Kikusui PAS 40-9, PAS 160-2, PAS 20-18, PAS 320-1, PAS 500-0.6, PAS 10-70, PAS 60-6, PAS 80-4.5, PAS 20-36, PAS 40-18, PAS 60-12, PAS 80-9, PAS 160-4, PAS 320-2, PAS 500-1.2, PAS 10-105, PAS 20-54, PAS 40-27, PAS 60-18, PAS 80-13.5, PAS 160-6, PAS 320-3, PAS 500-1.8 Operation Manual
Please read through and understand this Operation Manual before operating the
product. After
needed. When moving the product to another location, be sure to bring the manual as
well.
If you f
replaced.
either case, please contact Kikusui agent/distributor, and provide the "Part No." given
on cover
This manual has been prepared with the utmost care; however, if you have an
questions, or note an
ation Man
reading, always k
ind an
y incorrectly arranged or missing pages in this manual, the
If the manual it gets lost or soiled, a new copy can be provided for a fee.
.
ual
eep the manual nearby so that you may refer to it as
y will be
y errors or omissions, please contact Kikusui agent/distrib
y
utor
In
.
Microsoft and Visual Basic are re
NI-488.2 is re
Other compan
trademarks or re
All or an
written permission of Kikusui Electronics Corporation.
The contents of this manual are subject to change without notice.
gistered trademarks of National Instruments Corp., U.S.A.
y names and product names used in this manual are generally
gistered trademarks of the respective companies.
y parts of this manual may not be reproduced in an
ed.
gistered trademarks of Microsoft Corp., U.S.A.
y forms, without e
xpress
Saf ety Symbols
or the safe use and safe maintenance of this product, the
following symbols are used throughout this manual and on
the product. Understand the meanings of the symbols and
observe the instructions they indicate (the choice of sym
bols used depends on the products).
Indicates that a high voltage (over 1,000 V) is used here.
OR
Touching the part causes a possibly fatal electric shock. If
physical contact is required by your work, start work only
after you make sure that no voltage is output here.
-
DANGER
WARNING
CAUTION
Indicates an imminently hazardous situation which, if
ignored, will result in death or serious injury.
Indicates a potentially hazardous situation which, if
ignored, could result in death or serious injury.
Indicates a potentially hazardous situation which, if
ignored, may result in damage to the product and other
property.
Shows that the act indicated is prohibited.
Is placed before the sign "DANGER," "WARNING," or
"CAUTION" to emphasize these. When this symbol is
marked on the product, see the relevant sections in this
manual.
Indicates a protective conductor terminal.
Indicates a chassis(frame) terminal.
PAS SERIESSafety Symbols I
F
Saf ety Precautions
The f ollowing safety precautions must be observed to avoidfire hazard, electrical shock, accidents, and other failures.
Keep them in mind and make sure that all of them are
observed properly.
User s
Operation
Manual
This product must be used only by qualified
personnel who understand the contents of this
operation manual.
• If it is handled by disqualified personnel, personal
injury may result. Be sure to handle it under
supervision of qualified personnel (those who have
electrical knowledge.)
• This product is not designed or produced for home-
use or use by general consumers.
Purposes of use
Do not use the product for purposes other than
those described in the operation manual.
Line
Voltage
Input po wer
Use the product with the specified input power
voltage.
• For applying power, use the AC power cord
provided. Note that the provided power cord is not
use with some products that can switch among
different input power voltages or use 100 V and 200
V without switching between them. In such a case,
use an appropriate power cord. For details, see the
relevant page of this operation manual.
ver
There are parts inside the product which may cause
physical hazards. Do not remove the external cover.
II Safety PrecautionsPAS SERIES
•
•
•
Co
•
Installation
GNL
•
When installing products be sure to observe "1.2
Precautions for installation" described in this
manual.
• To avoid electrical shock, connect the protective
ground terminal to electrical ground (safety ground).
• When applying power to the products from a
switchboard, be sure work is performed by a
qualified and licensed electrician or is conducted
under the direction of such a person.
• When installing products with casters, be sure to
lock the casters.
Relocation
•
Turn off the power switch and then disconnect all
cables when relocating the product.
• Use two or more persons when relocating the
product which weights more than 20 kg. The weight
of the products can be found on the rear panel of the
product and/or in this operation manual.
• Use extra precautions such as using more people
when relocating into or out of present locations
including inclines or steps. Also handle carefully
when relocating tall products as they can fall over
easily.
• Be sure the operation manual be included when the
product is relocated.
Check?
PAS SERIES
Operation
•
Check that the AC input voltage setting and the fuse
rating are satisfied and that there is no abnormality
on the surface of the AC power cord. Be sure to
unplug the AC power cord or stop applying power
before checking.
• If any abnormality or failure is detected in the
products, stop using it immediately. Unplug the AC
power cord or disconnect the AC power cord from
the switchboard. Be careful not to allow the product
to be used before it is completely repaired.
Safety Precautions III
•
For output wiring or load cables, use connection
cables with larger current capacity.
• Do not disassemble or modify the product. If it must
be modified, contact Kikusui agent/distributor.
Maintenance and c
•
To avoid electrical shock, be absolutely sure to
unplug the AC power cord or stop applying power
before performing maintenance or checking.
• Do not remove the cover when performing
maintenance or checking.
• To maintain performance and safe operation of the
product, it is recommended that periodic
maintenance, checking, cleaning, and calibration be
performed.
Ser
vice
•
Internal service is to be done by Kikusui service
engineers. If the product must be adjusted or
repaired, contact Kikusui agent/distributor.
The PAS series is classified into three types depending on the output
capacity.
This operation manual describes the following models.
350W type
PAS10-35, PAS20-18, PAS40-9, PAS60-6, PAS80-4.5
REGULATED DC POWER SUPPLY
0-10V 35A
PAS10-35
VOLTAGE
OUTPUT
V W
CV
O N
PWR DSPL
OUTPUT
COARSE/FINE
CC
OFF
ALM
CURRENT
PAS160-2, PAS320-1, PAS500-0.6
PWR DSPL
A W
SHIFT
CONFIG
SET
ADDRESS
LOCK
OVP
OCP
700W type
REGULATED DC POWER SUPPLY
0-10V 70A
PAS10-70, PAS20-36, PAS40-18, PAS60-12, PAS80-9
PAS10-70
VOLTAGE
OUTPUT
V W
CV
O N
PWR DSPL
OUTPUT
COARSE/FINE
CC
OFF
ALM
CURRENT
PAS160-4, PAS320-2, PAS500-1.2
PWR DSPL
A W
SHIFT
CONFIG
SET
ADDRESS
LOCK
OVP
OCP
1000W type
REGULATED DC POWER SUPPLY
0-80V 13.5A
PAS80-13.5
PAS10-105, PAS20-54, PAS40-27, PAS60-18,
VOLTAGE
OUTPUT
V W
CV
O N
PWR DSPL
OUTPUT
COARSE/FINE
CC
OFF
ALM
CURRENT
PAS80-13.5, PAS160-6, PAS320-3,
PWR DSPL
A W
SHIFT
CONFIG
SET
ADDRESS
LOCK
OVP
PAS500-1.8
OCP
For details on the Power Supply Controller, see the operation manual
of the respective product. For connection to a Power Supply Controller and device messages. refer to the “Connecting & Programming
Guide” [Index.html] in the CD-ROM that came with the PIA4800
series.
Applicable firmware version of the PAS
This manual applies to PASs with firmware version 1.0x.
When contacting us about the product, please provide us the version
number and the manufacturing number that is affixed to the rear
panel.
For the procedure for checking the version, see "3.1 Turning on the
Power" .
PAS SERIESPreface P-1
Outline of the PAS series
The PAS series is a regulated DC power supply with a constant voltage/current automatic crossover function utilizing a switching regulator system. It is equipped with communication functions.
Features
■
P
(T
ower-factor improvement circuit
The po wer -f actor impro v ement circuit reduces the ef fects of har monic currents on the po wer line.
High effi ciency
The high po wer con v ersion ef fi cienc y reduces the cost of po wer and
the cost of heat radiation design during system confi guration.
Comm unication functions
Equipped with a digital remote control function through TP-B US
wist P air -B US) communication. (T otal length of TP-B US is 200
m.)
By combining with Kikusui's PIA4800 Series Po wer Supply Control ler , systemization for applications such as an automatic tester is pos sible.
Master-sla ve operation
Output v oltage or output current can be e xpanded by connecting mul tiple po wer supplies of the same model in series or in parallel and
controlling them with a single master de vice.
P-2 PrefacePAS SERIES
Options
Belo w are options a v ailable for the P AS series.
or details on the options, contact your Kikusui agent or distrib utor .
Rac k
able P-1 Rack mounting options
Product
Rack mount frame
57(2.24)
132.5(5.22)
37.75
(1.49)
149
100
24.5
460(18.11)
4
82
(18.9
460
480
Model
KRA3
KRA150
8)
Notes
Inch rack
EIA standard
Milli rack
JIS standard
KRA3
260(10.24)
KRA150
260
PAS SERIES
Fig.P-1Rack mount frame
Unit: mm (inch)
Preface
P-3
F
T
Analog Remote Control Connector Kit (OP01-P
AS)
A kit for connecting to the J1 connector on the rear panel.
ComponentQuantity
Socket1 pc.
Pins10 pcs.
Protection cover1 set
Chassis connection wire1 pc.
Fig.P-2
Analog remote control connector kit
P-4 Preface
PAS SERIES
Chapter
This chapter describes the necessary procedure from unpacking to
preparation before use.
. 1Setup
1.1
Checking at unpacking
When you receive the product, check that all accessories are included
and that the accessories have not been damaged during transportation.
If an
y of the accessories are damaged or missing, contact your
Kikusui agent /distrib
ACpowercord
utor
.
OperationManual
Accessories
NOTE
PAS SERIES
Fig.1-1
•
Packing/Unpacking (example for 700W type)
We recommend that all packing materials be saved, in case
the product needs to be transported at a later date.
The power cord that is provided varies depending on
Power cord, 1 pc.
the destination for the product at the factory-shipment.
Cable clamp: [P1-000-055] 1 pc.
Fastening plate: [D6-750-001] 1 pc.
Accompanying screws B: [M3-112-017] 2 pcs.
Cable: [85-10-0630] 1 pc.
For products with CE Marking (CE mark
on the top cover), an EMI core
AC power cord for 1000W type
(with cable clamp and no plug)
[96-01-0180] is embedded in the AC
power cord for 1000W type.
Rated voltage: 250 Vac
PLUG: GB1002
[85-10-0790]
TOP
1 pc.
[84-61-5102]
TP-BUS connector
1 pc.
[84-49-0110]
J1 protection socket *1
2 sets
M8 output terminal screws
2 pcs.
[M3-112-012]
Sensing terminal screws*1
*1: Attached to the product.
Fig.1-2
1-2
Setup
[M1-100-011]
[M5-101-007]
[M4-100-007]
Accessories
BOTTOM
1 set
[Q1-500-077]
OUTPUT terminal cover
1 pc.
[83-06-5060]
J1 lock lever*1
2 pcs.
[M3-112-026]
M4 output terminal screws
1 copy
[Z1-002-402]
Operation manual
PAS SERIES
1.2
Precautions for installation
Be sure to observ
po
wer supply
Do not use the power supply in a flammable atmosphere.
■
T
o pre v ent e xplosion or fi re, do not use the po wer supply near alco hol, thinner , or other comb ustible materials, or in an atmosphere con taining such v apors.
■
Avoid locations where the power supply is exposed to
high temperatures or direct sunlight.
Do not locate the po wer supply near a heater or in areas subject to
drastic temperature changes.
Operating temperature range: 0°C to +50°C (+32°F to +122°F)
Storage temperature range: -25°C to +70°C (-13°F to +158°F)
Avoid humid environments.
■
Do not locate the po wer supply in a high-humidity en vironment—
near a boiler , humidifi er , or w ater supply .
Operating humidity range: 20% to 85% RH
Storage humidity range: 90% RH or less
Condensation may occur e v en within the operating humidity range.
In that case, do not start using the po wer supply until the location is
completely dry .
Do not place the power supply in a corrosive atmosphere.
■
Do not install the po wer supply in a corrosi v e atmosphere or one con taining sulfuric acid mist or the lik e. This may cause corrosion of v ar ious conductors and imperfect contact with connectors, leading to
malfunction and f ailure, or in the w orst case, a fi re.
■
Do not locate the power supply in a dusty environment.
Dirt and dust in the po wer supply may cause electrical shock or fi re.
.
e the follo
wing precautions when installing the
(no de w condensation is allo wed)
(no de w condensation is allo wed)
PAS SERIES
Setup 1-3
Do not use the power supply where ventilation is poor.
■
e
The po wer supply emplo ys a forced air cooling system. Air is tak en in
from intak e ports located on the po wer supply's sides and front, and is
xhausted from the rear . Prepare suf fi cient space around the po wer
supply so that the intak e ports and e xhaust port are al w ays completely
unobstructed. Otherwise, heat may accumulate in the po wer supply ,
resulting in fi re.
■
P
Do not place any object on the power supply.
articularly a hea vy one, as doing so could result in a malfunction.
Do not place the power supply on a tilted surface or in a
■
location subject to vibrations.
If placed on a non-le v el surf ace or in a location subject to vibration,
the po wer supply may f all, resulting in damage and injury .
Do not use the power supply in locations affected by
■
strong magnetic or electric fields.
Operation in a location subject to magnetic or electric fi elds may
cause the po wer supply to malfunction, resulting in electrical shock
or fi re.
1.3 Precautions for moving
When mo ving or transporting the po wer supply to an installation site,
observ e the follo wing precautions.
■ T
Mo
urn the PO WER switch off.
ving the po wer supply with the po wer on may result in electrical
shock or damage.
urn off the switch on the switchboard, and remove all
■T
Mo
wirings connected.
ving the po wer supply with cables connected may break the cables
or cause the po wer supply to f all, resulting in injury .
For transportation, use the special packing material for the
■
T
power supply.
ransport the po wer supply in its original package to pre v ent vibra tion and f alls, which may damage the po wer supply . If you require
packing material, contact Kikusui agent/distrib utor .
1-4 Setup
PAS SERIES
1.4Connecting the AC power cord
The AC power cord provided with the product varies depending on
the type.
or the connection procedure, see the respective section for each type.
350W and 700W types
The AC power cord that is provided varies depending on the destination for the product at the factory-shipment.
WARNING
The power supply is designed to operate from the
overvoltage category II. Do not operate it from the
overvoltage category III or IV.
• The AC power cord for 100 V system shown in Fig.13 has a rated voltage of 125 VAC. If this AC power
cord is used at the line voltage of a 200 V system,
replace the AC power cord with that satisfying that
line voltage.
An appropriate AC power cord must be selected by
qualified personnel. If it is difficult to obtain the AC
power cord, consult your Kikusui distributor/agent.
• Secure adequate space around the power plug.
Do not insert the power plug to an outlet where
accessibility to the plug is poor. And, do not place
objects near the outlet that would result in poor
accessibility to the plug.
Do not use the AC power cord provided with the product as a AC
power cord for other instruments.
[85-AA-0004]
PLUG:NEMA5-15
Power cord for 100 V system
Rated voltage: 125 VAC
Rated current: 10 A
PAS SERIES
F
[85-AA-0005]
•
•
PLUG:CEE7/7
[85-10-0790]
PLUG:GB1002
Fig.1-3AC power cord
Power cord for 200 V system
Rated voltage: 250 VAC
Rated current: 10 A
Setup1-5
Connection procedure
Chec k that the supply v oltage is within the line v oltage
1.
r
ange of the po w er supply .
Input v oltage range: 100 V to 240 V A C
Frequenc y range: 50 Hz to 60 Hz
2.
T ur
n OFF the PO WER s witch.
Connect the A C po w er cord to the A C INPUT connector on
3.
the rear panel.
Use the pro vided po wer code or po wer code that is selected by qualifi ed
personnel.
Plug in the A C po w er cord.
4.
•
Direct connection to a s witchboard of 350W and 700W types
When directly connecting the product to a switchboard, k eep in mind
that the product is designed for Ov erv oltage Cate gory II.
Attach crimp terminals to the wires of the A C po wer cord when
directly connecting to a switchboard without using a plug.
WARNING
1-6 Setup
Connection of the AC power cord to the switchboard
must be carried out by qualified personnel.
• To prevent electric shock, turn OFF the switch on the
switchboard (to cut off the power feed from the
switchboard) and then connect the AC power cord.
• Install the AC power cord such that the distance
between the power supply and the switch on the
switchboard is within 3 m. This procedure facilitates
operation of the switch on the switchboard in the
event of emergency.
If the distance to the switch on the switchboard is to
be 3 m or more, install the AC power cord with a separate switch provided within 3 m from the power supply. For such a switch, use one with two poles that
can be disconnected simultaneously.
• For termination, attach crimp terminals that conform
to the terminal screws of the switchboard.
• Even if you cut the plug off the AC power cord,
observe the rated voltage of the AC power cord.
PAS SERIES
1000W type
The A C po wer cord that is included with the 1000W type can be used
on either a 100-V A C or 200-V A C system.
eep in mind that the product is designed for Ov erv oltage Cate gory II.
WARNING
CAUTION
Connection of the AC power cord to the switchboard
must be carried out by qualified personnel.
• To prevent electric shock, turn OFF the switch on the
switchboard (to cut off the power feed from the
switchboard) and then connect the AC power cord.
• Install the AC power cord such that the distance
K
•
between the power supply and the switch on the
switchboard is within 3 m. This procedure facilitates
operation of the switch on the switchboard in the
event of emergency.
If the distance to the switch on the switchboard is to
be 3 m or more, install the AC power cord with a separate switch provided within 3 m from the power supply. For such a switch, use one with two poles that
can be disconnected simultaneously.
• For termination, attach crimp terminals that conform
to the terminal screws of the switchboard.
• Inside the unit, protective circuits including input
fuses are connected to match the input terminal.
Make sure the colors of the wires connected to the
corresponding input terminals (L, N, and
(GND))
are correct.
Connection procedure
Chec k that the supply v oltage is within the line v oltage
1.
r
ange of the po w er supply .
Input v oltage range: 100 V to 240 V A C
Frequenc y range: 50 Hz to 60 Hz
2.
T ur
n OFF the PO WER s witch.
3.
Connect the pro vided A C po w er cord to the A C INPUT ter
minal board as sho wn in Fig.1-4 .
Attach cr imp ter minals to the A C po w er source side of the
A
4.
C po w er cord.
PAS SERIES
-
Setup 1-7
n OFF the s witchboard.
5.
T ur
6.
Connect the A C po w er cord to match the L, N, and GND of
the s witchboard.
N: White or blue
(GND): Green or green/yellow
Fastening plate
Fig.1-4 Connection of the AC power cord on the unit side
1.5 Grounding
•
Cable clamper
(GND)
N
L
AC INPUT terminal board
L: Black or brown
Fastening plate
Fix the covered part of the AC power
cord with the fastening plate.
WARNING
Electric shock may occur, if proper grounding is not
furnished.
• Connect the ground terminal to an electrical ground
(safety ground).
CAUTION
• If you do not ground the unit, malfunction may occur
due to external noise, or the noise generated by the
unit may become large.
Mak e sure to ground the unit for your safety.
350W and 700W types
Mak e sure to ground the unit.
Connect the 3-pin plug to a grounded 3-pin
receptacle.
1000W type
Mak e sure to connect the GND terminal of the A C INPUT terminal
block to the GND terminal of the switchboard.
1-8 Setup
PAS SERIES
Chapter . 2Before Using the Unit
Before using the unit, users are requested to thoroughly understand
the follo wing matters.
F
fi
1.
2.1 Inrush Current
An inrush current fl o ws when the PO WER switch is turned on. If you
are planning to use se v eral sets of the unit in a system and turn on
their PO WER switches simultaneously , check that the A C po wer
source or the switchboard is of suf fi cient capacity .
or details on the inrush current of each model, see Chapter8 " Speci cations " .
•
CAUTION
Allo w at least 10 seconds between power cycles.
Repeated on/off of the POWER switch at short intervals can cause malfunction of the inrush current limiting circuit and shorten the service life of the input
fuse and POWER switch.
2.2 Load
Note that the output will become unstable if the follo wing types of
loads are connected.
When Load Current Has Peaks or Is Pulse-Shaped
When the Load Generates a Re v erse Current to the Po wer Supply
When the Load Has Accumulated Ener gy Such as Batteries
2.
3.
2.2.1 When Load Current Has Peaks or Is PulseShaped
The current meter on the unit indicates only mean v alues. Ev en when
the indicated v alue is less than the preset current v alue, the peak v al ues may actually e xceed the preset current v alue. In such case, the
unit is instantaneously put into constant-current operation mode, and
the output v
F
or these types of loads, you must increase the preset current v
increase the current capacity
PAS SERIES
oltage drops accordingly
.
.
Before Using the Unit2-1
alue or
Preset constant current value
Meter indication value (mean value)
Preset constant current value
Meter indication value (mean value)
Fig.2-1
Load current with peaks
Fig.2-2 Pulse-shaped load cur-
rent
2.2.2
When the Load Generates a Reverse Current to
the Power Supply
The unit cannot absorb a reverse current from a re
such as an inverter
po
wer supply
output will fl
F
or these types of loads, connect a resistor RD as sho
bypass the reverse current. However, the current capacity to the load
decreases by Irp.
•
CAUTION
F
for the power (allowing sufficient margin).
If a resistor with insufficient rated power for the circuit
is used, it may burn out.
EO
Equivalent circuit of the unit
+IO
0
Output current
waveform
-IO
Fig.2-3 Remedy for regenerative load
, converter
. Consequently
, or transformer that supplies current to a
, the output v
oltage will increase and the
uctuate.
or resistor RD, select an appropr
−
RD
Reverse current
IO
Irp
+
Regenerative load
RD[Ω] ≤
I
EO[V]
[A]
rp
R
D: Reverse current bypass dummy load
EO: Output voltage
Irp: Max. reverse current
wn in
iate resistor rated
Load
generative load
Fig.2-3
to
2-2 Before Using the Unit
PAS SERIES
2.2.3
y
When the Load Has Accumulated Energy Such
as Batteries
Connecting a load with accumulated energy, such as a battery
, to the
unit may cause current to flow from the load to the internal circuit of
the unit. This current may damage the unit or reduce the life of the
load.
For this type of loads, connect a reverse-current-prevention diode
(DRP) between the unit and the load in series as shown in Fig.2-4.
CAUTION
• To protect the load and the unit, select DRP according
to the following criteria.
1. Reverse voltage withstand capacity: At least twice
the rated output voltage of the unit.
2. Forward current capacity: Three to ten times the
rated output current of the unit.
3. A diode with small loss.
• Be sure to take into account the heat generated by
DRP. DRP may burn out with inadequate heat dissipa-
tion.
• Cannot be used in combination with remote sensing.
DRP
DRP: Reverse-current-prevention diode
PAS SERIES
Unit
Load with accumulated energ
Fig.2-4 Remedy against load with accumulated energy
Before Using the Unit 2-3
2.3CV Power Supply and CC Power Supply
This unit is capable of both constant voltage and constant current
operation. This section describes these operations.
An ideal constant voltage power supply has zero output impedance at
all frequencies and maintains a constant voltage against all types of
load current variations. An ideal constant current power supply has
infinite output impedance at all frequencies and maintains constant
current by absorbing the load resistance variations by changing the
voltage.
Constant
Eo
OutputvoltageEo
00
Fig.2-5
Ideal constant voltage
power supply
Io
OutputcurrentIoOutputcurrentIo
Constant
Eo
OutputvoltageEo
Fig.2-6
Ideal constant current
power supply
Io
However, the output impedance of an actual constant voltage or constant current power supply is neither zero nor infinite and has a frequency response. In addition, since the output has limitations in terms
of maximum voltage and maximum current, power supplies are
unable to maintain a constant voltage or current for all types of load
current variations and load resistance variations. The following
describes the relationship between the basic operations in constant
voltage (CV) and constant current (CC) modes and the limit setting of
the unit.
The following description assumes a power supply with a DC output
of 100 V and 10 A (maximum rated output voltage of 100 V and maximum rated output current of 10A) as an example.
A resistive load of 10 Ω is connected to the output terminals of the
power supply, and the output current limit is set to 5 A. In this condition, the output voltage is raised gradually from 0 V. At this point, the
power supply is operating in the constant voltage (CV) mode. The
2-4 Before Using the UnitPAS SERIES
output current increases as the output voltage increases. When the
output voltage reaches 50 V (that is, the output current has reached 5
A), the output voltage no longer increases even if you attempt to raise
it. This is because the output current is limited to 5 A specified initially, causing the power supply to switch to the constant current (CC)
operation mode. In this way, the power supply automatically switches
from the constant voltage to constant current operation to prevent an
overcurrent from flowing. (The point at which the operation mode
switches is called the "crossover point".) If the current limit is raised
in this condition, the power supply returns to the previous constant
voltage operation, allowing you to increase the output voltage further.
If the current limit is increased from 5 A to 9 A in Fig.2-7, a voltage
of up to 90 V can be output.
Fig.2-7 Constant voltage operation and constant current
operation
Next, let's assume the case in which a load resistance of 4 Ω is used.
The output current limit is considered to be the rated maximum output current. If you increase the output voltage from 0 V, the output
current reaches the output current limit when the output voltage
reaches 40 V; the power supply cannot output a voltage above 40 V.
This is the limit even though the power supply is generating less than
PAS SERIESBefore Using the Unit 2-5
half its output capacity in terms of power. If you wish to increase the
output voltage further, the unit needs to be replaced by a model having larger current capacity. Particularly for loads into which a transient peak current flows, the current must be set such that its peak
does not reach (or exceed) the current limit. If the unit enters constant
current operation mode even when the current is set to the rated output current, the current capacity needs to be raised.
Next, we consider a case in which a load resistance of 25 Ω is used.
In this case, if the output current limit is set to 4 A or more, the power
supply can output voltages from 0 V to the rated maximum output
voltage in the constant voltage operation mode. The output voltage
limit is set to the rated maximum output voltage under this load condition, and the output current is gradually increased from 0 A. At this
point, the power supply is operating in the constant current (CC)
mode. The output voltage increases as the output current increases.
When the output voltage reaches 100 V, the output current no longer
increases even if you attempt to raise it. If you wish to increase the
current flow further in this condition, the unit needs to be replaced by
a model having higher output voltage. Particularly for loads that generate transient surge voltage, the voltage must be set so that the surge
voltage does not reach (or exceed) the voltage limit.
2-6 Before Using the UnitPAS SERIES
2.4Alarm
The unit is equipped with the following protection function. When the
protection function is activated, "ALM" on the front panel display
lights, and the OUTPUT is turned off or the POWER switch is shut
down. However, the only action available when OHP is activated is
turning off the OUTPUT. (See Fig.2-8.)
In addition, an ALARM signal is output to pin 20 of the J1 connector
when the protection function is activated. (See Fig.2-9.)
For details on selecting whether to turn off the OUTPUT or shut
down the POWER switch when an alarm is activated, see "3.2.4 Unit
Configuration (CONFIG)".
When POWER switch shutdown is selected, the illumination of
"ALM" and the ALARM signal output is held for approximately 0.5 s.
Recovery from an alarm
• When POWER switch shut down is selected
After clearing the abnormal condition that caused the alarm, turn
on the POWER switch.
• When OUTPUT OFF is selected
Turn off the POWER switch, clear the abnormal condition that
caused the alarm, and turn on the POWER switch.
Protection Function
■
•
F
OVP (overvoltage protection)
The o v erv oltage protection function protects a load from une xpect edly high v oltage. The function is acti v ated when the v oltage e xceeds
a preset v oltage (O VP trip point).
Selectable range: 10 % to 110 % of the rated output v oltage.
If the O VP function is acti v ated when CONFIG is set to OUTPUT
OFF , the v oltage display sho ws "O VP ."
or details, see "3.2.2 Setting the O VP (Ov erv oltage Protection) T rip
Point " .
PAS SERIESBefore Using the Unit 2-7
OCP (overcurrent protection)
CV
OUTPUT
OFF
ALM
V/
W
A/
W
CC
ON
The o v ercurrent protection function protects a load from une xpect edly high current. The function is acti v ated when the current e xceeds
a preset current (OCP trip point).
Selectable range: 10 % to 110 % of the rated output current.
If the OCP function is acti v ated when CONFIG is set to OUTPUT
OFF , the v oltage display sho ws "OCP ."
or details, see "3.2.3 Setting the OCP (Ov ercurrent Protection) T rip
Point " .
OHP (Overheat Protection)
This function is acti v ated when the internal temperature of the unit
raises abnormally .
This function protects the unit from the follo wing conditions.
When the unit is used in an environment exceeding the operation temperature range
• When the unit is used with the inlet or exhaust port blocked
• When the fan motor stops
If the OHP function is activated, the voltage display shows "OHP".
If the condition that caused the OHP to be activated is not corrected,
the OHP function is activated again when the POWER switch is
turned on.
•
F
•
•
CV
CC
Fig.2-8 ALARM indication example (OHP)
2-8 Before Using the Unit
ON
OUTPUT
OFF
V/
ALM
A/
PAS SERIES
SHUT (Shutdown)
The OUTPUT or the PO WER switch can be turned OFF by applying
a shutdo wn signal to the J1 connector on the rear panel. If the shut -
wn signal is applied when CONFIG is set to OUTPUT OFF , the
oltage display sho ws "SHUT ."
or details, see "4.1.7 Controlling the Output Shutdo wn Using Exter -
nal Contact "
Alarm Signal
■
.
Since the alarm signal output uses an open-collector photocoupler , it
is isolated from other terminals.
Maximum v oltage: 30 V
Maximum current: 8 mA
J1 connector
Inside
ALARM STATUS
ALARM COMMON
20
17
the unit
•
do
v
F
PAS SERIES
Fig.2-9 ALARM signal
Before Using the Unit 2-9
2.5 Grounding the Output Terminal
WARNING
The output terminal of the unit is isolated from the protecti ve grounding terminal. By connecting the GND wire of the AC power cord to
the ground terminal of the switchboard, the chassis of the unit is set to
ground potential (see Fig.2-10).
Consequently, the cable and load that are connected to the output terminal (including the sensing terminal) must have an insulation capacity that is greater than the isolation voltage of the unit with respect to
the chassis.
In addition, pins 3 through 9 of the J1 connector on the rear panel (for
analog remote control and output monitoring) are at approximately
the same potential as the - (neg.) output terminal of the unit. Therefore, cables and devices that are connected to these pins must also
have an insulation capacity that is greater than the isolation voltage of
the unit.
For safety reasons, even if the output terminal is
grounded, make sure the insulation capacity of the
output terminal (including the sensing terminal) is
greater than the isolation voltage of the unit.
If you cannot obtain a cable with sufficient rated voltage, secure adequate withstand voltage such as by
•
passing the cable through an insulation tube with a
withstand voltage greater than the isolation voltage of
the unit.
If adequate insulation measures are not taken
against the isolation voltage of the unit, electric shock
may occur when grounding is poor.
• If the unit is to be remotely controlled through an
external voltage source (Vext), do not ground the Vext
output (leave it floating). If the Vext output is
grounded in the example shown in Fig.2-11, the output is shor t-circuited (which can cause accidents).
xt, let's consider the case when the output terminal is grounded.
Fig.2-11 shows the case when the + (pos.) output terminal is connected to the chassis terminal. In this case, the + (pos.) output terminal is at ground potential. Therefore, the cable and load that are
connected to the output terminal (including the sensing terminal) only
require an insulation capacity that is greater than the maximum output voltage of the unit with respect to the chassis.
The same holds true when the - (neg.) terminal is connected to the
chassis terminal. The cable and load require an insulation capacity
Ne
F
that is greater than the maximum output voltage of the unit.
Fig.2-11 When the + (pos.) output terminal is grounded
L
N
AC
INPUT
or safety reasons, connect either output terminal to the chassis ter-
minal unless your application requires the output terminal to be float-
ing.
2-12 Before Using the Unit
PAS SERIES
Chapter . 3Basic Operation
CV
OUT P U T
OFF
ALM
V/
W
A/
W
CC
ON
This chapter describes ho w to turn on the po wer and the basic opera tions that you can carry out from the front panel.
3.1 Turning on the Power
CAUTION
• Allo w at least 10 seconds between power cycles.
Repeated on/off of the POWER switch at short intervals can cause malfunction of the inrush current limiting circuit and shorten the service life of the input
fuse and PO WER switch.
Power up procedure
1.
Chec k that the PO WER s witch is tur ned OFF .
Chec k that the A C po w er cord is correctly connected.
2.
T ur
No
3.
n on the PO WER s witch.
The v oltage and current displays sho w the v ersion number of the
unit for a fe w seconds (see Fig.3-1 ).
After a fe w seconds, the unit is ready for operation (displays the
output v alue).
w, the unit is ready for use.
ON
OFF
V/
ALM
CV
OUTPUT
CC
PAS SERIES
A/
Fig.3-1 Version display example at power up
Basic Operation 3-1
The display that appears when the PO WER switch is turned on for thefirst time corresponds to factory default settings.
The unit stores the panel settings (excluding OUTPUT ON/OFF condition) immediately before the POWER switch is turned off. The previous panel settings are used the next time the POWER switch is
turned on.
For factory default settings, see below.
actory default settings
Output v oltage
Output current
VP (o v erv oltage protection) : 110 % of the rated output v oltage
OCP (o v ercurrent protection) : 110 % of the rated output current
CONFIG settings
CV control
CC control: 0 (Panel control)
Remote sensing: 0 (OFF)
PWR ON OUTPUT: 0 (OFF at startup)
Master-slave operation: 0 (MASTER/LOCAL)
EXT OUTPUT: 0 (HIGH=ON)
TERMN: 0 (OFF)
POWER switch trip: 0 (Enable)
: 0 V
: Maximum preset current
(105 % of the rated output current)
: 0 (Panel control)
F
O
F
3.2 Basic Operation
First, the procedure for setting the output and the protection function
trip point will be e xplained. Ne xt, the procedure for using the unit as a
constant v oltage or constant current po wer supply will be described.
or details on the display sections and switches, see Chapter6
"Names and Functions of Controls" .
3-2 Basic Operation
PAS SERIES
3.2.1 Setting the Output
Here, we will look at an e xample in which the output is set to 35 V
and 7.5 A using the P AS40-9.
Setting the output of the P AS40-9 to 35 V and 7.5 A
Chec k that the LOCK s witch is tur ned off .
Y
1.
ou cannot set the output if this switch is illuminated.
2.
Chec k that OUTPUT OFF in the displa y section is illuminated.
If OUTPUT ON is illuminated, press the OUPUT switch to turn it
OFF .
Chec k that the SET s witch is illuminated.
•
3.
If it is not, press the SET switch to turn it on.
If this switch is not illuminated, the actual output v alue is dis played on the panel.
NOTE
If you turn the dial when the OUTPUT switch is off, the SET
switch is automatically illuminated even if it is not, and the
unit enters the setup condition.
• If you turn on the OUTPUT switch, the SET switch automatically turns off even if it is on, and the panel displays the output v alue.
Press the V OL T A GE s witch to select Coarse or Fine (preset
4.
Y
digit).
ou can also switch between Coarse and Fine by pressing the dial.
(The digit that is displayed brightly is the digit that you are set ting. The Coarse and Fine digits v ary depending on the model.)
n the dial to set the v alue to "35.00."
T ur
W
5.
e are done setting the voltage. Next, we will set the current. Proceed
step 6 .
to
6.
Press the CURRENT s witch to select Coarse or Fine (pre
-
Y
set digit).
ou can also switch between Coarse and Fine by pressing the dial.
(The digit that is displayed brightly is the digit that you are set ting. The Coarse and Fine digits v
n the dial to set the v alue to "7.5."
T ur
W
7.
ary depending on the model.)
e are done setting the current.
PAS SERIES
Basic Operation 3-3
3.2.2 Setting the OVP (Overvoltage Protection) Trip
Point
The O VP function protects a load from une xpectedly high v oltage.
When O VP is acti v ated, "ALM" on the display lights, and the OUT PUT is turned of f or the PO WER switch is tripped. (Selectable range:
10 % to 110 % of the rated output v oltage)
or details on setting whether to turn of f the OUTPUT or trip the
WER switch when O VP is acti v ated, see "PO WER switch trip
when the protection circuit is acti v ated (DEGIT H)" in "3.2.4 Unit
Confi guration (CONFIG)" .
If the PO WER switch trip is set to enable when the protection circuit
is acti v ated in CONFIG, the illumination of "ALM" and the ALARM
signal output is held for approximately 0.5 s.
o release the alarm when the PO WER switch is not set to trip when
the protection circuit is acti v ated in CONFIG, turn of f the PO WER
switch once.
NOTE
Setting the O VP trip point
1.
2.
3.
The OVP trip point is factory-preset to approximately 110 %
of the rated output voltage of the unit. When using the unit,
set an appropriate OVP trip point for the load.
• When checking the OVP operation, the unit must be started
with the OUTPUT turned off. Therefore, check that PWR
ON OUTPUT in the CONFIG settings is set to "0." For
details on CONFIG settings, see "3.2.4 Unit Configuration
(CONFIG)".
• The OVP function of the unit operates against the output terminal voltage. If you wish to operate the function against the
voltage across the load, set the OVP trip point by considering
the voltage drop of the load cable.
Chec k that no load is connected to the output ter minal.
v
Since we will check the O VP operation by actually outputting a
oltage after setting the O VP trip point, remo v e the load.
n on the PO WER s witch.
T ur
F
PO
T
Chec k that the OUTPUT OFF is illuminated.
•
3-4 Basic Operation
PAS SERIES
Press the O VP switch.
4.
The v oltage display sho ws the preset v alue, and the current dis play sho ws "O VP ."
Y
5.
Press the V OL T A GE s witch to select Coarse or Fine (preset
digit).
ou can also switch between Coarse and Fine by pressing the dial.
(The digit that is displayed brightly is the digit that you are set ting. The Coarse and Fine digits v ary depending on the model.)
n the dial to set the O VP tr ip point.
T ur
Ne
6.
xt, we will check the operation. Proceed to step 7 .
Press the O VP s witch to escape from the O VP setup mode .
7.
8.
Press the SET s witch to enter the output setup mode .
SET switch lights.
Press the V OL T A GE s witch and set the output v oltage to a
9.
v
alue signifi cantly less than the O VP tr ip point v oltage .
Press the OUTPUT s witch to illuminate OUTPUT ON.
10.
Gr
11.
adually tur n the dial cloc kwise , and chec k that the OUT
PUT tur ns off or the PO WER s witch tr ips when the output
v
oltage reaches the preset O
When the PO
WER switch is not set to trip when the protection
circuit is activated in CONFIG,
and the v
oltage display sho
VP tr
ip point v
oltage
ALM lights in the display section
ws "OVP."
.
-
W
e are done setting the OVP trip point.
You can set or confirm the OVP trip point even when OUTPUT is
turned on. In this case, if the OVP trip point voltage is set lower than
the preset output voltage, OVP is activated and the OUTPUT turns off
or the POWER switch trips.
The following conditions activate the OVP function.
• When the preset voltage is higher than the OVP trip point voltage.
• When the sensing wire comes loose.
• When the load is abnormal.
• When the unit is abnormal.
If you turn on the POWER switch without correcting the cause, OVP
is activated again.
PAS SERIES
Basic Operation 3-5
3.2.3
Setting the OCP (Overcurrent Protection) Trip
Point
The OCP function protects a load from une
When OCP is activated, "ALM" on the display lights, and the OUT
PUT is turned of
10 % to 110 % of the rated output current)
F
or details on setting whether to turn of
PO
WER switch when OCP is activated, see
when the protection circuit is activated (DEGIT H)"
Confi
guration (CONFIG)"
If the PO
v
ated in CONFIG, the illumination of "ALM" and the
output is held for approximately 0.5 s.
T
o release the alarm when the po
protection circuit is activated in CONFIG, turn of
switch once.
NOTE
Setting the OCP trip point
1.
2.
3.
4.
5.
WER switch is set to trip when the protection circuit is acti
•
The OCP trip point is factory-preset to approximately 110 %
of the rated output current of the unit. When using the unit,
set an appropriate OCP trip point for the load.
n on the PO WER s witch.
T ur
Chec k that the OUTPUT OFF is illuminated.
Press the O VP s witch while pressing the SHIFT s witch.
The v oltage display sho ws "OCP ," and the current display sho ws
the preset v alue.
P r e s s t h e C U R R E N T s w i t c h t o s e l e c t C o a r s e o r F i n e ( p r e s e t d i g i t ) . Y
ou can also switch between Coarse and Fine by pressing the dial.
(The digit that is displayed brightly is the digit that you are set ting. The Coarse and Fine digits v ary depending on the model.)
n the dial to set the OCP tr ip point.
T ur
W
f or the PO
WER switch is tripped. (Selectable range:
.
wer switch is not set to trip when the
xpectedly high current.
f the OUTPUT or trip the
"PO
WER switch trip
in
"3.2.4 Unit
ALARM signal
f the PO
-
-
WER
e are done setting the OCP trip point.
You can set or confirm the OCP trip point even when OUTPUT is
turned on. In this case, if the OCP trip point voltage is set lower than
the preset output current, OCP is activated and the OUTPUT turns off
or the POWER switch trips.
3-6 Basic Operation
PAS SERIES
The follo wing conditions activate the OCP function.
CV
OUT PUT
OFF
ALM
V/
W
A/
W
CC
ON
• When the preset current is higher than the OCP trip point voltage.
• When the load is abnormal.
• When the unit is abnormal.
If you turn on the POWER switch without correcting the cause, OCP
is activated again.
3.2.4 Unit Configuration (CONFIG)
o change v arious settings of the unit, use the v oltage and current dis -
play sections, the CONFIG switch, and the dial on the front panel.
DIGIT A:CV control
DIGIT B:CC control
DIGIT C:Remote sensing
DIGIT D:PWR ON OUTPUT
Voltage display section
DIGIT E:Parallel/Series master-slave
DIGIT G:TERMN during digital remote control
PAS SERIES
CV
CC
DIGIT F:EXT OUTPUT logic
DIGIT H:POWER switch trip when the
protection circuit is activated
Fig.3-2 CONFIG display
T
ON
OUTPUT
OFF
V/
ALM
Current display section
A/
Basic Operation 3-7
able 3-1 CONFIG settings
oltage display section
DIGIT ADIGIT BDIGIT CDIGIT D
Preset
value
0
Preset
value
0 MASTER/LOCAL HIGH=ON
3
CV controlCC controlRemote
anel controlPanel controlOFFOFF at startup
External v oltage
control
External resistance
control
→
10 k Ω
MAX OUT
External resistance
control
→
10 k Ω
0 OUT
(FAIL SAFE)
DIGIT EDIGIT FDIGIT GDIGIT H
Parallel/Series
master-slave
arallel slaveLOW=ONONDisable(not shutdown)
Series sla ve
External voltage
External resistance
10 k Ω
External resistance
10 k Ω
Current displa y section
EXT OUTPUT
control
control
3
→
MAX OUT
control
→
0 OUT
(FAIL SAFE)
logic
1 P
2
TERMN during
digital remote
sensing
ONON at startup
POWER switch trip
control
OFF
when the protection
circuit is activated
Enable(shutdo wn)
PWR ON
OUTPUT
Descriptions of setting items
■
v
F
v
F
CV control (DEGIT A)
Select the constant v oltage control from panel control, e xternal
oltage, e xternal resistance, and e xternal resistance (F AIL SAFE).
or details on e xternal control, see "4.1 Analog Remote Control" .
CC control (DEGIT B)
Select the constant current control from panel control, e xternal
oltage, e xternal resistance, and e xternal resistance (F AIL SAFE).
or details on e xternal control, see "4.1 Analog Remote Control" .
Remote sensing (DEGIT C)
Set "0" to disable remote sensing, "1" to enable it.
or details on remote sensing, see "3.6 Remote Sensing" .
3-8 Basic Operation
F
V
P
1
2
T
PAS SERIES
PWR ON OUTPUT (DEGIT D)
Set "0" to start up the unit with the OUTPUT turned of f when the
WER switch is turned on, "1" to start up the unit with the
OUTPUT turned on.
Master-sla ve series/parallel function (DEGIT E)
Set the master and sla v e units when using series or master -sla v e
parallel function. Set "0" to mak e the unit a maser when the mas ter -control connection is made to the J1 connector .
Set "2" to mak e the unit a sla v e during series operation, "1" during
parallel operation.
or details on master -sla v e series/parallel operation, see Chapter5
arallel and Series Operation" .
PO
F
"P
F
F
PO
EXT OUTPUT logic (DEGIT F)
When controlling the on/of f of the output through an e xternal con tact (J1 connector), set "1" to turn on the OUTPUT with a lo w sig nal, "0" to turn on the OUTPUT with a high signal.
or details on the on/of f control of the output using e xternal con tacts, see "4.1.6 Controlling the Output ON/OFF Using External
Contact" .
TERMN dur ing digital remote control (DEGIT G)
When performing digital remote control, TERMN (termination) is
set on the unit at each end of the b us.
or details on digital remote control, see "4.3 Digital Remote
Control" .
WER switch trip when the protection circuit is activated
(DEGIT H)
Set "0" to trip (turn of f) the PO
age protection), OCP (overcurrent protection), or SHUT (shut
do
wn) is activated, "1" not to trip the PO
If set to "1" the OUTPUT is turned of
WER switch when O
WER switch.
f when the above protection
VP (overv
olt
-
-
circuits are activated.
NOTE
PAS SERIES
•
Precautions when setting PWR ON OUTPUT to "1"
To check the OVP operation, set the PWR ON OUTPUT to
"0" (off at startup) first. Or, check the OVP operation first,
and then set PWR ON OUTPUT to "1" (on at startup).
If you check the OVP operation with PWR ON OUTPUT set
to "1" (on at startup) when the POWER switch trip is set to
Basic Operation 3-9
"0" (enable), the PO
WER switch may turn OFF every time
you turn ON the POWER switch after the initial OVP activation. This is because OVP is activated every time the power is
turned on. In such case, redo the CONFIG settings.
Setup procedure
n off the PO WER s witch.
1.
T ur
While pressing the CONFIG s witch, tur n on the PO WER
s
K
2.
witch.
eep pressing the CONFIG switch until the CONFIG switch
lights up (CONFIG setting mode, Fig.3-2 ) after the v ersion is dis played.
3.
Press the V OL T A GE or CURRENT s witch to mo v e betw een
Y
F
the digits , and use the dial to enter a v alue betw een 0 and 3.
The digit that is displayed brightly is the digit that is modifi ed.
ou can also mo v e between the digits by pressing the dial.
or the relationship between the position of the entered digit and
the v alue, see table 3-1 , "CONFIG settings"
(All v alues are f actory-preset to "0.")
When y ou done with the setup , tur n off the PO WER s witch
4.
T
W
and then tur n it on again.
CONFIG settings tak e ef fect by rebooting the unit.
o escape from the CONFIG setting mode e v en if you are not
making changes, turn of f the PO WER switch once.
e are done with the CONFIG settings of the unit.
You can check the settings by pressing the CONFIG switch. If you
press the CONFIG switch again, the unit returns to the previous display.
3-10 Basic Operation
PAS SERIES
3.2.5 Using the Unit as a Constant Voltage Power
Supply
This section describes the procedure for using the unit as a constant
oltage po wer supply .
Chec k that the PO WER s witch is tur ned OFF .
1.
F
2.
Connect the load to the output ter minal.
or details on connecting the load, see "3.3 Connecting the Load" .
n on the PO WER s witch.
T ur
3.
Chec k that the OUTPUT OFF is illuminated.
4.
5.
Press the SET s witch to enter the v oltage/current setup
mode .
Press the CURRENT s witch to select Coarse or Fine f or
6.
setting the current.
n the dial to set the v alue of the current that can f lo w to
T ur
7.
the load.
The v alue entered here becomes the current limit.
8.
Press the V OL T A GE s witch to select Coarse or Fine f or set
ting the v oltage .
n the dial to set the desired v oltage .
T ur
9.
Press the OUTPUT s witch to illuminate OUTPUT ON.
10.
V
11.
oltage is output to the output ter minal.
OUTPUT ON and CV light up, and the v oltage display sho ws the
actual output v oltage.
v
Y
•
-
ou can set the voltage while checking the actual output voltage even
when OUTPUT ON is illuminated.
The current limit must be changed by pressing the SET switch.
NOTE
PAS SERIES
If the output current exceeds the current limit that was specified in step 7 due to load fluctuations when the unit is operating in constant voltage mode, the unit switches to constant
current mode. When the unit switches to constant current
mode, CC lights up.
Basic Operation 3-11
3.2.6 Using the Unit as a Constant Current Power
Supply
This section describes the procedure for using the unit as a constant
current po wer supply .
Chec k that the PO WER s witch is tur ned OFF .
1.
F
2.
Connect the load to the output ter minal.
or details on connecting the load, see "3.3 Connecting the Load" .
n on the PO WER s witch.
T ur
3.
Chec k that the OUTPUT OFF is illuminated.
4.
5.
Press the SET s witch to enter the v oltage/current setup
mode .
Press the V OL T A GE s witch to select Coarse or Fine f or set
6.
ting the v oltage .
n the dial to set the v alue of the v oltage that can be
T ur
7.
applied to the load.
The v alue entered here becomes the v oltage limit.
8.
Press the CURRENT s witch to select Coarse or Fine f or
setting the current.
T ur
9.
Press the OUTPUT s witch to illuminate OUTPUT ON.
10.
11.
Current f lo ws to the output ter minal.
OUTPUT ON and CC light up, and the current display sho ws the
actual output current.
n the dial to set the desired current.
Y
•
-
ou can set the current while checking the actual output current even
when OUTPUT ON is illuminated.
The voltage limit must be changed by pressing the SET switch.
NOTE
3-12 Basic Operation
If the output voltage exceeds the voltage limit that was specified in step 7 due to load fluctuations when the unit is operating in constant current mode, the unit switches to constant
voltage mode. When the unit switches to constant voltage
mode, CV lights up.
PAS SERIES
3.3 Connecting the Load
This section describes the load cable used to connect the unit and the
load and the connection to the output terminal.
3.3.1 Load Cable
WARNING
To prevent the possibility of fire, use a load cable with
sufficient current capacity with respect to the rated
output current of the unit.
• To prevent the possibility of electric shock, use a load
cable with a higher voltage rating than the isolation
voltage of the unit.
For details on the isolation voltage of each model,
see Chapter8 "Specifications".
•
PAS SERIES
Basic Operation 3-13
Current capacity of load cab les
Load cables must be rated to carry the maximum rated output current
of the unit. If their current rating e xceeds the maximum rated output
current, the cable will remain intact e v en if the load is short-circuited.
The allo w able current of a wire is determined by the maximum allo w able temperature of the cable insulation, which in turn is go v erned by
a current-caused resistance loss, ambient temperature, and thermal
resistance to the outside. The allo w able currents in table 3-2 sho w the
capacity of current fl o wing through a heat-resistant PVC wire (single
wire) ha ving a maximum allo w able temperature of 60 ˚C when the
wire is stretched horizontally in the air at an ambient temperature of
30 ˚C. If the condition is such that PVC wires with lo wer heat-resis tant temperature are used, ambient temperature e xceeds 30 ˚C, or the
wires are b undled resulting in lo w heat radiation, the current capacity
needs to be reduced.
Based on this consideration, it is better to mak e heat radiation as great
as possible to allo w a lar ger current to fl o w , as long as wires ha ving
the same heat-resistant temperature are used. F or measures ag ainst
noise in the load cables, ho we v er , installing the + (pos.) and - (ne g.)
output lines side by side or b undling them together is more ef fecti v e
ainst unw anted noise. The Kikusui-recommended currents sho wn
in table 3-2 are allo w able current v alues that ha v e been reduced in
consideration of the potential b undling of load cables. Use these v al ues as a guideline when installing load wires.
Because wires have resistance, v
as the wire becomes longer or the current becomes lar
the v
oltage applied at the load end to be smaller. The P
po
wer supplies have a sensing function that compensates for this v
age drop. Compensation of up to approximately 0.6
a single line. If the v
oltage drop in wires becomes greater
oltage drop e
ger. This causes
AS series
V is available for
xceeds this level, wires ha
olt
ving a
greater cross-sectional area should be used.
ag
-
3-14 Basic Operation
PAS SERIES
T
able 3-2 Nominal cross-sectional area of cables and allow-
able currents
Nominal cross-
sectional area
[mm]
214(0.28)2710
3.512(3.31)37-
5.510(5.26)4920
88(8.37)6130
145(13.3)8850
223(21.15)11580
302(33.62)139-
381(42.41)162100
501/0(53.49)190-
602/0(67.43)217-
803/0(85.01)257200
1004/0(107.2)298-
125--344-
150--395300
200--469-
*1.
Excerpts from Japanese la
AWG(Reference
cross-sectional
area) [mm]
ws related to electrical equipment.
Allowable cur-
rent*1 [A]
(T
a = 30˚C)
Current recom
mended by
Kikusui [A]
-
Withstand v
F
or load cables, use cables with a higher v
tion v
cables is lo
rated output v
F
or details on the isolation v
oltage of load cables
oltage of the unit. In particular
wer than the isolation v
oltage of 40
Grounding the Output Terminal
PAS SERIES
oltage rating than the isola
, if the rated v
oltage of the po
oltage of load
wer supply ha
V or more, electric shock may occur
oltage and the insulation, see
"
Basic Operation 3-15
-
ving a
.
"2.5
3.3.2Connecting to the Output Terminals
Normally, the chassis terminal is connected to either the - (neg.) or +
(pos.) output terminal.
n off the PO WER s witch.
T ur
1.
2
with the
2.
Remo v e the OUTPUT ter minal co v er .
See "Attaching the OUTPUT terminal co v er" on the ne xt page,
and remo v e the OUTPUT terminal co v er by re v ersing the steps.
Connect the chassis ter minal to either the - (neg.) or +
3.
(pos .) output ter minal.
Fig.3-3 sho ws the case when the chassis terminal is connected to
the - (ne g.) output terminal.
Attach cr imp ter minals to the load cab le .
4.
The OUTPUT terminal has M4- (with taps) and M8-sized holes
for connecting the load cable. Attach the crimp terminal that
matches the scre ws.
Use crimp terminals that are less than equal to 5.5 mm
M4-sized holes.
Connect the load cab le to the OUTPUT ter minal.
5.
See Fig.3-3 or Fig.3-4 .
6.
Chec k the connection.
Attach the OUTPUT ter minal co v er .
7.
See "Attaching the OUTPUT terminal co v er" on the ne xt page.
Crimp terminal
Screw (M4 and spring washer)
Screw (M3 and spring washer)
Screw (M3 and spring washer)
Fig.3-3 Connection using M4 screws
3-16 Basic OperationPAS SERIES
Screw (M8)
r
Crimp terminal
Spring washe
Nut
Fig.3-4Connection using M8 screws
Attaching the OUTPUT terminal cover
The OUTPUT terminal cover consists of a BOTTOM cover and a
OP cover.
The TOP cover is the one with screws.
1.
Inser t the hook of the BO TT OM co v er into the hole located
abo v e and to the left of the output ter minal.
Insert the hook of the
BOTTOM cover to this hole.
T
PAS SERIES
Basic Operation 3-17
Align the hook of the BOTTOM cover to the groove located
2.
to the side of the output terminal.
Align the hooks of the BOTTOM
cover to these two grooves.
While holding the BOTTOM cover, insert the hook into the
3.
hole located above and to the left of the output terminal. At
this point, pull the load cable from the hole on the near side
of the terminal cover.
Slide the TOP cover align this hole.
Pull the load cable from this hole.
Using the screws attached to the TOP cover, fix the TOP
4.
cover and BOTTOM cover in place.
3-18 Basic Operation
Tighten this screw with an M3 screwdriver and you are done.
PAS SERIES
3.4 Switching the Power Display
The P AS series po wer supply allo w you to v ary the output v oltage or
output current while checking the output po wer .
When v arying the output voltage while checking the power
If you press the SHIFT+CURRENT switch (press the CURRENT
switch while pressing the SHIFT switch) when the OUTPUT is on,
the current display sho ws the output po wer .
The LED to the right of the unit lights up when po wer is being dis played.
In this condition, select Coarse or Fine using the V OL T A GE switch
and v ary the v oltage using the dial.
o clear the po wer display , press the SHIFT+CURRENT (or SET)
switch ag ain.
When v arying the output current while checking the power
If you press the SHIFT+V OL T A GE switch (press the V OL T A GE
switch while pressing the SHIFT switch), the v oltage display sho ws
the output po wer .
The LED to the right of the unit lights up when po wer is being dis played.
In this condition, select Coarse or Fine using the CURRENT switch
and v ary the v oltage using the dial.
o clear the po wer display , press the SHIFT+V OL T A GE (or SET)
switch ag ain.
T
T
Switching the displa y position
Once the po wer is displayed, you can switch the po wer display posi tion using the V OL T A GE or CURRENT switch.
PAS SERIES
Basic Operation 3-19
3.5 LOCK Function
A LOCK switch is pro vided as a function to pre v ent inadv ertently
changing the settings.
When the panel lock is enabled (LOCK switch lights up), the
switches on the front panel (e xcluding the OUTPUT switch) and the
dial do not function.
anel lock procedure
Conf igure necessar y all settings such as the output v oltage .
1.
T
T
•
•
2.
Press the LOCK s witch.
The LOCK switch lights up, and the panel lock is enabled.
o clear the panel lock, press the LOCK switch again.
3.6 Remote Sensing
The remote sensing function is used to reduce the infl uence of v oltage
drops due to the load cable resistance and stabilize the output v oltage
across the load.
The remote sensing function of this unit can compensate up to
approximately 0.6 V for a single line. Select a load cable with suf fi cient current capacity so that the v oltage drop of the load cable does
not e xceed the compensation v oltage.
o perform remote sensing, an electrolytic capacitor is required at the
sensing point (load terminal).
NOTE
Sensing wire connection procedure
WARNING
3-20 Basic Operation
The voltage drop compensation is approximately 0.6 V for a
single line. However, if remote sensing is performed near the
maximum output voltage, the output of the unit is limited by
the maximum voltage (105 % of the rated output voltage).
Never connect wires to the sensing terminals while
the POWER switch is turned on. Such acts can cause
electric shock or damage to the internal circuitry.
PAS SERIES
P
Press the PO WER s witch while pressing the CONFIG
1.
s
T
F
witch to enter the CONFIG setting mode .
urn on remote sensing through CONFIG setting.
or details on CONFIG settings, see "3.2.4 Unit Confi guration
(CONFIG)" .
T ur
2.
n off the PO WER s witch.
As sho wn in Fig.3-5 , connect the sensing wires betw een the
3.
T
ef
•
sensing ter minals and the load cab le b y using the scre ws
pro vided.
o decrease output ripple v oltages resulting from inducti v e
fects, use a 2-core shielded wire for the sensing wires. Connect
the shield to the - (ne g.) terminal.
If you cannot use shielded wires, twist the + (pos.) and - (ne g.)
wires thoroughly .
WARNING
For sensing cables, use cables with a higher voltage
rating than the isolation voltage of the unit. For
details, see "2.5 Grounding the Output Terminal"
Protect the uncovered section of the shielded wire by
using insulation tubes with a withstand voltage
greater than the isolation voltage of the unit.
• To turn on/off the power supplied to a load using a
mechanical switch, provide additional switches
between the sensing wires as shown in Fig.3-6 and
turn on/off the power and remote sensing cables
simultaneously. Be sure to turn off the OUTPUT
switch or POWER switch before turning on/off the
mechanical switch.
•
CAUTION
If the sensing wires come loose , the output voltage
across the load cannot be stabilized and may cause
excessive voltage to be applied to the load. Securely
connect the sensing wires such as by using crimp ter
-
minals .
4.
A s necessary, connect an electrolytic capacitor (C) between
0.1 μF to several hundred μF across the load terminals.
PAS SERIES
Basic Operation 3-21
CAUTION
•
Use a capacitor (C) whose withstand voltage is
greater than or equal to 120 % of the unit's rated voltage.
NOTE
5.
C
CAUTION
If the wiring to a load is long, the phase shift caused by the
inductance and capacitance of the wiring becomes non-negligible, thereby causing oscillation. In such case, the capacitor
(C) prevents oscillation.
If the load current changes suddenly to pulse form, the output voltage may increase due to the effects from the inductance component of the wiring. In such case, the capacitor
(C) also prevents variations in output.
In addition, twisting the load wires reduces the inductance
component, thereby stabilizing the output.
heck the sensing wire connection and CONFIG settings again.
•
When y ou are done using the remote sensing function, remove the sensing wires, and be sure to turn
off remote sensing in the CONFIG settings.
2-core shielded wire
+S
–S
Load
+
+
C
–
–
Fig.3-5 Remote sensing connection
+
C
–
Fig.3-6 Power on/off using mechanical switches
3-22Basic Operation
S
+
+
Load
•
•
•
–
+S
–S
–
PAS SERIES
Chapter . 4Remote Control
This chapter describes the remote control function of the unit.
Please read the w arnings and cautions thoroughly before operation.
There are tw o main methods for remotely controlling the unit.
Analog remote control
• Digital remote control
In analog remote control, the power supply and contacts that are connected to the J1 connector on the rear panel are used to control the
unit.
In digital remote control, the PIA4830, PIA4850 or PIA4810 Power
Supply Controller that is connected to the TP-BUS connector on the
rear panel is used to control the unit.
•
For details on the PIA4800 series Power Supply Controller, see the
operation manual of the respective product. For connection to a
Power Supply and device messages, refer to the “Connecting & Programming Guide” in the CD-ROM that came with the PIA4800
series.
If you are using the PIA3200 Power Supply Controller, contact your
Kikusui agent/distributor.
•
4.1 Analog Remote Control
The J1 connector on the rear panel can be used to control the unit in
the follo wing manner .
Control the output voltage using external voltage
• Control the output current using external voltage
• Control the output voltage using external resistance
• Control the output current using external resistance
• On/off control of the output using external contact
• Shutdown control using external contact
(turn off the OUTPUT or POWER switch)
PAS SERIES
Remote Control 4-1
4.1.1 About the J1 Connector
WARNING
The J1 connector contains pins that are at the same
electric potential as the output terminal. If you are not
using the J1 connector, to prevent the possibility of
electric shock, be sure to insert the protective socket
provided.
• To prevent the possibility of electric shock, be sure to
use the protective cover on the sockets.
The connector parts needed to connect the J1 connector (standard
MIL connector) are not pro vided. table 4-1 sho ws the tools an parts
that are needed.
or information on ho w to obtain the tools and parts, contact your
Kikusui agent or distrib utor .
An optional OP01-P AS Analog Remote Control Connector Kit is
ailable for making the connection.
•
F
a v
T
F
–
–
Fig.4-1 OP01-PAS
able 4-1 Connector parts by Omron needed to connect the
J1 connector
Product
Single contact
connection tool
Contact remo v al
tool
Pin (contact)
Socket
Protection coverXG5S-130184-49-0161 –
or details on ho w to use the tools, read the catalog by Omron.
4-2 Remote Control
Model
XY2B-7006
XY2E-0001 Y2-070-002
XG5W -003184-49-0100
XG5M-2632-N84-49-0160
Kikusui P arts
No.
Y2-070-001
Notes
Recommended wire
size AWG24 (UL-1061)
MIL standard type
socket
PAS SERIES
able 4-2 J1 connector arrangement
Pin No . Signal NameDescription
1A COM
D COM
OUT ON/OFF
CONT
EXT -V CV
CONT
EXT -V CC
CONT
EXT -R CV
CONT
EXT -R CC
CONT
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
VMON
IMON
SHUT DO
SER IN+
PRL IN+
SER IN-
PRL IN
[COMP IN]
NEXT PRL
OUT+
NEXT PRL
OUT-
[NEXT COMP
OUT]
ST
ATUS COM
CV ST
CC ST
ALM ST
OUT ON
ST
ATUS
PWR OFF
ST
ATUS
SER OUT+
Connected to the ne gative electrode (-S) of the sensing input when remote
sensing is used; connected to - (neg.) output when remote sensing is not used.
Connected to the ne gative electrode (-S) of the sensing input when remote
sensing is used; connected to - (neg.) output when remote sensing is not used.
OUTPUT ON/OFF
urns off when a low (or high) TTL level signal is applied. The internal cir-
cuit is pulled up to + 5 V through 10 k Ω .
External v oltage control of the output voltage
(0 % to 100 % of the rated output voltage in the range of 0 V to 10 V)
External v oltage control of the output current
(0 % to 100 % of the rated output current in the range of 0 V to 10 V)
External resistance control of the output v oltage
(1) 0 % to 100 % of the rated output voltage in the range of 0 k Ω to 10 k Ω or
(2) 100 % to 0 % of the rated output voltage in the range of 0 k
External resistance control of the output current
(1) 0 % to 100 % of the rated output current in the range of 0 k Ω to 10 kΩ or
(2) 100 % to 0 % of the rated output current in the range of 0 k
Output v
oltage monitor
(Outputs the 0 % to 100 % range of the rated voltage using 0 V to 10 V)
Output current monitor
(Outputs the 0 % to 100 % range of the rated current using 0
Shutdo
WN
*1
*1
ATUS
ATUS
ATUS
wn
Turns OUTPUT or POWER switch off when a low TTL level signal is
applied. The internal circuit is pulled up to + 5 V through 10 k
Positi
ve electrode input terminal during master-slave series operation.
Positi
ve electrode input terminal during master-slave parallel operation.
Ne
gative electrode input terminal during master-slave series operation.
Ne
gative electrode input terminal during master-slave parallel operation.
[Compensation signal input terminal during master-slave parallel operation]
Positi
ve electrode output terminal to the next device during master-slave par-
allel operation.
Ne
gative electrode output terminal to the next device during master-slave
parallel operation.
[Compensation signal output terminal to the next device during master-slave
parallel operation]
Common for status signals from pin 18 through 22.
T
urns ON during CV operation (open collector output by a photocoupler)
T
urns ON during CC operation. (open collector output by a photocoupler)
T
urns on when OVP, OCP, or OHP is activated or when a shutdown signal is
input.,(open collector output by a photocoupler, held for approx. 0.5 s when
the POWER switch is turned off)
T
urns on when OUTPUT is turned on.
(open collector output by a photocoupler)
T
urns on when the internal sub power supply is activated with the POWER
switch turned off. (open collector output by a photocoupler, held for approx.
*2
0.5 s)
Positi
ve electrode output terminal during master-slave series operation.
*2
*2
T
V to 10 V)
Ω
to 10 k Ω
Ω
to 10 kΩ
2
.
3
T
4
5
6
Ω
7
*2
*2
PAS SERIES
Remote Control 4-3
Pin No
. Signal NameDescription
24PRL OUT+
25
SER OUT-Ne
PRL OUT
[COMP OUT]
26
*1.Items inside brackets are for the 160 V, 320 V, and 500 V models.
*2.Open collector output (maximum voltage of 30 V and maximum current of 8 mA).
*1
It is insulated from the control circuit.
Positi
ve electrode output terminal during master-slave parallel operation.
gative electrode output terminal during master-slave series operation.
-
Negative electrode output terminal during master-slave parallel operation.
[Compensation signal output terminal during master-slave parallel operation]
4-4 Remote Control
PAS SERIES
4.1.2Controlling the Output Voltage Using External
Voltage
This method is used to control the output voltage using an external
voltage (Vext) in the range 0 V to approx. 10 V.
To control the output voltage using external voltage, you must set CV
control of CONFIG settings to "1." For details on CONFIG settings,
see "3.2.4 Unit Configuration (CONFIG)".
Press the SET switch to check the preset voltage.
WARNING
• The insulation of the external voltage source (Vext)
and the cable connecting it should be greater than
the isolation voltage of the unit. For details on the isolation voltage of each model, see Chapter8 "Specifi-
cations".
In addition, leave the output of the external voltage
source (Vext) floating. For details, see "2.5 Grounding
the Output Terminal".
• When using shielded wires for connection, protect the
uncovered section of the shielded wire by using insulation tubes with a withstand voltage greater than the
isolation voltage of the unit.
The output voltage (Eo) varies in the range of 0 to rated output voltage by setting the external voltage (Vext) in the range of 0 V to 10 V.
Eo = Ertg•Vext /10 [V]Vext = 10•Eo /Ertg [V]
Ertg: Rated output voltage [V]
For a portion of the 10 V, 20 V, 40 V, 60 V, and 80 V models, the products may be manufactured under the following specifications. See
also Chapter8 "Specifications".
The output voltage (Eo) varies in the range of 0 to rated output voltage by setting the
external voltage (Vext) in the range of approx. 0 V [0.5 V] to 10 V [9.5 V]. (The value
inside brackets is the design value.)
Eo = Ertg•(Vext-0.5) /9 [V]Vext = (Eo /Ertg•9) +0.5 [V]
0.5 ≤ Vext ≤ 9.5 [V]
Ertg: Rated output voltage [V]
PAS SERIESRemote Control 4-5
CAUTION
• Make sure the polarity of Vext is correct. Otherwise,
damage to the unit may result.
• Do not apply voltage or reverse voltage exceeding
10.5 V across the external voltage control pins. Otherwise, damage to the unit may result.
NOTE
• The input impedance across the external voltage control pins
is approximately 30 kΩ.
• Use a low-noise and stable voltage source for Vext. The noise
in Vext is multiplied by the amplification factor of the unit
and appears at the unit's output. Thus, the output ripple noise
may not meet the unit's specifications.
• To minimize the influence of noise on the output, use a 2-
core shielded wire or a twisted-pair wire to connect the control terminals and Vext. Make the wires as short as possible.
Susceptibility to the effects of noise increases as the wires
get longer. When wires are long, proper operation may be
hindered even if a cable with anti-noise measures is used.
When using a shielded cable, connect the shield to the -
(neg.) output terminal. If the shield needs to be connected to
the Vext side, see next page " Connecting the Shield to the
Vext Side".
■
External voltage source (Vext) connection
Pins 1 and 4 of the J1 connector are used.
2-core shielded or
twisted-pair wire
125
J1
24
Vext
+
–
13
1426
Fig.4-1 Connection of the output voltage control using
external voltage
4-6 Remote ControlPAS SERIES
Connecting the Shield to the Vext Side
•
CAUTION
When using shielded wires, some external voltage sources may
require that the shield be connected to the external voltage source
(Vext). In such case, the grounding method used for Vext and the unit
creates a condition in which the output is short-circuited, as shown in
Fig.4-2. Thus, do not connect the shield to the - (neg.) output terminal
of the unit.
If you are connecting the shield to the Vext side when
using external voltage control, do not connect the
shield to the - (neg.) output terminal of the unit.
WARNING
VextPAS
+
–
•
2-core shielded wire
+
–
Output is short-circuited
by the shield, causing
current to flow.
+
Ground the
+ (pos.)
output terminal.
–
Fig.4-2A connection in which the output is short-cir-
cuited by the shield
Leave the output of the external voltage source (Vext)floating. The potential of the J1 connector is nearly
equal to the - (neg.) output terminal, and short-circuit
current flows to the signal line even without the
shield.
PAS SERIES
Remote Control 4-7
4.1.3 Controlling the Output Voltage Using External
Resistance
This method is used to control the output v oltage using an e xternal
resistance (Re xt) in the range 0 k Ω to approx. 10 k Ω .
WARNING
ou can select the following two types of modes through CONFIG
settings. For details on CONFIG settings, see "3.2.4 Unit Configura-
tion (CONFIG)".
Press the SET switch to check the preset voltage.
10 k Ω
10 k Ω
The insulation of the external resistor (Rext) and the
cable connecting it should be greater than the isolation voltage of the unit. For details on the isolation
voltage of each model, see Chapter8 "Specifica-
tions".
• When using shielded wires for connection, protect the
uncovered section of the shielded wire by using insulation tubes with a withstand voltage greater than the
isolation v oltage of the unit.
MAX OUT CV mode
v
k Ω
Re
→
The output v oltage (Eo) v aries in the range of 0 to rated output
oltage by setting the e xternal resistance (Re xt) in the range of 0
to 10 k Ω .
Eo = Er tg•Re xt /10 [V]
tg: Rated output voltage [V]
0 OUT CV mode (FAIL SAFE)
→
The output v oltage (Eo) v aries in the range of rated output v oltage
to 0 by setting the e xternal resistance (Re xt) in the range of 0 k Ω
to 10 k Ω .
Eo =Er tg•(10-Re xt)/10 [V]
tg: Rated output voltage [V]
Er
•
Y
xt = 10•Eo /Er tg [V]
Re
Er
xt = 10•(Er tg-Eo)/Er tg [V]
4-8 Remote Control
PAS SERIES
or a portion of the 10 V, 20 V, 40 V, 60 V, and 80 V models, the prod-
ucts may be manufactured under the following specifications. See
also Chapter8 "Specifications".
→
k Ω
Re
10 k Ω
10 k Ω
CAUTION
MAX OUT CV mode
The output v oltage (Eo) v aries in the range of 0 to rated output v oltage by setting
the e xternal resistance (Re xt) in the range of approx. 0 k Ω [0.5 k Ω ] to 10 k Ω [9.5
]. (The v alue inside brack ets is the design v alue.)
Eo = Ertg•(Re xt-500)/9000 [V]
500 ≤ Rext ≤ 9500 [ Ω ]
Ertg: Rated output voltage [V]
→
0 OUT CV mode (FAIL SAFE)
The output v oltage (Eo) v aries in the range of rated output v oltage to 0 by setting
the e xternal resistance (Re xt) in the range of approx. 0 k Ω [0.5 k Ω ] to 10 k Ω [9.5
]. (The v alue inside brack ets is the design v alue.)
Eo =Ertg •(9500-Re xt)/9000 [V]
500 ≤ Rext ≤ 9500 [ Ω ]
Ertg: Rated output voltage [V]
k Ω
•
If Rext comes loose when using the 10 k Ω
xt = (Eo/Ertg•9000)+500 [ Ω ]
Re
xt = 9500-(Eo/Ertg•9000) [ Ω ]
MAX
Ω
→
OUT CV mode, excessive voltage may be applied to
the load. For your safety, it is recommended that fail-
•
•
safe 10 k
→
0 OUT CV mode be used.
• If you are using fixed resistors for Rext and controlling
the output voltage by switching through them, use a
short-circuit or continuous type switch.
NOTE
PAS SERIES
For Rext, use a 1/2 W or larger metal film or wire-wound
resistor with good temperature coefficient and small aging
effect.
F
To minimize the influence of noise on the output, use a 2core shielded wire or a twisted-pair wire to connect the control terminals and Rext. Make the wires as short as possible.
Susceptibility to the effects of noise increases as the wires
get longer. When wires are long, proper operation may be
hindered even if a cable with anti-noise measures is used.
When using a shielded cable, connect the shield to the -
(neg.) output terminal.
Remote Control 4-9
External resistor (Rext) connection
■
Pins 1 and 6 of the J1 connector are used.
2-core shielded or
twisted-pair wire
13
Rext
1426
125
J1
26
Fig.4-3 Connection of the output voltage control using
external resistance
4-10 Remote Control
PAS SERIES
4.1.4
Controlling the output current using external voltage
v
T
•
V e
Ir
F
e
This method is used to control the output current using an e xternal
oltage (V e xt) in the range 0 V to approx. 10 V .
o control the output current using e xternal v oltage, you must set CC
control of CONFIG settings to "1." F or details on CONFIG settings,
see "3.2.4 Unit Confi guration (CONFIG) " .
Press the SET switch to check the preset current.
V e
WARNING
The insulation of the external voltage source (Vext)
and the cable connecting it should be greater than
the isolation voltage of the unit. For details on the isolation voltage of each model, see Chapter8 "Specifi-
cations".
In addition, leave the output of the external voltage
source (Vext) floating. For details, see "2.5 Grounding
the Output Terminal".
• When using shielded wires for connection, protect the
uncovered section of the shielded wire by using insulation tubes with a withstand voltage greater than the
isolation v oltage of the unit.
The output current (Io) v aries in the range of 0 to rated output current
by setting the e xternal v oltage (V e xt) in the range of 0 V to 10 V .
Io = Ir tg•V e xt /10 [A]
xt = 10•Io /Ir tg [V]
tg: Rated output current [A]
or a portion of the 10 V , 20 V , 40 V , 60 V , and 80 V models, the prod ucts may be manuf actured under the follo wing specifi cations. See
also Chapter8 " Specifi cations " .
The output current (Io) v aries in the range of 0 to rated output current by setting the
xternal v oltage (V e xt) in the range of approx. 0 V [0.5 V] to 10 V [9.5 V]. (The v alue
inside brack ets is the design v alue.)
Io =Irtg •(V e xt-0.5)/9 [A]
0.5 ≤ Vext ≤ 9.5 [V]
Irtg: Rated output current [A]
xt = (Io/Irtg•9)+0.5 [V]
CAUTION
PAS SERIES
•
Mak e sure the polarity of Vext is correct. Otherwise,
damage to the unit may result.
Remote Control 4-11
If Vext comes loose, erroneous operation may result
•
•
•
due to external noise. Securely connect the wires to
the J1 connector.
• Do not apply voltage or reverse voltage exceeding
10.5 V across the external voltage control pins. Otherwise , damage to the unit may result.
NOTE
The input impedance across the external voltage control pins
is approximately 30 k Ω .
• Use a low-noise and stable voltage source for Vext. The noise
in Vext is multiplied by the amplification factor of the unit
and appears at the unit's output. Thus, the output ripple noise
may not meet the unit's specifications.
To minimize the influence of noise on the output, use a 2-core
shielded wire or a twisted-pair wire to connect the control terminals and Vext. Make the wires as short as possible.
Susceptibility to the effects of noise increases as the wires get
longer. When wires are long, proper operation may be hindered even if a cable with anti-noise measures is used.
When using a shielded cable, connect the shield to the - (neg.)
output terminal. If the shield needs to be connected to the Vext
side, see next page " Connecting the Shield to the Vext Side".
■
External voltage source (Vext) connection
Pins 1 and 5 of the J1 connector are used.
2-core shielded or
twisted-pair wire
Vext
Fig.4-4 Connection of the output current control using
4-12 Remote Control
+
–
external voltage
13
1525
J1
1426
2
PAS SERIES
Connecting the Shield to the Vext Side
•
CAUTION
When using shielded wires, some external voltage sources may
require that the shield be connected to the external voltage source
(Vext). In such case, the grounding method used for Vext and the unit
creates a condition in which the output is short-circuited, as shown in
Fig.4-5. Thus, do not connect the shield to the - (neg.) output terminal
of the unit.
If you are connecting the shield to the Vext side when
using external voltage control, do not connect the
shield to the - (neg.) output terminal of the unit.
WARNING
VextPAS
+
–
•
2-core shielded wire
+
–
Output is short-circuited
by the shield, causing
current to flow.
+
Ground the
+ (pos.)
output terminal.
–
Fig.4-5A connection in which the output is short-cir-
cuited by the shield
Leave the output of the external voltage source (Vext)floating. The potential of the J1 connector is nearly
equal to the - (neg.) output terminal, and short-circuit
current flows to the signal line even without the
shield.
PAS SERIES
Remote Control 4-13
4.1.5 Controlling the Output Current Using External
Resistance
This method is used to control the output current using an e xternal
resistance (Re xt) in the range 0 k Ω to approx. 10 k Ω .
Press the SET switch to check the preset current.
WARNING
ou can select the following two types of modes through CONFIG
settings. For details on CONFIG settings, see "3.2.4 Unit Configura-
tion (CONFIG)".
10 k Ω
10 k Ω
The insulation of the external resistor (Rext) and the
cable connecting it should be greater than the isolation voltage of the unit. For details on the isolation
voltage of each model, see Chapter8 "Specifica-
tions".
• When using shielded wires for connection, protect the
uncovered section of the shielded wire by using insulation tubes with a withstand voltage greater than the
isolation v oltage of the unit.
MAX OUT CC mode
Re
→
The output current (Io) v aries in the range of 0 to rated output cur rent by setting the e xternal resistance (Re xt) in the range of 0 k Ω
to 10 k Ω .
Io = Ir tg•Re xt /10 [A]
tg: Rated output current [A]
0 OUT CC mode (FAIL SAFE)
→
The output current (Io) v aries in the range of rated output current
to 0 by setting the e xternal resistance (Re xt) in the range of 0 k Ω
to 10 k Ω .
Io = Ir tg•(10-Re xt)/10 [A]
tg: Rated output current [A]
Ir
•
Y
xt = 10•Io /Ir tg [A]
Re
Ir
xt = 10•(Ir tg-Io)/Ir tg [A]
4-14 Remote Control
PAS SERIES
or a portion of the 10 V, 20 V, 40 V, 60 V, and 80 V models, the prod-
ucts may be manufactured under the following specifications. See
also Chapter8 "Specifications".
→
k Ω
Re
10 k Ω
10 k Ω
CAUTION
MAX OUT CC mode
The output current (Io) v aries in the range of 0 to rated output current by setting
the e xternal resistance (Re xt) in the range of approx. 0 k Ω [0.5 k Ω ] to 10 k Ω [9.5
]. (The v alue inside brack ets is the design v alue.)
Io = Irtg•(Re xt-500)/9000 [A]
500 ≤ Rext ≤ 9500 [ Ω ]
Irtg: Rated output current [A]
→
k Ω
0 OUT CC mode (FAIL SAFE)
The output current (Io) v aries in the range of rated output current to 0 by setting
the e xternal resistance (Re xt) in the range of approx. 0 k Ω [0.5 k Ω ] to 10 k Ω [9.5
]. (The v alue inside brack ets is the design v alue.)
Io =Irtg• (9500-Re xt) /9000 [A]
500 ≤ Rext ≤ 9500 [ Ω ]
Irtg: Rated output current [A]
•
If Rext comes loose when using the 10 k Ω
xt = (Io/Irtg•9000)+500 [ Ω ]
Re
xt = 9500-(Io/Irtg•9000) [ Ω ]
MAX
Ω
→
OUT CC mode, excessive current may flow through
the load. For your safety, it is recommended that fail-
•
safe 10 k
→
0 OUT CC mode be used.
• If you are using fixed resistors for Rext and controlling
the output voltage by switching through them, use a
short-circuit or continuous type switch.
NOTE
PAS SERIES
• F or Rext, use a 1/2 W or larger metal film or wire-wound
resistor with good temperature coefficient and small aging
effect.
F
To minimize the influence of noise on the output, use a 2core shielded wire or a twisted-pair wire to connect the control terminals and Rext. Make the wires as short as possible.
Susceptibility to the effects of noise increases as the wires
get longer. When wires are long, proper operation may be
hindered even if a cable with anti-noise measures is used.
When using a shielded cable, connect the shield to the -
(neg.) output terminal.
Remote Control 4-15
External resistor (Rext) connection
■
Pins 1 and 7 of the J1 connector are used.
2-core shielded or
twisted-pair wire
13
Rext
1426
1725
J1
2
Fig.4-6 Connection of the output current control using
external resistance
4-16 Remote Control
PAS SERIES
4.1.6 Controlling the Output ON/OFF Using External
Y
LO
Contact
This method is used to control the output on/of f status using e xternal
contacts.
ou can select the follo wing tw o types of modes through CONFIG
settings. F or details on CONFIG settings, see "3.2.4 Unit Confi gura tion (CONFIG) " .
W=ON mode
OUTPUT turns on when pin 3 of the J1 connector is set lo w (TTL le v el).
HIGH=ON mode
OUTPUT turns on when pin 3 of the J1 connector is set high (open).
When the e xternal contact is in the OUTPUT ON condition, the
OUTPUT switch on the front panel is valid.
If you wish to turn on the output using external contact after you have
turned off the output using the OUTPUT switch on the front panel,
set the external contact to the OUTPUT OFF condition once and then
set it to the OUTPUT ON condition again. When the external contact
is in the OUTPUT OFF condition, the OUTPUT switch on the front
panel is invalid.
■
e
T
•
ON/OFF control connection
Pins 2 and 3 of the J1 connector are used.
Use parts with a contact rating of 5 VDC and 10 mA or more for the
xternal contact.
o minimize the infl uence of noise on the output, use a 2-core
shielded wire or a twisted-pair wire to connect the control terminals
and the e xternal contact. Mak e the wires as short as possible. Suscep tibility to the ef fects of noise increases as the wires get longer . When
wires are long, proper operation may be hindered e v en if a cable with
anti-noise measures is used.
When using a shielded cable, connect the shield to the - (ne g.) output
terminal.
NOTE
PAS SERIES
If multiple units are used under floating conditions and a single external contact is used to turn on/off the output, ground
the negative outputside of each power supply unit. Or, use
relays or similar devices for the external contact signal to isolate the signal fl owing through each unit.
Remote Control 4-17
WARNING
The insulation of the external contact (S) and the
cable connecting it should be greater than the isolation voltage of the unit. For details on the isolation
voltage of each model, see Chapter8 "Specifica-
tions".
•
When using shielded wires for connection, protect the
uncovered section of the shielded wire by using insulation tubes with a withstand voltage greater than the
isolation voltage of the unit.
NOTE
The release voltage across pins 3 and 2 is approx. 5 V ± 5 %
maximum, and the short circuit current is approx. 500 μA ± 5
% maximum.
(The internal circuit is pulled up to 5 V through 10 kΩ.)
When wiring over a great distance, use a small relay and
extend the coil side of that relay.
2-core shielded or
twisted-pair wire
S
•
•
•
13
1325
J1
1426
For long-distance wiring
2
S
Extend
this line.
Fig.4-7ON/OFF control connection
4-18Remote Control
Relay
PAS SERIES
4.1.7 Controlling the Output Shutdown Using External Contact
This method is used to control the output shutdo wn using e xternal
contacts.
ou can select the follo wing tw o types of modes through CONFIG
settings. F or details on CONFIG settings, see "3.2.4 Unit Confi gura tion (CONFIG)".
When PO WER switch trip setting is enabled
The PO WER switch trips when pin 10 of the J1 connector is set
w (TTL le v el).
o reco v er , set pin 10 high (or release) and turn on the PO WER
switch.
When PO WER switch trip setting is disabled
The OUTPUT turns of f when pin 10 of the J1 connector is set lo w
(TTL le v el). (The PO WER switch is not tripped.)
o reco v er , set pin 10 high (or release), turn of f on the PO WER
switch, and turn it back on.
Y
lo
T
Shutdown control connection
■
e
T
Pins 2 and 10 of the J1 connector are used.
Use parts with a contact rating of 5 VDC and 10 mA or more for the
xternal contact.
o minimize the infl uence of noise on the output, use a 2-core
shielded wire or a twisted-pair wire to connect the control terminals
and the e xternal contact. Mak e the wires as short as possible. Suscep tibility to the ef fects of noise increases as the wires get longer . When
wires are long, proper operation may be hindered e v en if a cable with
anti-noise measures is used.
When using a shielded cable, connect the shield to the - (ne g.) output
terminal.
T
PAS SERIES
Remote Control 4-19
WARNING
The insulation of the external contact (S) and the
cable connecting it should be greater than the isolation voltage of the unit. For details on the isolation
voltage of each model, see Chapter8 "Specifica-
tions".
• When using shielded wires for connection, protect the
uncovered section of the shielded wire by using insulation tubes with a withstand voltage greater than the
isolation voltage of the unit.
NOTE
The release voltage across pins 10 and 2 is approx. 5 V ± 5 %
maximum, and the short circuit current is approx. 500 μA ± 5
% maximum.
(The internal circuit is pulled up to 5 V through 10 kΩ.)
• When wiring over a great distance, use a small relay and
xtend the coil side of that relay.
2-core shielded or
twisted-pair wire
•
•
e
S
125
J1
210131426
For long-distance wiring
S
Extend
this line.
Fig.4-8Shutdown control connection
4-20Remote Control
Relay
PAS SERIES
4.2 Remote Monitoring
4.2.1 External Monitoring of the Output Voltage and
Output Current
The J1 connector consists of monitor outputs for output v oltage and
output current.
able 4-3 Monitor output of output voltage and output
current
Pin No .Signal NameDescription
A COM Common for remote control input and output monitor
V MON
I MON
Monitor output of output v oltage
0 to approx. 10 V for 0 to rated output v oltage
Monitor output of output current
0 to approx. 10 V for 0 to rated output current
WARNING
NOTE
PAS SERIES
Shorting V MON and I MON to A COM can cause
damage to the unit.
Monitor output rating
T
•
•
•
1
8
9
Output impedance: 1 k Ω or less
Maximum output current: Approx. 10 mA
The monitor outputs are used to monitor the DC voltage
(mean value). They cannot be used to accurately monitor the
AC components (ripple, transient response, etc.) of the actual
output voltage or current.
Remote Control 4-21
4.2.2 External Monitoring of the Operation Mode
The J1 connector consists of status outputs that can be used to e xter nally monitor the operating condition of the unit. The status outputs
consist of the follo wing fi v e items.
The outputs are open collector outputs of photocouplers; the y are
insulated from the internal circuits of the unit.
able 4-4 Status output
Pin No . Signal NameDescriptionCircuit
ATUS
COM
18CV STATUS
19CC STATUS
20
21
22
ALM
STATUS
OUTON
STATUS
PWR OFF
STATUS
Common for status output
Photocoupler emitter output
Set to low level when in constant voltage
mode.
Photocoupler collector output
Set to low level when in constant current
mode.
Photocoupler collector output
Set to low level when a protection function is activated.
Photocoupler collector output
Set to low level when OUTPUT is turned
off.
Photocoupler collector output
Output a low level signal for approximately 0.5 s when the POWER switch
turned off.
Photocoupler collector output
17
18
19
20
21
22
T
•
17 ST
NOTE
Maximum rating of each signal terminal
Maximum applied voltage (to a single pin) of 30 V and maximum current of 8 mA
4-22 Remote Control
PAS SERIES
4.3
Digital Remote Control
In addition to operating the P
po
wer supply controller (PIA4830/PIA4850/PIA4810) to remotely
NOTE
4.3.1
control the P
Connecting of the Power Supply Controller and
AS via the USB, GPIB or RS232C interf
•
Version 2.10 or later is required for the PIA4800 series. If you
are using an earlier version, you need to upgrade. For details,
contact your Kikusui agent/distributor.
You can confirm a version of the PIA4800 series through the
IDN?.
AS from the front panel, you can use a
Device messages
The P
AS and po
Up to 32 de
T
o digital remotoly contorol the unit, You must set CV control and
CC control of CONFIG settings to “0” (panel control).
F
or details on CONFIG Setting, See
FIG)
"
F
or connection to a Po
refer to the “Connecting & Programming Guide” [inde
CD-R
OM that came with the PIA4800 series.
The “Connecting & Programming Guide” is HTML format.
HTML manual can be vie
Operating en
Bro
wser: Microsoft Internet Explorer 5.5 or later
The list of messages and connection of po
& Programming guide is pro
later is required to vie
The latest v
downloaded from Web site (http://www.kikusui.co.jp/en/download/).
wer supply controller are connected via a
vices can be connected to the
wer Supply Controller and de
wed using the follo
vironment: Windo
vided in a PDF fi
w the fi
le.
ersion of the “Connecting & Programming Guide” can be
TP-B
"3.2.4
Unit Confi
wing bro
ws 98 or later
wer supply of Connecting
le.
US.
Adobe Reader 6.0 or
ace.
TP-B
US.
guration (CON
vice messages,
x.html] in the
The
wsers.
-
PAS SERIES
Remote Control 4-23
4-24 Remote ControlPAS SERIES
Chapter. 5Parallel and Series Operation
The output voltage can be increased by connecting PAS series power
supplies with the same output rating in series and operating them in
master-slave series mode. Additionally, the output current can be
increased by connecting PAS series power supplies with the same
output rating in parallel and operating them in master-slave parallel
mode.
In a master-slave system, one of the connected units is made a master
and all others slaves. The master is used to control the all the connected power supply units.
The maximum number of connectable units including master and
slave devices varies depending on the model as follows.
Table 5-1 The maximum number of connectable units
Series modeParallel mode
350W type2 units5 units
700W type2 units3 units
1000W type2 units2 units
WARNING
• Master-slave series operation is not possible on the
320 V and 500 V models. If connected in series, the
output voltage will exceed the isolation voltage creating a dangerous condition.
NOTE
• During series/parallel operation, the accuracy of master and
slave units is the same as that of single units. However the
error in preset values between master and slave units is
within approx. 3 %.
PAS SERIESParallel and Series Operation 5-1
5.1Master-Slave Series Operation
CV
OUTPUT
OFF
ALM
V/
W
A/
W
CC
ON
CV
OUTPUT
OFF
ALM
V/
W
A/
W
CC
ON
WARNING
• Master-slave series operation is not possible on the
320 V and 500 V models. If connected in series, the
output voltage will exceed the isolation voltage creating a dangerous condition.
5.1.1Functions during Master-Slave Series Operation
The functions of the unit during master-slave series operation are
described below.
Voltage display and current display
As shown in Fig.5-1, the current is displayed only on the master unit,
and the voltage is displayed on each unit. For the total output voltage,
sum the voltages of the master and slave units.
CV
CC
ON
OUTPUT
OFF
V/
ALM
CV
CC
ON
OUTPUT
OFF
V/
ALM
A/
Master unitSlave unit
Fig.5-1 Panel display during series operation
NOTE
Remote sensing
5-2 Parallel and Series OperationPAS SERIES
• The power display can be switched only on the master unit.
However, the power of the entire system cannot be displayed.
Remote sensing function cannot be used during master-slave series
operation.
A/
Analog remote control
Analog remote control can be performed only against the master unit.
For details on the analog remote control, see "4.1 Analog Remote
Control".
For details, see "4.1 Analog Remote Control".
Remote monitoring
External monitoring of output voltage (V MON)
The output voltage of each master and slave unit can be monitored.
For the total output voltage, sum the monitor values of the master and
slave units.
External monitoring of output current (I MON)
The output current can be monitored only on the master unit.
Status monitors
Status of the constant voltage operation (CV STATUS), constant current operation (CC STATUS), OUTPUT ON, and POWER switch ON
can be monitored on each master and slave unit.
For details on ALM STATUS, see the next section, "Alarms"
For details on the remote monitoring, see "4.2 Remote Monitoring".
Alarms
Below is the operation of the units when alarms are activated through
OVP (overvoltage protection), OCP (overcurrent protection), and
OHP (overheat protection).
Slave unit
An alarm is activated independently, and OUTPUT or POWER
switch is turned off.
Master unit
By connecting ALM STATUS of the master unit and SHUT DOWN
of the slave units as shown in Fig.5-2, the OUTPUT or POWER
switch of the entire system can be turned off when an alarm on the
master unit is activated.
PAS SERIESParallel and Series Operation 5-3
5.1.2J1 Connector Connection (Series Operation)
For master-slave series operation, two units are connected as shown
in Fig.5-2.
The maximum output voltage during master-slave series operation is
twice the rated output voltage of a single unit.
Connecting the signal wires (series operation)
The connector needed to connect the J1 connector is not provided.
For detail, see "4.1.1 About the J1 Connector" .
WARNING
• The J1 connector contains pins that are at the same
electric potential as the output terminal. If you are not
using the J1 connector, to prevent the possibility of
electric shock, be sure to insert the protective socket
provided.
• To prevent the possibility of electric shock, be sure to
use the protective cover on the sockets.
Connection procedure
Decide the po w er supply that is to be the master unit.
1.
Connect the J1 connectors on the rear panel as sho wn in
11 SER IN+
13 SER IN−
10 SHUT DOWN
2 D COM
3 OUT ON/OFF CON
102
Slaveunit
Fig.5-2 Connection for series operation
1313 11
J1
5-4 Parallel and Series OperationPAS SERIES
5.1.3 Load Connection for Series Operation
WARNING
When you are done with the connection, be sure to
attach the output terminal cover to prevent the possibility of electric shock.
• Securely connect the protective conductor terminal of
the unit.
•
CAUTION
ake measures to securely connect the load cable to
the ter minals such as by using crimp terminals.
Connection procedure
1.
Chec k that the PO WER s witch is off on all po w er supply
units to be connected in ser ies .
Remo v e the output ter minal co v er .
2.
Connect the load cab le and chassis cab le as sho wn in
W
3.
Fig.5-3 .
Connect one of either the - (ne g.) terminal or the + (pos.) terminal
of the master or sla v e unit to the chassis terminal.
ire the load cables connecting the po wer supply units as thick
and as short as possible. If the v oltage drop in the output cable is
lar ge, the dif ference in potential between po wer supply units and
load fl uctuations becomes lar ge.
•
T
Refer to "3.3 Connecting the Load" and select a load cable with
suf fi cient current capacity .
4.
Attach the output ter minal co v er .
PAS SERIES
Load
Thick and short
Slave unitMaster unit
Fig.5-3 Load Connection for Series Operation
(Example in which the - (neg.) terminal of the
master unit is connected to the chassis terminal)
Parallel and Series Operation 5-5
5.1.4Master-Slave Series Operation Setup
CV
OUTPU T
OFF
ALM
V/
W
A/
W
CC
ON
o perform master-slave series operation, the master and slave units
as well as various protection functions must be set up.
Setting the master and slave units
Set the master and slave units through CONFIG settings.
NOTE
Set the slave units through CONFIG settings after setting the
VP trip point.
For details on CONFIG settings, see "3.2.4 Unit Configuration
(CONFIG)".
1.
W h i l e p r e s s i n g t h e C O N F I G s w i t c h , t u r n o n t h e P O W E R s w i t c h .
After displaying the v ersion, the CONFIG switch lights up (CON FIG setting mode).
Press the CURRENT s witch to mo v e to the left-most digit on
2.
the current displa y .
po w
3.
Use the dial to set as f ollo ws according to the roles of each
Y
er supply unit.
Master unit : 0
Slave unit: 2
CV
CC
ON
OUTPUT
OFF
V/
T
•
O
ALM
Fig.5-4 Setup example of a slave unit for series opera-
tion
ou can check the settings by pressing the CONFIG switch. The
5-6Parallel and Series Operation
external remote control settings are forced to local when units are set
to slave mode.
A/
PAS SERIES
VP (overvoltage protection) setting
VP (o v erv oltage protection) is set on both master and sla v e units
according to "3.2.2 Setting the O VP (Ov erv oltage Protection) T rip
Point" .
VP is set to 1/2 the v oltage to be protected on each unit.
, set the O VP trip point of the sla v e unit slightly higher than
that of the master unit, so that the O VP function of the master unit is
acti v ated fi rst. Set the trip point before specifying units to operate in
sla v e mode through CONFIG settings.
OCP (o vercurrent protection) setting
OCP (o v ercurrent protection) is set on both master and sla v e units
according to "3.2.3 Setting the OCP (Ov ercurrent Protection) T rip
Point" .
Set the OCP trip point of the sla v e unit slightly higher than that of the
master unit, so that the OCP function of the master unit is acti v ated
rst.
O
O
O
Ho we v er
fi
5.1.5 Master-Slave Series Operation Procedure
•
NOTE
When turning on the POWER switch, be sure to turn on the
master unit first.
When turning off the POWER switch, be sure to turn on the
slave units first.
• If you don’t keep the procedure, erroneous operation may
result.
The switches on the slave units are disabled. OUTPUT on/off operation is performed on the master unit.
When you are done with the steps described in "5.1.4 Master-Slave
Series Operation Setup" normal operations are performed on the master unit.
PAS SERIES
Parallel and Series Operation 5-7
5.2 Master-Slave Parallel Operation
CV
OUTPUT
OFF
ALM
V/
W
A/
W
CC
ON
CV
OUTPUT
OFF
ALM
V/
W
A/
W
CC
ON
5.2.1 Functions during Master-Slave Parallel Operation
The functions of the unit during master -sla v e parallel operation are
described belo w .
oltage display and current display
As sho wn in Fig.5-5 , the v oltage is displayed only on the master unit,
and the current is displayed on each unit. For the total output current,
sum the currents of the master and slave units.
CV
CC
Master unitSlave unit
Fig.5-5
NOTE
•
The power display can be switched only on the master unit.
Ho
Remote sensing
Remote sensing function can be used only on the master unit.
F
or details, see
Analog remote control
Analog remote control can be performed only ag
F
or details, see
ON
OUTPUT
OFF
V/
ALM
CV
CC
ON
OUTPUT
OFF
A/
Panel display during parallel operation
wever, the power of the entire system cannot be displayed.
"3.6 Remote Sensing"
"4.1
Analog Remote Control"
.
ainst the master unit.
.
V/
ALM
A/
V
5-8 Parallel and Series Operation
PAS SERIES
Remote monitor
Exter
nal monitoring of output voltage (V MON)
The output v
Exter
nal monitoring of output current (I MON)
The output current of each master and slave unit can be monitored.
F
or the total output current, sum the monitor v
slave units.
Status monitors
Status of the constant v
rent operation (CC STATUS), OUTPUT ON, and PO
can be monitored on each master and slave unit. However, slave units
always output the status of the constant current operation.
F
or details on
For details on the remote monitoring, see "4.2 Remote Monitoring".
ing
oltage can be monitored only on the master unit.
alues of the master and
oltage operation (CV STATUS), constant cur
WER switch ON
ALM STATUS, see the next section, "Alarms".
-
Alarms
Below is the operation of the units when alarms are activated through
OVP (overvoltage protection), OCP (overcurrent protection), and
OHP (overheat protection).
Slave unit
An alarm is activated independently, and OUTPUT or POWER
switch is turned off.
Master unit
By connecting ALM STATUS of the master unit and SHUT DOWN
of the slave units as shown in Fig.5-6, the OUTPUT or POWER
switch of the entire system can be turned off when an alarm on the
master unit is activated.
PAS SERIES
Parallel and Series Operation 5-9
5.2.2J1 Connector Connection (Parallel Operation)
For master-slave parallel operation, two units are connected as shown
in Fig.5-6.
The maximum output current during master-slave parallel operation
is equal to the number of units connected in parallel multiplied by the
rated output current of a single unit.
Connecting the signal wires (parallel operation)
The connector needed to connect the J1 connector is not provided.
For detail, see "4.1.1 About the J1 Connector" .
WARNING
Connection procedure
1.
2.
• The J1 connector contains pins that are at the same
electric potential as the output terminal. If you are not
using the J1 connector, to prevent the possibility of
electric shock, be sure to insert the protective socket
provided.
• To prevent the possibility of electric shock, be sure to
use the protective cover on the sockets.
Decide the po w er supply that is to be the master unit.
Connect the J1 connectors on the rear panel as sho wn in
Fig.5-6 .
When connecting more than tw o sla v e units, repeat the steps for
connecting sla v e units 1 and 2.
5-10 Parallel and Series OperationPAS SERIES
Master unit
21
17
Slave unit1
1717
13
Slave unit2
13
20
26 24
Master unit
PRL OUT + 24
PRL OUT
[PRL COMP OUT]
STATUS COM 17
ALM STATUS 20
OUTON STATUS 21
D COM 2
– 26
2
J1
12 PRL IN
14 PRL IN –
[PRL COMP IN]
17 STATUS COM
10 SHUT DOWN
3 OUT ON/OFF CON
15 NEXT PRL OUT
16 NEXT PRL OUT –
[NEXT PRL COMP OUT]
10
141612
Slave unit1
+
J1
Slave unit2
+
* [ ] in case of 160 V, 320 V and 500 V models.
12 PRL IN
14 PRL IN –
[PRL COMP IN]
10 SHUT DOWN
3 OUT ON/OFF CON
17 STATUS COM
Fig.5-6 Connection for parallel operation
5.2.3 Load Connection for Parallel Operation
WARNING
CAUTION
When you are done with the connection, be sure to
•
T
attach the output terminal cover to prevent the possibility of electric shock.
•
When connecting the output ter minal to the chassis
terminal, be sure that the output terminal of the same
polarity (+ or -) for each unit is connected to the chassis terminal. If you connect the output terminal of different polarities for each unit, the output is shortcircuited through the GND cable of the AC power
cord. This will result in failure to obtain proper outputs
and will burn the cable connected to the chassis.
•
ake measures to securely connect the load cable to
the terminals such as by using crimp terminals.
141512
10
J1
+
PAS SERIES
Parallel and Series Operation 5-11
Connection procedure
Chec k that the PO WER s witch is off on all po w er supply
1.
units to be connected in par allel.
2.
Remo v e the output ter minal co v er .
Connect the cab les as sho wn in Fig.5-7 .
W
3.
Refer to "3.3 Connecting the Load" and select a load cable with
suf fi cient current capacity . In addition, use the shortest load cables
of the same length and cross-sectional area from each po wer sup ply to the load.
ire the signal cable of the J1 connector and load cables as f ar
o perform master -sla v e parallel operation, the master and sla v e units
as well as v arious protection functions must be set up.
Setting the master and sla ve units
Set up the master and sla v e units through CONFIG settings.
NOTE
• Set the sla ve units through CONFIG settings after setting the
VP trip point.
For details on CONFIG settings, see "3.2.4 Unit Configuration
(CONFIG)".
T
O
1.
W h i l e p r e s s i n g t h e C O N F I G s w i t c h , t u r n o n t h e P O W E R s w i t c h .
After displaying the v ersion, the CONFIG switch lights up (CON FIG setting mode).
Press the CURRENT s witch to mo v e to the left-most digit on
2.
the current displa y .
po w
3.
Use the dial to set as f ollo ws according to the roles of each
Y
er supply unit.
Master unit : 0
Slave unit: 1
ON
OFF
V/
ALM
CV
OUTPUT
CC
external remote control settings are forced to local when units are set
to slave mode.
PAS SERIES
ou can check the settings by pressing the CONFIG switch. The
A/
Fig.5-8 Setup example of a slave unit for parallel operation
Parallel and Series Operation 5-13
VP (overvoltage protection) setting
VP (o v erv oltage protection) is set on both master and sla v e units
according to "3.2.2 Setting the O VP (Ov erv oltage Protection) T rip
Point".
, set the O VP trip point of the sla v e unit slightly higher than
that of the master unit, so that the O VP function of the master unit is
acti v ated fi rst. Set the trip point before specifying units to operate in
sla v e mode through CONFIG settings.
OCP (o vercurrent protection) setting
OCP (o v ercurrent protection) is set on both master and sla v e units
according to "3.2.3 Setting the OCP (Ov ercurrent Protection) T rip
Point".
Set the v alue equal to the current to be protected di vided by the num ber of units connected in parallel for OCP .
Set the OCP trip point of the sla v e unit slightly higher than that of the
master unit, so that the OCP function of the master unit is acti v ated
rst.
O
O
Ho we v er
5.2.5 Master-slave parallel Operation Procedure
fi
•
NOTE
When turning on the POWER switch, be sure to turn on the
master unit first.
When turning off the POWER switch, be sure to turn on the
slave units first. If you don’t keep the procedure, erroneous
operation may result.
The switches on the slave units are disabled. OUTPUT on/off operation is performed on the master unit.
When you are done with the steps described in "5.2.4 Master-Slave
Parallel Operation Setup" normal operations are performed on the
master unit.
5-14 Parallel and Series Operation
PAS SERIES
Chapter . 6
Names and Functions of Contr ols
This chapter describes the names and functions of switches, displays,
connectors, and other parts of the front panel and rear panel.
6.1 Front Panel
7
DISPLAY section
6 OUTPUT
5 SHIFT
4 CONFIG
3 LOCK
2 ADDRESS
1 POWER
Fig.6-1
8 VOLTAGE
OUTPUT
CONFIG
LOCK
PAS10-35
CV
CC
SHIFT
ADDRESS
REGULATED DC POWER SUPPLY
O N
OUTPUT
OFF
V W
A W
ALM
0-10V 35A
VOLTAGE
PWR DSPL
COARSE/FINE
CURRENT
PWR DSPL
SET
OVP
OCP
9 CURRENT/PWR DSPL
10 SET
11 OVP
12 Dial
Front panel (Example:350W type)
/PWR DSPL
/OCP
[1] POWER
Po
wer switch of the unit. Depress the switch to the (
c
the po wer on, (
○
) side to turn it of f.
) side to turn
│
[2] ADDRESS
Sets the unit's address in the range of 05 to 36 for digital remotely
controlling the unit. Press the switch to set the v alue; press it ag ain to
release. The specifi ed address tak es ef fect when the unit is po wer
ycled. F or details, see “Connecting & Programming Guide” in the
CD-R OM that came with the PIA4800 series.
PAS SERIES
Names and Functions of Controls 6-1
[3] LOCK
CV
OUTP U T
OFF
ALM
V/
W
A/
W
CC
ON
Switch used to disable all operations e xcept turning on/of f of the
OUTPUT .
The switch lights while the unit is lock ed.
o release, press the switch ag ain.
or details, see "3.5 LOCK Function " .
[4] CONFIG
If turn on the PO WER switch while pressing the CONFIG switch,
you can set the v arious setting of operation of the unit (CONFIG set ting mode). In addition, press the CONFIG switch when the unit is
turned on, the CONFIG setting can be confi
F
or details, see
[5]
SHIFT
"3.2.4
Unit Confi
guration (CONFIG)".
rmed.
Pressing a switch with blue characters while pressing this switch acti
v
ates the function indicated by the blue characters.
[6]
OUTPUT
Switch used to turn on/of
fi
rmed on the display when the unit is turned on.
Normally
PO
, the unit po
WER switch is turned on. You can set the unit so that it po
with the OUTPUT turned on. F
f the output.
The on/of
f status can be con
wers up with the OUTPUT turned of
or details, see
"3.2.4
Unit Confi
f when the
wers up
gura
tion (CONFIG)".
-
-
-
[7]
DISPLAY section
(3)OUTPUTON/OFF
CV
(4)CVindication
(5)CCindication
(7)Ammeter
Fig.6-2 Display section
6-2Names and Functions of Controls
CC
(8)Ammeterunit
ON
OUTPUT
OFF
(1)Voltmeter
(2)Voltmeter unit
V/
(9)Wattmeterunit
ALM
(6)ALMindication
A/
(9)Wattmeterunit
PAS SERIES
T
F
1)Voltmeter
Indicates the preset output v
SET switch is illuminated. Indicates the output v
SET switch is not illuminated. Indicates the O
the O
VP switch is illuminated.
Indicates the po
wer when the unit is switched to po
oltage during setup mode when the
oltage when the
VP trip point when
wer display
.
2)Voltmeter unit
Indicates the unit
3)
OUTPUT ON/OFF
V of the displayed v
oltage v
alue.
Indicates the ON/OFF status of OUTPUT.
4) CV indication
Illuminates when the unit is operating in the constant voltage
mode.
5) CC indication
Illuminates when the unit is operating in the constant current
mode.
6) ALM indication
Illuminates when any of the protection circuits, OVP, OCP, OHP,
or SHUT, is activated.
7) Ammeter
Indicates the preset output current during setup mode when the
SET switch is illuminated. Indicates the output current when the
SET switch is not illuminated. Indicates the OCP trip point if you
press the OCP switch while pressing the SHIFT switch.
Indicates the power when the unit is switched to power display.
8) Ammeter unit
Indicates the unit A of the displayed current value.
The unit displayed on the panel is mA on the 500 V model.
9) Wattmeter unit
Indicates the unit W of the displayed power value.
For details on the power display, see "3.4 Switching the Power
Display".
PAS SERIES
Names and Functions of Controls 6-3
[8] VOLTAGE/
PWR DSPL
Selects the digit when setting the v oltage. The digit changes for each
click.
Pressing the V OL T A GE switch while pressing the SHIFT switch dis plays the output po wer on the v oltage display . See "3.4 Switching the
wer Display " .
[9] CURRENT/
Selects the digit when setting the current.
PWR DSPL
The digit changes for each
click.
Pressing the CURRENT switch while pressing the SHIFT switch dis
plays the output po
Po
wer Display".
[10]
SET
Switch used to set or check the output v
v
alue.
When the switch is illuminated, the v
v
alue is indicated on the display
When the switch is not illuminated, the display section sho
measured v
[11]
OVP/
alues of the v
OCP
Pressing this switch displays the O
v
oltage on the display section.
F
or details on ho
O
VP (Ov
erv
Pressing the O
nates the switch and displays the OCP (overv
wer on the current display
. See
oltage v
"3.4
Switching the
alue or output current
alue can be entered.
.
oltage and current of the output terminals.
w to set the O
VP (overv
VP trip point, see
oltage protection) trip
"3.2.2
Setting the
oltage Protection) Trip Point".
VP switch while pressing the SHIFT switch illumi
oltage protection) trip
The
ws the
current on the display section.
F
or details on ho
OCP (Ov
ercurrent Protection) Trip Point".
w to set the OCP trip point, see
"3.2.3
Setting the
-
-
[12] Dial
Turn the dial (clockwise or counterclockwise) to set the voltage or
current, CONFIG settings, and node address.
You can also press when set the voltage or current, the dial to change
the digit.
6-4 Names and Functions of Controls
PAS SERIES
Po
6.2Rear Panel
16 TP-BUS
15 J1
14 DC OUTPUT
17
18 Sensing terminal
19 Exhaust port
13 AC INPUT
13 AC INPUT
1000W Type
Fig.6-3 Rear panel
[13] AC INPUT
AC power cord connector (350W and 700W types) or terminal board
(1000W type) used to supply power to the unit.
WARNING
• Improper handling can cause electric shock.
Be sure to follow the directions given in "1.4 Connect-
ing the AC power cord".
• For your safety, be sure to ground the unit.
For details, see "1.5 Grounding".
PAS SERIESNames and Functions of Controls 6-5
[14] DC OUTPUT
Output terminal.
WARNING
To prevent the possibility of electric shock, be sure to
turn off the POWER switch when handling this terminal.
• Be sure to attach the output terminal cover after wiring the load.
[15] J1
Connector for selecting analog remote control, parallel/series opera tion, and other functions. F or details, see "4.1 Analog Remote Con trol " and "4.2 Remote Monitoring " .
[16] TP-BUS
Connector used to connect to a Kikusui's PIA4800 Series Po wer Sup ply Controller using a twisted-pair cable when digital remotely con trolling the unit.
F
or details, see
[17]
T
erminal used to ground the unit to an electrical ground (safety
"4.3
(Protectiv
Digital Remote Control".
e conductor terminal)
ground).
•
WARNING
To prevent the possibility of electric shock, be sure to
turn off the POWER switch when handling this terminal.
[18]
Sensing terminal
T
erminal used to connect the sensing wires.
F
or details, see
[19]
Exhaust port
Exhaust port used to e
"3.6
Remote Sensing".
xhaust the internal heat using a f
Secure sufficient space around the e
quate v
entilation.
6-6 Names and Functions of Controls
an motor
.
xhaust port and the unit for ade
PAS SERIES
-
•
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.