Kidde Fire Systems Installation, Operation And Maintenance Manual
Specifications and Main Features
Frequently Asked Questions
User Manual
P/N 76-100016-001
®
PEGAsys
Intelligent Suppression-Control
and Fire-Alarm System
August 1999
Installation, Operation,
and Maintenance Manual
UL Listing File No. S2422
Factory Mutual Approval J.I. No. OB2A6.AY
R
LISTED
Fire Systems
PEGAsys
Intelligent Suppression-Control
and Fire-Alarm System
Installation, Operation,
And Maintenance Manual
Document No. PEGAsys
August 1999
This Manual Is To Be Used By Trained Distributors Only
FOREWORD
This manual is intended to clearly and accurately reflect the PEGAsys Fire Alarm/Suppression Control System. This publication describes the operation, installation and maintenance of the PEGAsys Fire Alarm/Suppression Control System, P/Ns 76-100000-501 for
Single-Loop System and 76-100000-600 for Multi-Loop System.
TERMS AND ABBREVIATIONS
ADAAmericans with Disabilities Act
AIAddressable Contact Input Device
AOAddressable Relay Output Device
BPMBeats Per Minute
CCMCentral Control Module
CCPCentral Control Panel
EDPElectronic Data Processing
EOCEvent Output Control
FCPFire Control Panel
GUIGraphical User Interface
I/OInput/Output
IDIdentification
IRIIndustrial Risk Insurers
NCNormally Closed
ACCEPTANCES, APPROVALS, AND CERTIFICATIONS
NONormally Open
NRNot Registered
NYCNew York City
P/NPart Number
PASPositive Alarm Sequence
PCPersonnel Computer
PCSPEGAsys Configuration Software
PC Line Power/Communication Line (RX/TX Loop)
PSPower Supply
RCURemote Control Unit
RTCReal Time Clock
RX/TXReceive Transmit
ULUnderwriter Laboratories
VDCVoltage Direct Current
PEGAsys Single-Loop System (P/N 76-100000-501)
•UL: Underwriter’s Laboratories Listing File Number S2422.
Terms and Abbreviations ................................................................................................................................i
List of Illustrations .......................................................................................................................................... vii
List of Tables ................................................................................................................................................. ix
1GENERAL INFORMATION ................................................................................................................................................1-1
1-2.7.4City Tie Module ............................................................................................................................................................... 1-4
2-1.1Mode of Operation ..........................................................................................................................................................2-1
2-2Control and Indicators ....................................................................................................................................................2-1
2-3.1Levels of Security............................................................................................................................................................ 2-2
2-5.2Accessing the System Menus ........................................................................................................................................ 2-4
2-5.3Exiting the System Menus .............................................................................................................................................. 2-4
2-5.4.1Isolate Menu Function ....................................................................................................................................................2-4
2-5.4.2List Menu Function .........................................................................................................................................................2-4
2-5.4.3Set Menu Function ..........................................................................................................................................................2-4
2-5.4.4Test Menu Function ........................................................................................................................................................2-4
2-6Modes of Operation ........................................................................................................................................................ 2-5
2-8.2.2Enable/Disable RTC Program Line Numbers ............................................................................................................ 2-12
2-8.3Types of Inputs and Outputs ........................................................................................................................................ 2-12
2-8.3.2Remote Control Unit (RCU) ......................................................................................................................................... 2-12
3-3.1Central Control Module ..................................................................................................................................................3-2
3-3.9City Tie Module ............................................................................................................................................................. 3-10
4-3.1Lamp Test .......................................................................................................................................................................4-1
4-3.2Loop Device Test ............................................................................................................................................................ 4-1
4-3.3Battery Test ..................................................................................................................................................................... 4-1
4-3.4Walk Test ........................................................................................................................................................................ 4-2
4-3.4.2Walk Test Procedure ......................................................................................................................................................4-2
4-3.5Alarm Simulation Test (AST) .......................................................................................................................................... 4-2
4-4Disarming and Rearming Release Circuits..................................................................................................................4-3
4-5Power-Down System ......................................................................................................................................................4-3
4-6Power-Up System .......................................................................................................................................................... 4-4
5-4Removal and Replacement ...........................................................................................................................................5-2
5-4.2Central Control Module ..................................................................................................................................................5-2
6PARTS LIST .................................................................................................................................................................... 6-1
7-2Materials Required For Installation ................................................................................................................................ 7-1
7-3Installation Procedure For Central Control Panel .........................................................................................................7-1
7-4Installation Procedure For Expansion Enclosures ........................................................................................................ 7-1
7-5Installation Procedure For I/O Motherboard ...................................................................................................................7-2
7-6Installation Procedure For Rx/Tx Module (Multi-Loop Only) ...........................................................................................7-2
7-7Installation of I/O Modules ..............................................................................................................................................7-3
7-7.8.Power Supply Communication Connections ................................................................................................................7-6
7-8Connecting AC Power ....................................................................................................................................................7-6
7-9Install And Connect DC Power ....................................................................................................................................... 7-6
7-10Field Device Connection To RX/TX Module ....................................................................................................................7-7
7-10.1Wiring the RX/TX PC Line ............................................................................................................................................... 7-7
7-11Output Signal Connection .............................................................................................................................................. 7-9
7-12External Power Failure Indicator Connection .............................................................................................................. 7-10
7-18Connection of Peripherals ............................................................................................................................................ 7-11
7-18.1Connecting a Terminal or Personal Computer ............................................................................................................7-11
7-18.2Connecting a Printer ..................................................................................................................................................... 7-11
DNOT USED .................................................................................................................................................................... D-1
NNETWORKABLE CENTRAL CONTROL MODULE (NCCM) ......................................................................................... N-1
OCENTRAL STATION OPERATION .................................................................................................................................. O-1
vi
LIST OF ILLUSTRATIONS
FIGURETITLE PAGE
1-1PEGAsys System Overall Diagram ................................................................................................................................ 1-0
1-2Central Control Module (CCM) ....................................................................................................................................... 1-2
1-144-inch Detector Base ...................................................................................................................................................... 1-5
1-156-inch Detector Base ...................................................................................................................................................... 1-5
1-20Loop Isolator, RX/TX Mount ............................................................................................................................................ 1-6
1-21Loop Isolator, 6” Detector Base Mount ........................................................................................................................... 1-6
2-1System Front Panel ........................................................................................................................................................ 2-1
2-2Level One Menu Structure .............................................................................................................................................. 2-6
2-3Level Two Menu Structure ............................................................................................................................................... 2-7
3-1Overall Block Diagram, Single-Loop System ................................................................................................................3-1
3-2Overall Block Diagram, Multi-Loop System ...................................................................................................................3-1
3-3Central Control Module, Details .....................................................................................................................................3-2
3-18Loop Isolator, 6” Detector Base Mount ......................................................................................................................... 3-13
5-1Installation for Single Loop ............................................................................................................................................ 5-2
5-2Installation for Multi-Loop ............................................................................................................................................... 5-2
7-5Installation for Multi-Loop ............................................................................................................................................... 7-3
7-11Conduit to CCP ...............................................................................................................................................................7-7
7-12Shielded Wire to CCP .................................................................................................................................................... 7-7
7-13Style 4, RX/TX PC Line Connections ..............................................................................................................................7-8
vii
LIST OF ILLUSTRATIONS (CONT.)
FIGURETITLE PAGE
7-14Style 6, RX/TX PC Line Connections ..............................................................................................................................7-8
7-15Style 6, RX/TX PC Line Connections with Loop Isolators .............................................................................................. 7-9
7-16Style 7, RX/TX PC Line Connection ................................................................................................................................7-9
7-17CCM Printer Port ........................................................................................................................................................... 7-12
2-1Controls and Indicators .................................................................................................................................................. 2-3
2-2Isolate Menu Function ....................................................................................................................................................2-8
2-3List Menu Function .........................................................................................................................................................2-8
2-4Set Menu Function ..........................................................................................................................................................2-9
2-5Test Menu Function ...................................................................................................................................................... 2-10
5-1Troubleshooting Index ...................................................................................................................................................5-1
6-1PEGAsys System Parts List ........................................................................................................................................... 6-1
7-2Aux. Power Supply Module Connections to Rev. A .........................................................................................................7-5
7-3Aux. Power Supply Module Connections to Rev. C ........................................................................................................ 7-5
ix
SAFETY SUMMARY
Installation Precautions Adherence to the following will aid in problem-free installation with long-term reliability:
Warning - Several different sources of power can be connected to this fire alarm control panel. Disconnect all sources of power
before servicing. Control unit and associated equipment may be damaged by removing and/or inserting cards, modules, or interconnecting cables while the unit is energized. Do not attempt to install, service, or operate this unit until this manual is read and understood.
CAUTION - System Reacceptance Test after Software Changes: To ensure proper system operation, this product must be tested in
accordance with NFPA - 1996 Chapter 7 after any programming operation or change in site-specific software. Reacceptance testing is
required after any change, addition or deletion of system components, or after any modification, repair or adjustment to system hardware
or wiring.
All components, circuits, system operations, or software functions known to be affected by a change must be 100% tested. In addition,
to ensure that other operations are not inadvertently affected, at least 10% of initiating devices that are not directly affected by the change,
up to a maximum of 50 devices, must also be tested and proper system operation verified.
This system meets NFPA requirements for operation at 0 to 49° C and at a relative humidity of 85% RH (non-condensing) @ 30°C.
However, the useful life of the system’s standby batteries and the electronic components may be adversely affected by extreme temperature ranges and humidity. Therefore, it is recommended that this system and its peripherals be installed in an environment with a nominal
room temperature of 60-80°F.
Like all solid state electronic devices, this system may operate erratically or can be damaged when subjected to lightning induced
transients. Although no system is completely immune from lightning transients and interference, proper grounding will reduce susceptibility. The use of overhead or outside aerial wiring is not recommended due to the increased susceptibility to nearby lightningstrikes. Consult with the Applications Engineering Department if any problems are anticipated or encountered.
Disconnect AC power and batteries prior to removing or inserting circuit boards. Failure to do so can damage circuits.
Remove all electronic assemblies prior to any drilling, filing, reaming, or punching of the enclosure. When possible, make all cable
entries from the sides. Before making modifications, verify that they will not interfere with battery and printed circuit board location.
Do not over tighten screw terminals, over tightening may damage threads, resulting in reduced terminal contact pressure and difficult
with screw terminal removal.
This system contains static-sensitive components. Always ground yourself with a proper wrist strap before handling any circuits so that
static charges are removed from the body. Use static suppressive packaging to protect electronic assemblies removed from the unit.
Follow the Instructions in the installation, operating, and programming manuals. These instructions must be followed to avoid damage to
the control panel and associated equipment. PEGAsys operation and reliability depend upon proper installation.
Fire Alarm System Limitations While installing a fire alarm system may make lower insurance
rates possible, it is not a substitute for fire insurance!
An automatic fire alarm system - typically made up of smoke detectors, heat detectors, manual pull stations, audible warning devices,
and a fire alarm control with remote notification-capability can provide early warning of a developing fire. Such a system, however, does
not assure protection against property damage or loss of life resulting from a fire.
Any fire alarm system may fail for a variety of reasons:
Smoke detectors may not sense fire where smoke cannot reach the detectors such as in chimneys, in walls, or roofs, or on the other side
of closed doors. Smoke detectors also may not sense a fire on another level or floor of a building. A second floor detector, for example,
may not sense a first floor or basement fire. Furthermore, all types of smoke detectors - both ionization and photoelectric types, have
sensing limitations. No type of smoke detector can sense every kind of fire caused by carelessness and safety hazards like smoking in
bed, violent explosions, escaping gas, improper storage of flammable materials, overloaded electrical circuits, children playing with
matches, or arson.
Audible warning devices such as bells may not alert people if these devices are located on the other side of closed or partly open doors
or are located on another floor of a building.
A fire alarm system will not operate without electrical power. If AC power fails, the system will operate from standby batteries only for a
specified time.
Rate-of-Rise heat detectors may be subject to reduced sensitivity over time. For this reason, the rate-of-rise feature of each detector
should be tested at least once per year by a qualified fire protection specialist.
x
Auxiliary Equipment used in the system may not be technically compatible with the control panel. It is essential to use only equipment
listed for service with your control panel.
Telephone lines needed to transmit alarm signals from a premise to a central monitoring station may be out of service or temporarily
disabled.
The most common cause of fire alarm malfunctions, however, is inadequate maintenance. All devices and system wiring should be
tested and maintained by professional fire alarm installers following written procedures supplied with each device. System inspection
and testing should be scheduled monthly or as required by National and/or local fire codes. Adequate written records of all inspections
should be kept.
GENERAL SAFETY NOTICES The following must be observed to maintain personnel safety.
The following general safety notices supplement specific warnings and cautions appearing in the manual. The safety precautions in this
section must be understood and applied during operation and maintenance. This manual is to be used by trained distributors/technicians.
The entire manual should be read and fully understood prior to installation.
TEST EQUIPMENT
Make certain test equipment is in good operating condition. Do not touch live equipment or personnel working on live equipment while
holding a test meter. Some types of measuring devices should not be grounded; these devices should not be held when taking measurements.
FIRST AID
Any injury, no matter how slight, should never go unattended. Always obtain first aid or medical attention immediately.
GENERAL PRECAUTIONS
The following general safety precautions are to be observed at all times:
1.All electrical components associated with equipment shall be installed and grounded in accordance with NEC, NFPA and local
regulation requirements.
2.Special precautionary measures are essential to prevent applying power to equipment at any time maintenance work is in progress.
3.Before working on electrical equipment, use a voltmeter to ensure that system is not energized.
4.When working near electricity, do not use metal rules, flashlights, metallic pencils, or any other objects having exposed conductive
material.
5.When connecting a meter to terminals for measurement, use range higher than expected voltage.
xi
Intelligent Suppression Control/Fire Alarm System
CHAPTER 1
GENERAL INFORMATION
1-1INTRODUCTION
This manual contains the operation, maintenance, troubleshooting, parts listing, and installation information necessary to support the PEGAsys Intelligent Suppression Control and Fire Alarm
System.
NOTE: This manual is to be used by trained distributors only.
The entire manual should be read and fully understood
prior to installation.
1-1.1System Description
PEGAsys is a fire alarm/suppression control system which can
be used for local, auxiliary, remote protective signaling and releasing device service. The system is a microprocessor based
design for use with intelligent detectors and loop devices.
The system utilizes distributed intelligent field devices. These
devices are typically smoke detectors, contact input devices
relay outputs and signal output modules which represent a single
fire alarm initiation/indicating zone. Each device contains its own
data transceiver, micro controller, 4k of memory and applicable
algorithms which allows each device to operate independent of
the control system. These unique devices have the ability to
analyze information, make decisions and store information within
themselves. They communicate with the PEGAsys system using the BIP protocol which utilizes a two-wire (Style 4), four wire
(Style 6) or isolated (Style 7) multiplex trunk. The PEGAsys can
support up to 255 device addresses per loop with a maximum
of 8 loops for a total of 2040 Intelligent device points per system.
The PEGAsys is capable of controlling a wide variety of auxiliary devices, such as relays, audible visual indicating signal
devices and agent/sprinkler release systems. The system also
supports the use of serial printers which provide hard copy of
system status information.
1-1.2System Components
The system is comprised of three major components as shown
in Figure 1-1: the Central Control Panel (CCP) communicates
with the field devices and drives output devices such as alarm
signals that communicate with central stations and various types
of control equipment. A display panel located on the CCP provides system status LED’s, Control Switches and a 80-character LCD for alphanumeric display of system status information.
The single-loop PEGAsys Central Control Panel (P/N 76100000-501) consists of the Central Control Module (CCM) assembly, one receiver/transmitter (RX/TX) module and one power
supply assembly. Optionally the system can add a motherboard
assembly which allow the installation of optional output modules. An auxiliary power supply module can be added which
increases the base system power supply capacity to 8.0 amps
at 24 VDC.
PEGAsys
In multi-loop form the PEGAsys ML panel (P/N 76-100000-600)
consists of a CCM, one power-supply assembly, one RX/TX module and one multi-loop motherboard mounted in the enclosure.
The unique multi-loop motherboard provides the ability to connect
up to eight RX/TX modules to the system allowing a full 2040 addressable points to be connected to the PEGAsys ML system.
Auxiliary enclosures are available to allow the system to be expanded. The auxiliary enclosure has the same dimensions as that
of the main enclosure with the absence of the window in the door.
There are optional back planes which install in the expansion enclosure. This allows the number of I/O modules and system power
supplies to be expanded. To allow for maximum system flexibility
expansion enclosure(s) and backplane(s) can be added to the
system. Refer to Appendix B for further system expansion details.
1-2COMPONENT DESCRIPTION
The following paragraphs give a brief description of each components used in the PEGAsys system. For functional descriptions of each component see Chapter 3 of this manual.
1-2.1Central Control Module (CCM)
The CCM assembly is the heart of the system and is comprised
of two PCB assemblies, the display module and the main processor module. The CCM controls the operation and supervision of all the system modules and software within the PEGAsys
system. It receives loop device data from the RX/TX module,
processes the data based on pre-programmed instructions and
transmits output commands to the output modules, field devices,
and display module(s).
1-2.2Display Module
The display module assembly, attached to the main processor
PCB, provides the system with the operator interface for control
switches, system status LED’s, system trouble/alarm buzzer, a
80-character (2 x 40) LCD display and an integral numeric keypad. The keypad is used for entering the security password and
navigating through the user menus. The system buzzer provides two distinctly different signaling patterns for audible warning of system alarms and troubles.
76-100016-001
1-1August 1999
PEGAsys
Display Reset Switch
Intelligent Suppression Control/Fire Alarm System
•Battery charging and supervision
•AC power supervision
•24 VDC supervision
•Battery load test
•24 VDC ground fault detection (+/-)
•Auxiliary 24 VDC outputs
Loop Isolator
for Style 7
Figure 1-2. Central Control Module (CCM)
System Status
POWER ON
GROUND FAULT
ACKLDGERESET
SILENCE
SCROLLDRILL2DRILL
ALARM
PREALARM
TROUBLE
CPU ERROR
14
7890
6
SUPERVISORY
SILENCE
3
5
Figure 1-3. Display Module Assembly
1-2.3Receiver/Transmitter Module (RX/TX)
The RX/TX functions as the hardware & software interface between the field devices and the CCM. The RX/TX receives control requests from the CCM and establishes communications
with the field devices. The RX/TX receives status changes from
the field devices and reports these changes to the CCM. The
RX/TX shown in Figure 1-4 is capable of communicating with
up to 255 intelligent devices and complies with the wiring requirements of NFPA Style 4, 6 & 7 (with the use of the loop
isolator device). Style 4 initiation circuit wiring will permit “T”
tapping, or branch circuitry.
Figure 1-4. Receiver/Transmitter Module (RX/TX)
Figure 1-5. Power Supply/Charger Assembly
1-2.4Power Supply/Charger Assembly
The power supply/charger assembly (P/N 76-100009-010) is
comprised of a printed circuit board (PCB) assembly and a AC/
DC switching power supply unit. The switching power supply
unit provides 4 amps of 24 VDC from the 120/240 VAC input
power. The PCB assembly is a microprocessor based unit which
provides the system with:
1-2.5Basic Motherboard
The basic I/O motherboard assembly (P/N 76-100007-001) is
an assembly which can accept up to 8 I/O module circuit board
assemblies. The motherboard is mounted to the back of the
system enclosure and /or the auxiliary enclosures. It distributes
the system 24 VDC power and I/O bus communications to the I/
O modules. The I/O bus communications are provided by a RJ12 (flat phone cable) style connection. The 24 VDC is provided
by the system power supply via a 2-conductor wiring harness.
1-2August 199976-100016-001
Intelligent Suppression Control/Fire Alarm System
PEGAsys
The I/O motherboard mounts to standoffs on the back of the main
and expansion enclosures with screws provided.
Figure 1-6. Basic I/O Motherboard
1-2.6Multi-Loop Motherboard
The multi-loop I/O motherboard assembly (P/N 76-100017-001)
is an assembly which can accept up to 8 RX/TX modules and
provide connections for up to 7 I/O module circuit board assemblies. The ML motherboard is mounted to standoffs on the
back of the main system enclosure. It distributes system 24
VDC power, CCM-RX/TX communications for up to 8 RX/TX
modules and I/O bus communications to the I/O modules. The
I/O bus communications are provided by a RJ-12 (flat phone
cable) style connection. A single RJ-12 connection connects
the ML motherboard to the CCM for RX/TX communications.
The 24 VDC is provided by the system power supply via a 2conductor wiring harness.
1-2.7.1 SIGNAL OUTPUT MODULE
The PEGAsys panel has the capacity for a maximum of (8) Alarm
Sounder/Signal Output cards, thus providing 32 possible signal circuits. Each Alarm Sounder/Signal Output card, Figure 18, is equipped with supervised 24 VDC outputs which can
operate as Style “Y” or Style “Z” indicating circuits.
76-100003-001
Figure 1-7. Multi-Loop I/O Motherboard
1-2.7Input/Output Modules
The optional input/output modules allow the PEGAsys system
to interface with external auxiliary devices. These auxiliary devices can be audible/visual signal devices, HVAC systems, elevator recall, power shut down, remote annunciators, agent/
sprinkler release system and any other control type input or
output which may need to be interfaced to the system.
The input and output modules plug into the motherboard assembly located on the back plate of the system enclosure. Each
I/O module occupies one slot in the motherboard assembly which
has 8 slots available. The I/O modules and the CCM communicate over the RS-485 based I/O bus, which uses a 6-conductor
phone type cable to connect the CCM to the motherboard.
The PEGAsys single-loop panel has the ability to support a
maximum of 16 I/O modules, in any combination. However, no
more than 8 of any one type of module can be used. If using a
City-Tie module, the limit is one per system.
The PEGAsys multi-Loop panel has the ability to support a maximum of 23 I/O modules, in any combination, on the system.
However, no more than 8 of any one type module can be used.
If using a City-Tie module, the limit is one per system.
The following paragraphs describe each available I/O module
in greater detail.
Figure 1-8. Signal Output Module
1-2.7.2 RELAY OUTPUT MODULE
The PEGAsys panel has the capacity for a maximum of 8 Auxiliary Relay Output cards, allowing up to 32 relays. Each Auxiliary Relay Output card is equipped with four (4), Form C,
dry-contact relay outputs. The ability to isolate an individual relay
output is provided through the system operator menu.
76-100016-001
1-3August 1999
PEGAsys
Figure 1-9. Relay Output Module
1-2.7.3 AGENT RELEASE OUTPUT MODULE
The PEGAsys panel has the capacity for a maximum of 8 agent
release output modules, providing up to 8 release circuits and
24 maximum signal outputs on those modules.
Intelligent Suppression Control/Fire Alarm System
76-100002-001
Figure 1-11. City Tie Module
1-2.8Standby Batteries
Space is provided within the central control panel enclosure for
up to two (2) 12-V, 17 Amp Hour, sealed lead-acid batteries
used for 24, 60 or 90 hour standby operation. If additional batteries are required, an optional battery enclosure is available.
The enclosure (Figure 1-12) is a heavy duty steel cabinet which
can house up to two 40AH batteries. For installation information see Paragraph 7-9.1.
Figure 1-10. Agent Release Output Module
1-2.7.4 CITY-TIE MODULE
The City-Tie (Notification) Module will provide connection and
operation for local energy, shunt type master box and reverse
polarity styles of output.
FIREALARM SYSTEM
STANDBYBATTERIES
KIDDE
Figure 1-12. Battery Enclosure
1-2.9Intelligent Loop Devices
The SmartOneTM Series of Intelligent Fire Alarm devices provide the PEGAsys control system with smoke and heat detection and necessary monitoring and control functions required
by today’s advanced fire alarm systems. The following paragraphs describe each available intelligent detection device.
Figure 1-13. SmartOne Detection Device
1-2.9.1 SmartOne IONIZATION DETECTORS
The SmartOne Ionization smoke detectors provide true distributed-intelligence, addressable microprocessor-based smoke
detection to the PEGAsys system.
1-4August 199976-100016-001
Intelligent Suppression Control/Fire Alarm System
1-2.9.2 SmartOne PHOTOELECTRIC DETECTORS
The SmartOne Photoelectric smoke detectors provide true distributed-intelligence, addressable microprocessor-based smoke
detection to the PEGAsys system.
1-2.9.3 SmartOne HEAT DETECTORS
The SmartOne Thermistor heat detectors provide true distributed-intelligence, addressable, microprocessor-based heat detection to the PEGAsys system.
1-2.10 SmartOne Detector Bases
The SmartOne series of detection devices all use universal
mounting bases which are available in three styles. The 4SB is
a European-Style 4-inch base whose outside diameter matches
that of the low profile SmartOne detectors, which when combined, provides a very attractive unit. The 4SB, shown in Figure
1-14, mounts to standard 3, 3.5-inch, or 100-mm electrical boxes
with ease.
PEGAsys
Figure 1-16. Addressable Contact Input Device
1-2.12 Addressable Relay Output Devices
The addressable relay output device (P/N 70-408004-001) provides the PEGAsys system with a Form-C dry-contact interface
for remote control applications.
Figure 1-14. Four-inch Detector Base
The 6SB model, shown above, is a traditional style detector
base with an integral trim ring which provides coverage for any
inconsistencies between the electrical box and ceiling material.
The 6SB mounts to standard 3, 3.5 and 4 inch electrical boxes
with ease.
Figure 1-15. 6-inch Detector Base
1-2.11 Addressable Contact Input Devices
The SmartOne Contact Monitor (P/N 70-407008-00X) allows
an installer the ability to interface typical NO/NC fire alarm devices, such as water flow and tamper switches to the PEGAsys
system. The contact monitor is also used to interface to the
manual alarm, manual release and abort stations.
Figure 1-17. Addressable Relay Output Device
1-2.13 Model DH-2000 Air Duct Housing
The DH-2000 air duct housing is designed for detecting particles of combustion products in air-handling systems.
76-100016-001
Figure 1-18. Air Duct Housing
1-5August 1999
PEGAsys
Intelligent Suppression Control/Fire Alarm System
1-2.14 Loop Isolator Devices
The SmartOne series of loop devices, shown in Figures 1-19
through 1-21, offer optional loop isolation which protects the
loop from wire to wire short conditions (NFPA Style 7.0).
Figure 1-19. Loop Isolator, Stand-Alone
SHORT-1SHORT-2
J1
Underwriters
Laboratories Inc.
R
REFER TO
INSTALLATION MANUAL
P/N 76-100016-001
FOR MODULE INSTALL.
PROCEDURES
LISTED
DS2DS1
R
KIDDE-FENWAL, INC.
ASHLAND, MA 01721
LOOP ISOLATOR
RX/TX
Table 1-1. System Specifications
METISCITSIRETCARAHC
ylppuSrewoP
:tnemeriuqeRrewoP*zH06/05,V022/021
)eludoMreP(tupnI.S.P
spmA9.1,CAV021
spmA59.,CAV022
)eludoMreP(tuptuO.S.PspmA4,CDV42
:tuptuOregrahC.taBspmA3,CDV4.62
)2(:stuptuO.xuAhcaespmA5.1,CDV42
MCC
:tuptuOlangiSspmA2,CDV42
:tuptuOesaeleRspmA2,CDV42
:gnitaRtcatnoCyaleRCDV03@pmA1
:gnitaRyaleRelbuorTCDV03@pmA1
eludoMXTXR
:egatloV.xaMCDV4.62
:egatloV.niMCDV0.91
:ecnaticapaCeniL.xaMFu0.1
:ecnatsiseReniL.xaMsmhO62
elbasserddA.xaM
:seciveD
XTXRrep552
eludoMesaeleR
Figure 1-20. Loop Isolator, RX/TX Mount
Figure 1-21. Loop Isolator, 6" Detector Base Mount
1-3SYSTEM SPECIFICATION
System power specifications are outlined in Table 1-1.
tuptuOesaeleRCDV42@spmA2
tuptuOlangiShcaeCDV42@spmA2
:epyTtuptuOesaeleR
eludoMelbiduAlangiS
:stuptuOlangiS
eludoMyaleR
:gnitaRtcatnoC
eludoMeiTytiC
:tcatnoCtnuhS
:tuptuOygrenElacoL
:yrosivrepuSygrenElacoLAm11
:daoLygrenElacoL
gnisaelerfoelbapaC
noisserppus(sdionelos
)relknirpsdna
elyts)2(ro"Y"elyts)4(
CDV42@spmA2"Z"
hcae
,stcatnoCCmroF)4(
roCDV03@spmA2
CAV021@pmA1
,CDV42@spmA5
evitsiseR
,CDV42@.xamAm005
.miLtnerruC
tnerruCpirTxoBretsaM
lacipyt.spmA52.0
*Refer to Appendix A for total system power and AC branch
circuit requirements.
1-6August 199976-100016-001
Intelligent Suppression Control/Fire Alarm System
CHAPTER 2
OPERATION
2-1INTRODUCTION
This chapter describes the PEGAsys system controls and indicators located on the display panel. It also describes the
operating procedures and menu system.
2-2.1Modes of Operation
There are two modes of PEGAsys system operation:
•In the default operation the panel will be set to latch all
alarm inputs on the system. The latching operation will not
allow the loop input devices to generate an "alarm off" signal that would possibly interrupt a discharge time delay
sequence. To return the panel to normal the "RESET" button will need to be pushed.
•The second mode of operation is non-latching. This option
can be enabled, using the PCS (PEGAsys Configuration
Software) to define if a loop device input is to be non-latching. The non-latching operation will allow the loop input
devices to generate an "Alarm Off" signal to the panel. When
this signal is received the panel would interrupt the discharge time delay sequence of operation. However, all outputs that had been activated previous to the "Alarm Off"
signal will remain on and latched until the panel is reset.
The advantage of offering a latching or non-latching operation
per loop input device, allows the installer/designer to customize the system. This allows the inter mixing of latching and nonlatching devices to protect critical areas where both type may
be specified
PEGAsys
When an Alarm returns to a normal state (Alarm Off), the buzzer
will sound in a pulsed fashion, the alarm off condition must be
acknowledged to silence the buzzer. During the Trouble Off
condition, the audible device provides no sound. The following
summarizes the buzzer operation:
•Alarm condition is indicated by a continuous ON signal,
•Alarm OFF is indicated by a ½ second ON ½ second OFF
signal,
•Trouble condition is indicated by a 1 second ON and 1 second OFF continuous beeping,
Every individual change of status must be individually acknowledged by pressing the ACKLDGE (acknowledge) pushbutton
to silence the Audible device.
2-2CONTROLS AND INDICATORS
The control and indicators of the PEGAsys system are located
on the display panel, shown in Figure 2-1. The display panel is
mounted on top of the CCM. To gain access to the CCM, the
panel door must be open. Table 2-1 lists controls and indicators
for the display unit, giving name and functional description.
2-2.1LCD Display
The display panel contains an 80-character (2X40) alphanumeric display. This LCD display is used to present system status. In the procedure section of this chapter there will be several
System Status
POWER ON
GROUND FAULT
ACKLDGERESET
SCROLLDRILL
SILENCE
DRILL
ALARM
PREALARM
Figure 2-1. System Front Panel
2-1
TROUBLE
CPU ERROR
14
6
SUPERVISORY
SILENCE
2
7890
3
5
August 199976-100016-001
PEGAsys
Intelligent Suppression Control/Fire Alarm System
simulated LCD display readouts. The LCD display readouts
will be used to aid users in the operation of the system.
2-2.2Audible Device
The Display Panel also contains an audible device which generates two separate audible tones, one for alarms and one for
troubles. This device sounds continuously when a new alarm
condition is received until the condition is acknowledged. It also
sounds intermittently when a trouble, supervisory, or pre-alarm
condition is received until the condition is acknowledged.
2-2.3Control and Indicator Description
Refer to Table 2-1 for complete description of controls and indicators.
2-3SYSTEM SECURITY
The PEGAsys system provides three distinct levels of program
protection, as required by UL Standard 864. The user can only
access the system by entering a valid password. Typical valid
passwords consist of three or four characters but may be up to
eight characters in length.
2-3.1Levels of Security
The three security levels are: Level One, Level Two, and System Manufacturer. The highest security level is reserved for the
system manufacturer. System owner is level one, system installer is level two. Passwords consist of numeric characters (0
- 9) which allows access from the integral keypad of the CCM.
Alphanumeric characters can only be used with the PCS program and if used they will lock out any possible entry using the
CCM keypad to gain entrance to the menus.
If alphanumeric passwords are necessary for a particular application, it is recommended that the Level One password be numeric and the Level Two password be alphanumeric so as to
allow the user to retrieve system information (system information lists) and also prevent a user from changing any programmed system parameters.
2-3.2Default Passwords
The PEGAsys system provides protection from unauthorized
entry to the system menus by utilizing two levels of default passwords, level one and level two. This feature provides two separate passwords which increases the security of the system.
Default passwords are set when the system is shipped from
Kidde. These default passwords are:
Level One = 987
Level Two = 1865
These default passwords are valid until other passwords are
programmed into the system.
2-3.3Entering Passwords
The password entry procedure is listed below:
a.Verify that the system status is displayed.
b.Press 0 (zero) key. Verify that the display reads:
PLEASE ENTER PASSWORD
c.Type in three or four digit password into keypad. Ensure a
pound sign (#) appears for each key pressed.
NOTE: Use the default password, if a new password has not
been set.
d.Press the return (
↵↵
↵) key. Verify that the display reads:
↵↵
1:ISOLATE2:LIST
3:SET4:TEST
2-4SYSTEM POWER-UP
The following step-by-step procedure is for initial power-up of
the CCP.
a.Perform the installation check-out procedure in Chapter 7
of this manual.
b.Set the circuit breaker for the CCP power to ON. Verify that
the display reads "Main Processor Power On" and that the
CPU ERROR indicator is lit. Ensure that the audible device
is buzzing continuously.
c.Press the display module reset switch. Verify that the CPU
ERROR indicator is extinguished and the audible device is
silenced.
d.Verify that the display reads as follows:
MAIN PROCESSOR
POWER ON
e.After ten seconds, verify that the display reads as follows:
RXTX NON-MONITORING TROUBLE ON
RXTX1
NOTE: For multi-loop systems only. The above and below RX/
TX messages will repeat themselves for each RX/TX
module installed in the system. The above message
will be displayed while the system is initializing itself.
This initialization can take up to 90 seconds.
To clear the below RX/TX message use the AutoLearn
function from the menu function or upload the
configuration from the PCS program. If using PCS
software, verify that the correct number of RX/TX loops
are enabled in the Loops Topic of the configuration file
prior to uploading.
RX/TX 1 NOT REGISTERED ON
RX/TX LOOP 1
f.Verify that the POWER ON and TROUBLE indicators are
lit.
g.Connect the backup batteries to the CCP in accordance to
the procedure in Chapter 7.
h.Press the ACKLDGE pushbutton. After approximately one
minute the display will momentarily read :
RXTX NON-MONITORING TROUBLE OFF
i.Verify the display reads the incorrect time and date.
j.Set time and date as follows:
(1) Press 0 (zero) key. Verify that the display reads:
PLEASE ENTER PASSWORD
(2) Type in the default 1st level password (987).
(3) Press the return (↵) key. Verify that the display reads:
(4) Type in 3111 on the keypad. Verify that the display
reads:
SYSTEM TIME (AM/PM)
ENTER THE TIME _ _ : _ _ (HH:MM)
(5) Type in the time (HH=hours 0-12 and then MM=minutes
0-59). Press the return key. Verify that the display reads:
SYSTEM TIME (AM/PM)
1:AM2:PM
(6) Type in appropriate selection (1 for AM or 2 for PM).
NOTE: If there has been a mistake in the entered data, press
the backspace key as many times as required to get to
the mistake, then re-enter data from that point.
k.The power-up procedure is complete at this point. The sys-
tem is now ready for loop device registration and programming which is covered in this chapter.
2-5SYSTEM MENUS
PEGAsys has a built-in menu structure. This menu structure
has been implemented to aid users with system operating functions. The following paragraphs describe the menu structure,
accessing the menu, exiting the menu and menu functions. Figure 2-2 shows the system's Level One menu structure. Figure
2-3 shows the system's Level Two menu structure.
2-5.1Menu Structure
The PEGAsys menu structure consists of a main menu, and
multiple sub-level menus. The sub-level menus may also contain multiple sub-level menus. The main menu displays after
you enter a valid password. You can also access the Top Level
menu from any sub-level menu at almost anytime by pressing
the backspace key located on the keypad.
NOTE: The top level menu may not be available by using the
backspace key while certain types of programming are
being performed.
It is possible to access a previous higher level menu from a
lower level menu by pressing the backspace key.
The choices of available sub menus after a valid password has
been entered, correspond to the security level password that
has been entered.
The main menu for the 1
security level is:
st
level, 2nd level, and Manufacturer
1:ISOLATE2:LIST
3:SET4:TEST
2-5.3Exiting the System Menus
To exit the system's menus, perform the following steps:
a.Press the backspace key as many times necessary to reach
the top level menu, shown in the top of the next column:
1:ISOLATE2:LIST
3:SET4:TEST
b.Press the backspace key. Verify that the system returns to
standby. The display should read:
SYSTEM STATUS NORMAL HH:MM MM-DD YR
40 CHARACTER CUSTOM MESSAGE
NOTE: When exiting the system menus, if the system is normal
the display panel should show the time and date as
shown in the above step.
2-5.4Menu Functions
Tables 2-2 through 2-5 list and provide a brief description of all
functions that you can perform using the PEGAsys system’s
menus. In addition, the tables provide the security access level
and a keystroke formula for each function. The keystroke formula is a sequence of numbers you enter via the system’s keypad to access a particular function. These formulas provide the
path from the main menu to the desired function. Formulas are
provided for each access level. After you enter the formula, some
of the functions require you to press the return key to start implementing the function.
Most functions will require that you enter additional data to implement the function, such as a device address or desired alarm
threshold.
2-5.4.1 ISOLATE MENU FUNCTION
The isolate menu function (Table 2-2) permits the operator to
isolate field devices and output modules. Isolating any device
immediately places the system in a trouble condition, and initiates an audible trouble alarm and a printout with the time, date,
and device isolated. The feature is typically used to temporarily
isolate auxiliary devices during a system test.
2-5.4.2 LIST MENU FUNCTION
The list menu function (Table 2-3) permits the operator to list
various system parameters. All lists are real time actual system
conditions which are displayed and printed with the time and
date.
2-5.4.3 SET MENU FUNCTION
The set menu function permits the operator to program various
system parameters within the system. A few examples are shown
in Table 2-4.
Any one of the basic functions listed in a main menu can be
selected by pressing the numeric key of the system’s keypad
which corresponds to the desired function. (Example: To select
the LIST function from the main menu, press the 2 key on the
system keypad.) You also select lower level functions from sublevel menus using the numeric keys.
2-5.2Accessing the System Menus
Perform the steps in Paragraph 2-3.3.
August 199976-100016-001
2-5.4.4 TEST MENU FUNCTION
The test menu function, shown in Table 2-5, allows the operator
to test individual or a group of field devices. On command, a
detector or contact input device can be tested, and results will
be printed and displayed at the Central Control Panel. The Test
procedure in the device is activated by imposing a signal within
the device that will cause an alarm output. The Control Panel
verifies that an alarm output is generated and reports “Test
Result OK” for each device.
2-4
Intelligent Suppression Control/Fire Alarm System
2-6MODES OF OPERATION
The PEGAsys system has four modes of operation. Each mode
has different indications and action required. The following Paragraphs describe each mode, indications and action if required.
2-6.1Normal Standby Mode
This is the typical mode of the system. In this mode, no alarm,
trouble, or supervisory conditions exist in the system. The system display will show the time, day of the week, and date. For
example:
SYSTEM STATUS NORMAL 11:06 AM_05-04-90
40_CHARACTER_CUSTOM_MESSAGE
The system provides an option which allows the System Status
Normal message to be replaced with a display of battery charging voltage and current for the system standby batteries. For
example:
The green AC POWER LED will be illuminated to indicate that
the system’s main power source is normal.
NOTE: In the Normal Standby Operation state, it is possible
for the 80-character display to show data other than
the time, day of date. This occurs when the system
menus are being accessed either locally or remotely
through one of its serial ports. This condition will be
indicated by the menu selections being displayed on
the display panel being illuminated.
In the Normal Standby Mode, no indicating LED’s will be illuminated other than the “AC POWER.”
2-6.2Active Alarm Mode
The system enters an alarm mode if a device (or devices) has
detected an alarm condition, such as smoke / heat above the
alarm threshold level. There are two types of alarms which can
occur:
Device Alarm
An alarm in which a device has communicated the alarm status
properly to the Central Control Panel, by providing the alarmed
device address for indication to the operator.
Zone Alarm
An alarm condition detected by one or several devices, but which
cannot be reported by a specific device due to a malfunction in
communications between the system and the alarmed device(s).
This is a redundant feature to increase system reliability and is
called Failsoft Mode.
NOTE: A device can signal a zone alarm to the system during
some communication failures.
2-6.2.1 ALARM MODE INDICATIONS
The following indicates the system is in its alarm mode of operation.
a.The red “ALARM” LED will be illuminated and there will be
a continuous audible signal by the system buzzer at the
panel.
PEGAsys
b.The 80-character display will cycle between all currently
active alarms. Example:
NOTE: If the alarm is a zone alarm, the Device Address “1000
- 8000” will be displayed depending on which RX/TX
module detects the zone alarm.
b.The outputs which have been previously programmed for
activation upon alarm by the specific devices will be turned
on. (Example: Signal audible signaling devices, control relays for HVAC shutdown or elevator recall.)
2-6.2.2 ALARM MODE USER ACTION
The following steps should be performed when the system is
set into alarm.
a.Press the display panel’s ACKLDGE pushbutton to acknowl-
edge the displayed alarm condition. The 80-character display will continue to cycle between any remaining alarms
which have not been acknowledged. The “ACKNOWLEDGE” switch must be operated once for each alarm received at the panel.
b.Once all current alarms have been acknowledged, the alarm
indicating circuits (audible devices) can be silenced by operating the “SILENCE” switch.
c.After all of the current alarms have been acknowledged,
verify that the display reads: XXX ALARMS REMAIN. The
“XXX” representing the total of all active alarms. All active
alarms can be viewed on the display by pressing the scroll
pushbutton.
NOTE: The first 64 alarms will only be displayed. Subsequent
alarms over the initial 64 will not be displayed, even
when any or all of the first 64 alarms clear. However,
all alarms regardless of total will be processed in the
EOC. For a complete list of active alarms access the
event buffer menu using the CCM keypad.
d.Any subsequent alarms will cause the alarm audible cir-
cuits to resound. Each additional alarm must be acknowledged before the alarm indicating circuits can be silenced.
e.When a device goes out of alarm, the display will indicate
the device address and an alarm off (AOF) message (nonlatching mode). Example: