Kieback&Peter MD15/230-HR, MD15/230-DA, MD15/230-HE Product Description

Kieback&Peter GmbH & Co. KG Tempelhofer Weg 50, 12347 Berlin/Germany Telefon: +49 30 60095-0, Telefax: +49 30 60095-164 www.kieback-peter.de, info@kieback-peter.com
MD15/230-HR, MD15/230-HE, MD15/230-DA
3.09-20.250-01-EN | 2018-08-06
Q
MD15/230-HR, MD15/230-HE and MD15/230-DA Small actuator
For R15xx, R20xx, RW15x and Danfoss RA Series Valves
Application
Actuator for three-point control systems in zone post-treatment devices for heating, ventilation and air conditioning systems.
Content Page
Important Information Regarding Product Safety ..................................................................................................2
Item........................................................................................................................................................................3
Technical Data.....................................................................................................................................................3
Dimensions ..........................................................................................................................................................4
Connection...........................................................................................................................................................5
R15xx, R20xx and RW15x Two-Way/Three-Way Valves for the MD15/230-HE Actuator ....................................6
Types ...................................................................................................................................................................6
Technical Data: Rxx and RWxx Valves ...............................................................................................................6
Valve Installation....................................................................................................................................................8
Mounting and Commissioning the Actuator ...........................................................................................................9
Dismounting the Actuator ....................................................................................................................................12
Manual adjustment ..............................................................................................................................................13
Initialization and adjustment to the valve stroke ..................................................................................................14
Page 2 / 16
3.09-20.250-01-EN | 2018-08-06
Q
Important Information Regarding Product Safety
Safety Instructions
This data sheet contains information on installing and commissioning the product "MD15/230-HR, MD15/230-HE, MD15/230-DA". Each person who carries out work on this product must have read and understood this data sheet. If you have any questions that are not resolved by this data sheet, you can obtain further information from the supplier or manufacturer.
If the product is not used in accordance with this data sheet, the protection provided will be impaired.
Applicable regulations must be observed when installing and using the device. Within the EU, these include regulations regarding occupational safety and accident prevention as well as those from the VDE (Association for Electrical, Electronic & Information Technologies). If the device is used in other countries, it is the responsibility of the system installer or operator to comply with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified technicians. Qualified technicians are persons who are familiar with the described product and who can assess given tasks and recognize possible dangers due to technical training, knowledge and experience as well as knowledge of the appropriate regulations.
Legend
WARNING
Indicates a hazard of medium risk which can result in death or severe bodily injury if it is not avoided.
CAUTION
Indicates a hazard of low risk which can result in minor or medium bodily injury if it is not avoided.
!
CAUTION
Indicates a hazard of medium risk which can result in material damage or malfunctions if it is not avoided.
NOTE
Indicates additional information that can simplify the work with the product for you.
Notes on Disposal
For disposal, the product is considered waste from electrical and electronic equipment (electronic waste) and must not be disposed of as household waste. Special treatment for specific components may be legally binding or ecologically sensible. The local and currently applicable legislation must be observed.
Page 3 / 16
MD15/230-HR, MD15/230-HE, MD15/230-DA
3.09-20.250-01-EN | 2018-08-06
Q
Item
Technical Data
MD15/230-HE Small actuator for R15xx, R20xx and RW15x
radiator valves and other valves with an M30x1.5 connection that were manufactured by Heimeier, Honeywell-MNG, Junkers, Hon­eywell-Baukmann, Oventrop (2001 and later) and Cazzaniga
MD15/230-DA Small actuator for radiator valves that were
manufactured by Danfoss of the RA-N, RA-FN or RA-U series
MD15/230-HR Small actuator for valve series R15/x
andRW15/x (manufacturer Hora, series 216Z and316Z) that were discontinued in 11-2015
Nominal voltage AC 230 V ±10%; 50/60 Hz
Power consumption Dimensioning: 4.4 VA
Nominal: MD15/230-DA 2.8 VA; MD15/230-HR 3.0 VA; MD15/230-HE 2.6 VA
Switch-on current Max. 10 A for a short time
Control Three-point signal (open/stop/close) or two-point signal (open/close)
Connection Built-in cable: 1.5 m, 3 x 0.75 mm
2
Motor switch-off Actuator spindle: extending = load-dependent, retracting = load-dependent
Actuating noise <28 dB
Positioning stroke MD15/230-HE and MD15/230-DA: 3 mm; MD15/230-HR: 9 mm
Positioning time 22 s/mm
Positioning force MD15/230-DA nominal 100 N; MD15/230-HR nominal 240 N
MD15/230-HE nominal 140 N
Position indicator Stroke range scale
Manual adjustment Only when disconnected from the power supply
Socket for hexagon key on the actuator cover, Key socket 4 mm
Permitted medium tem­perature in valve
0..120 °C
Ambient temperature 0..50° C
Ambient humidity During operation: 0..85 % r.h., non-condensing
Out of operation: 0..85 % r.h., non-condensing
Overvoltage category III
Level of contamination 2
Degree of protection IP40
Protection class II in accordance with EN 60730
Installation position Anywhere from vertical to horizontal
Maintenance Maintenance-free
Weight 242 g
Page 4 / 16
3.09-20.250-01-EN | 2018-08-06
Q
Dimensions
- MD15/230-HR and MD15/230-HE
-MD15/230-DA
85 47
56,5
47,5
76,5
M30 x 1,5 (MD15/230-HE) M30 x 1 (MD15/230-HR)
85 47
56,5
47,5
94,5
M30x1,5 DIN 13
M4
Ø 25,0
Ø 30,0
Page 5 / 16
MD15/230-HR, MD15/230-HE, MD15/230-DA
3.09-20.250-01-EN | 2018-08-06
Q
Connection
!
CAUTION
A 1 A pre-fuse is required to operate the actuator.
!
CAUTION
Temporary peak loads of up to 10 A may occur when switching on the actuator. Ensure suitability of switching components (e.g. controller connection) to ensure proper functioning and to avoid malfunc­tions and damage.
NOTE
The actuation direction can be changed by switching the supply lines to terminals 2 and 3 on the actuator.
- Three-point control - Two-point control
GY
230 V AC
BU BN
0 V AC
MD15/230-HR MD15/230-HE MD15/230-DA
M
1
2
3
MD15/230-HR MD15/230-HE MD15/230-DA
M
1
2
3
GY
230 V AC
BU
BN
0 V AC