16 channels are returned as “setting 1” and “setting 2” using 16 bits.
(Example) If scanner channels 1 through 5 are currently set to HIGH, channels 6
<setting 2>
8 to HIGH, and the other channels to OPEN,
A:SCANW #H00F0,#HFF00
OPEN in setting 2 has priority over setting 1.
through 10 to OPEN, and the other channels to LO
31,992 is returned.
W,
3-18 Messages and RegistersTOS9200 GPIB/RS-232C
ACW:CONTACTCHECK (A:CCH)
Sets ON/OFF of the contact check function for an AC withstanding voltage test.
Also inquires about the status of the function.
Program message
• Syntax
Command message:
Query message:ACW:CONTACTCHECK?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the contact check to ON,
A:CCH ON
Response message
To A:CCH?, the current setting for the contact check is returned.
(Example) If the contact check is currently set to ON,
1 is returned.
ACW:CONTACTCHECK_<{ON|OFF}>
A:CCH_<{ON|OFF}>
A:CCH?
TOS9200 GPIB/RS-232CMessages and Registers 3-19
3.3Messages Used Exclusively for DC
Withstanding Voltage Testing
This section explains the messages used to check the test conditions and settings for
DC withstanding voltage testing.
These messages are exclusively designed for the TOS9201 equipped with a DC
withstanding v
With the
DCW:TESTV (D:TES)
Sets the test voltage for a DC withstanding voltage test. Also inquires about the set
or setting test voltage
oltage testing function.
TOS9200, these messages are invalid. However, they do not cause an error.
NOTE
• This message is valid even during a test. However, make only fine voltage adjustments rather than large changes to the voltage. A substantial change may activate
the protective circuit to shift the tester to the protection status.
Program message
• Syntax
Command message:
Query message:DCW:TESTV?
• Program data
Data format:Real number
Set value:0.00 E3to 6.10 E3 (or 0 to 6100)
Resolution:0.01 E3
Unit:V
(Example) To set the test voltage to 5.00 kV,
D:TES 5.00E3
Response message
To D:TES?, the currently set test voltage is returned.
(Example) If the test voltage is currently set to 2.50 kV,
2.50E3 is returned.
DCW:TESTV_<voltage>
D:TES_<
D:TES?
voltage>
3-20 Messages and RegistersTOS9200 GPIB/RS-232C
DCW:LOWER (D:LOW)
Sets the lower current (LOWER) and ON/OFF of the lower judgment function for a
DC withstanding voltage test. Also inquires about the lower current and the ON/
OFF status of the lower judgment function.
Program message
• Syntax
Command message:
Query message:DCW:LOWER?
• Program data <lower current>
Data format:Real number
Set value:0.01 E-3 to 11.0 E-3
Resolution:0.01 for 0.01 E-3 to 9.99 E-3, 0.1 for 10.0 E-3 to 11.0 E-3
Unit:A
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the lower current to 1 mA,
D:LOW 1E-3,ON
DCW:LOWER_<lower current, {ON|OFF}>
D:LOW_<
D:LOW?
<{ON|OFF}>
lower current, {ON|OFF}>
Response message
To D:LOW?, the currently set lower current and the ON/OFF status of the lower
judgment function are returned as “lower current, ON/OFF.”
(Example) If the lower current is currently set to 2.0 mA and the lower judgment
function to OFF
“2.00E-3,0” is returned.
,
TOS9200 GPIB/RS-232CMessages and Registers 3-21
DCW:UPPER (D:UPP)
Sets the upper current (UPPER) for a DC withstanding voltage test. Also inquires
about the set or setting upper current.
CAUTION
• If the upper current is set above 5 mA, the protective circuit may be activated. To prevent this, set the output time below 1 minute and the pause to
longer than the output time.
Program message
• Syntax
Command message:
Query message:DCW:UPPER?
• Program data
Data format:Real number
Set value:0.01 E-3 to 11.0 E-3
Resolution:0.01 for 0.01 E-3 to 9.99 E-3, 0.1 for 10.0 E-3 to 11.0 E-3
Unit:A
(Example) To set the upper current to 5 mA,
A:UPP 5E-3
Response message
To D:UPP?, the preset upper current is returned.
(Example) If the upper current is currently set to 2.00 mA,
2.00E-3 is returned.
DCW:UPPER_<upper current>
D:UPP_<
D:UPP?
upper current>
DCW:TIMER (D:TIM)
Sets the test time (TEST TIME) and ON/OFF of the timer function for an DC withstanding voltage test. Also inquires about the current test time and the ON/OFF status of the timer function.
Program message
• Syntax
Command message:
Query message:DCW:TIMER?
• Program data <test time>
Data format:Real number
3-22 Messages and RegistersTOS9200 GPIB/RS-232C
DCW:TIMER_<test time, {ON|OFF}>
D:TIM_<
D:TIM?
test time, {ON|OFF}>
Set value:0.3 to 999
Resolution:0.1 for 0.3 to 99.9, 1 for 100 to 999
Unit:s
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the test time to 5 s,
Response message
To D:TIM?, the current test time and the ON/OFF status of the timer function are
returned as “test time, 1/0.”
(Example) If the test time is currently set to 2.0 s and the timer function to OFF,
<{ON|OFF}>
D:TIM 5,ON
2.0,0 is returned.
DCW:STARTV (D:STAR)
Sets the start voltage for a DC withstanding voltage test. Also inquires about the set
or setting start voltage.
Program message
• Syntax
Command message:
Query message:DCW:STARTV?
• Program data
Data format:Integer
Set value:0 to 99
Resolution:1
Unit:%
(Example) To set the start voltage to 10% of the test voltage,
D:STAR 10
Response message
To D:STAR?, the current start voltage is returned.
(Example) If the start voltage is currently set to 0%,
0 is returned.
DCW:STARTV_<start voltage>
D:STAR_<
D:STAR?
start voltage>
TOS9200 GPIB/RS-232CMessages and Registers 3-23
DCW:RISETIME (D:RTIM)
Sets the voltage rise time (RISE TIME) for a DC withstanding voltage test. Also
inquires about the set or setting voltage rise time.
Program message
• Syntax
Command message:
Query message:DCW:RISETIME?
• Program data
Data format:Real number
Set value:0.1 to 200
Resolution:0.1 for 0.1 to 99.9, 1 for 100 to 200
Unit:s
(Example) To set the voltage rise time to 1 s,
D:RTIM 1
Response message
To D:RTIM?, the current voltage rise time is returned.
(Example) If the voltage rise time is currently set to 2.0 s,
2.0 is returned.
DCW:RISETIME_<voltage rise time>
D:RTIM_<
D:RTIM?
voltage rise time>
DCW:WAITTIME (D:WTIM)
Sets the WAIT TIME for a DC withstanding voltage test. Also inquires about the set
or setting WAIT TIME.
Program message
• Syntax
Command message:
Query message:DCW:WAITTIME?
• Program data
Data format:Real number
Set value:0.3 to 10.0
Resolution:0.1
Unit:s
(Example) To set the WAIT TIME to 1 s,
D:WTIM 1
DCW:WAITTIME_<WAIT TIME>
D:WTIM_<
D:WTIM?
WAIT TIME>
3-24 Messages and RegistersTOS9200 GPIB/RS-232C
Response message
To D:WTIM?, the currently set WAIT TIME is returned.
(Example) If the WAIT TIME is currently set to 2.0 s,
DCW:GND (D:GND)
Sets LOW/GUARD of the GND for a DC withstanding voltage test. Also inquires
about the set or setting value of the GND.
2.0 is returned.
WARNING
• If it is not known whether a DUT or jig is grounded, never select GUARD.
If GUARD is selected with a DUT grounded, the ammeter will be short-cir-
cuited, disabling measurement and posing a grave danger. See Fig. 3-2
(B).
• When GUARD is selected, do not connect the tester to devices grounded
on a single side
, such as Kikusui’s high-v
oltage digital voltmeter 149-10A
or current calibrator TOS1200. Otherwise, the ammeter will be short-circuited. See Fig. 3-2 (A).
HIGH VOLTAGE terminal
D
U
T
Ammeter
LOW
terminal
TOS9201
Setting to GUARD
149-10A
(A) Connecting the 149-10A
HIGH VOLTAGE terminal
D
U
T
Ammeter
LOW
terminal
TOS9201
Setting to GUARD
Insulation
resistance of test
lead wire and jig
(B) Selecting GUARD when the DUT is grounded
Fig.3-2Dangerous connections
TOS9200 GPIB/RS-232CMessages and Registers 3-25
CAUTION
• When the tester’s LOW terminal is connected to the HIGH or LOW terminal of the earth continuity tester TOS6200, the ammeter will suffer measurement errors if GUARD is selected, as the resistor in the TOS6200 is
connected in parallel with the tester’s ammeter. To use the TOS6200,
either do not connect one terminal to another, or set the LOW terminal to
LOW.
Program message
• Syntax
Command message:
Query message:DCW:GND?
• Program data
Data format:Character
Set value:LOW (0), GUARD (1)
(Example) To set the GND to GUARD,
D:GND 1
Response message
To D:GND?, the current GND setting is returned.
(Example) If the GND is currently set to LOW,
0 is returned.
DCW:GND_<{GUARD|LOW}>
D:GND_<{GUARD|LOW}>
D:GND?
DCW:SCAN (D:SCAN)
Sets HIGH/LOW/OPEN for the scanner channel in a DC withstanding voltage test.
Also inquires about the current setting for the scanner channel.
Program message
• Syntax
Command message:
Query message:DCW:SCAN?_<channel>
• Program data <channel>
Data format:Integer
Set value:1 to 16
Resolution:1
• Program data
Data format:Character
Set value:O (0): OPEN; L (1): LOW; H (2): HIGH
DCW:SCAN_<channel, {H|L|O}>
D:SCAN_<
D:SCAN?_<
<{H|L|O}>
channel, {H|L|O}>
channel>
3-26 Messages and RegistersTOS9200 GPIB/RS-232C
(Example) To set scanner channel 1 to HIGH,
D:SCAN 1,H
Response message
To D:SCAN?2, the preset value for scanner channel 2 is returned.
(Example) If scanner channel 2 is currently set to OPEN,
0 is returned.
DCW:SCANW (D:SCANW)
Sets HIGH/LOW/OPEN for 16 channels at a time using 16 bits in a DC withstanding voltage test. Also inquires about the current settings for all 16 channels.
Program message
• Syntax
Command message:
Query message:DCW:SCANW?
DCW:SCANW_<setting 1, setting 2>
D:SCANW_<
D: SCANW?
setting 1, setting 2>
• Program data <setting 1>
Data format:Integer
Set value:0 to 65535 (#HFFFF)
Resolution:1
LOW is represented by 0 and HIGH by 1.
• Program data
Data format:Integer
Set value:0 to 65535 (#HFFFF)
Resolution:1
OPEN is represented by 1 and NOT OPEN by 0.
(Example) To set scanner channels 1 through 4 to LOW, scanner channels 5
Response message
To D:SCANW?, the settings for all 16 channels are returned as “setting 1” and “setting 2” using 16 bits.
(Example) If scanner channels 1 through 5 are currently set to HIGH, channels 6
<setting 2>
through 8 to HIGH, and the other channels to OPEN,
D:SCANW #H00F0,#HFF00
OPEN in setting 2 has priority over setting 1.
through 10 to OPEN, and the other channels to LO
“31,992” is returned.
W,
TOS9200 GPIB/RS-232CMessages and Registers 3-27
DCW:CONTACTCHECK (D:CCH)
Sets ON/OFF of the contact check function for a DC withstanding voltage test. Also
inquires about the status of the function.
Program message
• Syntax
Command message:
Query message:DCW:CONTACTCHECK?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the contact check to ON,
D:CCH ON
Response message
To D:CCH?, the current setting for the contact check is returned.
(Example) If the contact check is currently set to ON,
1 is returned.
DCW:CONTACTCHECK_<{ON|OFF}>
D:CCH_<{ON|OFF}>
D:CCH?
3-28 Messages and RegistersTOS9200 GPIB/RS-232C
3.4Messages Used Exclusively for Insulation
Resistance Testing
This section explains the messages used to check the test conditions and settings for
insulation resistance testing.
IR:TESTV (I:TES)
Sets the test voltage for an insulation resistance test. Also inquires about the preset
test voltage.
NOTE
• This message is valid even during a test. However, make only fine voltage adjustments rather than a large change to the voltage. A substantial change may activate
the protective circuit to shift the tester to the protection status.
Program message
• Syntax
Command message:
Query message:IR:TESTV?
• Program data
Data format:Integer
Set value:10 to 1020
Resolution:1
Unit:V
(Example) To set the test voltage to 500 V,
I:TES 500
Response message
To I:TES?, the currently set test voltage is returned.
(Example) If the test voltage is currently set to 250 V,
250 is returned.
IR:TESTV_<voltage>
I:TES_<
I:TES?
voltage>
TOS9200 GPIB/RS-232CMessages and Registers 3-29
IR:LOWER (I:LOW)
Sets the lower resistance (LOWER) and ON/OFF of the lower judgment function
for an insulation resistance test. Also inquires about the lower resistance and the
ON/OFF status of the lower judgment function.
CAUTION
• If the lower or upper judgment function is OFF, no FAIL judgment is made
for that function. With this setting, note that, a PASS judgment is made
when the timer is turned on.
Program message
• Syntax
Command message:
Query message:IR:LOWER?
• Program data
Data format:Real number
Set value:0.01 E6 to 9.99 E9
Resolution:0.01 E6 (0.01 E6 to 9.99 E6)
Unit:
(Example) To set the lower resistance to 99.9 MΩ,
I:LOW 99.9E6,1
IR:LOWER_<lower resistance, {ON|OFF}>
I:LOW_<
I:LOW?
0.1 E6 (10.0 E6 to 99.9 E6)
1 E6 (100 E6 to 999 E6)
0.01 E9 (1.00 E9 to 9.99 E9)
Ω
lower resistance, {ON|OFF}>
Response message
To I:LOW?, the currently set lower resistance and the ON/OFF status of the lower
judgment function are returned as “lower resistance, 1/0.”
(Example) If the lower resistance is currently set to 1.00 G
ment function to OFF,
1.00E9,0” is returned.
“
3-30 Messages and RegistersTOS9200 GPIB/RS-232C
Ω and the lower judg-
IR:UPPER (I:UPP)
Sets the upper resistance (UPPER) and ON/OFF of the upper judgment function for
an insulation resistance test. Also inquires about the set or setting upper resistance
and the ON/OFF status of the upper judgment function.
Program message
• Syntax
Command message:
Query message:IR:UPPER?
• Program data
Data format:Real number
Set value:0.01 E6 to 9.99 E9
Resolution:0.01 E6 (0.01 E6 to 9.99 E6)
Unit:
• Program data <{ON|OFF}>
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the upper resistance to 1.00 G
IR:UPPER_<upper resistance, {ON|OFF}>
I:UPP_<
I:UPP?
0.1 E6 (10.0 E6 to 99.9 E6)
1 E6 (100 E6 to 999 E6)
0.01 E9 (1.00 E9 to 9.99 E9)
Ω
I: UPP 1.00E9,1
upper resistance, {ON|OFF}>
Ω,
Response message
To I:UPP?, the preset upper resistance and the ON/OFF status of the upper judgment function are returned as “upper resistance, 1/0.”
(Example) If the upper resistance is currently set to 5.00 G
IR:TIMER (I:TIM)
Sets the test time (TEST TIME) and ON/OFF of the timer function for an insulation
resistance test. Also inquires about the current test time and the ON/OFF status of
the timer function.
Program message
• Syntax
Command message:
ment function to OFF,
5.00E9,0” is returned.
“
IR:TIMER_<test time, {ON|OFF}>
I:TIM_<
Ω and the upper judg-
test time, {ON|OFF}>
TOS9200 GPIB/RS-232CMessages and Registers 3-31
Query message:IR:TIMER?
I:TIM?
• Program data <test time>
Data format:Real number
Set value:0.5 to 999
Resolution:0.1 for 0.5 to 99.9, 1 for 100 to 999
Unit:s
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the test time to 5 s,
Response message
To I:TIM?, the current test time and the ON/OFF status of the timer function are
returned.
(Example) If the test time is currently set to 2 s and the timer function to OFF,
<{ON|OFF}>
I:TIM 5,ON
“
2.0,0” is returned.
IR:RISETIME (I:RTIM)
Sets the voltage rise time (RISE TIME) for an insulation resistance test. Also
inquires about the set or setting voltage rise time.
Program message
• Syntax
Command message:
Query message:IR:RISETIME?
• Program data
Data format:Real number
Set value:0.1 to 200
Resolution:0.1 for 0.1 to 99.9, 1 for 100 to 200
Unit:s
(Example) To set the voltage rise time to 1 s,
I:RTIM 1
Response message
To I:RTIM?, the current voltage rise time is returned.
(Example) If the voltage rise time is currently set to 2.0 s,
2.0 is returned.
IR:RISETIME_<voltage rise time>
I:RTIM_<
I:RTIM?
voltage rise time>
3-32 Messages and RegistersTOS9200 GPIB/RS-232C
IR:WAITTIME (I:WTIM)
Sets the WAIT TIME for an insulation resistance test. Also inquires about the set or
setting WAIT TIME.
Program message
• Syntax
Command message:
Query message:IR:WAITTIME?
• Program data
Data format:Real number
Set value:0.3 to 10.0
Resolution:0.1
Unit:s
(Example) To set the WAIT TIME to 1 s,
I:WTIM 1
Response message
To I:WTIM?, the currently set WAIT TIME is returned.
(Example) If the WAIT TIME is currently set to 2.0 s,
2.0 is returned.
IR:WAITTIME_<WAIT TIME>
I:WTIM_<
I:WTIM?
WAIT TIME>
IR:GND (I:GND)
Sets LOW/GUARD of the GND for an insulation resistance test. Also inquires
about the set or setting value of the GND.
WARNING
• If it is not known whether a DUT or jig is grounded, never select GUARD. If
GUARD is selected with a DUT grounded, the ammeter is short-circuited,
disabling measurement and posing gr
• When GUARD is selected, do not connect the tester to devices grounded
on a single side
or current calibrator TOS1200. Otherwise, the ammeter will be short-circuited. See Fig. 3-3 (A).
ave danger. See Fig. 3-3 (B).
, such as Kikusui’s high-v
oltage digital voltmeter 149-10A
TOS9200 GPIB/RS-232CMessages and Registers 3-33
TOS9200/9201
(A) Connecting the 149-10A
HIGH VOLTAGE terminal
Ammeter
LOW
terminal
Setting to GUARD
D
U
T
149-10A
CAUTION
HIGH VOLTAGE terminal
D
U
T
Ammeter
LOW
terminal
TOS9200/9201
Setting to GUARD
Insulation
resistance of
the test lead
wire and jig
(B) Selecting GUARD when the DUT is grounded
Fig.3-3Dangerous connections
• When the tester’s LOW terminal is connected to the HIGH or LOW terminal on the earth continuity tester TOS6200, the ammeter will suffer measurement errors if GUARD is selected, as the resistor in the TOS6200 is
connected in parallel with the tester’s ammeter. To use the TOS6200,
either do not connect one terminal to another, or set the LOW terminal to
LOW.
Program message
• Syntax
Command message:
IR:GND_<{GUARD|LOW}>
I:GND_<{GUARD|LOW}>
Query message:IR:GND?
I:GND?
• Program data
Data format:Character
Set value:LOW (0), GUARD (1)
(Example) To set the GND to GUARD,
I:GND 1
3-34 Messages and RegistersTOS9200 GPIB/RS-232C
Response message
To I:GND?, the current GND setting is returned.
(Example) If the GND is currently set to LOW,
IR:SCAN (I:SCAN)
Sets HIGH/LOW/OPEN for the scanner channel in an insulation resistance test.
Also inquires about the current setting of the high-voltage scanner channel.
Program message
• Syntax
Command message:
Query message:IR:SCAN?_<channel>
• Program data <channel>
Data format:Integer
Set value:1 to 16
Resolution:1
• Program data <{H|L|O}>
Data format:Character
Set value:O (0): OPEN; L (1): LOW; H (2): HIGH
(Example) To set scanner channel 1 to HIGH,
0 is returned.
I:SCAN 1,H
IR:SCAN_<channel, {H|L|O}>
I:SCAN_<
I:SCAN?_<
channel, {H|L|O}>
channel>
Response message
To I:SCAN? 2, the scanner channel 2 setting is returned.
(Example) If the scanner channel is currently set to OPEN,
0 is returned.
TOS9200 GPIB/RS-232CMessages and Registers 3-35
IR:SCANW (I:SCANW)
Sets HIGH/LOW/OPEN for 16 scanner channels at a time using 16 bits for an insulation resistance test. Also inquires about the settings for all 16 channels.
Program message
• Syntax
Command message:
Query message:IR:SCANW?
• Program data <setting 1>
Data format:Integer
Set value:0 to 65535 (#HFFFF)
Resolution:1
LOW is represented by 0 and HIGH by 1.
• Program data
Data format:Integer
Set value:0 to 65535 (#HFFFF)
Resolution:1
OPEN is represented by 1 and NOT OPEN by 0.
(Example) To set scanner channels 1 through 4 to LOW, scanner channels 5
through 8 to HIGH, and the other channels to OPEN,
I:SCANW #H00F0,#HFF00
OPEN in setting 2 has priority over setting 1.
IR:SCANW_<setting 1, setting 2>
I:SCANW_<
I:SCANW?
<setting 2>
setting 1, setting 2>
Response message
To I:SCANW?, the settings for all 16 channels of the high-voltage scanner are
returned as “setting 1” and “setting 2” using 16 bits.
(Example) If scanner channels 1 through 5 are currently set to HIGH, channels 6
through 10 to OPEN, and the other channels to LO
31,992 is returned.
W,
3-36 Messages and RegistersTOS9200 GPIB/RS-232C
IR:CONTACTCHECK (I:CCH)
Sets ON/OFF of the contact check function for an insulation resistance test. Also
inquires about the status of the function.
Program message
• Syntax
Command message:
Query message:IR:CONTACTCHECK?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the contact check to ON,
I:CCH ON
Response message
To I:CCH?, the current setting for the contact check is returned.
(Example) If the contact check is currently set to ON,
1 is returned.
IR:CONTACTCHECK_<{ON|OFF}>
I:CCH_<{ON|OFF}>
I:CCH?
TOS9200 GPIB/RS-232CMessages and Registers 3-37
3.5Messages Common to All Tests
This section explains the messages commonly used in all tests.
VDATA (VDAT)
Inquires about the monitor voltage for each test. During the test, the real-time voltage is returned. After the test, the previous test voltage is returned.
Program message
• Syntax
Query message:
Response message
To VDAT?, the monitor voltage is returned for ACW in an AC withstanding voltage
test, for DCW in a DC withstanding voltage test, and for IR in an insulation resistance test.
(Example) If the current monitor voltage in an AC withstanding voltage test is 1.5
,
kV
1.50E3 is returned.
VDATA?
VDAT?
NOTE
• In insulation resistance testing with the lower judgment function off, even if set-
IDATA (IDAT)
Inquires about the monitor current.
During the test, the measured normal value or the maximum value is returned,
depending on the MEAS MODE setting in the system settings. After the test, the
previous test current is returned.
Program message
• Syntax
tings are made so that the test voltage divided by the lower resistance exceeds 1.1
mA, testing can be performed. However, when the voltage value which is out of
the range of ±(10 % of setting +50 V) is detected during the test, the measurement
voltage value flashes on the LCD.
In this case, -1 is returned.
Query message:
IDATA?
IDAT?
3-38 Messages and RegistersTOS9200 GPIB/RS-232C
Response message
To IDAT?, the monitor current is returned for ACW in an AC withstanding voltage
test and for DCW in a DC withstanding voltage test.
(Example) If the present monitor current in an AC withstanding voltage test is 10.0
RDATA (RDAT)
Inquires about the monitor resistance
During the test, the measured normal value or the minimum value is returned,
depending on the MEAS MODE setting in the system settings. After the test, the
previous monitor resistance is returned.
Program message
• Syntax
Response message
To RDAT?, the monitor resistance is returned for IR in an insulation resistance test.
(Example) If the current monitor resistance is 10.0 M
mA,
10.0E-3 is returned.
Query message:
10.0E6 is returned.
RDATA?
RDAT?
Ω,
NOTE
• In insulation resistance testing, when the resistance value to exceed 9.99 GΩ is detected.
9.99 G
99.9 GΩ≤: “99.9” flashes on the LCD and -1 is returned.
Ω < 99.9 GΩ:The returned resistance value is not warranted.
REALDATA (REAL)
Inquires about the real current.
During the test, the real-time real current is returned. After the test, the previous real
current is returned.
Program message
• Syntax
Query message:
Response message
To REAL?, the present real current is returned.
(Example) If the present real current is 1 mA,
REALDATA?
REAL?
1E-3 is returned.
TOS9200 GPIB/RS-232CMessages and Registers 3-39
IMAGDATA (IMAG)
Inquires about the imaginary current. During the test, the real-time imaginary current is returned. After the test, the previous imaginary current is returned.
Program message
• Syntax
Query message:
Response message
To IMAG?, the present imaginary current is returned.
(Example) If the present imaginary current is 20
TIME
Inquires about the test time elapsed (the remaining time when the timer function is
on) and the test status
IMAGDATA?
IMAG?
μA,
20E-6 is returned.
MON
Program message
• Syntax
Query message:
Response message
To TIME?, the time elapsed (the remaining time when the timer function is on) and
the test status are returned as “time, status.”
(Example) If the time elapsed (or the remaining time) is 7.0 s and the test is under
y,
wa
7.0,1 is returned.
Inquires about each monitor value
Program message
• Syntax
Query message:
TIME?
MON?
Response message
To MON?, the current monitor value is returned.
When no test is under way, the previous test results are returned.
3-40 Messages and RegistersTOS9200 GPIB/RS-232C
Returning in AC withstanding voltage testing
Test type (0: ACW), monitor voltage, monitor current NORM, monitor current
MAX, real current, imaginary current, elapsed (remaining) time, test status (0: Rise/
1: Test/2: Fall/3: End)
Returning in DC withstanding voltage testing
Test type (1: DCW), monitor voltage, monitor current NORM, monitor current
MAX, monitor resistance MIN, elapsed (remaining) time, test status (0: Rise/1:
Test/3: End)
Returning in insulation resistance testing
Test type (2: IR), monitor voltage, monitor resistance NORM, monitor resistance
MIN, monitor current , 0, elapsed (remaining) time, test status (0: Rise/1: Test/3: End)
(Example) If an AC withstanding voltage test is under way at a monitor voltage of
2.50 kV
mA, real current of 5 mA, imaginary current of 10 μA, and remaining
time of 2.6 s,
“
, monitor current NORM of 5.2 mA, monitor current MAX of 12
0,2.5E3,5.2E-3,12E-3,5E-3,10E-6,2.6,1” is returned.
NOTE
• In insulation resistance testing with the lower judgment function off, even if settings are made so that the test voltage divided by the lower resistance exceeds 1.1
mA, testing can be performed. However, when the voltage value which is out of
the range of ±(10 % of setting +50 V) is detected during the test, the measurement
voltage value flashes on the LCD. In this case, -1 is returned.
• In insulation resistance testing, when the resistance value to exceed 9.99 G
9.99 G
99.9 GΩ≤: “99.9” flashes on the LCD and -1 is returned.
Ω < 99.9 GΩ: The returned resistance value is not warranted.
SCANTYPE (STYP)
Inquires about the number of valid connected channels and the model name of the
scanner
Program message
• Syntax
Query message:
Response message
To STYP?, the number of valid channels and the model name of the scanner are
returned as follows:
Number of valid channels, scanner 1, scanner 2, scanner 3, scanner 4
0: None; 1: TOS9220; 2: TOS9221
(Example) If there are 12 valid channels and scanners TOS9220, TOS9220, and
Ω is detected.
SCANTYPE?
STYP?
OS9221 (in that order, from the nearest to the tester) are connected
T
without a fourth scanner connected,
12,1,1,2,0” is returned.
“
TOS9200 GPIB/RS-232CMessages and Registers 3-41
CFAILCH (CFCH)
Inquires about the channel in the C FAIL status
Program message
• Syntax
Query message:
Response message
To CFCH?, the channel in the CONTACT FAIL status is returned.
(Example) If channel 12 is currently in the CONTACT FAIL status,
12 is returned.
CFAILCH?
CFCH?
3.6System-Related Messages
This section describes the messages to be set on the system screen.
MEASMODE (MMOD)
Sets the display mode (MEAS MODE) of the measured current (or measured resistance). Also inquires about the display mode of the measured current (or measured
resistance).
Program message
• Syntax
Command message:
Query message:MEASMODE?
• Program data
Data format:Character
Set value:NORM: Real Time; MAX: Max Hold (Min Hold)
(Example) To set the display mode of the measured current (or resistance) to Max
Hold (Min Hold for resistance),
MMOD MAX
Response message
To MMOD?, the present display mode of the measured current (or resistance) is
returned as 0 for NORM and 1 for MAX.
(Example) If the display mode of the present measured current is set to Real Time,
0 is returned.
MEASMODE_<{NORM|MAX}>
MMOD_<{NORM|MAX}>
MMOD?
3-42 Messages and RegistersTOS9200 GPIB/RS-232C
PASSHOLD (PHOL)
Sets the PASS hold time in a PASS judgment. Also inquires about the current PASS
hold time.
Program message
• Syntax
Command message:
Query message:PASSHOLD?
• Program data
Data format:Real number, character
Set value:0.2 to 10.0, HOLD
Unit:s
(Example) To set the PASS hold time to HOLD,
Response message
To PHOL?, the current PASS hold time is returned.
(Example) If the current PASS hold time is 0.5 s,
PHOL HOLD
0.5 is returned.
PASSHOLD_<set value>
PHOL_<
PHOL?
set value>
BUZZERVOL (BVOL)
Set the buzzer volume. Also inquires about the current buzzer volume.
Program message
• Syntax
Command message:
Query message:BUZZERVOL?
• Program data
Data format:Integer
Set value:0 to 10
Resolution:1
(Example) To set the buzzer volume to 5,
BVOL 5
BUZZERVOL_<set value>
BVOL_<
BVOL?
set value>
TOS9200 GPIB/RS-232CMessages and Registers 3-43
Response message
To BVOL?, the current volume is returned.
(Example) If the current buzzer volume is 3,
CONTRAST (CON)
Sets the LCD contrast. Also inquires about the current LCD contrast.
Program message
• Syntax
Command message:
Query message:CONTRAST?
• Program data
Data format:Integer
Set value:0 to 10
Resolution:1
(Example) To set the LCD contrast to 5,
3 is returned.
CON 5
CONTRAST_<set value>
CON_<
CON?
set value>
Response message
To CON?, the current LCD contrast is returned.
(Example) If the current LCD contrast is 6,
6 is returned.
MOMENTARY (MOM)
Sets the start momentary function (MOMENTARY). Also inquires about the current
start momentary setting.
Program message
• Syntax
Command message:
Query message:MOMENTARY?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
MOMENTARY_<{ON|OFF}>
MOM_<{ON|OFF}>
MOM?
3-44 Messages and RegistersTOS9200 GPIB/RS-232C
(Example) To set the start momentary function to OFF,
Response message
To MOM?, the current start momentary setting is returned.
(Example) If the start momentary function is currently ON,
FAILMODE (FMOD)
Sets the FAIL mode (FAIL MODE). Also inquires about the current FAIL mode setting.
Program message
• Syntax
Command message:
Query message:FAILMODE?
MOM OFF
1 is returned.
FAILMODE_<{ON|OFF}>
FMOD_<{ON|OFF}>
FMOD?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the FAIL mode to OFF,
FMOD OFF
Response message
To FMOD?, the current FAIL mode setting is returned.
(Example) If the FAIL mode function is currently ON,
1 is returned.
DOUBLE ACTION (DAC)
Sets the double-action mode (DOUBLE ACTION). Also inquires about the current
double-action mode setting.
Program message
• Syntax
Command message:
Query message:DOUBLEACTION?
DOUBLEACTION_<{ON|OFF}>
DAC_<{ON|OFF}>
DAC?
• Program data
Data format:Character
TOS9200 GPIB/RS-232CMessages and Registers 3-45
Set value:OFF (0), ON (1)
(Example) To set the double-action mode to OFF,
Response message
To DAC?, the current double-action mode setting is returned.
(Example) If the double-action mode is currently ON,
SIGHVON (SHV)
Sets H.V ON of Status Signal Output. Also inquires about the H.V ON setting.
Program message
• Syntax
DAC OFF
1 is returned.
Command message:
Query message:SIGHVON?
SIGHVON_<{ON|OFF}>
SHV_<{ON|OFF}>
SHV?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set H.V ON of Status Signal Output to OFF,
Response message
To SHV?, the current H.V ON setting for Status Signal Output is returned.
(Example) If H.V ON for Status Signal Output is currently set to ON,
SIGTEST (STES)
Sets TEST for Status Signal Output. Also inquires about the current TEST setting.
Program message
• Syntax
Command message:
Query message:SIGTEST?
SHV OFF
1 is returned.
SIGTEST_<{ON|OFF}>
STES_<{ON|OFF}>
STES?
• Program data
Data format:Character
3-46 Messages and RegistersTOS9200 GPIB/RS-232C
Set value:OFF (0), ON (1)
(Example) To set TEST for Status Signal Output to OFF,
Response message
To STES?, the current TEST setting for Status Signal Output is returned.
(Example) If the TEST status of Status Signal Output is currently set to ON,
SIGPASS (SPAS)
Sets PASS for Status Signal Output. Also inquires about the current PASS setting.
Program message
• Syntax
Command message:
Query message:SIGPASS?
STES OFF
1 is returned.
SIGPASS_<{ON|OFF}>
SPAS_<{ON|OFF}>
SPAS?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the PASS status of Status Signal Output to OFF,
Response message
To SPAS?, the current PASS setting for Status Signal Output is returned.
(Example) If the PASS status of Status Signal Output is currently set to ON,
SIGUFAIL (SUF)
Sets U FAIL for Status Signal Output. Also inquires about the current U FAIL setting.
Program message
• Syntax
SPAS OFF
1 is returned.
Command message:
Query message:SIGUFAIL?
SIGUFAIL_<{ON|OFF}>
SUF_<{ON|OFF}>
SUF?
TOS9200 GPIB/RS-232CMessages and Registers 3-47
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the U FAIL status of Status Signal Output to OFF,
Response message
To SUF?, the current U FAIL setting for Status Signal Output is returned.
(Example) If the U FAIL status of Status Signal Output is currently set to ON,
SIGLFAIL (SLF)
Sets L FAIL for Status Signal Output. Also inquires about the current LOW FAIL
setting.
Program message
• Syntax
SUF OFF
1 is returned.
Command message:
Query message:SIGLFAIL?
SIGLFAIL_<{ON|OFF}>
SLF_<{ON|OFF}>
SLF?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the L FAIL status of Status Signal Output to OFF,
Response message
To SLF?, the current L FAIL setting for Status Signal Output is returned.
(Example) If the L FAIL status of Status Signal Output is currently set to ON,
SIGREADY (SREA)
Sets READY for Status Signal Output. Also inquires about the current READY setting.
Program message
• Syntax
Command message:
SLF OFF
1 is returned.
SIGREADY_<{ON|OFF}>
SREA_<{ON|OFF}>
3-48 Messages and RegistersTOS9200 GPIB/RS-232C
Query message:SIGREADY?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the READY status of Status Signal Output to OFF,
SREA OFF
Response message
To SREA?, the current READY setting for Status Signal Output is returned.
(Example) If the READY status of Status Signal Output is currently set to ON,
1 is returned.
SIGPROTECTION (SPR)
Sets PROTECT for Status Signal Output. Also inquires about the current PROTECT
setting.
Program message
• Syntax
Command message:
Query message:SIGPROTECTION?
SREA?
SIGPROTECTION_<{ON|OFF}>
SPR_<{ON|OFF}>
SPR?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the PROTECT status of Status Signal Output to OFF,
SPR OFF
Response message
To SPR?, the current PROTECT setting for Status Signal Output is returned.
(Example) If the PROTECT status of Status Signal Output is currently set to ON,
1 is returned.
TOS9200 GPIB/RS-232CMessages and Registers 3-49
SIGPOWERON (SPOW)
Sets POWER ON for Status Signal Output. Also inquires about the current POWER
ON setting.
Program message
• Syntax
Command message:
Query message:SIGPOWERON?
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the POWER ON status of Status Signal Output to OFF,
SPOW OFF
Response message
To SPOW?, the current POWER ON setting for Status Signal Output is returned.
(Example) If the POWER ON status of Status Signal Output is currently set to ON,
1 is returned.
SIGPOWERON_<{ON|OFF}>
SPOW_<{ON|OFF}>
SPOW?
SIGCFAIL (SCF)
Sets C FAIL for Status Signal Output. Also inquires about the current C FAIL setting.
Program message
• Syntax
• Program data
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set the C FAIL status of Status Signal Output to OFF,
Response message
To SCF?, the current C FAIL setting for Status Signal Output is returned.
(Example) If the CONTACT FAIL status of Status Signal Output is currently set to
Command message:
Query message:SIGCFAIL?
SCF OFF
ON,
1 is returned.
SIGCFAIL_<{ON|OFF}>
SCF_<{ON|OFF}>
SCF?
3-50 Messages and RegistersTOS9200 GPIB/RS-232C
COMMENT (COM)
Inputs a comment (memo). Also inquires about the current comment. Up to three
lines can be entered, with a maximum of 12 characters per line.
Program message
• Syntax
Command message:
Query message:COMMENT?
• Program data
Data format:String
Set value:ASCII Code 20H to 7EH
(Example) To enter “KIKUSUI” in the 1st line, a blank in the 2nd line, and
(Example) If “KIKUSUI” is entered in the 1st line and
“123456789ABCDEFGHIJK” in the 3rd line, with no entry in the 2nd
line, the following comment is returned ( = space):
KIKUSUI,,
123456789ABCDEFGHIJK
TOS9200 GPIB/RS-232CMessages and Registers 3-51
3.7Memory-Related Messages
This section explains the messages used in connection with memory.
ACW:RECALL (A:REC)
Recalls the contents of memory stored in an AC withstanding voltage test
Program message
• Syntax
Command message:
• Program data
Data format:Integer
Set value:0 to 99
Resolution:1
(Example) To recall memory 10 for AC withstanding voltage testing,
A:REC 10
ACW:RECALL_<memory number>
A:REC_<
memory number>
DCW:RECALL (D:REC)
Recalls the contents of memory stored in a DC withstanding voltage test
Program message
• Syntax
Command message:
• Program data
Data format:Integer
Set value:0 to 99
Resolution:1
(Example) To recall memory 10 for DC withstanding voltage testing,
D:REC 10
DCW:RECALL_<memory number>
D:REC_<
memory number>
3-52 Messages and RegistersTOS9200 GPIB/RS-232C
IR:RECALL (I:REC)
Recalls the contents of memory stored in an insulation resistance test
Program message
• Syntax
Command message:
• Program data
Data format:Integer
Set value:0 to 99
Resolution:1
(Example) To recall memory 10 for insulation resistance testing,
I:REC 10
ACW:STORE (A:STOR)
Stores the current settings for an AC withstanding voltage test. Note that the memory name is not stored (the existing memory name is not replaced).
IR:RECALL_<memory number>
I:REC_<
memory number>
Program message
• Syntax
Command message:
• Program data
Data format:Integer
Set value:0 to 99
Resolution:1
(Example) To store the current settings for an AC withstanding voltage test to
memory 10,
A:STOR 10
ACW:STORE_<memory number>
A:STOR_<
memory number>
TOS9200 GPIB/RS-232CMessages and Registers 3-53
DCW:STORE (D:STOR)
Stores the current settings for a DC withstanding voltage test. Note that the memory
name is not stored (the existing memory name is not replaced).
Program message
• Syntax
Command message:
• Program data
Data format:Integer
Set value:0 to 99
Resolution:1
(Example) To store the current settings for a DC withstanding voltage test to mem-
ory 10,
D:STOR 10
IR:STORE (I:STOR)
DCW:STORE_<memory number>
D:STOR_<
memory number>
Stores the current settings for an insulation resistance test. Note that the memory
name is not stored (the existing memory name is not replaced).
Program message
• Syntax
Command message:
• Program data
Data format:Integer
Set value:0 to 99
Resolution:1
(Example) To store the current settings for an insulation resistance test to memory
10,
I:STOR 10
IR:STORE_<memory number>
I:STOR_<
memory number>
3-54 Messages and RegistersTOS9200 GPIB/RS-232C
ACW:MEMORY (A:MEM)
Stores the test conditions for an AC withstanding voltage test to a specified memory
number. Also inquires about the contents of the memory with the specified number.
Program message
• Syntax
Command message:
name", test voltage, lower current, upper
current, test time, frequency
judgment
start voltage, voltage rise time, voltage fall
time, voltage range
response speed
check
Query message:ACW:MEMORY?
• Program data <memory number>
Data format:Integer
Set value:0 to 99
Resolution:1
• Program data <
Data format:String
Set value:ASCII Code 20H to 7EH (up to 12 characters)
0.1 E-3 (10.0 E-3 to 99.9 E-3)
1 E-3 (100 E-3 to 110 E-3)
upper current>
TOS9200 GPIB/RS-232CMessages and Registers 3-55
Resolution:0.01 E-3 (0.01 E3 to 9.99 E-3)
0.1 E-3 (10.0 E-3 to 99.9 E-3)
1 E-3 (100 E-3 to 110 E-3)
Unit:A
• Program data <
test time>
Data format:Real number
Set value:0.3 to 999
Resolution:0.1 for 0.3 to 99.9, 1 for 100 to 999
Unit:s
• Program data <
frequency>
Data format:Character
Set value:50, 60
Unit:Hz
• Program data <
lower judgment{ON|OFF}>
Data format:Character
Set value:OFF, ON (0, 1)
• Program data
<offset{ON|OFF}>
Data format:Character
Set value:OFF, ON (0, 1)
• Program data
<timer{ON|OFF}>
Data format:Character
Set value:OFF, ON (0, 1)
• Program data <
start voltage>
Data format:Integer
Set value:1 to 99
Resolution:1
Unit:%
• Program data <
voltage rise time>
Data format:Real number
Set value:0.1 to 200
Resolution:0.1 for 0.1 to 99.9, 1 for 100 to 200
Unit:s
• Program data <
voltage fall time>
Data format:Real number
Set value:0.0 to 200
Resolution:0.1 for 0.1 to 99.9, 1 for 100 to 200
Unit:s
• Program data <
test-voltage range{0|1}>
Data format:Integer
Set value:0: AUTO; 1: 5 kV
3-56 Messages and RegistersTOS9200 GPIB/RS-232C
• Program data <current-detection response speed{0|1|2}>
Data format:Integer
Set value:0: SLOW; 1: MID; 2: FAST
• Program data <
GND{GUARD|LOW}>
Data format:Character
Set value:LOW (0), GUARD (1)
• Program data <
contact check{ON|OFF}>
Data format:Character
Set value:OFF, ON (0, 1)
• Program data <
scanner Hi/Low>
Data format:Integer
Set value:0 to 65535 (#HFFFF)
Resolution:1
LOW is represented by 0 and HIGH by 1.
• Program data <
scanner Open>
Data format:Integer
Set value:0 to 65535 (#HFFFF)
Resolution:1
OPEN is represented by 1 and NOT OPEN by 0.
OPEN has priority over HIGH/LOW.
Response message
To A:MEM? _<memory number>, the contents of memory specified by memory
number are returned.
The memory contents are returned in the same order as with program messages.
(Example) If memory 10, at inquiry, contains the memory name ACW10, test volt-
age of 5.00 kV, lower current of 5.00 mA, upper current of 80.0 mA, test
time of 2.0 s, frequenc
y of 50 Hz, lower judgment set to ON, of
fset set to
OFF, timer set to ON, start voltage of 15%, voltage rise time of 0.2 s,
voltage fall time of 0.4 s, voltage range of AUTO, current-detection
response speed of SLOW, GND set to LOW, contact check set to ON,
scanners 1 through 5 set to Low, scanners 6 through 10 set to High, and
the other scanners set to Open, then,
ACW10,5.00E3,5.00E-3,80.0E-3,2.0,50,1,0,1,15,
“
0.2,0.4,0,0,0,1,992,64512” is returned.
TOS9200 GPIB/RS-232CMessages and Registers 3-57
DCW:MEMORY (D:MEM)
Stores the test conditions for a DC withstanding voltage test to a specified memory
number. Also inquires about the contents of the memory with the specified number.
Program message
• Syntax
Command message:
"memory name", test voltage, lower current, upper
current
timer{ON|OFF}, start voltage, voltage rise time,
WAIT TIME, GND{GUARD|LOW}, contact check{ON|OFF},
scanner Hi/Low, scanner Open>
Query message:DCW:MEMORY?
• Program data <memory number>
Data format:Integer
Set value:0 to 99
Resolution:1
• Program data <memory name>
Data format:String
Set value:ASCII Code 20H to 7EH (up to 12 characters)
• Program data <
Data format:Real number
Set value:0.00 to 6.00 E3
Resolution:0.01 E3
Unit:V
• Program data <
Data format:Real number
Set value:0.01 E-3 to 11.0 E-3
Resolution:0.01 for 0.01 E3 to 9.99 E-3, 0.1 for 10.0 E-3 to 11.0 E-3
Unit:A
• Program data <
Data format:Real number
Set value:0.01 E-3 to 11.0 E-3
Resolution:0.01 for 0.01 E3 to 9.99 E-3, 0.1 for 10.0 E-3 to 11.0 E-3
To D:MEM? _<memory number>, the contents of the memory specified by
memory number are returned. The memory contents are returned in the same order
as with program messages.
(Example) If memory 12, at inquiry, contains the memory name DCW12, test volt-
age of 5.50 kV, lower current of 5.00 mA, upper current of 10.0 mA, test
time of 2.0 s., lo
of 20%, voltage rise time of 0.2 s, WAIT TIME of 0.5 s, GND set to
LOW, contact check set to ON, scanners 1 through 5 set to Low, scanners 6 through 10 set to High, and the other scanners set to Open, then,
DCW12,5.50E3,5.00E-3,10.0E-3,2.0,1,1,20,0.2,
“
0.5,0,1,992,64512
wer judgment set to ON, timer set to ON, start voltage
” is returned.
IR:MEMORY (I:MEM)
Stores the test conditions for an insulation resistance test to a specified memory
number. Also inquires about the contents of the memory with the specified number.
Program message
• Syntax
Command message:
"memory name", test voltage, lower resistance,
upper resistance, test time, lower judgment
{ON|OFF}, upper judgment{ON|OFF}, timer{ON|OFF},
voltage rise time, WAIT TIME, GND{GUARD|LOW},
contact check{ON|OFF}, scanner Hi/Low, scanner
Open
Query message:IR:MEMORY?
• Program data <memory number>
Data format:Integer
Set value:0 to 99
Resolution:1
IR:MEMORY (I: MEM)_<memory number,
>
I:MEM?
3-60 Messages and RegistersTOS9200 GPIB/RS-232C
• Program data <memory name>
Data format:String
Set value:ASCII Code 20H to 7EH (up to 12 characters)
To I:MEM? _<memory number>, the contents of the memory specified by memory number are returned.
The memory contents are returned in the same order as with program messages.
(Example) If memory 15, at inquiry, contains the memory number IR15, test volt-
age of 50 V, lower resistance of 0.05 M
Ω, upper resistance of 10.0 MΩ,
test time of 2.0 s., lower judgment set to ON, upper judgment set to OFF,
timer set to ON, voltage rise time of 0.2 s, WAIT TIME of 0.5 s, GND
set to LOW, contact check set to ON, scanners 1 through 5 set to Low,
scanners 6 through 10 set to High, and the other scanners set to Open,
then
IR15,50,0.05E6,10.0E6,2.0,1,0,1,0.2,0.5,0,1,992
“
,64512
3-62 Messages and RegistersTOS9200 GPIB/RS-232C
” is returned.
3.8Program-Related Messages
This section describes the messages used in connection with the program (AUTO).
PRGNAME (PNAM)
Specifies a program number and names the program. Also inquires about the program name.
Program message
• Syntax
Command message:
Query message:PRGNAME?_<program number>
• Program data <program number>
Data format:Integer
Set value:0 to 99
Resolution:1
• Program data <program name>
Data format:String
Set value:ASCII Code 20H to 7EH (up to 12 characters)
PRGEDIT_<program number, step number,
mode selection {0|1|2|3}>, memory
number
PED_<
mode selection {0|1|2|3}, memory number
number
PED?_<
, interval time>
program number, step number,
, interval time>
>
program number, step number>
3-64 Messages and RegistersTOS9200 GPIB/RS-232C
• Program data <mode selection {0|1|2|3}>
Data format:Integer
Set value:0: ACW; 1: DCW; 2: IR; 3: EC
• Program data <
memory number>
Data format:Integer
Set value:0 to 99
Resolution:1
• Program data <
interval time>
Data format:Real number, character
Set value:0.2 to 9.9, HOLD
Resolution:0.1
Unit:s
NOTE
• All parameters must be entered, even if the value isn’t changed.
• Do not skip a step number. Overwrite the existing step, or add a new step after the
last step.
• Up to 500 steps can be used in a set of programs.
For example, if 100 steps are set for each of programs 0 to 4, no step is available
for program 5.
(Example) At step 15 of program 10, to program memory 3 for AC withstanding
voltage testing at an interval time of 2 s,
PED 10,15,0,3,2.0
Response message
To PED?_<program number, step number>, the contents of the specified
step of a specified program are returned.
(Example) If, at step 15 of program 10, memory 3 for AC withstanding voltage test-
ing is programmed at an interval time of 2 s,
0,3,2” is returned.
“
TOS9200 GPIB/RS-232CMessages and Registers 3-65
PRGRETURN (PRET)
Makes the RETURN/END settings for a specified program.
Also inquires about the RETURN/END setting for a specified program.
Program message
• Syntax
Command message:
Query message:PRGRETURN?_<program number>
• Program data <program number>
Data format:Integer
Set value:0 to 99
Resolution:1
• Program data <
Data format:Character
Set value:OFF (0), ON (1)
(Example) To set program 10 to RETURN,
PRET 10,ON
PRGRETURN_<program number,{ON|OFF}>
PRET_<
PRET?_<
program name>
program number,{ON|OFF}>
program number>
Response message
To PRET?_<program number>, the RETURN setting for the specified program
is returned.
(Example) If program 10 is set to the END mode,
PRGNEW (PNEW)
Deletes a specified program.
Program message
• Syntax
Command message:
• Program data
Data format:Integer
Set value:0 to 99
Resolution:1
(Example) To delete program 10,
0 is returned.
PNEW 10
PRGNEW_<program number>
PNEW_<
program number>
3-66 Messages and RegistersTOS9200 GPIB/RS-232C
PRGTOTAL (PTOT)
Inquires about the total number of steps in a specified program
Program message
• Syntax
Query message:
• Program data <program number>
Data format:Integer
Set value:0 to 99
Resolution:1
Response message
To PRET?_<program number>, the total number of steps in a specified program
is returned.
(Example) If the total number of step in program 10 is 55,
55 is returned.
PRGTORAL?_<program number>
PTOT?_<
program number>
PRGINS (PIN)
Inserts a memory number into the specified step of a specified program. Following
the execution of this message, the tester automatically displays the program edit
screen.
EXE (Execution Error):
been received
FREQ command during the test, etc.
CME EXE3210
Syntax error, data error,
When an invalid message has
Read by *ESR?
RQS
Issuance of a
service request
Logical
sum
7
MSS
&
76
ESB DSB
&
ESB DSB
Fig.3-4Structure of status data
READY
Event Status Byte
Dvice Status Byte
&
Read by DSE?
(initial value:
80H)
Logical
sum
Read by serial polling
3210
&
&
&
&
3210
Status byte
register
Read by
*STB?
Service-request
enable register
This register is set
by *SRE and read
by *SRE?.
(Initial value: 70H)
3-70 Messages and RegistersTOS9200 GPIB/RS-232C
NOTE
• In a command message in each register, hexadecimal data can be used by adding
“#H”.
• In a query message in each register, all response data is composed of decimals.
• For each bit of each register, 1 represents “set” and 0 represents “reset.”
• The contents of the enable register are not backed up.
Status Byte register, Service-Request Enable register
BitDescription
7Not used with this tester
"RQS
6
(Request)
"MSS
(Master Summary Status)"
"ESB
5
(Standard Event Status Bit)"
"DSB
4
(Device Status Bit)"
3Not used with this tester
2Not used with this tester
1Not used with this tester
0Not used with this tester
Confirms that a service request has been issued. Reset by being read by series
polling.
Logical sum of the status byte register and the service-request enable register.
Read by *STB?
Indicates that a bit of the event status register has been set
Indicates that a bit of the device status register has been set
Table 3-1Status Byte register and Service-Request Enable register
Event Status register
BitDescription
7Not used with this tester
6Not used with this tester
5CME (Command Error)Indicates a syntax error, data error, or our-of-range error
4EXE (Execution Error)
3Not used with this tester
2Not used with this tester
1Not used with this tester
0Not used with this tester
Table 3-2Event Status register
Indicates that an invalid message has been received during the test or in the
protection status
TOS9200 GPIB/RS-232CMessages and Registers 3-71
Device Status register, Device-Status Enable register
BitDescription
7PROT (Protection)Protection status
6STOPSuspension of the test
5FAILFAIL judgment
4PASSPASS judgment
3HV ONWaiting for a contact check and outputting a voltage
2TESTOutputting a test voltage
1INV SET (Invalid setting)
0READYREADY status
LCD displaying an invalid message such as “UP≤LOW” or “OVER 550 VA”
(“OVER 55 W” in DC)
Table 3-3Device Status register and Device-Status Enable register
Contact Check
TEST
HV ON
Fig.3-5Relation of TEST (Bit 2) to HV ON (Bit 3).
Protection register 1
BitDescription
7Not used with this tester
6Not used with this tester
5Not used with this tester
4OVER LOADWhen 550 VA is exceeded in ACW (55 W in DCW)
3LVP (Low Voltage Protection)When 1.1 mA is exceeded in IR
2OCP (24 V)
OHP TIMER
1
(Over Heat Timer)
0OHP (Over Heat Protection)When the internal temperature has increased abnormally
When a 24 V overcurrent has been detected in the SIGNAL I/O connector or INTERLOCK connector
When a current exceeding 50 mA has been detected for over 30 minutes
during the test
Table 3-4Protection register
Protection register 2
BitDescription
7TOS6200 PROT (Protection)When the TOS6200 is in the protection status
TOS6200 COMM
6
(Communication Error)
5REN (Remote Enable)Change in the Enable signal for SIGNAL I/O
4REM IO (Remote In/Out)When the remote-control connector has been connected/disconnected
3SCAN (Scanner In/Out)
2INTERLOCKIn the INTERLOCK status
110 %±50 V (Setting 10 %±50 V) When the test voltage has deviated from 10% ±50 V
0100/200 (Select 100/200)When a source voltage outside the preset range has been applied
When an error has occurred in communication with the TOS6200
When the scanner connector has been connected/disconnected, or when a
channel specified at a step during the AUTO test is disconnected.
Table 3-5Protection register
3-72 Messages and RegistersTOS9200 GPIB/RS-232C
Fail register
BitDescription
7Not used with this tester
6Not used with this tester
5Not used with this tester
4Not used with this tester
3Not used with this tester
2UPPER FAILIndicates FAIL for the upper cutoff value
1LOWER FAILIndicates FAIL for the lower cutoff value
0CONTACT FAILIndicates FAIL in a contact check
Table 3-6Fail register
Invalid-Setting register
BitDescription
7Not used with this tester
6Not used with this tester
5Not used with this tester
4SCANNER CHANNELWhen an unconnected channel has been specified
3WAIT TIMEAt rise time + test time ≤ wait time
2UP≤LOWWhen the lower cutoff value exceeds the upper cutoff value
1OVER 1.1mA
0OVER 550VA
In IR, when the test voltage divided by the lower resistance has exceeded
1.1 mA
In ACW, when the test voltage multiplied by the upper current has
exceeded 550 VA (55 W in DCW)
Table 3-7Invalid-Setting register
Error register
BitDescription
7Not used with this tester
6Not used with this tester
5Not used with this tester
4Not used with this tester
3Invalid messageIndicates an invalid message
2Out-of-range errorIndicates an out-of-range error
1Data ErrorIndicates a data error
0Syntax ErrorIndicates a header error
Table 3-8Error register
TOS9200 GPIB/RS-232CMessages and Registers 3-73
3.10Message List
The symbols in parentheses in the Header column represent abbreviated messages.
R/W represents a query message (R) or command message (W).
Note 1: The commands that are valid during a rise time, test time, fall time, pass
judgment, f
commands are indicated by “
ail judgment, or interval time are mark
②”. The commands valid only in the ready
status or interval hold status are marked with “
ed with “
③”.
Note 2: The commands valid in the protection status are marked with “
invalid commands are marked with “
②”.
3.10.1Register-related messages and general messages
Data
Resolution
Unit
Initializes devices.
(Resets to factory settings, except for the INTERFACE
screen settings)
Clears the status byte register, event status register,
device status register, protection register 1, protection
register 2, fail register, invalid-setting register, and error
register.
Clears all registers and sets a Stop flag
(same as DCL and SDC).
Starts a test.
(valid in the ready status and the interval hold status)
Shifts between modes.
0: ACW; 1: DCW; 2: IR; 3: AUTO TEST;
4: AUTO EDIT; 5: SYSTEM; 6: OFFSET ADJ;
7: INTERFACE
Returns the current mode.
0: ACW; 1: DCW; 2: IR; 3: AUTO TEST;
4: AUTO EDIT; 5: SYSTEM; 6: OFFSET ADJ;
7: INTERFACE
Function and response data
*RST
1
*IDN?
2
ERR?
3
TRM
4
TRM?
5
*CLS
6
*STB?
7
*SRE
8
*SRE?
9
*ESR?
10
DSE
11
DSE?
12
DSR?
13
PROTECTION?
14
(PROT?)
FAIL?
15
INVALID? (INV?)
16
CLR
17
SILENT (SIL)
18
SILENT? (SIL?)
19
START (STAR)
20
STOP
21
FUNCTION
(FUN)
22
FUNCTION?
(FUN?)
23
LOCAL (LOC)
24
Header
R/WMin. Max.
W--
R--
R--Returns an error value and clears it.
W03--
R--Returns the preset terminator value.
W--
R--Returns the status-byte-register value.
W0255--Sets the service-request enable register.
R--Returns the service-request-enable-register value.
R--Returns the event-status-register value and clears it.
W0255--Sets the device-status enable register.
R--Returns the device-status-enable-register value.
R--Returns the device-status-register value.
R--Returns the values of protection registers 1 and 2.
R--Returns the fail-register value.
R--Returns the invalid-setting-register value.
W--
W010/1--Acknowledge message (RS-232C)
R--Returns the acknowledge-message (RS-232C) value.
W--
W--Suspends the test and cancels the protection status.
W071--
R--
WReturn to the LOCAL from the REMOTE state.
①”, and invalid
①”, and the
Note 1 Note 2
AB
①①
①①
①①
②②
①①
①①
①①
②②
①①
①①
②②
①①
①①
①①
①①
①①
①①
②②
①①
③②
①①
②②
①①
②①
3-74 Messages and RegistersTOS9200 GPIB/RS-232C
3.10.2Messages for AC withstanding voltage testing
Header
25ACW:TESTV (A:TES) W0.00
ACW:TESTV?
26
(A:TES?)
ACW:FREQUENCY
27
(A:FREQ)
ACW:FREQUENCY?
28
(A:FREQ?)
ACW:LOWER
29
(A:LOW)
ACW:LOWER?
30
(A:LOW?)
ACW:UPPER
31
(A:UPP)
ACW:UPPER?
32
(A:UPP?)
ACW:TIMER
33
(A:TIM)
ACW:TIMER?
34
(A:TIM?)
ACW:OFFSET
35
(A:OFF)
ACW:OFFSET?
36
(A:OFF?)
ACW:STARTV
37
(A:STAR)
ACW:STARTV?
38
(A:STAR?)
ACW:RISETIME
39
(A:RTIM)
ACW:RISETIME?
40
(A:RTIM?)
ACW:FALLTIME
41
(A:FTIM)
ACW:FALLTIME?
42
(A:FTIM?)
ACW:VRANGE
43
(A:VRAN)
ACW:VRANGE?
44
(A:VRAN?)
ACW:RESPONSE
45
(A:RES)
ACW:RESPONSE?
46
(A:RES?)
47ACW:GND (A:GND)WLOW
ACW:GND?
48
(A:GND?)
ACW:SCAN
49
(A:SCAN)
ACW:SCAN?
50
(A:SCAN?)
ACW:SCANW
51
(A:SCANW)
R/W Min.Max.
0.00 E35.20
R
W506050/60Hz Sets the output frequency.
RHz Returns the output-frequency setting.
0.01
E-3
W
OFFONOFF/ON-- Turns ON/OFF the low judgment function.
R
0.01
W
E-3
RA Returns the upper current.
0.39990.1, 1sTimer set value (0.3 to 99.9/100 to 999)
W
OFFON0/1-- Timer function
R
WOFFON0/1-- Offset function.
R--
W0991% Sets the start voltage.
R% Returns the start-voltage setting.
W0.12000.1, 1sSets the voltage rise time (0.1 to 99.9/100 to 200).
RsReturns the voltage-rise-time setting.
W02000.1, 1sSets the voltage fall time (0.1 to 99.9/100 to 200).
RsReturns the voltage-fall-time setting.
W010/1-- Sets VRANGE (0: AUTO; 1: 5 kV).
R010/1-- Returns the VRANGE setting (0: AUTO; 1: 5 kV).
W020/1/2--Sets the response filter (0: SLOW; 1: MID; 2: F
R--
R-- Returns the GUARD/LOW setting for GND as 1 or 0.
1161--
W
OHH/L/O--
R1161--
W0
0
Data
Resolution
5.20 E30.01
E3
110
E-3
110
E-3
GUARD
65535
#HFFFF
65535
#HFFFF
Unit
V Sets the test voltage.
E3
V Returns the test-voltage setting.
0.01,
0.1, 1
0.01,
0.1, 1
0/1-- 1 to set GND to GUARD, and 0 to set to LOW.
1--
1--
Lower current
A
(0.01 to 9.99/10.0 to 99.9/100 to 110)
Returns the lower current and the ON/OFF status of the
A,
judgment function.
-Returns ON/OFF as 1 or 0.
Upper current
A
(0.01 to 9.99/10.0 to 99.9/100 to 110)
s, Returns the timer ON/OFF setting.
--
Returns ON/OFF as 1 or 0.
Returns the ON/OFF status of the offset function
Returns ON/OFF as 1 or 0.
Returns the response-filter setting.
(0: SLOW; 1: MID; 2: FAST)
Sets channels 1 through 16 to Hi/Low/Open
(0: Open; 1: Low; 2: High).
Returns the Hi/Low/Open setting for channels 1
through 16 (0: Open; 1: Low; 2: High).
The 1st data represents channels 1 through 16 with 0:
Low and 1: Hi, using 16 bits. The 2nd data represents
Open and Not Open, with 1 for Open.
The Open setting for the 2nd data has priority over the
1st data.
Function and response data
AST).
AB
Note 1 Note 2
①②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
TOS9200 GPIB/RS-232CMessages and Registers 3-75
Data
Resolution
Unit
Returns a WORD-type value for Hi/Low and Open/Not
Open.
Returns the ON/OFF status of the scanner contact check
function.
Function and response data
ACW:SCANW?
52
(A:SCANW?)
ACW:CONTACT
53
CHECK
(A:CCH)
ACW:CONTACT
54
CHECK?(A:CCH?)
Header
R/W Min.Max.
R--
WOFFON0/1-- Sets ON/OFF for the scanner contact check function.
R010/1--
3.10.3Messages for DC withstanding voltage testing
AB
Note 1 Note 2
①①
②②
①①
Header
DCW:TESTV
55
(D:TES)
DCW:TESTV?
56
(D:TES?)
DCW:LOWER
57
(D:LOW)
DCW:LOWER?
58
59DCW:UPPER (D:UPP) W
60
61DCW:TIMER (D:TIM) W
62
63
64
65
66
67
68
69DCW:GND(D:GND)WLOW
70
71
72
73
74
W?)
(D:LO
DCW:UPPER?
(D:UPP?)
DCW:TIMER?
(D:TIM?)
DCW:STARTV
(D:STAR)
DCW:STARTV?
(D:STAR?)
DCW:RISETIME
(D:RTIM)
DCW:RISETIME?
(D:RTIM?)
DCW:WAITTIME
(D:WTIM)
DCW:WAITTIME?
(D:WTIM?)
DCW:GND?
(D:GND?)
DCW:SCAN
(D:SCAN)
DCW:SCAN?
(D:SCAN?)
DCW:SCANW
(D:SCANW)
DCW:SCANW?
(D:SCANW?)
R/W Min.Max.
W0.00
0.00 E36.00
R
0.01
E-3
W
OFFONOFF/ON-- Turns the low judgment function ON/OFF.
R
0.01
E-3
RA Returns the upper current.
0.19990.1, 1sTimer set value (0.3 to 99.9/100 to 999)
OFFON0/1-- Timer function
R
W0991% Sets the start voltage.
R% Returns the start-voltage setting.
W0.12000.1, 1sSets the voltage rise time (0.1 to 99.9/100 to 200)
RsReturns the voltage-rise-time setting.
W0.3100.1sSets the WAIT TIME (0.3 to 10.0)
RsReturns the judgment-wait-time setting.
R--
1161--
W
HLH/L/O--
R1161--
W0
0
R--
Data
6.00
E3
E3
11.0
E-3
11.0
E-3
GUARD
65535
#HFFFF
65535
#HFFFF
Resolution
0.01,0.1A Lower current (0.01 to 9.99/10.0 to 11.0)
0.01,0.1A Upper current (0.01 to 9.99/10.0 to 11.0)
Unit
0.01
E3
0/1-- 1 to set GND to GUARD, and 0 to set to LOW
V Sets the test voltage.
V Returns the test-voltage setting.
Returns the lo
A,
judgment function.
-Returns ON/OFF as 1 or 0.
Returns the timer ON/OFF setting.
s,
--
Returns ON/OFF as 1 or 0.
Returns the GUARD/LOW setting for GND
as 1 or 0.
Sets channels 1 through 16 to Hi/Low/Open
(0: Open; 1: Low; 2: High).
Returns the Hi/Low/Open setting for channels 1
through 16 (0: Open; 1: Low; 2: High).
1--
1--
The 1st data represents channels 1 through 16 with 0:
Low and 1: Hi, using 16 bits. The 2nd data represents
Open and Not Open, with 1 for Open.
The Open setting for the 2nd data has priority over the
1st data.
Returns a WORD-type value for Hi/Low and Open/Not
Open.
Function and response data
wer current and the ON/OFF status of the
AB
Note 1 Note 2
①②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
3-76 Messages and RegistersTOS9200 GPIB/RS-232C
Data
Resolution
Unit
Returns the ON/OFF status of the scanner contact check
function.
Function and response data
DCW:CONTACT
75
CHECK
(D:CCH)
DCW:CONTACT
76
CHECK?
(D:CCH?)
Header
R/W Min.Max.
WOFFON0/1-- Sets ON/OFF of the scanner contact check function.
R010/1--
3.10.4Messages for insulation resistance testing
AB
Note 1 Note 2
②②
①①
Header
IR:TESTV
77
(I:TES)
IR:TESTV?
78
(I:TES?)
IR:LOWER
79
(I:LOW)
IR:LOWER?
80
(I:LOW?)
IR:UPPER
81
(I:UPP)
IR:UPPER?
82
(I:UPP?)
IR:TIMER
83
(I:TIM)
IR:TIMER?
84
(I:TIM?)
IR:RISETIME
85
(I:RTIM)
IR:RISETIME?
86
(I:RTIM?)
IR:WAITTIME
87
(I:WTIM)
IR:WAITTIME?
88
(I:WTIM?)
89IR:GND (I:GND)WLOW
90IR:GND? (I:GND?)R--Returns the GUARD/LOW setting for GND as 1 or 0.
IR:SCAN
91
(I:SCAN)
IR:SCAN?
92
(I:SCAN?)
IR:SCANW
93
(I:SCANW)
IR:SCANW?
94
(I:SCANW?)
IR:CONTACT
95
CHECK (I:CCH)
IR:CONTACT
96
CHECK?(I:CCH?)
R/W Min.Max.
W1010201V Sets the test voltage.
RV Returns the test-voltage setting.
W
OFFONOFF/ON
RΩ
W
OFFONOFF/ON-- Turns the upper judgment function ON/OFF.
R
W
OFFON0/1-- Timer function
R
W0.12000.1, 1sSets the voltage rise time (0.1 to 99.9/100 to 200).
RsReturns the voltage-rise-time setting.
W0.3100.1sSets the WAIT TIME (0.3 to 10.0).
RsReturns the judgment-wait-time setting.
W
R1161--
W
R--
WOFFON0/1-- Sets ON/OFF for the scanner contact check function.
R010/1--
Data
Resolution
0.01E69.99
E9
0.01E69.99
E9
0.59990.1, 1sTimer set value (0.5 to 99.9/100 to 999)
GUARD
1161--
HLH/L/O--
65535
0
#HFFFF
65535
0
#HFFFF
Unit
0.01
0.01
0/1-- 1 to set GND to GUARD, and 0 to set it to LOW
1--
1--
Lower resistance (0.01 M to 9.99 M,
Ω
10.0 M to 99.9 M, 100 M to 999 M, 1.00 G to 9.99 G)
Returns the lower resistance. Uses MΩ as the unit.
Returns the ON/OFF status of the judgment function.
Returns ON/OFF as 1 or 0.
Upper resistance (0.01 M to 9.99 M,
Ω
10.0 M to 99.9 M, 100 M to 999 M, 1.00 G to 9.99 G)
Returns the upper resistance (in MΩ) and the ON/OFF
Ω
status of the upper judgment function. Returns ON/OFF
-as 1 or 0.
s, Returns the timer value and the ON/OFF status of the
timer
-Returns ON/OFF as 1 or 0.
Sets channels 1 through 16 to Hi/Low/Open.
Returns the Hi/Low/Open settings for channels 1
through 16.
The 1st data represents channels 1 through 16 with 0:
Low and 1: Hi, using 16 bits. The 2nd data represents
Open and Not Open, with 1 for Open.
The Open setting for the 2nd data has priority over the
1st data.
Returns a WORD-type value for Hi/Low and Open/Not
Open.
Returns the ON/OFF status of the scanner contact check
function.
Function and response data
.
AB
Note 1 Note 2
①②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
②②
①①
TOS9200 GPIB/RS-232CMessages and Registers 3-77
3.10.5Messages common to all tests
Header
VDATA?
97
(VDAT?)
IDATA?
98
(IDAT?)
RDATA?
99
(RDAT?)
REALDATA?
100
(REAL?)
IMAGDATA?
101
(IMAG?)
TIME?
102
MON?RTest type (0: ACW; 1: DCW; 2: IR)
103
SCANTYPE?
104
(STYP?)
CFAILCH?
105
(CFCH?)
R/W Min.Max.
RV
RA
RΩ
RA
RA
R
R--
R--
Data
Resolution
Unit
Monitor voltage (ACW: 0 E3 to 9.99 E3)
(DCW: 0 E3 to 99.9 E3)
(IR: 0 to 9999 )
Monitor current (ACW: 0 to 999
Ε−3, 10.0 Ε−3 to 99.9 Ε−3, 100 Ε−3 to 999 Ε−3)
(DCW: 0 to 999 Ε−6, 1.00 Ε−3 to 9.99 Ε−3, 10.0 Ε−3
to 99.9 Ε−3)
Monitor resistance (0.01 E6 to 9.99 E6, 10.0 E6 to 99.9
E6, 100 E6 to 999 E6, 1.00 E9 to 9.99 E9)
Real current (0 to 999 Ε−6, 1.00 E-3 to 9.99 E-3, 10.0
E-3 to 99.9 E-3, 100 E-3 to 999 E-3)
Imaginary current (0 to 999 Ε−6, 1.00 E-3 to 9.99 E-3,
10.0 E-3 to 99.9 E-3, 100 E-3 to 999 E-3)
s, --Returns the elapsed (remaining) time (0 s to 99.9 s,
100 s to 999 s) and Rise/Test/Fall/End (0/1/2/3).
Returns the elapsed time when the timer is off.
Returns the remaining time when the timer is on.
Monitor voltage (W: 0 E3 to 99.9 E3; IR: 0 to 9999 )
Monitor current Norm (0 to 999 Ε−6, 1.00 E-3 to
9.99 E-3, 10.0 E-3 to 99.9 E-3, 100 E-3 to 999 E-3)
Monitor current MAX (0 to 999 Ε−6, 1.00 E-3 to
9.99 E-3, 10.0 E-3 to 99.9 E-3, 100 E-3 to 999 E-3)
Monitor resistance Norm (0.01 E6 to 9.99 E6, 10.0 E6
to 99.9 E6, 100 E6 to 999 E6, 1.00 E9 to 9.99 E9)
Monitor resistance Min (0.01 E6 to 9.99 E6, 10.0 E6 to
99.9 E6, 100 E6 to 999 E6, 1.00 E9 to 9.99 E9)
Real current (0 to 999 Ε−6, 1.00 E-3 to 9.99 E-3, 10.0
E-3 to 99.9 E-3, 100 E-3 to 999 E-3)
Imaginary current (0 to 999 Ε−6, 1.00 E-3 to 9.99 E-3,
10.0 E-3 to 99.9 E-3, 100 E-3 to 999 E-3)
Monitor current IR (0 to 999 E-9, 1.00 Ε−6 to 9.99 Ε−6,
100 Ε−6 to 999 Ε−6, 1.00 E-3 to 9.99 E-3, 10.0 E-3 to
99.9 E-3, 100 E-3 to 999 E-3)
Monitor resistance DCW (0.01 E6 to 9.99 E6, 10.0 E6
to 99.9 E6, 100 E6 to 999 E6, 1.00 E9 to 9.99 E9, 10.0
E9 to 99.9 E9, 100 E9 to 999 E9)
Elapsed (remaining) time (0 s to 99.9 s, 100 s to 999 s)
Separates Rise/Test/Fall/End (0/1/2/3) using “,” in this
order and then returns it.
The results of the previous test are returned except during the test.
Returns the monitor current in ACW and DCW, and the
monitor resistance in IR.
Returns the number of valid channels and the scanner
type (Units 1 through 4).
(0: none; 1: TOS9220; 2: TOS9221)
Returns the channel number (1 through 16) in the CONTACT FAIL status.
Function and response data
AB
Note 1 Note 2
①①
Ε−6, 1.00 Ε−3 to 9.99
①①
①①
①①
①①
①①
①①
①①
①①
3-78 Messages and RegistersTOS9200 GPIB/RS-232C
3.10.6System-related messages
Header
MEASMODE
106
(MMOD)
MEASMODE?
107
(MMOD?)
PASSHOLD
108
(PHOL)
PASSHOLD?
109
(PHOL?)
BUZZERVOL
110
(BVOL)
BUZZERVOL?
111
(BVOL?)
CONTRAST
112
(CON)
CONTRAST?
113
(CON?)
MOMENTARY
114
(MOM)
MOMENTARY?
115
(MOM?)
FAILMODE
116
(FMOD)
FAILMODE?
117
(FMOD?)
DOUBLEACTION
118
(DAC)
DOUBLEACTION?
119
(DAC?)
SIGHVON
120
(SHV)
SIGHVON?
121
(SHV?)
SIGTEST
122
(STES)
SIGTEST?
123
(STES?)
SIGPASS
124
(SPAS)
SIGPASS?
125
(SPAS)
SIGUFAIL
126
(SUF)
SIGUFAIL?
127
(SUF?)
SIGLFAIL
128
(SLF)
SIGLFAIL?
129
(SLF)
SIGREADY
130
(SREA)
SIGREADY?
131
(SREA?)
SIGPROTECTION
132
(SPR)
SIGPROTECTION?
133
(SPR?)
134 SIGCFAIL (SCF)WOFFONOFF/ON--
R/W Min.Max.
W NORM MAX--
R010/1--
W0.2
Rs
W0101-- Sets the buzzer volume.
R-- Returns the buzzer-volume setting.
W0101-- Sets the contrast level.
R-- Returns the contrast setting.
WOFFONOFF/ON-- Start momentary
R--
WOFFONOFF/ON--
R--
WOFFONOFF/ON-- Start double action
R--
WOFFONOFF/ON-- Sets the value of Status Signal Output: HVON.
R-- ON/OFF is returned as 1 or 0.
WOFFONOFF/ON-- Sets the value of Status Signal Output: TEST.
R-- ON/OFF is returned as 1 or 0.
WOFFONOFF/ON-- Sets the value of Status Signal Output: PASS.
R-- ON/OFF is returned as 1 or 0.
WOFFONOFF/ON-- Sets the value of Status Signal Output: U FAIL.
R-- ON/OFF is returned as 1 or 0.
WOFFONOFF/ON-- Sets the value of Status Signal Output: L FAIL.
R-- ON/OFF is returned as 1 or 0.
WOFFONOFF/ON-- Sets the value of Status Signal Output: READY.
R-- ON/OFF is returned as 1 or 0.
WOFFONOFF/ON-- Sets the value of Status Signal Output: PROTECTION.
R-- ON/OFF is returned as 1 or 0.
Data
10
HOLD
Resolution
Unit
0.1sPass hold time
Function and response data
Sets the measured-current (resistance) display mode.
NORM: Real Time; MAX: Max Hold
Sets the measured-current (resistance) display mode.
0: Real Time; 1: Max Hold
Returns the pass hold time.
0.2 to 10.0 or HOLD
Returns the start-momentary setting.
ON/OFF is returned as 1 or 0.
Fail mode (The STOP key used to cancel the Fail and
Protection statuses.)
Returns the Fail-mode value.
ON/OFF is returned as 1 or 0.
Returns the start-double-action value.
ON/OFF is returned as 1 or 0.
Sets the value of Status Signal Output: CONTACT
FAIL.
AB
Note 1 Note 2
②②
①①
②②
①①
①①
①①
①①
①①
②②
①①
②②
①①
②②
①①
①①
①①
①①
①①
①①
①①
①①
①①
①①
①①
①①
①①
①①
①①
①①
TOS9200 GPIB/RS-232CMessages and Registers 3-79
Data
Resolution
20H7EH-- Comment (memo) 20 characters in the 1st line *1
20H7EH-- Comment (memo) 20 characters in the 2nd line *1
20H7EH-- Comment (memo) 20 characters in the 3rd line *1
Unit
Returns a comment (memo).
--,--,
--
1st line, 2nd line, 3rd line
SIGCFAIL?
135
(SCF?)
SIGPOWERON
136
(SPOW)
SIGPOWERON?
137
(SPOW?)
COMMENT
138
(COM)
COMMENT?
139
(COM?)
Header
R/W Min.Max.
R-- ON/OFF is returned as 1 or 0.
WOFFONOFF/ON-- Sets the value of Status Signal Output: POWER ON.
R-- ON/OFF is returned as 1 or 0.
W
(“*1: 20H to 7EH are ASCII code. Put Set value in 22Hs (".) Except (“), (‘), (,), (;), and
(@) )
02000.1, 1sVoltage fall time
010/1--V RANGE (0: AUTO; 1: 5 kV)
020/1/2--Response settings (0: SLOW; 1: MID; 2: FAST)
010/1--GND (0: LOW; 1: GUARD)
010/1--Contact Check
0655351--Scanner Hi/Low (0 to 0xFFFF:16Bit, 0:Low, 1:Hi)
0655351--
Resolution
5.2
110
E-30.01,
110
E-3
0.01V Test voltage
E3
0.1, 1
Unit
Stores the current settings in ACW memory
(except for the memory name).
Stores the current settings in DCW memory
(except for the memory name).
Stores the current settings in IR memory
(except for the memory name).
Stores the next contents in the memory corresponding
to an ACW memory number.
Memory name: 12 characters
(20H to 7EH are ASCII code. Put Set value in 22Hs (".)
Except (“), (‘), (,), (;), and (@) )
A Lower current
A Upper current
Scanner Open
(0 to 0xFFFF:16Bit, 0:Hi or Low, 1:Open)
Function and response data
AB
Note 1 Note 2
②②
②②
②②
②②
②②
②②
②②
3-80 Messages and RegistersTOS9200 GPIB/RS-232C
ACW:MEMORY?
147
(A:MEM?)
DCW:MEMORY
148
(D:MEM)
DCW:MEMORY?
149
(D:MEM?)
IR:MEMORY
150
(I:MEM)
Header
Data
R/W Min.Max.
R0991--
0991--
20H7EH--
0
0.01
E-311E-3
0.01
E-311E-3
W
0.39990.1, 1sTest time
OFFONOFF/ON-- Lower ON/OFF
OFFONOFF/ON-- Timer ON/OFF
Returns the contents of memory corresponding to the
CW memory number (memory name, test v
A
wer current, upper current, test time, frequency, lower
lo
ON/OFF, offset ON/OFF, timer ON/OFF, start-voltage/
test-voltage ratio, voltage rise time, voltage fall time, V
RANGE (0/1), response filter setting (0/1/2), GND,
contact check, scanner Hi/Low, scanner Open).
ON/OFF is returned as 1 or 0.
Scanner Hi/Low and scanner Open are returned in decimal form using 16 bits.
Stores the next contents in the memory corresponding
to a DCW memory number.
Memory name: 12 characters
(20H to 7EH are ASCII code. Put Set value in 22Hs (".)
Except (“), (‘), (,), (;), and (@) )
"Scanner Open
(0 to 0xFFFF:16Bit, 0:Hi or Low, 1:Open)"
Returns the contents of memory corresponding to the
DCW memory number (memory name, test voltage,
lower current, upper current, test time, lo
timer ON/OFF, start-voltage/test-voltage ratio, voltage
rise time, WAIT TIME, response filter setting (0/1/2),
GND, contact check, scanner Hi/Low, scanner Open).
ON/OFF is returned as 1 or 0.
Scanner Hi/Low and scanner Open are returned in decimal form using 16 bits.
Stores the next contents in the memory corresponding
to an IR memory number.
Memory name: 12 characters
(20H to 7EH are ASCII code. Put Set value in 22Hs (".)
Except (“), (‘), (,), (;), and (@) )
Lower current
Upper current
"Scanner Open
(0 to 0xFFFF:16Bit, 0:Hi or Low, 1:Open)"
Function and response data
AB
Note 1 Note 2
oltage,
①①
②②
wer ON/OFF,
①①
②②
TOS9200 GPIB/RS-232CMessages and Registers 3-81
Data
Resolution
Unit
Returns the contents of the memory corresponding to an
IR memory number (memory name, test v
resistance, upper resistance, test time, upper ON/OFF
timer ON/OFF, voltage rise time, WAIT TIME, GND,
contact check, scanner Hi/Low, scanner Open).
ON/OFF is returned as 1 or 0.
Scanner Hi/Low and scanner Open are returned in decimal form using 16 bits.
IR:MEMORY?
151
(I:MEM?)
Header
R/W Min.Max.
R0991--
3.10.8Program-related messages
Function and response data
oltage, lo
AB
Note 1 Note 2
wer
,
①①
PRGNAME
152
(PNAM)
PRGNAME?
153
(PNAM?)
PRGTEST
154
(PTES)
PRGEDIT (PED)
155
Note 3
PRGEDIT?
156
(PED?)
PRGRETURN
157
(PRET)
PRGRETURN?
158
(PRET?)
PRGNEW
159
(PNEW)
PRGTOTAL?
160
(PTOT?)
PRGINS (PIN)
161
Note3
PRGDEL
162
(PDEL)
AUTORUNNING?
163
(ARUN?)
Header
Data
R/W Min.Max.
0991-- Program number
W
20H7EH--
R0991
W0991-- Sets the program corresponding to a program number.
0991-- Program number
0991-- Program step number
031-- 0: ACW, 1: DCW, 2: IR, 3: EC
W
0991-- Memory number
0.2
0991-- Returns the contents of a program corresponding to a
R
0991-0991-- Program number
W
OFFONOFF/ON--
R0991--
W0991-- Clears the program corresponding to a program number.
R0991--
0991-- Program number
0991-- Program step number
W
031-- 0: ACW, 1: DCW, 2: IR, 3: EC
0991-- Memory number
0991-- Program number
W
0991-- Program step number
RReturns the step currently being executed by a program.
9.9,
HOLD
Resolution
0.1s
Unit
Program name: 12 characters
(20H to 7EH are ASCII code. Put Set value in 22Hs (".)
Except (“), (‘), (,), (;), and (@) )
Returns the program name corresponding to a program
number
Interval time
Proceeds to the next step by pressing the START key
when in the HOLD status.
program number and step number.
OFF: END (Ends the program)
ON: RET (Returns to the first step)
Returns ON/OFF of the RETURN setting for the program corresponding to a program number.
Returns the total number of steps in the program corresponding to a program number.
Function and response data
AB
Note 1 Note 2
②②
①①
②②
②②
①①
②②
①①
②②
①①
②②
②②
①①
Note 3: When PRGEDIT (PED) or PRGINS (PIN) is executed, the program EDIT
screen automatically appears.
3-82 Messages and RegistersTOS9200 GPIB/RS-232C
Index
Symbols
*CLS 3-1
*ESR 3-2
*IDN 3-2
*RST 3-2
*SRE 3-3
*STB 3-3
A
acknowledge message 2-4, 3-7
ACW:CONTACTCHECK (A:CCH) 3-19
ACW:FALLTIME (A:FTIM) 3-14
ACW:FREQUENCY (A:FREQ) 3-10
ACW:GND (A:GND) 3-16
ACW:LOWER (A:LOW) 3-10
ACW:MEMORY (A:MEM) 3-55
ACW:OFFSET (A:OFF) 3-13
ACW:RECALL (A:REC) 3-52
ACW:RESPONSE (A:RES) 3-15
ACW:RISETIME (A:RTIM) 3-14
ACW:SCAN (A:SCAN) 3-17
ACW:SCANW (A:SCANW) 3-18
ACW:STARTV (A:STAR) 3-13
ACW:STORE (A:STOR) 3-53
ACW:TESTV (A:TES) 3-9
ACW:TIMER (A:TIM) 3-12
ACW:UPPER (A:UPP) 3-11
ACW:VRANGE (A:VRAN) 3-15
all registers 3-4
AUTORUNNING (ARUN) 3-69
B
CLR 3-4
comment 3-51
COMMENT (COM) 3-51
communication speed 1-3
contrast 3-44
CONTRAST (CON) 3-44
current detection response speed 3-15
D
data length 1-3
DCW:CONTACTCHECK (D:CCH) 3-28
DCW:GND (D:GND) 3-25
DCW:LOWER (D:LOW) 3-21
DCW:MEMORY (D:MEM) 3-58
DCW:RECALL (D:REC) 3-52
DCW:RISETIME (D:RTIM) 3-24
DCW:SCAN (D:SCAN) 3-26
DCW:SCANW (D:SCANW) 3-27
DCW:STARTV (D:STAR) 3-23
DCW:STORE (D:STOR) 3-54
DCW:TESTV (D:TES) 3-20
DCW:TIMER (D:TIM) 3-22
DCW:UPPER (D:UPP) 3-22
DCW:WAITTIME (D:WTIM) 3-24
delete a specified program 3-66
deletes the specified step 3-68
device status register 3-4, 3-72
device-status enable register 3-4, 3-72
DOUBLE ACTION 3-45
DOUBLE ACTION (DAC) 3-45
DSE 3-4
DSR 3-4
buzzer volume 3-43
BUZZERVOL (BVOL) 3-43
C
C FAIL 3-42, 3-50
CFAILCH (CFCH) 3-42
TOS9200 GPIB/RS-232CIndex I-1
E
each monitor value 3-40
ERR 3-5
error register 3-5, 3-73
event status register 3-2, 3-71
F
L
FAIL 3-5
FAIL MODE 3-45
FAIL MODE (FMOD) 3-45
fail register 3-5, 3-73
FUNCTION (FUN) 3-5
G
GPIB address 1-2
GPIB cable 1-2, 2-1
H
H.V ON 3-46
HIGH/LOW/OPEN for 16 channels 3-27
HIGH/LOW/OPEN for 16 scanner channels
3-18, 3-36
HIGH/LOW/OPEN for the scanner channel 3-17,
3-26, 3-35
I
IDATA (IDAT) 3-38
IMAGDATA (IMAG) 3-40
imaginary current 3-40
initialization 3-2
inserts a memory number into the specified step
3-67
INVALID (INV) 3-6
invalid-setting register 3-6, 3-73
IR:CONTACTCHECK (I:CCH) 3-37
IR:GND (I:GND) 3-33
IR:LOWER (I:LOW) 3-30
IR:MEMORY (I:MEM) 3-60
IR:RECALL (I:REC) 3-53
IR:RISETIME (I:RTIM) 3-32
IR:SCAN (I:SCAN) 3-35
IR:SCANW (I:SCANW) 3-36
IR:STORE (I:STOR) 3-54
IR:TESTV (I:TES) 3-29
IR:TIMER (I:TIM) 3-31
IR:UPPER (I:UPP) 3-31
IR:WAITTIME (I:WTIM) 3-33
L FAIL 3-48
list of GPIB functions 2-1
LOW/GUARD of the GND 3-16, 3-25, 3-33
lower current 3-10, 3-21
lower resistance 3-30
M
MEASMODE (MMOD) 3-42
message 2-3, 3-74
MOMENTARY 3-44
MOMENTARY (MOM) 3-44
MON 3-40
monitor current 3-38
monitor resistance 3-39
monitor voltage 3-38
O
offset 3-13
ON/OFF of the contact check function 3-19,
3-28, 3-37
ON/OFF of the lower judgment function 3-10
ON/OFF of the timer function 3-12, 3-22
output-voltage range 3-15
P
parity 1-4
PASS 3-47
PASS hold time 3-43
PASSHOLD (PHOL) 3-43
POWER ON 3-50
PRGDEL (PDEL) 3-68
PRGEDIT (PED) 3-64
PRGINS (PIN) 3-67
PRGNAME (PNAM) 3-63
PRGNEW (PNEW) 3-66
PRGRETURN (PRET) 3-66
PRGTEST (PTES) 3-64
PRGTOTAL (PTOT) 3-67
program 3-64
program messages 2-3
I-2 IndexTOS9200 GPIB/RS-232C
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.