PAD-L, TYPE I3
PAD8-30L PAD16-30L PAD35-20L PAD55-10L PAD70-8L PAD110-5L PAD160-3.5L PAD250-2.5L
80.10.21
8043020
Power requirements of this product have been changed and the relevant sections of the Operation Manual should be revised accordingly.
(Revision should be applied to items indicated by a check mark .)
Input voltage
The input voltage of this product is ______ VAC,
and the voltage range is ______ to ______ VAC. Use the product within this range only.
Input fuse
The rating of this product's input fuse is ______A, _____VAC, and _____.
WARNING
The product is porvided with AC power cables described below. If the cable has no power plug, attach a power plug or crimp-style terminals to the cable in accordance with the wire colors specified in the drawing.
WARNING The attachment of a power plug or crimp-style terminals must be carried out by qualified personnel.
PAGE
SECTION | 1. GENERAL | 1 |
1-1. | Description | 1 |
1-2. | Specifications | 3 |
* | Power Consumption Chart | 5 |
:* | Mechanical Outline Drawing | 7 |
SECTION | 2. OPERATION | 8 |
- 2-1. | Precaution for Operation (Installation) | 8 |
2-2. | AC Input Requirements | 12 |
* | Front and Rear Panel | 13 |
2-3. | Explanation of Front and Rear | 14 |
2-4. | Constant-voltage Operation | 17 |
2-5. | Constant-current Operation | 19 |
SECTION | 3. PROTECTORS | 20 |
3-1. | Description | 20 |
3-2. | Explanation of Protective Circuits | 21 |
3-3. | Operation Method of Overvoltage Protector (OVP) | 22 |
SECTION | 4. APPLICATIONS | 24 |
4-1. | Remote Sensing | 24 |
4-2. | Output-voltage Control with an External Voltage or | |
Resistance | 25 | |
4-3. | On-off Control of Output | 30 |
4-4. | Output-current Control with an External Voltage or | |
Resistance | 31 | |
4-5. | One-control Parallel Operation | 34 |
4-6. | One-control Series Operation | 36 |
4-7. | Constant-current Charge/Discharge of Battery or | |
Capacitor | 39 | |
4-8. | Remote Turning Off of The Power Switch | 42 |
88.8.26
42 V J S
ά,
- A -
SECTION | 5. THEORY OF OPERATION | 43 |
---|---|---|
5-1. | Description of Pre-regulation Circuit | 43 |
5-2. | Controlled Rectifier Circuit and Filter Circuit | 45 |
5-3. | Phase Control Circuit | 46 |
5-4. | Constant-voltage Circuit | 47 |
5-5. | Constant-current Circuit | 49 |
5-6. | Differences from Ideal Power Supply | 51 |
* | Block diagram | 54 |
SECTION | 6. MAINTENANCE | 55 |
6-1. | Inspection and Adjustment | 55 |
6-2. | Troubleshooting | 60 |
PAGE
N. C. V
The PAD-L Power supply is designed for high operation reliability and excellent electrical performance. It is a universal-purpose industrial power supply which can be used as a variable power source for research and development, or as a fixed power source for long time aging test. Features of the PAD-L Power Supply can be summarized as follows:
1. Improved power factor at low output voltage:
A choke input system is used for the rectifier filter circuit, thereby reducing the apparent input current and improving the power factor. This led to a smaller power transformer and consequently to a compact and light power supply.
2. Less waveform distortion caused to the AC input line:
As the choke input system is used, the input current waveform is less distorted with harmonics, thereby reducing waveform distortion to the AC input line.
3. Excellent temperature coefficient:
Very low temperature drift characteristics of 50 ppm/°C is attained by using premium-quality parts, improved circuits, and forced air cooling. Time-elapse drift (aging drift). also is very low.
4. Fast transient response:
A wide-band error amplifier is used to ensure stable frequency - gain, phase characteristics.
- 1 -
5. Low ripple and noise voltages:
Ripple and noise voltages are low, both in rms and peak values.
The output voltage is finely adjustable from 0 V to the rated voltage with a 10-turn potentiometer.
The power supply has a current/voltage limit switch to preset a current/voltage value. The set value of constant-voltage/ constant-current operation can be checked when in operation.
The power supply has internal protection such as voltage detector, current detector and temperature detector circuits. An overvoltage protector (OVP), voltage adjustable from the front panel, also is incorporated as a standard feature. A high speed overvoltage protector (a thyristor crowbar protection circuit) is available as an option.
The power supply is housed in a casing for bench top use. It can be installed on a standard 19-inch (500-mm) rack.
The user is requested to read thoroughly this instruction manual before operating the power supply.
* It is highly recommended to use the thyristor crowbar highspeed overvoltage protector (OVP: option) for a load whose allowable voltage range is very narrow and which could be damaged when a slight overvoltage is applied.
- 2 -
1-2. Specifications
PAD | PAD | PAD | PAD | PAD | PAD · | PAD | PAD | |||
---|---|---|---|---|---|---|---|---|---|---|
Taboli | 8-30L | 16-30L | 35-20L | 55-10L | 70-8L | 110-5L | 160-3.5L | 250-2.5L | ||
Inpu | t | |||||||||
L | Input supply | 120V | '±10%, 50 | Hz/60Hz AC, | 1 ø | |||||
I | Power consymption 120V AC Rated load |
Approx.
720VA |
Approx.
1.1kVA |
Approx.
1.5kVA |
Approx.
1.1kVA |
Approx.
1.1kVA |
Approx.
1.0kVA |
, Approx.
1.0kVA |
Approx.
1.1kVA |
|
Outp | ut | |||||||||
Output voltage range 10 turns | 0-8V | 0-16V | 0-35V | 0-55V | 0-70V | 0-110V | 0-160V | 0-250V | ||
Voltage resolution (theoretical value) | 1.5mV | 3mV | 6.3mV | 10mV | 13mV | 20mV | 29mV | 4.5mV | ||
_ | Output current range 1 turn | 0-30A | 0-30A | 0-20A | 0-10A | 0-8A | 0-5A | 0-3.5A | 0-2.5A | |
1 | Current resolution (theoretical value) | 102mA | 102mA | 68mA | 34mA | 27mA | 17mA | 12mA | 8.5mA | |
Cons | tant voltage characteristics | |||||||||
L | Regulation *1 | , | ||||||||
Source effect (line regulation)
(For ±10% change of line voltage) |
0.0 | )5% + 1mV |
0.005%
+ 2mV |
|||||||
Load effect (load regulation)
(For 0 to 100% change of output current) |
0.0 | 05% + 2mV |
-000
+ |
5%
V |
0.005%
+ 2mV |
0.005%
+ 3mV |
||||
Ripple and noise (5 Hz - 1 MHz) rms *2 | 500µV | 500µV | 500µV | 500µV | 1mV | lmV | 1mV | 5mV | ||
1 | Transient response (typical) *3 | 20 / | usec. | (5 - 100% | change) | |||||
1 | Temperature coefficient (typical) | 201 | pm/°C | |||||||
1 | Remote control resistance and voltage | IddA | cox. 0 - 1 | 0k.Ω, 0 - ] | 0 V | |||||
Cons | stant current characteristics | |||||||||
L | Regulation | |||||||||
Source effect (line regulation)
(For ±10% change of line voltage) |
3тА | ЗтА | ЗтА | ЗтА. | lmA | lmA | 1mA | 1mA | ||
Load effect (load regulation)
(For 0 to 100% change of output voltage) |
ЗтА | ЗтА | ЗтА | ЗтА | ЭшА | 2mA | 2mA | lmA | ||
L | Ripple and noise (5 Hz - 1 MHz) rms *2 | SmA | SmA | 3mA | 3mA | 2mA | lmA | 1mA | 2mA | |
L | Remote control resistance/voltage, approx. [k0/v] | 1/0.5 | 1/0.5 | 1/0.6 | 1/0.6 | 1/0.9 | 1/1.1 | 1/0.8 | 1/1.1 | |
Oper | cating ambient temperature range | - 0 | 40°C (32 | - 104°F) | ||||||
Oper | cating ambient humidity range | 10% | – 90% RH | |||||||
Cool | ling method | For | ced air co | oling with | fan | |||||
Pols | arity of output voltage | Pos | itive or n | egative gro | ounded | |||||
Isol | lation from ground | ±25( | OV DC | ±500V | DC |
- 3 -
Notes: *1. Measured using the sensing terminals. *2. Measured with the positive or negative output grounded. *3. Recovery time within 0.05% + 10mV of the output voltage.
804308B
88, 6. 13
Hu
Model |
. PAD
8-30L |
PAD
16-30L |
PAD
35-20L |
PAD
55-10L |
PAD
70-8L |
PAD
110-5L |
PAD
160-3.5L |
PAD
250-2.5L |
|
---|---|---|---|---|---|---|---|---|---|
Protections | |||||||||
Operation | Input power | switch is t | urned off. | ||||||
Trip temperature of thermal protector | 100°C (212° |
?) at coolin |
g pacage | ||||||
Overvoltage protection (OVP) | |||||||||
Voltage setting range *4 | 3-10V | 6-18V | 6–38V | 11-60V | 15-80V | 20-130V | 30-180V | 50-280V | |
Trigger pulse width *4 | 50msec. | ||||||||
Input fuse rating | |||||||||
At 120V AC source | TOA | | 15A | 20A | 15A | 15A | 15A | 15A | 15A | |
Output fuse rating | 30A | 30A | 20A | 10A | 8A | 5A | 4A | 3A | |
Meters | |||||||||
Voltmeter, Full scale, Class 2.5 (JIS) | 80 | 16V | 35V | 60V | 707 | 110V | 17.5V | 250V | |
Ammeter, Full scale, Class 2.5 (JIS) | 30A | 30A | 22A | 12A | 8A | 6A | 3.5A | 2.5A | |
Constant voltage mode indication | C.V : Wit | n green LED | |||||||
1 | Constant current mode indication | C.C : Wit | n red LED | ||||||
Insulation resistances | |||||||||
Between chassis and line | 500V DC, mo | re than 30MΩ | |||||||
Between chassis and output terminal | 500V DC, mo | re than 20MN | - | ||||||
Dimentions *5 | |||||||||
210W × 140H | × 410D mm ( | 8.3W × 5.5H | × 16.2D in | ||||||
Maximum dimentions | 230W×160H | × 475D mm (9.1W | ×6.3H×18.7D in.) | 230W× | 160H× 463D | mm (9.1W×6 | .3H×18.2D i | n.) | |
Weight |
Approx.
19 kg |
Approx.
25 kg |
Approx.
24 kg |
Approx.
24 kg |
Approx.
24 kg |
Approx.
24 kg |
Approx.
24 kg |
Approx.
24 kg |
|
Accessories (in carton) | |||||||||
Instruction manual | 1 copy | ||||||||
Input line fuse (spare) | |||||||||
For 120V AC | 10A, 2 ea. | 15A, 2 ea. | 20A, 2 ea | • | 15A, | 2 ea. | |||
Input cord | 3-core cabt | ire cord | . 1 | ||||||
Others | Guard cap . | ••••••••••••••••••••••••••••••••••••••• | . 1 set |
s: *4. Typical value *5. With rack mount brackets (option), can be mounted on a standard 19-inch or 500-mm rack.
Notes:
- 4 -
- 5 -
- 6 -
Ľ, J
Figure 1-1. N
Mechanical outline drawing
- 7 -
8043110
88.1.13
2-1. Precaution for Operation (Installation)
15A for 120 V (10A for PAD8-30L, 20A for PAD35-20L)
Figure 2-1. Cross section of cabtire cable
o The output power is available either at the front panel (binding post terminals) or at the rear panel (terminal blocks).
o The ambient temperature range for the power supply to satisfy the specification performances is 0°C to 40°C (32°F to 104°F). The power supply should be used within this range. If it is operated at a high ambient temperature, the internal temperature detector circuit trips and the input power switch is turned off. If this has happened, cool it and then turn on the power again. There is an exponential relationship between ambient temperature and semiconductor life, electrolytic capacitor life and transformer insulation life. Note that components are rapidly deteriorated at high temperatures. It is important not to operate the power supply at an abnormally high ambient temperature also from the viewpoint of its life.
- 9 -
Note that the output may become unstable depending on characteristics of loads as follows:
(a) When the meter reading (average value) is less than the preset value, if the current has peaks which exceed the preset value, the operation is driven into the constant current domain for the short periods of time and the output voltage falls. Observing carefully, it can be seen that the constant-current indicator lamp becomes dim.
Figure 2-3. Load current with peaks
In this case, raise the preset value or increase the current rating.
(b) When a regenerative load (such as inverter, converter, or transformer) is connected to the power supply, as it cannot absorb the reverse current fed from the load, the output voltage increases and becomes unstable. In such a case, connect a bypass resistor (R) in parallel with the load and feed in this resistor a current larger than the maximum reverse current.
where, E0: Output voltage IRP: Maximum reverse current
- 11 -
Table 2-1. Wire gauges and current ratings
Т | a= | 3 | 0 | °C | |
---|---|---|---|---|---|
• | u | ~ | v |
Nominal c
sectio |
eross
on |
Maximum current
recommended by Kikusui |
Maximum current designated by
Electrical Installation Technical Ordinance (Article 29) JAPAN |
---|---|---|---|
2 m | m 2 | 10 A | 27 A |
5.5 m | m 2 | 20 A | 49 A |
8 m | m 2 | 30 A | 61 A |
14 m | m2 | 50 A | 88 A |
2.2 m | ım² | 80 A | 115 A |
30 m | m 2 | 139 A | |
38 m | m2 | 100 A | 162 A |
50 m | m2 | 190 A | |
60 m | m² | 217 A | |
80 m | m² | 200 A | 257 A |
100 m | m2 | 298 A | |
125 m | um2 | 344 A | |
150 m | 1m 2 | 300 A | 395 A |
200 m | m² | . 469 A |
N918 202
This instrument can be modified for operation on AC line (Input) voltages of 100 - 120 V or 200-240 V by changing the input power transformer taps. However, as the surge absorber and fan and some other components also need to be changed accordingly, contact Kikusui agent in your area when such modification is required.
Figure 2-4. Front panel and rear panel
- 13 -
9- 6 88
204314B
2-3. Explanation of Front and Rear
Panel items and descriptions
1. POWER switch/Circuit Breaker:
Circuit breaker serves as AC power switch. When thrown to the upper position, the input power is turned on and C.V. or C.C. lamp lights.
Note: The input power is automatically turned off when any one of the internal protectors (over voltage protector, voltage detector, current detector and temperature detector) has tripped. The input power cannot be turned on immediately after it is turned off by the above cause. Eliminate the cause, wait about 60 seconds and then turn on the input power.
2. CURRENT/VOLTAGE LIMIT switch:
Push to set crossover point of CV/CC. The ammeter indicates the preset constant-current value and the voltmeter indicates the preset constant-voltage value.
Monitors output current. Class 2,5
43120
Monitors output voltage. Class 2.5
5. Voltage setting knob:
Adjusts output voltage for constant-voltage operation. 10-turn potentiometer (NOTE: See Figure 2-5, page 17.)
Adjusts output current for constant-current operation. 1 turn potentiometer (NOTE: See Figure 2-5, page 17.)
7. C.V. (constant-voltage operation indicator lamp):
Energizes in constant-voltage mode. Green LED
8. C.C. (constant-current operation indicator lamp):
Energizes in constant-current mode. Red LED
9. Voltmeter calibration (R101):
For voltmeter calibration. (Periodically calibrate the voltmeter referring to SECTION 6 "MAINTENANCE.")
10. Ammeter calibration (R102):
For ammeter calibration. (Periodically calibrate the ammeter referring to SECTION 6 "MAINTENANCE.")
11. Overvoltage protector (OVP) (See 3-3 "Operation Method of Overvoltage Protector."):
When the output voltage has exceeded the set value due to inadvertent operation or instrument failure, the input power switch is instantaneously cut off to protect the load.
12. Zero adjustment of voltmeter:
To adjust the voltmeter at 0 V.
13. Zero adjustment of ammeter:
To adjust the ammeter at 0 A.
14. "-" output terminal:
White binding post
15. "+" output terminal: Red binding post
16. GND terminal:
Be sure to connect this terminal to a good earth ground.
20. Input fuse holder:
15A for 120V AC (20A for 120V AC, PAD35-20L only inside), (10A for 120V AC, PAD8-30L only)
21. Input terminal board:
For input power connection. Use the power cord supplied accompanying.
22. Terminal board:
Terminals for "-", "-S", "+", "+S", remote control, one control series/parallel operation of two or more units. (See SECTION 4. "APPLICATIONS".)
23. Fan exhauset area:
Air exit of the cooling package. As hot air comes out of this outlet, do not obstruct. The outlet must be positioned 30 cm or over from wall.
24. Tapped holes for M4 screws:
For a high speed over voltage protector ( a thyristor crowbar OVP, option).
25. Output voltage offset control (V.os)
For adjustment of output voltage when the voltage setting knob is turned to the counterclockwise extreme position or for adjustment of input offset voltage when in remote control with voltage signal.
26. Output current offset control (I.os)
For adjustment of output current when the current setting knob is turned to the counterclockwise extreme position or for adjustment of input offset voltage when in remote control with voltage signal.
(Note): When a guard cap (accessory) used, the potentiometer
0
11
Check at first that the AC line voltage is 120V ±10% AC. Then, proceed as follows:
Turn the current setting knob to the extremely counterclockwise position.
80432
171
- 18 -
2-5. Constant-current Operation
00
V
- 19 -
Regulated DC power supplies are used, as their name indicates, to supply regulated powers to loads of various types of electronic equipment. Demands for regulated DC power supplies have rapidly increased in recent years. As is the case for other types of electronic equipment, these instruments are required to include features of fast response, high reliability, high efficiency, high power factor, compactness, light weight, and economical price. Various types of power supplies are available on the market today. When selecting regulated DC power supplies, in addition to satisfying the required performances, special attention must be paid to some particular requirements which are slightly different from those required by other types of electronic equipment which handle electronic signals.
The above difference comes from the fact that regulated DC power supplies handle "powers." Malfunctioning or erroneous operation of the power supply leads to shut down of the overall system, damage to the power supply equipment and expensive load equipment, or to a fire in an extreme case. As the power supply provides the base for the entire electric and electronic circuits of the system to which it supplies the power, its reliability is very important. Protective features, which prevent serious damage when the power supply should fail, are important factors to be taken into consideration when selecting a power supply.
The PAD-L Regulated Power Supplies have been designed fully taking the above matters into consideration, as instruments of very high reliability. They employ premium quality components, with sufficient derating. They are incorporated with protector which lead them to "the safer side" should they fail. Individual protectors are explained in this section.
- 20 -
When the rated voltage of the electrolytic filter capacitor is exceeded due to such erroneous operation as disconnected jumper of the terminal block on the rear panel or due to a failure of the rectifier circuit, the input power switch is instantaneously cut off.
(3) Current detection circuit:
When in such erroneous operation as that the jumper of the terminal block of the rear panel is inadvertently left disconnected or when the current limiting circuit has failed, the control transistors are cut off and at the same time the input power switch is cut off or the current is limited at approximately 120% of the rated current.
しこうかのみ
Detects temperature of the cooling package (semiconductor cooling unit). When temperature of the cooling fins have become higher than approximately 100°C due to ambient temperature rise or cooling fan failure, the input power switch is cut off.
(5) High-speed overvoltage protector (option):
When the output voltage has exceeded the preset voltage due to erroneous operation or an external pulse voltage,
- 21 -
a thyristor circuit connected between the output terminals instantaneously conducts to short-circuit the output and, at the same time, the input power switch is instantaneously cut off. The operation time is selectable from a range of several microseconds to several hundreds microseconds.
Model PAD- | 8-30L | 16-30L | 35-20L | 55-10L |
---|---|---|---|---|
OVP type |
OVP
16-50L |
OVP
16-50L |
OVP
35-30L |
OVP
55-20L |
Model PAD- | 70-8L | 110-5L | 160-3.5L | 250-2.5L | |
---|---|---|---|---|---|
OVP type |
OVP
110-10L |
OVP
110-10L |
OVP
250-10L |
OVP
250-10L |
Table 3-1
(6) Power fuse:
Limits the input current.
(7) Output fuse:
Limits the output current.
Both fuses are current limiting type of fuses meeting the requirements of JIS and model-approved by the Electrical Appliance Control Ordinance. The fuses employ a ceramic insulation tube and silica sand arc killer, and are free of flame when blown out.
3-3. Operation Method of Overvoltage Protector (OVP)
Setting procedure
P
Voltage drop caused by the load connection wire resistance and contact resistance can be compensated for.
C1, C2: 100µF, 16WV
Notes: 1. By this remote sensing feature, up to approximately 1.2 V of voltage drop per one-way of connection wire can be compensated for. Note that, if the voltage drop is larger than 0.3 V, the maximum rated voltage is reduced by the corresponding amount.
Figure 4-2
64228
Output voltage Eo = [V]
Where, 10 > R1 [kΩ]
Emax: Rated output voltage [V]
*Note 1: Use a 2-core shielded cable or a pair of stranded wires. Connect the shield wire to the "+" output terminal.
o Application
540,0
(This method is a fail-safe method free from overshoots even when resistors are switched.)
The output voltage (Eo) is inversely proportional to the resistance (R2) as shown below. Therefore, when the circuit has become open due to switching of resistors or a failure, the resistance becomes infinity and the output is reduced to zero.
PAD - | 8-30L | 16-30L | 35-20L | 55-10L |
---|---|---|---|---|
a [kΩ] | 3.4 | 3.3 | 3.4 | 5.5 |
b [kΩ] | 2.7 | 5.2 | 12 | 30 |
PAD - | 70-8L | 110-5L | 160-3.5L | 250-2.5L | |
---|---|---|---|---|---|
a [kΩ] | 7.4 | 9.8 | 9.7 | 9 . 9 · | |
b [kΩ] | 52 | 108 | 156 | 248 |
Table 4-1
- 27 -
o Control with an external voltage
88
5
204332-51
The terminal for the common line of the control voltage signal is (S). The external control voltage signal must be of an isolated type. Note that the power supply may be damaged if the control voltage signal is not of an isolated type. When the output is controlled for both constant-current and constant-voltage simultaneously, the respective control voltage signals must be of an isolated type because the common lines of the two control circuits are not connected in common.
* The instrument may be damaged if there is a wrong connection or an abnormally large voltage is applied. Check for them once more before turning on the instrument power.
Figure 4-5
Output voltage Eo = Emax·Ei [V]
Where, 0 < Ei < 11 V
Eo: Output voltage [V]
Ei: Input control voltage [V]
Emax: Maximum rated voltage [V]
o There is an offset voltage between the input control voltage and the output voltage as shown below.
The input offset voltage can be adjusted with the output voltage offset control.
88. 8 . 88. 8
804-333-2H
Figure 4-8
Output current Io = R2·Iomax [A] *Note 2
Where, R2 ≤ 1000 [Ω] R3: Approx. 10 - 30 [Ω] Iomax: Rated output current [A]
*Note 1: Use a 2-core shielded cable. Connect the shield wire to the "+" output terminal.
*Note 2: Linearity between R2 and Io is approximately 5%.
o Control with an external voltage
1. Turn off the power switch.
98.
ĉ
804336
4. Connect electrolytic capacitor between terminals (9) and (10).
5. Apply the external control voltage between terminals (9) and (10).
The potential of control common terminal (10) is alomost identical with that of output terminal (+). The external control voltage signal must be of an isolated type.
- 32 -
Figure 4-9
Iout ÷ Ein [A]
シススとものよ
Where, Ein [V] ≤ Einmax
Iout: Output current
Ein: Input current
R: Detecting resistor
Einmax: Maximum input voltage
Type PAD- | 8-30L | 16-30L | 35-20L | 55-10L |
---|---|---|---|---|
R [Ω] | 0.015 | 0.015 | 0.025 | 0.05 |
Einmax [mV] | 500 | 500 | 560 | 600 |
Type PAD- | 70-8L | 110-5L | 160-3.5L | 250-2.5L | |
---|---|---|---|---|---|
R [Ω] | 0.1 | 0.2 | 0.2 | 0.4 | |
Einmax [mV] | 880 | 1100 | 770 | 1100 |
Notes: 1. Make sure that the output current does not exceed the maximum rated current.
4. Be sure to throw switch SWl to the original state (lower position) after the operation in the remote control mode is over.
o There is an offset voltage between the input control voltage and the output current as shown below.
For particular applications which do not tolerate this offset voltage, adjust it with the output current offset control.
4-5. One-control Parallel Operation
8,88
96.
land
Ľ
One master unit and any number of slave units can be operated in parallel to increase the current capacity, controlled by one unit (master unit) for operation.
↔ Nagative ground←→ Positive ground
Set the constant-voltage setting knobs of all slave units to maximum position. Of the master unit, the green LED lamp lights to indicate the constantvoltage mode; of the slave units, the red LED lamps light to indicate the constant-current mode.
- 35 -
4-6. One-control Series Operation
One master unit and any number of slave units can be operated in series to obtain a higher output voltage (up to 250 V), controlled by one unit (master unit) for operation.
Figure 4-12. Rear terminal connections
A ↔ : Positive ground
B ↔ : Negative ground
Figure 4-13. GND terminal connections
Resistance Calculation for External Resistor R1 (R2)
8103540 B
Where, R1 and R2 \ge 0 [k\O]
E1 [V]: Output voltage of master unit
A, B : Constants of slave units. (See Table 4-2.)
E2 ≤ A/B E1 ..... condition of range for E2
E3 ≤ A/B E2 ..... condition of range for E3
PAD | 8-30L | 16-30L | 35-20L | 55-10L |
---|---|---|---|---|
A [kΩ] | 2.7 | 5.2 | 12 | 30 |
B [kΩ] | 3.4 | 3.3 | 3.4 | 5.5 |
PAD | 70-8L | 110-5L | 160-3.5L | 250-2.5L | |
---|---|---|---|---|---|
A [kΩ] | 52 | 108 | 156 | 248 | |
B [kΩ] | 7.4 | 9.8 | 9.7 | 9.9 |
- 37 -
o Charge (constant current)
- 39 -
o Discharge (constant current)
Figure 4-15
Resistance of R:
Power consumption by R: P = I2R [W]
where, E: Terminal voltage of battery or capacitor when starting discharge
0
(7
First, disconnect the power cord from the AC line receptacle. Remove the instrument cover. To turn off the power, shortcircuit between terminals 3 and 4 of PCB A-095 which is mounted on the rear terminal board. (Run the leadwires to outside through the hole near the terminals.)
Note: As terminals 3 and 4 of PCB A-095 are at the potential of the "+" terminal of the rectifier filter capacitor, a floated (isolated) external contact signal is required for the remote control signal.
Figure 4-16
Removing the cover:
Figure 4-17
Remove the four screws A (M4) with a screwdriver and the two screws B (M4) with a hex wrench.
- 42 -
Before describing the operating principles of individual circuits of the power supply, history of variable regulated DC power supplies are very briefly introduced in the following.
Figure 5-1 shows a series control circuit. This circuit, as compared with other types of control circuits, has a higher control accuracy and provides an output of higher quality. The output voltage is variable for a wide range. Therefore, this circuit is widely used for variable DC power supplies. This circuit, however, has a disadvantage that, when the output power is supplied to a load at a low voltage, VCE increases and consequently collector loss PC (PC = VCE × IC) increases and, therefore, rectifier voltage VC is required to be varied with respect to the output voltage.
Figure 5-2 shows a power supply circuit which employs a relay system. Variation of the output voltage is detected and transformer taps are switched with a relay circuit to compensate for
Figure 5-1 Series-controled power supply
Figure 5-2 Variable regulated DC power supply circuit with relay switching.
- 43 -
output variation. The PAC Series Power Supplies employs this system. This system provides excellent power supplies up to approximately 200 watts. For larger power supplies, however, this relay system has such disadvantages that mechanical contacts have limited life and require maintenance, a number of relays are required to reduce the collector loss, and consequently the reliability falls and the cost rises. To solve the problem, solid-state switching circuit has become most common.
Figure 5-3 shows the SCR system employed by the PAD Series Power Supplies. This system provides a fast response and VCE can be maintained almost constant by phase control and, therefore, it enables high-accuracy largerating variable power supplies. Thus, a large number of this type of power supplies have been manu-
Figure 5-4 Principle of PAD-L Series Power Supplies
factured by Kikusui. However, problems have risen regarding increase of ripple current of the electrolytic capacitor as the filter circuit is a capacitor input type, the surge current of SCRs, and overheating due to copper loss of the transformer when the power factor has become poor.
The PAD-L Series Power Supplies have solved the above problems by using a choke-input type filter circuit, and are the most reliable variable regulated DC power supplies available.
5-2. Controlled Rectifier Circuit and Filter Circuit
solves the problems of ripple current of electrolytic filter capacitor and overheating of the transformer, and reduces the rectified output ripples. The PAD-L Series Power Supplies also employ a bridge rectifier circuit.
5-3. Phase Control Circuit
This circuit is a pulse phase modulator which operates in synchronization with the AC line frequency. When the collectoremitter voltage (VCE) is large, the generated pulse signal is for a wider conduction angle and, when the voltage is lower, the signal is for a narrower conduction angle and, thus, the circuit so controls SCRs that VCE becomes constant.
- 46 -
Eref 1: Reference voltage 1 Eref 2: Reference voltage 2 Ri: Input resistance Rf: Feedback resistance
Output voltage Eout can be expressed as follows (Al is an ideal amplifier):
Eout = Eref 2
H
Thus, the output voltage depends only on Eref 2, Ri and Rf. The output voltage is linearly proportional to Rf and Eref 2. For this power supply, Eref 2 is varied to control the output voltage. Eref 2 is produced by amplifying Eref 1, and this voltage is linearly varied by R2.
To obtain a stable output voltage, such components as Eref 1 diode, R1, R2, Ri, Rf, A1 and A2 must be sufficiently stable against change in external conditions. This power supply employs for the Eref 1 diode a zener diode of excellent temperature
- 47 -
characteristics. The resistors are metal-film resistors and wound-wire resistors of excellent temperature coefficient and aging characteristics. Amplifiers Al and A2 employ monolythic ICs which ensure high gain, wide band and low drift.
The major factors caused by line voltage variation are variation of the operating point of the error amplifier and variation of the reference voltage due to dynamic resistance of the reference diode. To guard against these variations, a stabilized internal auxiliary voltage source is used. Load variation ( ∂Vo/∂Io : output variation caused by output current variation) is affected by output impedance (internal resistance) Zo. (See Figure 5-8.)
Denoting by A the open loop gain attained by error amplifier A2 and power transtor Q, output impedance Zo can be expressed as follows:
where,
Ro: Output impedance of the circuit when no error amplifier is connected
The above equation indicates that the output impedance is improved to 1/(1+AB) by connecting amplifier A2 and effecting a feedback circuit.
- 48 -
Figure 5-9
Output current Iout can be expressed as follows (Al assumes an ideal amplifier):
Iout =
This equation indicates that the output current depends on Eref, R1, R2 and R3. Of this power supply, the output current is controlled by varying R2. Note that the relationship between R2 and Iout is not linear as indicated with a solid line in Figure 5-10.
To ensure a stable output current, Eref, R1, R2 and R3 must be sufficiently stable against change in external conditions (line voltage change, ambient temperature change, aging, and load change). Error amplifier A1 must be a high-gain wide-band DC amplifier with less drift.
ROYJEZ A
Of the constant-current circuit, the larger the output impedance (Zout), the smaller is the load variation ( ∂ Io/ ∂ Vo: output current variation caused by output voltage variation). (See Figure 5-11).
Io = I - I1
where, I1 = Eo/Zo = Load current variation component
Denoting by gm the mutual conductance attained by erro amplifier A2 and power transistor Q, output impedance Zo can be written as follows:
Zo = (1 + gm R3) Ro
In this equation, Ro is the output impedance of the circuit before connecting the error amplifier. This equation indicates that the output impedance is improved by (1 + gm R3) times by connecting amplifier A2 and providing negative feedback.
J1012225 €
Figure 5-12 shows an equivalent circuit of a series-controlled constant-voltage power supply of the type used for this and other power supplies. An ideal diode is connected in series. This type of power supply is for a load of such type that it simply drains the current and does not send back the current. For such load as a battery which sends back a current, however this power supply cannot sink such current.
This problem can be solved by using a parallel-controlled power supply or one which has a bi-polarity output. Such power supplies, however, will provide less efficiency and high cost for the same power.
The problem can be solved by connecting a resistor in parallel with the load and feeding in the resistor a current larger than the maximum reverse current. When the reverse current is small, the problem may be solved by connecting an electrolytic capacitor in parallel with the load. When the load is an inverter, a filter circuit may be provided in the input circuit to reduce the reverse current.
- 51 -
o Output impedance is not infinity, with certain frequency characteristics:
Figure 5-13 shows that the output impedance (internal resistance) of this power supply increases as the frequency increases. This is because the gain of the loop including the error amplifier decreases. Better frequency characteristics, as well as DC output impedance characteristics such as for load variation, are a desirable feature for the power supply.
This feature must be such that not only the high gain region of the error amplifier is extended to a higher frequency range but also the phase characteristics are correct.
A shorter transient response time means better frequency characteristics of output impedance. Transient response time is an index for evaluation at the time range and output impedance is that at the frequency range.
5-6B. Difference from Ideal Constant-current Power Supply
Figure 5-14
- 52 -
Figure 5-14 shows an equivalent circuit of this power supply operating as a constant-current source. A capacitor is connected in parallel with an ideal power supply.
There is no problem when the load is resistive. However, if the load is of such nature that it varies rapidly, pay attention to the fact that the output voltage also varies rapidly and the charge/discharge current of the capacitor is superimposed on the output current.
H3
6-1. Inspection and Adjustment
Periodically inspect and adjust the power supply so that it maintains its initial performance for a long time.
6-1-1. Removing Dust and Dirt
6-1-2. Inspecting the Power Cord and Plug
6-1-3. Calibrating the Voltmeter
6-1-4. Calibrating the Ammeter
6-1-5. Calibrating the Current/Voltage Limit Switch
6-1-1. Removing Dust and Dirt
When the instrument panel has become dirty, lightly wipe it with a cloth moistened with diluted neutral soapsuds and, then, wipe it with a dry cloth. Do not use benzine or thinner. Blow away dust collected inside the instrument and in the ventilation holes of the casing, using a compressed air or a vacuum cleaner.
6-1-2. Inspecting the Power Cord and Plug
Check for that the vinyl cover of the cord is not damaged. Check the plug for play , loose screws and damage.
6-1-3. Calibrating the Voltmeter
5
00
Connect an external voltmeter of an accuracy of 0.5% or better to the output terminals, set the output voltage at the value indicated on Table 6-1, and calibrate the instrument voltmeter
with R101 at the right-hand section on the front panel. (See the panel illustration on page 13.)
6-1-4. Calibrating the Ammeter
Connect an external ammeter of an accuracy of 0.5% or better in the output circuit, set the output current at the value indicated on Table 6-1, and calibrate the instrument ammeter with R102 at the right-hand section on the front panel. (See the panel illustration on page 13.)
6-1-5. Calibrating the Current/Voltage Limit Switch
o Calibration of limit current
Set the output current at the value indicated on Table 6-1. Press the current/voltage limit switch and so adjust R253 that the ammeter indicates the set current value.
o Calibration of limit voltage
Set the output voltage at the value indicating on Table 6-1. Press the current/voltage limit switch and so adjust R209 that the voltmeter reads the set voltage value. (See Table 6-1.)
6-1-6. Adjustment of Maximum Variable Constant-voltage Range
Connect to the output terminals an external voltmeter of an accuracy of 0.5% or better, set the constant-voltage setting knob in the maximum position (extremely clockwise position), and so adjust R220 on PCB A-200 that the instrument voltmeter reads the value indicated on Table 6-1.
Connect in the output circuit an external ammeter of an accuracy of 0.5% or better, set the constant-current setting knob in the maximum position (extremely clockwise position), and so adjust R249 on PCB A-200 that the instrument ammeter reads the value indicated on Table 6-1. (See Figure 6-1.)
6-1-8. Adjustment of VCE of Series Transistor
Maintain constant the AC input voltage at 100 V. Connect the load and apply the rated voltage and feed the rated current. In this state, connect a mean-value-indicating voltmeter between the "+" terminal of the filter capacitor and "+" output terminal and so adjust R326 that the voltmeter reads the value indicated on Table 6-1.
PAD | 8-30L | 16-30L | 35-20L | 55-10L | |
---|---|---|---|---|---|
Voltmeter adj | R101 | 8 V | 16 V | 35 V | 55 V 👡 |
Ammeter adj | R102 | 30 A | 30 A | 20 A | 10 A |
Current limit adj | R253 | 30 A | 30 A | 20 A | 10 A |
Voltage limit adj | R209 | 8 V | 16 V | 35 V | 55 V |
Maximum voltage adj | R220 | 8.5 V | 16.5 V | 35.6 V | 56.0 V |
Maximum current adj | R249 | 31 A | 31 A | 21 A | 10.5 A |
V CE adj | R326 | 4.7 V | 4.5 V | 5.6 V | 8.6 V |
PAD | 70-8L | 110-5L | 160-3.5L | 250-2.5L | ||
---|---|---|---|---|---|---|
Voltmeter adj | R101 | 70 V | 110 V | 160 V | 250 V | |
Ammeter adj | R102 | 8.0 A | 5.0 A | 3.5 A | 2.5 A | |
Current limit adj | R253 | 8.0 A | 5.0 A | 3.5 A | 2.5 A | |
Voltage limit adj | R209 | 70 V | 110 V | 160.V | 250 V | |
Maximum voltage adj | R220 | 72 V | 112 V | 165 V | 260 V | |
Maximum current adj | R249 | 8.2 A | 5.2 A | 3.6 A | 2.6 A | |
V CE adj | R326 | 10.9 V | 13.1 V | 20.8 V | 16.1 V |
Table 6-1
H
Figure 6-1
- 59 -
H
17
80436408
The most probable causes of troubles are shown in the following table. When a failure of the power supply is found, contact Kikusui agent in your area.
Symptom | Check item | Probable cause | |
---|---|---|---|
Power switch
cannot be turned off |
1. Has the overvoltage
protector tripped? |
o Set voltage too low | |
(or turns off
soon). |
2. Shorting bar
disconnected? |
o Disconnected or loose
shorting-bar |
|
3. Is fan stalled? |
o Trip of overheat protector
(Replace fan.) |
||
4. Other than the above |
o Trip of protector due to
a failure of rectifier circuit |
||
No output
(No output is produced at all or only a slight output is produced.) |
1. Is the input power
fuse blown? |
|
|
2. Is lamp lighted? |
If not lighted, d
o Open-circuiting of power cord |
||
3. Are the lamps
alternately lighting, indicating rapid tran- sitions of operating domains |
o Too narrow constant-
voltage and constant- current setting ranges |
- 60 -
Symptom | Check item | Probable cause | ||
---|---|---|---|---|
4. Are the shorting-bars correctly connected? |
o Wrong connection of
shorting-bar(s) |
|||
5. Is the output power
fuse blown out? |
o Output current flowed
exceeding the rated value o Power transistor failure |
|||
6. Is the circuit
oscillating? |
o Phase inversion caused |
|||
7. Is a current flowing
despite no load? |
If flowing,
o Failure of the protective diode connected in para- llel with the output (This diode may be damaged if such load as battery is connected in the reverse polarity.) |
|||
8. Other than the above | o Circuit failure | |||
Abnormally high
output |
1. Is the shorting-bar disconnected? (Between 3 and 4 .) |
o Disconnected or loose
shorting-bar o Malfunctioning OVP circuit |
5
204367 ×
- 61 -
Symptom | Check item | Probable cause |
---|---|---|
2. Output voltage (current)
cannot be reduced |
o Power transistor
failure o Bleeder circuit failure |
|
Unstable
output |
1. Is the shorting-bar(s)
loose? |
o Incorrect connection
of the shorting-bar(s) |
2. Is the AC line voltage
correct? |
o AC line voltage not
within the specified range |
|
3. Special type of load | o See 2-4. | |
4. When matter of drift
is critical |
o Allow approximately
30 minutes of stabili- zation time. |
|
5. Other than the above | o Circuit failure | |
Large ripple
voltage |
1. Is the AC line voltage |
o Input voltage too low |
2. Are the sensing terminals
securely connected to the output terminals? |
o Securely connect the sensing terminals | |
3. Is a strong source
of magnetic or electric field present near the power supply? (Is there no nearby auto-transformer, power transformer, or an oscil- lating source?) (Especially when in the constant-current mode) |
o Electromagnetic
induction (Move the source of ttouble. Strand the wires.) |
|
4. Other than the above |
o Circuit failure
o (Re-adjust) |
- 62 -
804366 A 🖈
5