Kidde Fire Systems SmartOne K-76-227 Quick Start Manual

®
Hand-Held Device Programmer
For SmartOne® Devices and DS Series Detectors
K-76-227
FEATURES
Single or sequential device addressing modes
Compact design; user-friendly
AC and battery power operation
Adjustable LCD Contrast
Integral detector base: photo, ion, thermal detectors
Adapter Base for DS Series Detectors included
Snap-in AI/AO Module Adapter for easy changeover
SLC Interface Adapter Connector—no SLC wiring
No wiring or End-of-Line resistors required (except NC AIs)
Less than 15 seconds addressing time per device
DESCRIPTION
Note: Prior to using the Programmer, ensure that you have
the following supplied accessories:
SLC Interface Adaptor
AC Adaptor (120V)
AI/AO Module Adaptor
4 NiMH Rechargeable AA Batteries
Storage Case
Effective: January 2017
2. Verify that the green “Status” LED is lit, and the LCD dis­play message reads “SLC Programmer.” After approximately 4 seconds, the LCD display should show the first Main Menu level option, “Single Address- ing.”
OPERATION OVERVIEW
To turn the Programmer on:
1. Press the button labeled “ON.”
LCD Display
Status LED
Keypad Buttons
ON”
Button
“Charging”
LED
To turn the Programmer off
:
From the Main Menu, press <> or <> until the LCD display reads “Power Off”; then press < E > (Enter), and the Program­mer will turn off. If you leave the Programmer idle, the Automatic Power Off fea­ture will turn the Programmer off after the pre-set default time of 5 minutes. You can adjust the Power Off time to between 1 and 10 minutes.
GENERAL MENU NAVIGATION
Detector Base
Smoke Detector
Index Marker
AI/AO Module Adaptor
General menu navigation rules include the following keypad instructions:
1. Press the <> and <> buttons to navigate the menu
levels.
2. Press <E> (Enter) to enter any sub-menu
higher level.
3. Press the <> button to return to a previous menu.
from any
MAIN MENU LEVEL SELECTIONS
To access Main Menu selections, press the <> and <> buttons until the LCD display shows the desired selection, then press <E>. There are four Main Menu selections:
Single Addressing - Set an address for a single device at
a time.
Sequential Addressing - Set an address range
start address and end address), and give each device a unique address within that range. Program multiple devices quickly, and reduce the possibility of setting dupli­cate addresses.
Alarm Test - Test the alarm initiating responses of initiating
devices. A device that fails the Alarm Test should not be installed.
Options - Adjust LCD settings; show current firmware ver-
sion; adjust the Power-Off timer.
(with a
CONNECTING TO VARIOUS SMARTONE DEVICES
(The power may be ON or OFF when connecting the various SmartOne devices.)
Smoke/Heat Detectors
Snap the detector into the detector base, orient the index marker on the device to the five o’clock position, then rotate clockwise.
Addressable Input/Addressable Output Modules
1. Connect the AI/AO Module Adaptor to the detector base, orient the index marker on the device to the five o’clock position, then rotate clockwise.
2. Insert the AI or AO module so that the terminal block faces left. Tilt the module into the recess of the adaptor so that the terminal block screws make contact with the spring­loaded probes; then snap the back of the module into the right half of the recess.
Other Devices
Plug the SLC Interface Adaptor jack into the Programmer Con­nector marked “SLC OUT.” Locate terminal blocks on device labeled “SLC” or “PC Line.” Connect one SLC Interface Adaptor wire to Terminal “A” on the device, and the other wire to Termi­nal “B.”